HomeMy WebLinkAbout2003-2675 - Ordinance - 11/13/2003ORDINANCE NO. 2675
AN ORDNANCE AMENDING CHAPTER 3, "BUILDING REGULATIONS", OF THE CODE
OF ORDINANCES OF THE CITY OF COLLEGE STATION, TEXAS, BY AMENDING
CERTAIN SECTIONS AS SET OUT BELOW; PROVIDING A SEVERABILITY CLAUSE;
DECLARING A PENALTY; AND PROVIDING AN EFFECTIVE DATE.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF COLLEGE STATION,
TEXAS:
PART 1:
That Chapter 3, "Building Regulations", Appendix 2, "Electrical Code Adopted",
of the Code of Ordinances of the City of College Station, Texas, be amended as
set out in Exhibit "A", attached hereto and made a part of this ordinance for all
purposes.
PART 2:
That if any provisions of any section of this ordinance shall be held to be void or
unconstitutional, such holding shall in no way effect the validity of the remaining
provisions or sections of this ordinance, which shall remain in full force and
effect.
PART 3:
That any person, firm, or corporation violating any of the provisions of this
chapter shall be deemed guilty of a misdemeanor, and upon conviction thereof
shall be punishable by a fine of not less than Twenty-five Dollars ($25.00) nor
more than Two Thousand Dollars ($2000.00). Each day such violation shall
continue or be permitted to continue, shall be deemed a separate offense. Said
Ordinance becomes effective on 1 January 2004.
PASSED, ADOPTED and APPROVED this 13 th day of November
,2003.
ATTEST:
Connie Hooks. City Secretary
APPROVED:
RON-SI~VIA, Mayor
APPROVED:
~y ARVey
O/group/legal/ordinance/amendmentform. doc
ORDNANCE NO. 2675
Page 2
EXHIBIT "A"
That Chapter 3, "Building Regulations", Appendix 2, "Electrical Code Adopted", of the Code of
Ordinances of the City of College Station, Texas, is hereby amended, by amending certain
sections as set out hereafter to read as follows:
APPENDIX 2
ELECTRICAL CODE ADOPTED
A booklet entitled 'National Electrical Code 2002 Edition' as amended and as hereafter may be
amended, at least one (1) copy of which is on file in the office of the Building Official of the
City of College Station, Texas, is hereby adopted and designated as the Electrical Code of the
City of College Station, Texas.
AMENDMENTS TO NATIONAL ELECTRICAL CODE
mo
The above referenced 'National Electrical Code' is hereby amended as follows:
o
Section 210.23 (A) 15 and 20 Ampere Circuits shall be amended to delete the
reference to 15-ampere branch circuits. It shall also be amended to include the
following sentence after said section: 'However, a circuit of twenty (20) amperes
shall not serve more than ten openings.'
,
Table 210.24 Summary of Branch-Circuit Requirements shall be amended by
placing an asterisk next to all 14 AWG conductors indicated in the table and by
adding this footnote at the bottom of the table * special note' Except for fixture
wires in UL or other listed fixtures, no conductor of a size smaller than 12 AWG
copper is allowed in branch circuit wiring.'
.
Section 210.52 (B) Small Appliances shall be amended by adding the following
subsection' (4) Separate Circuit Required. A separate circuit is required for
each refrigerator, deep freeze, dishwasher, disposal, trash compactor or any other
load exceeding six (6) amperes.'
,
Section 210.52 (C) Countertops shall be amended to include after the words
'...with 210.52 (C) (1) through (5) the following sentence: However, a separate
circuit is required for microwave ovens or any other counter top appliance with a
load exceeding six (6) amperes.'
o
Section 210.52 (F) Laundry Areas shall be amended to include after the words '.
.. for the laundry' the following sentence: 'However, a separate circuit is required
ORDINANCE NO. 2675
Page 3
for a washing machine or any other laundry appliance with a load exceeding six
(6) amperes.'
o
Section 210.52 Dwelling Unit Receptacle Outlets shall be amended by adding
the following subsection: '(I) Other Locations. A separate circuit is required for
each well pump or other outdoor loads exceeding six (6) amperes.'
o
Article 230 Services shall be amended by adding the following section' 230.11
Meter Mounting Heights. Individual meters shall be mounted at a height not
greater than 5'-6" nor less than 4'-6" above finished grade, measured to the
centerline of the meter base. Meter packs shall be mounted with its horizontal
centerline not greater than 4'-6" nor less than 4'-0" above finished grade.
Exception- Meters and meter packs may be mounted at a different height by
special permission of the Building Official or his designee when special
conditions make the installation at the above heights impractical.
o
Section 230.70 General shall be amended by adding the following subsection:
'(D) Service Disconnecting Means for Commercial Buildings and Structures.
For commercial buildings and structures, the service disconnecting means shall be
installed on the outside of the building or structure. A power operated disconnect
switch (shunt trip) shall be permitted for service disconnects rated 1000 amps or
more. All shunt trip disconnecting means shall be of the momentary contact type
and installed in an approved, lockable enclosure. All service disconnects shall be
clearly marked in a permanent manner.
Exception' A power operated disconnect switch (shunt trip) may be allowed on
service disconnects rated less than 1000 amps, if the applicant requests an
exception from the Electrical Division and Building Official and satisfies the
official that one of the following criteria has been met.
(a)
A power operated disconnect switch (shunt trip) may be used for a service
disconnect rated less than 1000 amps when the building or structure is
served by a single transformer and the transformer is not anticipated to be
used for multiple services; or
(b)
A power operated disconnect switch (shunt trip) may be used for a service
disconnect rated less than 1000 amps on an existing building or structure
when space is not available to mount an external disconnect.
o
Section 250.52 (A) (5) Rod and Pipe Electrodes shall be amended by deleting
the section in its entirety and replacing with the following' Rod and Pipe
ORDINANCE NO. 2675
Page 4
Electrodes. Rod and pipe electrodes shall not be less than eight (8) feet in length,
not less than 5/8" in diameter and shall be copper coated..
10.
Section 310.2 (B) Conductor Material shall be amended by deleting the section
in its entirety and replacing with the following: 'Conductor Material.
Conductors in this article shall be of copper only.'
11.
Section 320.12 Uses Not Permitted shall be amended by deleting the section in
its entirety and replacing with the following: 'Uses Not Permitted. Type AC
cable shall not be permitted in commercial buildings as a wiring method.'
12.
Section 334.12 (A) Types NM, NMC, and NMS. shall be amended to include
the following subsection: (11) In educational occupancies as defined by the
City's "adopted building code."