HomeMy WebLinkAbout2022-4352 - Ordinance - 04/28/2022ORDINANCE NO. 2022-4352
AN ORDINANCE AMENDING CHAPTER 103, “BUILDING REGULATIONS,”
ARTICLE III, “TECHNICAL CODES,” DIVISION 2 “BUILDING CODES” AND
DIVISION 3 ELECTRICAL CODE, OF THE CODE OF ORDINANCES OF THE CITY
OF COLLEGE STATION, TEXAS, BY AMENDING CERTAIN SECTIONS RELATING
TO BUILDING REGULATIONS; PROVIDING A SEVERABILITY CLAUSE;
DECLARING A PENALTY; AND PROVIDING AN EFFECTIVE DATE.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF COLLEGE STATION,
TEXAS:
PART 1: That Chapter 103, “Building Regulations,” Article III, “Technical Codes,” Division
2 “Building Codes” and Division 3 “Electrical Code” of the Code of Ordinances of
the City of College Station, Texas, be amended as set out in Exhibit “A” and
Exhibit “B” attached hereto and made a part of this Ordinance for all purposes.
PART 2: If any provision of this Ordinance or its application to any person or circumstances
is held invalid or unconstitutional, the invalidity or unconstitutionality does not
affect other provisions or application of this Ordinance or the Code of Ordinances
of the City of College Station, Texas, that can be given effect without the invalid
or unconstitutional provision or application, and to this end the provisions of this
Ordinance are severable.
PART 3: That any person, corporation, organization, government, governmental subdivision
or agency, business trust, estate, trust, partnership, association and any other legal
entity violating any of the provisions of this Ordinance shall be deemed guilty of a
misdemeanor, and upon conviction thereof shall be punishable by a fine of not less
than twenty five dollars ($25.00) and not more than five hundred dollars ($500.00)
or more than two thousand dollars ($2,000) for a violation of fire safety, zoning, or
public health and sanitation ordinances, other than the dumping of refuse. Each day
such violation shall continue or be permitted to continue, shall be deemed a separate
offense.
PART 4: This Ordinance is a penal ordinance and becomes effective June 1, 2022.
PASSED, ADOPTED and APPROVED this 28TH day of April 2022.
ATTEST: APPROVED:
_____________________________ _____________________________
City Secretary Mayor
APPROVED:
_______________________________
City Attorney
ORDINANCE NO. 2022-4352 Page 2 of 54
EXHIBIT A
That Chapter 103, “Building Regulations,” Article III, “Technical Codes,” Division 2 “Building
Codes” is hereby amended to read as follows:
Sec. 103-131. – International Building Code adopted.
A booklet entitled 'International Building Code 2021 Edition' as amended and as hereafter may be
amended, at least one (1) copy of which is on file in the office of the Building Official of the City
of College Station, Texas, is hereby adopted and designated as the Building Code of the City of
College Station, Texas. In addition, Appendix D of the 2021 International Building Code is hereby
adopted.
Sec. 103-132. – International Building Code amended.
The above referenced International Building Code is hereby amended as follows:
1. Section 105 (Permits) is amended by adding Section 105.1.3 to read as follows:
105.1.3 Registration of Contractors.
It shall be the duty of every individual who makes contracts to construct, enlarge,
alter, repair, move, demolish, or change the occupancy of a building or str ucture,
or to erect, install enlarge, alter, repair, remove, convert or replace any electrical,
gas, mechanical, or plumbing system, the installation of which is regulated by this
code, or to cause any such work to be done, and every individual making such
contracts and subletting the same or any part thereof, to first register with the
Building Official, giving full name, residence, name and place of business, and in
case of removal from one place to another to have made corresponding change to
the Building Official.
Exception: Homeowner permits as provided per local amendment by added Section
R105.2.4, International Residential Code.
Plumbing Contractors - Plumbing contractors shall be licensed as prescribed by the
State of Texas and shall register their license with the City of College Station before
a plumbing permit is issued by the City.
Air Conditioning, Refrigeration and Heating Contractors - Air Conditioning,
Refrigeration and Heating Contractors shall be licensed by the State of Texas and
shall register their license with the City of College Station before a mechanical
permit is issued by the City.
Licensed Irrigators - Irrigation Contractors shall be licensed Irrigators by the State
of Texas shall register their license with the City of College Station before a lawn
irrigation permit is issued by the City.
ORDINANCE NO. 2022-4352 Page 3 of 54
Electrical Contractors - Electrical Contractors shall be licensed by the State shall
register their license with the City of College Station before an electrical permit is
issued by the City.
Electrical Sign Contractors – Electrical Sign Contractors shall be licensed by the
State shall register their license with the City of College Station before a permit is
issued.
Before any license is registered with the City, the applicant shall have adequate
insurance coverage for general liability as provided for by State law for the
respective trade.
2. Section 105.2 (Work exempt from permit) is amended by deleting item #2 under
“Building” and replacing with the following:
“2. Fences of wood, chain link, or similar material, and less than eight feet in height,
and walls of brick, stone, concrete, or similar material, and less than six feet in
height, shall not be construed to be a structure, nor shall they require a building
permit.
3. Section 105.2 (Work exempt from permit) is amended by adding the following
under
“Electrical”:
Replacing Fuses: No permit shall be required for replacing fuses of like
rating.
Replacing Flush or Snap Switches: No permit shall be required for
replacing flush or snap switches, receptacles, lamp sockets, the installation
of lamps, or minor repairs on permanently connected electrical appliances.
Conveying Signals: No permit shall be required for the installation, main-
tenance or alteration of wiring, poles and down guys, apparatus, devices,
appliances or equipment for telegraph, telephone, signal service or central
station protective service used in conveying signals or intelligence, except
where electrical work is done on the primary side of the source of power at
a voltage over 50 volts and of more than 500 watts.
Wiring by Electric Public Service Company: No permit shall be required
for the installation, maintenance or alteration of electric wiring, apparatus
devices, appliances or equipment to be installed by an electric public service
company for the use of such company in the generation, transmission,
distribution, sale or utilization of electrical energy. However, an electric
public service company shall not do any wiring on a customer's distribution
system, including metering equipment wherever located and transformer
ORDINANCE NO. 2022-4352 Page 4 of 54
vaults in which customer's transformers are located, nor shall any of its em-
ployees do any work other than done for said company as hereinbefore
provided for by virtue of this exception.
Temporary Wiring: No permit shall be required for the installation of
temporary wiring, apparatus, devices, appliances or equipment used by a
recognized electrical training school or college.
Railway Crossing Signal Devices: No permit shall be required for the
installation and maintenance of railway crossing signal devices, when such
is performed by due authority of the railroad and in accordance with the
standards of the American Railroad Association, and in collaboration with
and approval of the Department of Public Services of the City of College
Station.
4. Section 107.1 (General) is amended to include the following at the end of the
section and before the exception: “The design professional shall be an architect or
engineer legally registered and in compliance under the laws of Texas and shall
affix his official seal to the construction documents for the following:
1. All group A, E and I occupancies.
2. Building and structures three or more stories in height
3. Buildings and structures 5,000 square feet or more in total area
Exception: “Group R-3 buildings, regardless of size”
5. Section 109.4 (Work commencing before permit issuance) is amended by deleting
the existing text in its entirety and replacing it with the following:
“Any person who commences any work on a building, structure electrical, gas,
mechanical or plumbing system before obtaining the necessary permits shall be
subject to a penalty of 100% of the usual fee in addition to the required permit fees.”
6. Section 109.6 (Refunds) is amended by deleting the existing text in its entirety and
replacing it with the following:
“The City Manager or his designee is authorized to establish a refund policy.”
7. Section [A] 110.3.1 (Footing and foundation inspection) is amended by adding the
following to the end of said section:
“The Building Official shall have the authority to require a form survey to verify
building setbacks. Such survey shall be provided to the Building Official prior to
ORDINANCE NO. 2022-4352 Page 5 of 54
placement of concrete and prepared by a surveyor licensed to perform work in the
State of Texas.”
8. Section 110.3.6 (Lath and gypsum board inspection) is amended by deleting the
section in its entirety.
9. Section 111.2 (Certificate issued) is amended by deleting items number 4, 5, 7, 10,
and 11.
10. Section 113 (Means of Appeals) is amended by deleting the section in its entirety.
11. Section 116.1 (Unsafe Conditions) is amended by deleting the sentence, “Unsafe
structures shall be taken down and removed or made safe, as the building official
deems necessary and as provided for in this section.” and replacing it with the
following: “Unsafe structures shall be taken down, removed or made safe as
provided for in Section 1 (C), Chapter 3, Code of Ordinances.”
12. Section 202 (Definitions) is amended by adding “Porte-Cocheres”
1. A passageway through a building or screen wall designed to let vehicles pass
from street to an interior courtyard.
2. A roofed structure extending from the entrance of a building over an adjacent
driveway and sheltering those getting in or out of vehicles.
13. Section 202 (Definitions) is amended by deleting the Townhouse definition and
replacing it with the following:
“Townhouse. A single-family dwelling unit constructed in a group of attached units
separated by property lines in which each unit extend from foundation to roof and
with open space on at least two sides.”
14. Section 303.4 (Assembly Group A-3) is amended by adding “tutorial services”.
15. Section 502.1 (Address identification) is amended by deleting the existing text in
its entirety and replacing it with the following:
“502.1 Address identification. An official address, assigned by the Building
Official or his designee, shall be provided and placed pursuant to this section in
such a position as to be clearly visible from the public street or roadway fronting
the property. Addresses placed pursuant to this section shall be a minimum four
(4) inches in height and stroke of minimum one-half (1/2) inch, composed of a
durable material and of a color that provides a contrast to the background itself. The
official address shall be placed a minimum of thirty-six (36) inches and a maximum
of thirty (30) feet in height measured from the ground level. Buildings or structures
located more than fifty (50) feet from the street curb shall have an official address
ORDINANCE NO. 2022-4352 Page 6 of 54
at least five (5) inches in height. Durable materials used for the official address shall
include, but not be limited to, wood, plastic, metal, weather resistant paint, weather
resistant vinyl, or weather resistant material designed for outside use on a glass
surface. For single family residences, the requirement of this section may be met
by providing a minimum of two (2) inch high numbers on both sides of a U. S.
mailbox located near the curb in front of the house, or a freestanding structure with
numbers at least four (4) inches in height.
A building complex composed of multiple structures or dwellings shall have an
official suite or unit number assigned to each building, suite or tenant as well as a
street address number. If there is sufficient street frontage, each building, suite or
tenant may also be assigned an official street address number. The official street
address number of each structure must be prominently posted on the building so
that it is visible from the nearest public street or designated fire lane. Each number
designated by the Building Official, or his designee, for each individual suite or
unit must be conspicuously posted on each suite or unit.
Commercial buildings with side or rear access in addition to the main entrance,
shall also display the business name and official address on each side or rear door
with characters at least two (2) inches in height. Residential structures which
provide for rear vehicular access from a dedicated public alley, street or designated
fire lane shall conspicuously post an official address at least two (2) inches in height
so that it is visible from the public alley, street or designated fire lane.
The owner or manager of a building complex, which contains an enclosed shopping
mall, shall submit to the Fire Official four (4) copies of diagrams acceptable to the
Fire Marshal of the entire complex, indicating the location and number of each
business. When a change in a business name or location is made, the owner or
manager shall so advise the Fire Marshal in writing of the change.
When required by the Fire Code Official, address numbers shall be provided in
additional approved locations to facilitate emergency response.”
16. Table 803.13 (Interior Wall And Ceiling Finish Requirements by Occupancy) is
amended by deleting the existing text in footnote “d” and replacing it with the
following:
“Class A interior finish material shall be required in all areas of all assembly
occupancies, whether sprinklered or not, except as provided for in notes e and f
below.”
17. Section 902.1.2 (Marking on access doors). Is amended by replacing 2 inches with
4 inches.
18. Section 903.1 (General) is amended by adding the following text at the end of said
section:
ORDINANCE NO. 2022-4352 Page 7 of 54
"For the purpose of this section, the term "fire area" shall be replaced with "building
area."
19. Section 903.2 (Where Required) is amended by adding the following text at the
end of the section:
In addition to the requirements of this section, an automatic sprinkler system shall
be provided throughout all new buildings and structures as follows:
1. Where the total building area exceeds 12,000 square feet in area.
2. Where the height exceeds two stories, regardless of area.
20. Section 903.2.1.6 (Assembly Occupancies on Roofs) is amended by deleting the
exception in its entirety.
21. Section 903.2.3 (Group E) is amended by deleting the exception in its entirety.
22. Section 903.2.4 (Group F-1) is amended by deleting items "2" and "3."
23. Section 903.2.4.2 (Group F-1 distilled spirits) is amended to add: An automatic
sprinkler system shall be provided throughout a Group F-1 fire area used for the
manufacture of distilled spirits involving more than 120 gallons of distilled spirits
(>16% alcohol) in the fire area at any one time.
24. Section 903.2.7 (Group M) No. 2 is amended by replacing "three stories above
grade" with "two stories in height" and by deleting No. 3 in its entirety.
25. Section 903.2.8 (Group R) is amended by deleting the section in its entirety.
26. Section 903.2.9 (Group S-1) is amended by replacing "three stories above grade"
with "two stories above grade" in item "2" and by replacing "24,000 square feet"
with "12,000 square feet" in item "3."
27. Section 903.2.9.3 (Group S-1 Distilled spirits or wine) is amended to add: An
automatic sprinkler system shall be provided throughout a Group F-1 fire area used
for the manufacture of distilled spirits involving more than 120 gallons of dist illed
spirits (>16% alcohol) in the fire area at any one time.
28. Section 903.2.10 (Group S-2 Parking Garage) is amended by deleting the
exception in its entirety.
27. Section 903.2.13 (Porte-cocheres). All porte-cocheres shall be protected with fire
sprinklers.
ORDINANCE NO. 2022-4352 Page 8 of 54
Exception: Porte-cocheres of non-combustible construction or a distance of 10 foot
or greater.
29. Section 903.3.1.1.1 (Exempt locations) is amended by deleting item number 4.
30. Section 903.3.1.2.2 (Corridors and balconies in the means of egress) is amended as
follows:
903.3.1.2.2 (Corridors and balconies in the means of egress). Sprinkler protection
shall be provided in all corridors and for all balconies in the means of egress.
31. Section 903.3.1.2.3 (Attics). is amended by deleting items 3.4 and 4.5
32. Section 903.4 (Sprinkler systems supervision and alarms) is amended by adding
the following:
Exceptions: 9. Valves located outside buildings or in a vault that are sealed or
locked in the open position.
33. Section 904.3.5, (Monitoring). is amended by deleting the section and replacing it
with:
904.3.5 (Monitoring). All automatic fire extinguishing system shall be monitored
with a system in accordance with NFPA 72.
34. Section 905.1, (General). is amended by adding Section 905.1.1, Safety factor, as
follows:
905.1.1 (Safety factor). All standpipe systems with the exception of manual
standpipes shall be designed with a minimum safety factor of 5 PSI or 10% of
required pressure (whichever is greater) taken at the source for the hydraulically
most demanding system and/or outlet.
35. Section 905.4, (Location of Class I standpipe hose connections), is amended as
follows with all other code text to remain as written:
905.4 (Location of Class I standpipe hose connections). Class I standpipe hose
connections shall be provided in all of the following locations:
1. In every required interior exit stairway, a hose connection shall be provided
for each story above and below grade plane. Hose connections shall be
located at [the main] an intermediate [floor] landing between stories unless
otherwise approved by the fire code official.
ORDINANCE NO. 2022-4352 Page 9 of 54
Exception: A single hose connection shall be permitted to be installed in the open
corridor or open breezeway between open stairs that are not greater than 75 feet (22
860 mm) apart.
36. Section 906.1 (Where required) is amended by deleting exception 1 and 2 all others
remain the same.
37. Section 907.2.1 (Group A) is amended by adding the following section:
907.2.1.3 Group A-2. An automatic alarm system shall be provided for fire areas
containing Group A-2 occupancies that have an occupant load of 100 or more.
38. Section 907.2.7.1, (Occupant notification). is repealed in its entirety.
39. Section 907.2.8.2, (Automatic smoke detection system), is hereby amended to read
as follows:
907.2.8.2 (Automatic smoke detection system). An automatic smoke detection
system that activates the occupant notification system in accordance with Section
907.5 shall be installed throughout all interior corridors serving sleeping units. The
automatic smoke detection system requirement is met only by the installation of
smoke or beam detectors whenever possible. If environmental conditions do not
allow the installation of smoke detectors, fire alarm heat detectors may be used on
a limited basis when approved by the fire code official.
Exception: An automatic smoke detection system is not required in buildings that
do not have interior corridors serving sleeping units and where each sleeping unit
has a means of egress door opening directly to an exit or to an exterior exit access
that leads directly to an exit.
Exception: An automatic smoke detection system is not required in buildings that
do not have interior corridors serving sleeping units and where each sleeping unit
has a means of egress door opening directly to an exit or to an exterior exit access
that leads directly to an exit.
40. Section 907.2.12.2, (System response), is hereby deleted in its entirety.
41. Section 907.2.12.1.2, (Duct smoke detection), is amended to read as follows:
907.2.12.1.2 (Duct smoke detection). Duct smoke detectors complying with
Section 907.3.1 shall be located in accordance with the NFPA 90A: Standard for
the Installation of Air-Conditioning and Ventilating Systems or as follows:
1. In the main return air and exhaust air plenum of each air-conditioning
system having a capacity greater than 2,000 cubic feet per minute (cfm)
ORDINANCE NO. 2022-4352 Page 10 of 54
(0.94 m3/s). Such detectors shall be located in a serviceable area
downstream of the last duct inlet.
2. At each connection to a vertical duct or riser serving two or more stories
from a return air duct or plenum of an air-conditioning system. In Group R-
1 and R-2 occupancies, a smoke detector is allowed to be used in each return
air riser carrying not more than 5,000 cfm (2.4 m3/s) and serving not more
than 10 air-inlet openings.
42. Section 907.2, (Where required) - new buildings and structures, is amended by
adding Section 907.2.24, Fire alarm systems for property protection, to read as
follows:
907.2.24 (Fire alarm systems for property protection). Fire alarm systems dedicated
solely to the protection of property are permitted to be installed in facilities where
a fire alarm system is not required by other sections of this code or the International
Building Code provided the following conditions are met:
1. Any and all automatic detection is installed, located and maintained in
accordance with the requirements of NFPA 72 and a documentation cabinet
as required by NFPA 72 is provided and installed.
2. The installed system is monitored by a supervising station which provides
remote and central station service.
3. One manual means of activation is installed in an approved location
4. Where the fire alarm system control unit is located in an area that is not
readily accessible to response personnel, a remote fire alarm system
annunciator panel is installed.
43. Section 907.2, (Where Required) – is amended by adding Section 907.2.25, Fire
alarm systems for property protection, to read as follows:
907.2.25 (Group R-4) Fire alarm systems and smoke alarms shall be installed in
Group R-4 occupancies as required in Sections 907.2.10.1 through 907.2.10.3.
Section 907.2.10.1 Manual fire alarm system. A manual fire alarm system that
activates the occupant notification system in accordance with Section 907.5 shall
be installed in Group R-4 occupancies.
Exceptions:
1. A manual fire alarm system is not required in buildings not more than two
stories in height where all individual sleeping units and contiguous attic and
crawl spaces to those units are separated from each other and public or
ORDINANCE NO. 2022-4352 Page 11 of 54
common areas by not less than 1-hour fire partitions and each individual sleeping
unit has an exit directly to a public way, egress court or yard.
2. Manual fire alarm boxes are not required throughout the building where all
of the following conditions are met:
2.1. The building is equipped throughout with an automatic sprinkler system
installed in accordance with Section 903.3.1.1 or 903.3.1.2.
2.2. The notification appliances will activate upon sprinkler water flow.
2.3. Not fewer than one manual fire alarm box is installed at an approved
location.
3. Manual fire alarm boxes in resident or patient sleeping areas shall not be
required at exits where located at all nurses’ control stations or other
constantly attended staff locations, provided such stations are visible and
continuously accessible and that the distances of travel required in Section
907.4.2.1 are not exceeded.
907.2.10.2 Automatic smoke detection system. An automatic smoke
detection system that activates the occupant notification system in
accordance with Section 907.5 shall be installed in corridors, waiting areas
open to corridors and habitable spaces other than sleeping units and
kitchens.
Exceptions:
1. Smoke detection in habitable spaces is not required where the facility is
equipped throughout with an automatic sprinkler system installed in
accordance with Section 903.3.1.1.
2. An automatic smoke detection system is not required in buildings that do
not have interior corridors serving sleeping units and where each sleeping
unit has a means of egress door opening directly to an exit or to an exterior
exit access that leads directly to an exit.
907.2.10.3 Smoke alarms. Single- and multiple-station smoke alarms shall
be installed in accordance with Section 907.2.11.
44. Section 907.3.1, (Duct smoke detectors), is amended to read as follows:
907.3.1 (Duct smoke detectors). Smoke detectors installed in ducts shall be listed
for the air velocity, temperature and humidity present in the duct. Duct smoke
detectors shall be connected to the building's fire alarm control unit where a fire
alarm system is required by Section 907.2. Activation of a duct smoke detector shall
ORDINANCE NO. 2022-4352 Page 12 of 54
initiate a visible and audible supervisory signal at a Central monitoring station and
shall perform the intended fire safety function in accordance with this code, NFPA
90A: Standard for the Installation of Air-Conditioning and Ventilating Systems and
the International Mechanical Code. In facilities that are required to be monitored
by a supervising station, duct smoke detectors shall report only as a supervisory
signal and not as a fire alarm. They shall not be used as a substitute for required
open area detection. 2021 International Building-Related Codes
Exceptions:
1. In occupancies not required to be equipped with a fire alarm system,
actuation of a smoke detector shall activate a visible and an audible signal
in an approved location. Smoke detector trouble conditions shall activate a
visible or audible signal in an approved location and shall be identified as
air duct detector trouble.
2. For fire alarm systems which cannot be programmed for supervisory
signals, duct detectors shall be allowed to activate the alarm signal.
45. Section 907.3., (Fire safety functions), is amended by adding 907.3.5, Fire alarm
systems - emergency control, as follows:
907.3.5 (Fire alarm systems - emergency control). At a minimum, the following
functions, where provided, shall be activated by the fire alarm system:
1. Elevator capture and control in accordance with ASME/ANSI A17.1b,
Safety Code for Elevators and Escalators.
2. Release of automatic door closures and hold open devices
3. Stairwell and/or elevator shaft pressurization.
4. Smoke management and/or smoke control systems.
5. Initiation of automatic fire extinguishing equipment.
6. Emergency lighting control.
7. Unlocking of doors.
8. Emergency shutoff of gas and fuel supplies that may be hazardous provided
the continuation of service is not essential to the preservation of life.
9. Emergency shutoff of audio systems for sound reinforcement or
entertainment (i.e. music systems, systems for announcement and
ORDINANCE NO. 2022-4352 Page 13 of 54
broadcast which are separate from public address systems) provided that
such systems are not used to issue emergency instructions.
10. Emergency shutoff of systems used for the creation of displays or special
effects (i.e. lighting effects, laser light shows, projection equipment).
46. Section 907.4.2.1, (Location), is amended to add the Exception to read as follows:
907.4.2.1 (Location). Manual fire alarm boxes shall be located not more than 5 feet
(1524 mm) from the entrance to each exit. In buildings not protected by an
automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2,
additional manual fire alarm boxes shall be located so that the distance of travel to
the nearest box does not exceed 200 feet (60 960 mm).
Exception: Where construction of the building prohibits the proper installation of a
pull station (e.g. glass walls, interior brick or rock walls), a pull station shall be
allowed to be located in the normal path of egress, where approved by the Fire
Marshal or his/her designee.
47. Section 907.5.1.1, (Presignal feature), is amended to read as follows:
907.5.1.1 (Presignal feature and positive alarm sequences). A presignal feature or
Positive Alarm Sequence as defined in NFPA 72 shall not be installed unless
approved by the fire code official. Request to use a presignal feature or a Positive
Alarm Sequence must be submitted in writing to the Fire Marshal and approval
granted before installation. Where a presignal feature or Positive Alarm Sequence
is provided, a signal shall be annunciated at a constantly attended location approved
by the fire code official, so that occupant notification can be activated in 2018
International Building-Related Codes the event of fire or other emergency. When
approved by the fire code official, the presignal feature or Positive Alarm Sequence
shall be implemented in accordance with the requirements of NFPA 72.
48. Section 907.5.2.1, (Audible alarms), is amended by adding Section 907.5.2.1.4,
Testing of audible alarms in occupancies other than Group R, and Section
907.5.2.1.5, Testing of audible alarms in Group R occupancies, as follows:
907.5.2.1.4 (Testing of audible alarms in occupancies other than Group R).
Audibility levels for all occupancies other than Group R shall be in accordance with
the public mode requirements of NFPA 72, and shall be tested utilizing the
following criteria:
1. A UL listed sound pressure level meter, which has been calibrated within
the last calendar year, and supplied by the fire alarm system installing
contractor, shall be utilized to obtain readings. The sound pressure level
meter will be held five feet above floor, pointed in the direction of the
audible device.
ORDINANCE NO. 2022-4352 Page 14 of 54
2. All doors within the occupancy, including the bathroom and balcony doors
shall be in the closed position.
3. Measurements shall be taken in the most remote areas of the occupancy
first, including bathrooms and balconies.
4. Initial measurements to confirm the average ambient sound level in each
area shall be taken.
5. The fire alarm system shall be activated and measurements in the tested
areas shall be retaken and compared with the requirements.
907.5.2.1.5 (Testing of audible alarms in Group R occupancies). Audibility levels
for all Group R occupancies shall be in accordance with the requirements of Section
907.5.2.1.1, and shall be tested utilizing the following criteria:
1. A UL listed sound pressure level meter, which has been calibrated within
the last calendar year, and supplied by the fire alarm system installing
contractor, shall be utilized to obtain readings. The sound pressure level
meter will be held five feet above floor, pointed in the direction of the
audible device.
2. All doors within the occupancy, including the bathroom and balcony doors
shall be in the closed position.
3. Ambient sound level shall be established with the television set at 50% of
maximum volume, showers running, bathroom exhaust systems running,
and air conditioning units running.
4. Measurements shall be taken in the most remote area of the dwelling or
sleeping unit first, including bathrooms and balconies.
5. Initial measurements to confirm the ambient sound level in each area shall
be taken.
6. The fire alarm system shall be activated and measurements in the tested
areas shall be retaken and compared with the requirements.
49. Section 907.5.2.2, (Emergency voice/alarm communication systems), is amended
to read as follows:
907.5.2.2 (Emergency voice/alarm communication systems). Emergency
voice/alarm communication systems required by this code shall be designed and
installed in accordance with NFPA 72. The operation of any automatic fire detector,
sprinkler waterflow device or manual fire alarm box shall automatically sound an
alert tone followed by voice instructions giving approved information and
ORDINANCE NO. 2022-4352 Page 15 of 54
directions for a general or staged evacuation in accordance with the building's fire
safety and evacuation plans required by Section 404 of the International Fire Code.
In high-rise buildings, the system shall operate on at least the alarming floor, the
floor above and the floor below. If the system is not reset after five minutes, the
building shall sound the general evacuation signal 2021 International Building-
Related Codes and message in all zones unless an alternative Positive Alarm
Sequence has been approved by the Fire Marshal. Speakers shall be provided
throughout the building by paging zones. At a minimum, paging zones shall be
provided as follows:
1. Elevator groups.
2. Interior exit stairways.
3. Each floor.
4. Areas of refuge as defined in Chapter 2.
Exception: In Group I-1 and I-2 occupancies, the alarm shall sound in a constantly
attended area and a general occupant notification shall be broadcast over the
overhead page.
50. Section 907.5.2.2.4, (Emergency voice/alarm communication captions), is repealed
in its entirety.
51. Section 907.5.2.3, (Visible alarms), is amended by adding a subsection 907.5.2.3.4,
Group R-2 sleeping areas, and Section 907.5.2.3.5, Combination devices, to read
as follows:
907.5.2.3.4 (Group R-2 sleeping areas). Living rooms in Group R-2 occupancies
shall have audible notification appliances that meet the sleeping area audible
requirements of NFPA 72, Chapter 18, Section 18.4.5, and Subsection 18.4.5.1.
When such units are required to be equipped with visible notification for the hearing
impaired or when such units are designated as accessible in accordance with
ICC/ANSI A117.1, combination audible and visible notification appliances that
meet both the sleeping area audible requirements of NFPA 72, Chapter 18, Section
18.4.5, Subsection 18.4.5.1 and the effective intensity settings of NFPA 72, Chapter
18.5.5.7.2 shall be installed.
907.5.2.3.5 (Combination devices). Combination 120 VAC single or multiple-
station smoke detectors with an onboard visible notification appliance if utilized to
meet the requirements of Section 907.2.11, will not be given credit for meeting the
visible alarm notification requirements of Section 907.5.2.3.3 if these devices do
not have the capability of supplying backup power for the visible notification
appliance portion of the device. Should such devices be utilized to comply with
Section 907.2.11, the visible appliance side of the device shall flash in
synchronization with the notification appliances required in the unit.
ORDINANCE NO. 2022-4352 Page 16 of 54
52. Section 907.5.2.3.1 (Public Use Areas and Common Use Areas) is amended by
deleting the exception and adding Section 907.5.2.3.1.1 to read as follows:
Section 907.5.2.3.1.1 (Employee Work Areas). Where a fire alarm and detection
system is required, employee work areas shall be provided with devices that provide
audible and visible alarm notification.
53. Section 907.6.3, (Initiating device identification), is amended to read as follows
with exceptions to remain as written:
907.6.3 (Initiating device identification). The fire alarm system shall identify the
specific initiating device address, location, device type, and floor level where
applicable and status including indication of normal, alarm, trouble and supervisory
status, to the fire alarm panel, annunciator panel and to the supervising station as
appropriate.
54. Section 912, (Fire Department Connections), is amended by adding Section 912.8,
Location and type, as follows:
912.8 (Location and type). Sprinkler system and standpipe fire department hose
connections shall be as follows:
1. Within 40 feet of a public street, approved fire lane, or access roadway.
2. Within 100 feet of an approved fire hydrant measured per hose lay.
3. All structures are required to have a five inch “Storz” connection.
a. Where provided, the five inch “Storz” inlet shall be installed at a 30-
degree angle pointing down.
i. Exception: NFPA 13R system requiring less than 250 gpm.
4. Minimum of two feet above finished grade and a maximum of four feet
above finished grade for standard inlets and minimum of 30 inches at lowest
point above finished grade and maximum of four feet above finished grade
for the five inch "Storz" inlet.
5. Freestanding FDCs shall be installed a minimum of one foot and a
maximum of seven feet from the gutter face of the curb.
6. The Fire Code Official shall approve the location of freestanding fire
department connections. Freestanding FDCs must be physically protected
against impact per the requirements of Section 312 or other approved
means.
ORDINANCE NO. 2022-4352 Page 17 of 54
7. Fire department connections for H occupancies shall be freestanding,
remote and located as determined by the fire code official.
8. Fire department connections for systems protecting fuel storage tanks shall
be freestanding, remote and located as determined by the fire code official.
9. No FDC is required for projects designed per NFPA 13D.
55. Section 912.2.1, (Visible location), is amended by adding the following sentence
to the end of that section to read as follows:
912.2.1 (Visible location). Fire department connections shall be located on the
street side of buildings or facing approved fire apparatus access roads, fully visible
and recognizable from the street, fire apparatus access road or nearest point of fire
department vehicle access or as otherwise approved by the fire code official. The
fire department connection shall be identified by a sign installed above the
connection with the letters “FDC” not less than 6 inches high and mounted at least
3 feet above the FDC to the bottom edge of the sign unless approved by the fire
code official and if multiple FDC’s a sign identifying the corresponding riser.
56. Section 912.2.2, (Existing buildings), is amended to read as follows:
912.2.2 (Existing buildings). On existing buildings, wherever the fire department
connection is not visible to approaching fire apparatus, the fire department
connection shall be indicated by an approved sign mounted on the street front or on
the side of the building. Such sign shall have the letters “FDC” not less than 6 inches
(152 mm) high and words in letters not less than 2 inches (51 mm) high or an arrow
to indicate the location. Signs shall be mounted no lower than 7 feet from grade to
the bottom edge of the sign and are subject to the approval of the fire code official.
57. Section 912.2 (Location), is amended to add the following:
Section 912.2.3 (Distance). Fire department connection shall not be located further
than 100 feet from the fire hydrant measured by lay of hose from the engine.
58. Section 912.4.1, (Locking fire department connection caps), is amended to read as
follows:
912.4.1 (Locking fire department connection caps). Locking caps are required on
all fire department connections for water-based fire protection systems including
but not limited to FDC’s and standpipes.
59. Section 1004.5.1 (Increased occupant load) is amended by deleting the section in
its entirety.
ORDINANCE NO. 2022-4352 Page 18 of 54
60. Section 1004.9 (Posting of occupant load) is amended by adding the following text
to the end of said section:
“For the purposes of this section, the occupant load shall be the number of
occupants computed at the rate of one occupant per unit of area as prescribed in
Table 1004.5.”
61. Section 1612.3 (Establishment of flood hazard areas) is amended by inserting
“Brazos County” for name of jurisdiction and “July 2, 1992 or February 9, 2000”
for the date of issuance.
62. Section 1907 (Minimum slab provisions) is amended by adding Section 1907.2 to
read as follows:
“Section 1907.2 Minimum foundation standard. All slabs-on-grade with turned-
down footings shall comply with the Minimum Foundation Standard as shown in
figure 1.”
ORDINANCE NO. 2022-4352 Page 19 of 54
1. APPENDIX D (FIRE DISTRICTS) is hereby adopted.
ORDINANCE NO. 2022-4352 Page 20 of 54
Sec. 103-133. - Fire limits.
The fire district referenced in any code or ordinance adopted by the City shall be construed to be
the following described area.
1. Beginning at the south corner of Farm Highway No. 60 and Old Highway No. 6, Block
8 Boyett Addition;
Thence northeast along center of Farm Highway No. 60 through Blocks 8,1, and 2 to
east corner of Tauber Street and Farm Highway No. 60;
Thence northwest approximately 189 feet;
Thence southwest to east corner of Block 1, Lot 21, to corner of Main and Patricia
Streets;
Thence northwest approximately 50 feet;
Thence southwest approximately 190 feet which includes Lots 21 to 26 inclusive, also
Block 1, Boyett Addition;
Thence northwest approximately 150 feet to the Church Avenue;
Thence southwest approximately 52 feet to Patricia Street which includes Lots 18 to 27
and 28, Block 1, Boyett Addition;
Thence southwest on Patricia Street to Old Highway No. 6;
Thence southeast approximately 200 feet along center of Old Highway No. 6 to the place
of beginning.
2. Save and except the area described as follows:
Beginning at the intersection of the northwest right-of-way line of the University Drive
and the northeast right-of-way line of Boyett Street;
Thence northwest along the northeast right-of-way line of Boyett Street to the southeast
right-of-way line of Patricia Street;
Thence northeast along the southeast right-of-way line of Patricia Street approximately
235 feet;
Thence southeast through Lot. No. 11, Block No. 1, Boyett addition, 25 feet from and
parallel to the line between Lot No. 11 and Lot No. 12 to the northwest right-of-way
line of University Drive;
ORDINANCE NO. 2022-4352 Page 21 of 54
Thence southwest along the northwest right-of-way line of University Drive to the place
of beginning and being all of Lot No. 13, all of Lot No. 12, and the southwest 25 feet of
Lot No. 11, Block No. 1, Boyett Addition.
3. Beginning at the corner of George Bush Drive and Montclair Street, Block 8, West
Park Addition;
Thence southwest along centerline to Highlands Street, which includes Lots 1 to 13
inclusive;
Thence southeast along centerline of Highlands Street, 100 feet to alley;
Thence northeast to east corner of Lot No. 1, Block No. 8, Montclair Avenue;
Thence northwest 100 feet to place of beginning.
ORDINANCE NO. 2022-4352 Page 22 of 54
Sec. 103-134. – Amendments to the International Residential Code.
The International Residential Code adopted by reference in Section 101.2, 2021 International
Building Code, is hereby amended as follows:
1. Section R102.4 (Referenced codes and standards) is amended by adding the
following to said section:
“Any reference to the ICC Electrical Code shall mean the National Electrical Code, as
adopted and amended by the City of College Station.”
2. Section R105.2 (Work exempt from permit) is amended by deleting number one
under “Building” and replacing it with the following:
“1. One detached accessory structure per residential lot, provided the floor area does not
exceed 120 square feet and the structure complies with all of the following:
a. The accessory structure is not located in a surface drainage easement.
b. The accessory structure is not permanently affixed to the ground.
c. The accessory structure is located in the rear yard.
d. The accessory structure is not provided with utilities (sewer, water, gas or
electricity).”
3. Section R105.2 (Work exempt from permit) is amended by deleting number ten under
“Building” and replacing with the following:
“10. Uncovered decks, patios or other raised floor surfaces located not more than 30
inches above adjacent grade and are not attached to a dwelling.”
4. Section R105.2.4 is added to read as follows:
“R105.2.4 Homeowner permit. A property owner may obtain a building permit to
perform work on a building owned and occupied by him as his homestead without
registering with the City as a contractor. However, work involving the electrical,
plumbing and mechanical systems must be permitted and installed by licensed
contractors.”
5. Section R106.3.1 (Approval of construction documents) is amended by deleting the
last sentence in said section.
6. Section R108.3 (Building permit valuations) is amended by adding the following to
said section:
“If, in the opinion of the building official, the valuation is underestimated on the
application, the permit shall be denied, unless the applicant can show detailed estimates
ORDINANCE NO. 2022-4352 Page 23 of 54
to meet the approval of the building official. Final permit valuation shall be set by the
building official.”
7. Section R108.5 (Refunds) is amended by deleting the text in said section and replacing
it with the following:
“The City Manager or his designee is authorized to establish a refund policy.”
8. Section R109.1.1 (Foundation Inspection) is amended by adding the following to the
end of said section:
“The Building Official shall have the authority to require a form survey to verify
building setbacks. Such survey shall be provided to the Building Official prior to
placement of concrete and prepared by a surveyor licensed to perform work in the State
of Texas.”
9. Section R112 (Board of Appeals) is amended by deleting the section in its entirety.
10. Section R202 (Definitions) is also amended by adding the following definitions:
Air Gap, Irrigation System. A complete physical separation between the free flowing
discharge end of a potable water supply pipeline and an open or non-pressure receiving
vessel.
Atmospheric Vacuum Breaker. An assembly containing an air inlet valve, a check
seat, and an air inlet port. The flow of water into the body causes the air inlet valve to
close the air inlet port. When the flow of water stops the air inlet valve falls and forms
a check against back-siphonage. At the same time it opens the air inlet port allowing air
to enter and satisfy the vacuum. Also known as an Atmospheric Vacuum Breaker Back-
Siphonage Prevention Assembly.
Backflow Prevention, Irrigation System. The mechanical prevention of reverse flow,
or back siphonage, of nonpotable water from an irrigation system into the potable water
source.
Backflow Prevention Assembly. Any assembly used to prevent backflow into a potable
water system. The type of assembly used is based on the existing or potential degree of
health hazard and backflow condition.
Completion of Irrigation System Installation. When the landscape irrigation system
has been installed, all minimum standards met, all tests performed, and the irrigator is
satisfied that the system is operating correctly.
Consulting, Irrigation System. The act of providing advice, guidance, review or
recommendations related to landscape irrigation systems.
ORDINANCE NO. 2022-4352 Page 24 of 54
Cross-Connection. An actual or potential connection between a potable water source
and an irrigation system that may contain contaminates or pollutants or any source of
water that has been treated to a lesser degree in the treatment process.
Design, Irrigation System. The act of determining the various elements of a landscape
irrigation system that will include, but not be limited to, elements such as collecting site
specific information, defining the scope of the project, defining plant watering needs,
selecting and laying out emission devices, locating system components, conducting
hydraulics calculations, identifying any local regulatory requirements, or scheduling
irrigation work at a site. Completion of the various components will result in an
irrigation plan.
Design Pressure, Irrigation System. The pressure that is required for an emission
device to operate properly. Design pressure is calculated by adding the operating
pressure necessary at an emission device to the total of all pressure losses accumulated
from an emission device to the water source.
Double Check Valve. An assembly that is composed of two independently acting,
approved check valves, including tightly closed resilient seated shutoff valves attached
at each end of the assembly and fitted with properly located resilient seated test cocks.
Also known as a Double Check Valve Backflow Prevention Assembly.
Emission Device. Any device that is contained within an irrigation system and that is
used to apply water. Common emission devices in an irrigation system include, but are
not limited to, spray and rotary sprinkler heads, and drip irrigation emitters.
Employed, Irrigation Systems. Engaged or hired to provide consulting services or
perform any activity relating to the sale, design, installation, maintenance, alteration,
repair, or service to irrigation systems. A person is employed if that person is in an
employer-employee relationship as defined by Internal Revenue Code, 26 United States
Code Service, §3212(d) based on the behavioral control, financial control, and the type
of relationship involved in performing employment related tasks.
Head-to-Head Spacing, Irrigation System. The spacing of spray or rotary heads equal
to the manufacturer’s published radius of the head.
Health Hazard, Irrigation System. A cross-connection or potential cross-connection
with an irrigation system that involves any substance that may, if introduced into the
potable water supply, cause death or illness, spread disease, or have a high probability
of causing such effects.
Hydraulics. The science of dynamic and static water; the mathematical computation of
determining pressure losses and pressure requirements of an irrigation system.
Installer, Irrigation System. A person who actually connects an irrigation system to a
private or public raw or potable water supply system or any water supply, who is
licensed according to Title 30, Texas Administrative Code, Chapter 30 (relating to
Occupational Licenses and Registrations).
ORDINANCE NO. 2022-4352 Page 25 of 54
Irrigation Inspector. A person who inspects irrigation systems and performs other
enforcement duties for a municipality or water district as an employee or as a contractor
and is required to be licensed under Title 30, Texas Administrative Code, Chapter 30
(relating to Occupational Licenses and Registrations).
Irrigation Plan. A scaled drawing of a landscape irrigation system which lists required
information, the scope of the project, and represents the changes made in the installation
of the irrigation system.
Irrigation Services. Selling, designing, installing, maintaining, altering, repairing,
servicing, permitting, providing consulting services regarding, or connecting an
irrigation system to a water supply.
Irrigation System. An assembly of component parts, including the backflow device and
all equipment downstream, that is permanently installed for the controlled distribution
and conservation of water to irrigate any type of landscape vegetation in any location,
and/or to reduce dust or control erosion. This term does not include a system that is used
on or by an agricultural operation as defined by Texas Agricultural Code, §251.002.
Irrigation Technician. A person who works under the supervision of a licensed
irrigator to install, maintain, alter, repair, service or supervise installation of an irrigation
system, including the connection of such system in or to a private or public, raw or
potable water supply system or any water supply, and who is required to be licensed
under Title 30, Texas Administrative Code, Chapter 30 (relating to Occupational
Licenses and Registrations).
Irrigation Zone. A subdivision of an irrigation system with a matched precipitation rate
based on plant material type (such as turf, shrubs, or trees), microclimate factors (such
as sun/shade ratio), topographic features (such as slope) and soil conditions (such as
sand, loam, clay, or combination) or for hydrological control.
Irrigator. A person who sells, designs, offers consultations regarding, installs,
maintains, alters, repairs, services or supervises the installation of an irrigation system,
including the connection of such system to a private or public, raw or potable water
supply system or any water supply, and who is required to be licensed under Title 30,
Texas Administrative Code, Chapter 30.
Irrigator-in-Charge. The irrigator responsible for all irrigation work performed by an
exempt business owner, including, but not limited to obtaining permits, developing
design plans, supervising the work of other irrigators or irrigation technicians, and
installing, selling, maintaining, altering, repairing, or servicing a landscape irrigation
system.
Landscape Irrigation. The science of applying the necessary amount of water to
promote or sustain healthy growth of plant material or turf.
Irrigation License. An occupational license that is issued by the Texas Commission on
Environmental Quality under Title 30, Texas Administrative Code, Chapter 30 to an
ORDINANCE NO. 2022-4352 Page 26 of 54
individual that authorizes the individual to engage in an activity that is covered by Title
30, Texas Administrative Code, Chapter 30.
Mainline, Irrigation System. A pipe within an irrigation system that delivers water
from the water source to the individual zone valves.
Maintenance Checklist, Irrigation System. A document made available to the
irrigation system’s owner or owner’s representative that contains information regarding
the operation and maintenance of the irrigation system, including, but not limited to:
checking and repairing the irrigation system, setting the automatic controller, checking
the rain or moisture sensor, cleaning filters, pruning grass and plants away from
irrigation emitters, using and operating the irrigation system, the precipitation rates of
each irrigation zone within the system, any water conservation measures currently in
effect from the water purveyor, the name of the water purveyor, a suggested seasonal or
monthly watering schedule based on current evapotranspiration data for the geographic
region, and the minimum water requirements for the plant material in each zone based
on the soil type and plant material where the system is installed.
Major Maintenance, Alteration, Repair, or Service (Irrigation System). Any
activity that involves opening to the atmosphere the irrigation main line at any point
prior to the discharge side of any irrigation zone control valve. This includes, but is not
limited to, repairing or connecting into a main supply pipe, replacing a zone control
valve, or repairing a zone control valve in a manner that opens the system to the
atmosphere.
Master Valve, Irrigation System. A remote control valve located after the backflow
prevention device that controls the flow of water to the irrigation system mainline.
Matched Precipitation Rate. The condition in which all sprinkler heads within an
irrigation zone apply water at the same rate.
New Installation, Irrigation System. An irrigation system installed at a location where
one did not previously exist.
Pass-through Contract. A written contract between a contractor or builder and a
licensed irrigator or exempt business owner to perform part or all of the irrigation
services relating to an irrigation system.
Pressure Vacuum Breaker. An assembly containing an independently operating
internally loaded check valve and an independently operating loaded air inlet valve
located on the discharge side of the check valve. Also known as a Pressure Vacuum
Breaker Back-siphonage Prevention Assembly.
Reclaimed Water. Domestic or municipal wastewater which has been treated to a
quality suitable for beneficial use, such as landscape irrigation.
ORDINANCE NO. 2022-4352 Page 27 of 54
Records of Landscape Irrigation Activities. The irrigation plans, contracts, warranty
information, invoices, copies of permits, and other documents that relate to the
installation, maintenance, alteration, repair, or service of a landscape irrigation system.
Reduced Pressure Principle Backflow Prevention Assembly. An assembly
containing two independently acting approved check valves together with a
hydraulically operating mechanically independent pressure differential relief valve
located between the two check valves and below the first check valve.
Static Water Pressure. The pressure of water when it is not moving.
Supervision, Landscape Irrigation. The on-the-job oversight and direction by a
licensed irrigator who is fulfilling his or her professional responsibility to the client
and/or employer in compliance with local or state requirements. Also a licensed installer
working under the direction of a licensed irrigator or an irrigation technician who is
working under the direction of a licensed irrigator to install, maintain, alter, repair or
service an irrigation system.
Water Conservation, Irrigation System. The design, installation, service, and
operation of an irrigation system in a manner that prevents the waste of water, promotes
the most efficient use of water, and applies the least amount of water that is required to
maintain healthy individual plant material or turf, reduce dust, and control erosion.
Zone Flow. A measurement, in gallons per minute or gallons per hour, of the actual
flow of water through a zone valve, calculated by individually opening each zone valve
and obtaining a valid reading after the pressure has stabilized. For design purposes, the
zone flow is the total flow of all nozzles in the zone at a specific pressure.
Zone Valve, Irrigation System. An automatic valve that controls a single zone of a
landscape irrigation system.
11. Section R302.1 (Exterior walls) is amended by deleting the existing text and replacing
it with the following:
R302.1 Exterior walls. Exterior walls with a fire separation distance less than 3 feet
shall have not less than a one hour fire-resistive rating with exposure from both sides.
The above provisions shall not apply to walls which are perpendicular to the line used
to determine the fire separation distance.
Exception: Tool and storage sheds, playhouses and similar structures exempted from
permits by Section R105.2 are not required to provide wall protection based on location
on the lot.
Projections. Projections may extend beyond the exterior wall on zero lot line
construction. Projections shall be constructed from non-combustible material on the
underside and may allow manufactured perforated soffit material installed for attic
ORDINANCE NO. 2022-4352 Page 28 of 54
ventilation.. The soffit may project a maximum of 18 inches, excluding non-
combustible gutters, over the adjacent property line.
Exception: Tool and storage sheds, playhouses and similar structures exempted from
permits by Section R 105.2 shall not extend over the lot line in zero lot line construction.
Combustibles in maintenance easement. The construction of any structure utilizing
combustible material or the storage of combustible material is prohibited within the
maintenance easement. The term “maintenance easement” is defined in Article 11 of the
UDO.
Exception: A wood fence may be installed in the maintenance easement.
12. Section R302.6 (Dwelling-garage fire separation) is amended by adding the following
exception:
Exception: One unprotected attic access opening, not exceeding 30 inches by 54 inches
in size, is allowed per garage.
13. Section R310.2.1 (Minimum size) is amended by deleting this section in its entirety.
14. Section R311.7.8.4 (Continuity) is amended by deleting the following text in said
section:
“Handrail ends shall be returned or shall terminate in newel posts or safety terminals.”
15. Section R313 (Automatic Fire Sprinkler Systems) is amended by deleting the section
in its entirety.
16. Section R318.2 (Chemical termiticide treatment) is amended by adding the following
to the end of said section:
“The method of application and contractor hired to apply the chemicals shall submit to
the Building Department when applying for the Building Permit, and verification of the
application turned in prior to issuance of the Certificate of Occupancy.”
17. Section R319.1 (Address Identification) is amended by deleting the existing text in its
entirety and replacing it with the following:
“Premises identification shall comply with Section 502.1, International Building Code,
as amended.”
18. Section 322.2.1 (Elevation requirements) is amended by deleting the existing text,
save the exception, and replacing it with the following:
ORDINANCE NO. 2022-4352 Page 29 of 54
“1. Buildings and structures shall have the lowest floors elevated in accordance with the
City of College Station Code of Ordinances, Chapter 13 (Flood Hazard Protection) and
the City of College Station Drainage Policy and Design Standards (refer to Section II.D).
2. In areas of shallow flooding (AO Zones), buildings and structures shall have the
lowest floor (including basement) elevated above the highest adjacent grade as the depth
number specified in feet on the Flood Insurance Rate Maps, or at least 2 feet if a depth
number is not specified, plus the additional footage requirements in the City of College
Station Code of Ordinances, Chapter 13 (Flood Hazard Protection) and the City of
College Station Drainage Policy and Design Standards (refer to Section II.D).
3. Basement floors that are below grade on all sides shall be elevated in accordance with
the City of College Station Code of Ordinances, Chapter 13 (Flood Hazard Protection)
and the City of College Station Drainage Policy and Design Standards (refer to Section
II.D).
19. Section R403.1.3.3 (Slabs-on-ground with turned-down footings) is amended by
deleting the existing text and replacing it with the following to read as follows:
“All slabs-on-ground with turned-down footings shall comply with the minimum
foundation standard in Section 1907.2, International Building Code.”
20. Chapter 11 (Energy Efficiency) is amended by deleting this chapter in its entirety and
replacing it with the following.
“One-and-two family dwellings shall comply with the 2021 International Energy
Conservation Code as amended.”
21. Section M1411.3 (Condensate disposal) is amended by deleting the existing text and
replacing with the following:
“Condensate from all cooling coils or evaporators shall be conveyed from the drain pan
outlet to the sanitary sewer system, if available. The condensate drain shall be connected
to the sanitary sewer system in a manner approved by the code official.
Exception: When a sanitary sewer system is not available on the premises, or
connection thereto is not practical, the condensate shall discharge into an approved
french drain.”
22. Section M1501.1 (Outdoor discharge) is amended by deleting the last sentence in said
section.
23. Section M1505.2 (Recirculation of air) is amended by deleting the second sentence in
said section, and replacing it with the following:
ORDINANCE NO. 2022-4352 Page 30 of 54
“Exhaust air from bathrooms and toilet rooms shall discharge directly to the outdoors or
the vent termination shall be unobstructed and within 6 inches of the soffit vent or ridge
vent.”
24. Section G2408.3 (Private garages) is amended by deleting the section in its entirety.
25. Section G2414.4.3 (Copper or copper-alloy tubing) is amended by deleting said
section in its entirety.
26. Section G2417.1.2 (Repairs and additions) is amended by deleting the existing text in
its entirety and replacing it with the following:
“In the event repairs or additions are made after the pressure test, the affected piping
shall be tested. If approved by the code official, minor repairs and additions are not
required to be pressure tested provided the work is inspected and connections are tested
with a noncorrosive leak-detecting fluid or other leak detecting methods.”
27. Section G2417.4 (Test pressure measurement) is amended by deleting the existing text
in its entirety and replacing it with the following:
“Test pressure measurement shall comply with Section 406.4, 2021 International Fuel
Gas Code, as amended.”
28. Section G2417.4.1 (Test pressure) is amended by deleting the existing text in its entirety
and replacing it with the following:
“Test pressure shall comply with Section 406.4.1, 2021 International Fuel Gas Code, as
amended.”
29. Section P2503.8 (Inspection and testing of backflow prevention devices) is amended by
deleting the section in its entirety and replacing with the following:
“Inspection and testing of backflow prevention devices shall comply with Section
312.10, 2021 International Plumbing Code, as amended.”
30. Section P2804.6.1 (Requirements for discharge pipe) is amended by deleting the text in
number five and replacing it with the following:
“Discharge to an indirect waste receptor or to the outdoors.”
31. Section P2902.5.3 (Lawn irrigation systems) is amended by deleting the existing text in
its entirety and replacing it with the following:
P2902.5.3 Lawn Irrigation Systems
ORDINANCE NO. 2022-4352 Page 31 of 54
P2902.5.3.1 Valid License Required. Any person who connects an irrigation
system to the water supply within the city or the city’s extraterritorial jurisdiction,
commonly referred to as the ETJ, must hold a valid license, as defined by Title 30,
Texas Administrative Code, Chapter 30 and required by Chapter 1903 of the Texas
Occupations Code, or as defined by Chapter 365, Title 22 of the Texas
Administrative Code and required by Chapter 1301 of the Texas Occupations Code.
Exception: A property owner is not required to be licensed in accordance with
Texas Occupations Code, Title 12, §1903.002(c)(1) if he or she is performing
irrigation work in a building or on a premises owned or occupied by the person as
the person’s home. A home or property owner who installs an irrigation system
must meet the standards contained in Title 30, Texas Administrative Code, Chapter
344 regarding spacing, water pressure, spraying water over impervious materials,
rain or moisture shut-off devices or other technology, backflow prevention and
isolation valves. See Texas Occupations Code §1903.002 for other exemptions to
the licensing requirement.
P2902.5.3.2 Permit Required. Any person installing an irrigation system within the
territorial limits or extraterritorial jurisdiction of the city is required to obtain a
permit from the city prior to beginning work on the irrigation system. A completed
irrigation permit application and irrigation plan must be a submitted to the city and
approved before a permit will be issued by the city. The irrigation plan must be in
compliance with the requirements of this section.
Exceptions:
(1) An irrigation system that is an on-site sewage disposal system, as defined by
Section 366.002, Health and Safety Code; or
(2) An irrigation system used on or by an agricultural operation as defined by
Section 251.002, Agriculture Code; or
(3) An irrigation system connected to a groundwater well used by a property owner
strictly for domestic use.
P2902.5.3.3 Backflow Prevention Methods and Devices. Any irrigation system that
is connected to the potable water supply must be connected through a backflow
prevention method approved by the Texas Commission on Environmental Quality
(TCEQ). The backflow prevention device must be approved by the Foundation for
Cross-Connection Control and Hydraulic Research, the University of Southern
California, the International Plumbing Code, or any other laboratory that has
equivalent capabilities for both the laboratory and field evaluation of backflow
prevention assemblies. The backflow prevention device must be installed in
accordance with the laboratory approval standards or if the approval does not
include specific installation information, the manufacturer's current published
recommendations. If conditions that present a health hazard exist, one of the
following methods must be used to prevent backflow;
(1) An air gap may be used if:
(a) there is an unobstructed physical separation; and
ORDINANCE NO. 2022-4352 Page 32 of 54
(b) the distance from the lowest point of the water supply outlet to the flood
rim of the fixture or assembly into which the outlet discharges is at least one
inch or twice the diameter of the water supply outlet, whichever is greater.
(2) Reduced pressure principle backflow prevention assemblies may be used if:
(a) the device is installed at a minimum of 12 inches above ground in a location
that will ensure that the assembly will not be submerged; and
(b) drainage is provided for any water that may be discharged through the
assembly relief valve.
(3) Atmospheric vacuum breakers may only be used as replacements on existing
systems utilizing atmospheric vacuum breakers if:
(a) no back-pressure will be present;
(b) there are no shutoff valves downstream from the atmospheric vacuum
breaker;
(c) the device is installed at a minimum of six inches above any downstream
piping and the highest downstream opening. Pop-up sprinklers are measured
from the retracted position from the top of the sprinkler;
(d) there is no continuous pressure on the supply side of the atmospheric
vacuum breaker for more than 12 hours in any 24-hour period; and
(e) a separate atmospheric vacuum breaker is installed on the discharge side of
each irrigation control valve, between the valve and all the emission devices
that the valve controls.
(4) Pressure vacuum breakers may be used if:
(a) no back-pressure condition will occur; and
(b) the device is installed at a minimum of 12 inches above any downstream
piping and the highest downstream opening. Pop-up sprinklers are measured
from the retracted position from the top of the sprinkler.
All backflow prevention devices used in applications designated as health
hazards must be tested upon installation and annually thereafter.
If there are no conditions that present a health hazard, double check valve
backflow prevention assemblies may be used to prevent backflow if the device
is tested upon installation and test cocks are used for testing only. A double
check valve may be installed below ground if:
(a) the double check valve assembly is installed in a vault or other approved
enclosure that which is constructed of a durable material. The vault or
enclosure shall either be of solid (waterproof) construction with an integral
bottom or bottomless to facilitate drainage. If the vault or enclosure is
bottomless, a minimum of four (4) inches of washed gravel shall be installed
below the assembly. The washed gravel shall have a diameter of between 3/8
inch and 3/4 inch (inclusive);
(b) the test cocks are plugged with a non-ferrous material (brass, plastic, etc.)
except when the double check valve is being tested;
(c) the test cock plugs are threaded, water-tight, and made of non-ferrous
material;
ORDINANCE NO. 2022-4352 Page 33 of 54
(d) a y-type strainer is installed on the inlet side of the double check valve;
(e) a minimum clearance of three (3) inches is provided between any fill
material and the bottom of the double check valve to allow space for testing
and repair; and
(f) a minimum clearance of four (4) inches is provided on the sides of the
double check valve to test and repair the double check valve.
If an existing irrigation system without a backflow-prevention assembly
requires major maintenance, alteration, repair, or service, the system must be
connected to the potable water supply through an approved, properly installed
backflow prevention method before any major maintenance, alteration, repair,
or service is performed.
If an irrigation system is connected to a potable water supply through a double
check valve, pressure vacuum breaker, or reduced pressure principle backflow
assembly and includes an automatic master valve on the system, the automatic
master valve must be installed on the discharge side of the backflow prevention
assembly.
The irrigator shall ensure the backflow prevention device is tested by a
licensed Backflow Prevention Assembly Tester prior to being placed in
service. The tester must be registered with the City of College Station and the
test results must be provided to the local water purveyor and the irrigation
system's owner or owner's representative within ten business days of testing of
the backflow prevention device.
P2902.5.3.4 Specific Conditions and Cross-Connection Control. Before any
chemical is added to an irrigation system connected to the potable water supply, the
irrigation system must be connected through a reduced pressure principle backflow
prevention assembly or air gap.
Connection of any additional water source to an irrigation system that is connected
to the potable water supply can only be done if the irrigation system is connected
to the potable water supply through a reduced-pressure principle backflow
prevention assembly or an air gap.
Irrigation system components with chemical additives induced by aspiration,
injection, or emission system connected to any potable water supply must be
connected through a reduced pressure principle backflow device.
If an irrigation system is designed or installed on a property that is served by an on-
site sewage facility, as defined in Title 30, Texas Administrative Code, Chapter
285, then:
(1) all irrigation piping and valves must meet the separation distances from the On-
Site Sewage Facilities system as required for a private water line in Title 30, Texas
Administrative Code, Section 285.91(10);
ORDINANCE NO. 2022-4352 Page 34 of 54
(2) any connections using a private or public potable water source that is not the
city’s potable water system must be connected to the water source through a
reduced pressure principle backflow prevention assembly as defined in Title 30,
Texas Administrative Code, Section 344.50; and
(3) any water from the irrigation system that is applied to the surface of the area
utilized by the On-Site Sewage Facility system must be controlled on a separate
irrigation zone or zones so as to allow complete control of any irrigation to that area
so that there will not be excess water that would prevent the On-Site Sewage
Facilities system from operating effectively.
P2902.5.3.5 Water Conservation. All irrigation systems shall be designed,
installed, maintained, altered, repaired, serviced, and operated in a manner that will
promote water conservation as defined in the Definitions section of this ordinance.
P2902.5.3.6 Irrigation Plan Design. An irrigator shall prepare an irrigation plan for
each site where a new irrigation system will be installed. A paper or electronic copy
of the irrigation plan must be on the job site at all times during the installation of
the irrigation system. A drawing showing the actual installation of the system is
due to each irrigation system owner after all new irrigation system installations.
During the installation of the irrigation system, variances from the original plan
may be authorized by the licensed irrigator if the variance from the plan does not:
(1) diminish the operational integrity of the irrigation system;
(2) violate any requirements of this ordinance; and
(3) go unnoted in red on the irrigation plan.
The irrigation plan must include complete coverage of the area to be irrigated. If
a system does not provide complete coverage of the area to be irrigated, it must
be noted on the irrigation plan.
All irrigation plans used for construction must be drawn to scale. The plan must
include, at a minimum, the following information:
(1) the irrigator's seal, signature, and date of signing;
(2) all major physical features and the boundaries of the areas to be watered;
(3) a North arrow;
(4) a legend;
(5) the zone flow measurement for each zone;
(6) location and type of each:
(a) controller; and
(b) sensor (for example, but not limited to, rain, moisture, wind, flow, or
freeze);
(7) location, type, and size of each:
(a) water source, such as, but not limited to a water meter and point(s) of
connection;
(b) backflow prevention device;
ORDINANCE NO. 2022-4352 Page 35 of 54
(c) water emission device, including, but not limited to, spray heads, rotary
sprinkler heads, quick-couplers, bubblers, drip, or micro-sprays;
(d) valve, including but not limited to, zone valves, master valves, and
isolation valves;
(e) pressure regulation component; and
(f) main line and lateral piping.
(8) the scale used; and
(9) the design pressure.
P2902.5.3.7 Design and Installation. No irrigation design or installation shall
require the use of any component, including the water meter, in a way which
exceeds the manufacturer's published performance limitations for the component.
P2902.5.3.7.1 Spacing. The maximum spacing between emission devices
must not exceed the manufacturer's published radius or spacing of the
device(s). The radius or spacing is determined by referring to the
manufacturer's published specifications for a specific emission device at a
specific operating pressure. New irrigation systems shall not utilize above-
ground spray emission devices in landscapes that are less than 48 inches not
including the impervious surfaces in either length or width and which
contain impervious pedestrian or vehicular traffic surfaces along two or
more perimeters. If pop-up sprays or rotary sprinkler heads are used in a
new irrigation system, the sprinkler heads must direct flow away from any
adjacent surface and shall not be installed closer than four inches from a
hardscape, such as, but not limited to, a building foundation, fence,
concrete, asphalt, pavers, or stones set with mortar.
Exception:
Narrow paved walkways, jogging paths, golf cart paths or other small areas
located in cemeteries, parks, golf courses or other public areas if the runoff
drains into a landscaped area.
P2902.5.3.7.2 Water Pressure. Emission devices must be installed to
operate at the minimum and not above the maximum sprinkler head pressure
as published by the manufacturer for the nozzle and head spacing that is
used. Methods to achieve the water pressure requirements include, but are
not limited to, flow control valves, a pressure regulator, or pressure
compensating spray heads.
P2902.5.3.7.3 Piping. Piping in irrigation systems must be designed and
installed so that the flow of water in the pipe will not exceed a velocity of
five feet per second for polyvinyl chloride (PVC) pipe.
P2902.5.3.7.4 Irrigation Zones. Irrigation systems shall have separate zones
based on plant material type, microclimate factors, topographic features,
soil conditions, and hydrological requirements.
ORDINANCE NO. 2022-4352 Page 36 of 54
P2902.5.3.7.5 Matched Precipitation Rate. Zones must be designed and
installed so that all of the emission devices in that zone irrigate at the same
precipitation rate.
P2902.5.3.7.6 Impervious Surfaces. Irrigation systems shall not spray water
over surfaces made of concrete, asphalt, brick, wood, stones set with mortar,
or any other impervious material, such as, but not limited to, walls, fences,
sidewalks, streets, etc.
P2902.5.3.7.7 Master Valve. When provided, a master valve shall be
installed on the discharge side of the backflow prevention device on all new
installations.
P2902.5.3.7.8 PVC Pipe Primer Solvent. All new irrigation systems that are
installed using PVC pipe and fittings shall be primed with a colored primer
prior to applying the PVC cement in accordance with the International
Plumbing Code (Section 605).
P2902.5.3.7.9 Rain or Moisture Sensor. All new automatically controlled
irrigation systems must include sensors or other technology designed to
inhibit or interrupt operation of the irrigation system during periods of
moisture or rainfall. Rain or moisture shut-off technology must be installed
according to the manufacturer's published recommendations. Repairs to
existing automatic irrigation systems that require replacement of an existing
controller must include a sensor or other technology designed to inhibit or
interrupt operation of the irrigation system during periods of moisture or
rainfall.
P2902.5.3.7.10 Isolation Valve. All new irrigation systems must include an
isolation valve between the water meter and the backflow prevention
device.
P2902.5.3.7.11 Depth Coverage of Piping. Piping in all irrigation systems
must be installed according to the manufacturer's published specifications
for depth coverage of piping. If the manufacturer has not published
specifications for depth coverage of piping, the piping must be installed to
provide minimum depth coverage of six inches of select backfill, between
the top of the pipe and the natural grade of the topsoil. All portions of the
irrigation system that fail to meet this standard must be noted on the
irrigation plan. If the area being irrigated has rock at a depth of six inches
or less, select backfill may be mounded over the pipe. Mounding must be
noted on the irrigation plan and discussed with the irrigation system owner
or owner's representative to address any safety issues. If a utility, man-made
structure or roots create an unavoidable obstacle, which makes the six-inch
depth coverage requirement impractical, the piping shall be installed to
ORDINANCE NO. 2022-4352 Page 37 of 54
provide a minimum of two inches of select backfill between the top of the
pipe and the natural grade of the topsoil. All trenches and holes created
during installation of an irrigation system must be backfilled and compacted
to the original grade.
P2902.5.3.7.12 Irrigation System Wiring. Underground electrical wiring
used to connect an automatic controller to any electrical component of the
irrigation system must be listed by Underwriters Laboratories as acceptable
for burial underground. Electrical wiring that connects any electrical
components of an irrigation system must be sized according to the
manufacturer's recommendation. Electrical wire splices which may be
exposed to moisture must be waterproof as certified by the wire splice
manufacturer. Underground electrical wiring that connects an automatic
controller to any electrical component of the irrigation system must be
buried with a minimum of six inches of select backfill.
P2902.5.3.7.13 Irrigation System Water. Water contained within the piping
of an irrigation system is deemed to be non-potable. No drinking or
domestic water usage, such as, but not limited to, filling swimming pools or
decorative fountains, shall be connected to an irrigation system. If a hose
bib (an outdoor water faucet that has hose threads on the spout) is connected
to an irrigation system for the purpose of providing supplemental water to
an area, the hose bib must be installed using a quick coupler key on a quick
coupler installed in a covered purple valve box and the hose bib and any
hoses connected to the bib must be labeled "non potable, not safe for
drinking." An isolation valve must be installed upstream of a quick coupler
connecting a hose bib to an irrigation system.
P2902.5.3.7.14 Licensed Person On Site During Installation. Beginning
January 1, 2010, either a licensed irrigator or a licensed irrigation technician
shall be on-site at all times while the landscape irrigation system is being
installed. When an irrigator is not onsite, the irrigator shall be responsible
for ensuring that a licensed irrigation technician is on-site to supervise the
installation of the irrigation system.
P2902.5.3.8 Completion of Irrigation System Installation. Upon completion of the
irrigation system, the irrigator or irrigation technician who provided supervision for
the on-site installation shall be required to complete the following four items:
(1) a final walk through with the irrigation system's owner or the owner's
representative to explain the operation of the system;
(2) The maintenance checklist on which the irrigator or irrigation technician shall
obtain the signature of the irrigation system's owner or owner's representative and
shall sign, date, and seal the checklist. If the irrigation system's owner or owner's
representative is unwilling or unable to sign the maintenance checklist, the irrigator
shall note the time and date of the refusal on the irrigation system's owner or owner's
representative's signature line. The irrigation system owner or owner's
ORDINANCE NO. 2022-4352 Page 38 of 54
representative will be given the original maintenance checklist and a duplicate copy
of the maintenance checklist shall be maintained by the irrigator.
The items on the maintenance checklist shall include but are not limited to:
(a) the manufacturer's manual for the automatic controller, if the system is
automatic;
(b) a seasonal (spring, summer, fall, winter) watering schedule based on either
current/real time evapotranspiration or monthly historical reference
evapotranspiration (historical ET) data, monthly effective rainfall estimates,
plant landscape coefficient factors, and site factors;
(c) a list of components, such as the nozzle, or pump filters, and other such
components; that require maintenance and the recommended frequency for
the service; and
(d) the statement, "This irrigation system has been installed in accordance with
all applicable state and local laws, ordinances, rules, regulations or orders. I
have tested the system and determined that it has been installed according to
the Irrigation Plan and is properly adjusted for the most efficient application
of water at this time."
(3) A permanent sticker which contains the irrigator's name, license number,
company name, telephone number and the dates of the warranty period shall be
affixed to each automatic controller installed by the irrigator or irrigation
technician. If the irrigation system is manual, the sticker shall be affixed to the
original maintenance checklist. The information contained on the sticker must be
printed with waterproof ink and include:
(4) The irrigation plan indicating the actual installation of the system must be
provided to the irrigation system's owner or owner representative.
P2902.5.3.9 Maintenance, Alteration, Repair, or Service of Irrigation Systems. The
licensed irrigator is responsible for all work that the irrigator performed during the
maintenance, alteration, repair, or service of an irrigation system during the
warranty period. The irrigator or business owner is not responsible for the
professional negligence of any other irrigator who subsequently conducts any
irrigation service on the same irrigation system. All trenches and holes created
during the maintenance, alteration, repair, or service of an irrigation system must
be returned to the original grade with compacted select backfill. Colored PVC pipe
primer solvent must be used on all pipes and fittings used in the maintenance,
alteration, repair, or service of an irrigation system in accordance with the adopted
International Plumbing Code (Section 605). When maintenance, alteration, repair
or service of an irrigation system involves excavation work at the water meter or
backflow prevention device, an isolation valve shall be installed, if an isolation
valve is not present.
P2902.5.3.10 Reclaimed Water. Reclaimed water may be utilized in landscape
irrigation systems if:
ORDINANCE NO. 2022-4352 Page 39 of 54
(1) there is no direct contact with edible crops, unless the crop is pasteurized before
consumption;
(2) the irrigation system does not spray water across property lines that do not
belong to the irrigation system's owner;
(3) the irrigation system is installed using purple components;
(4) the domestic potable water line is connected using an air gap or a reduced
pressure principle backflow prevention device, in accordance with §290.47(i) of
this title (relating to Appendices);
(5) a minimum of an eight inch by eight inch sign is prominently posted on/in the
area that is being irrigated, that reads, "RECLAIMED WATER – DO NOT
DRINK" ; and
(6) backflow prevention on the reclaimed water supply line shall be provided in
accordance with the regulations of the city’s water provider.
P2902.5.3.11 Advertisement Requirements. All vehicles used in the performance
of irrigation installation, maintenance, alteration, repair, or service must display the
irrigator's license number in the form of "LI________" in a contrasting color of
block letters at least two inches high, on both sides of the vehicle. All forms of
written and electronic advertisements for irrigation services must display the
irrigator's license number in the form of "LI___________." Any form of
advertisement, including business cards, and estimates which displays an entity's
or individual's name other than that of the licensed irrigator must also display the
name of the licensed irrigator and the licensed irrigator's license number. Trailers
that advertise irrigation services must display the irrigator's license number. The
name, mailing address, and telephone number of the commission must be
prominently displayed on a legible sign and displayed in plain view for the purpose
of addressing complaints at the permanent structure where irrigation business is
primarily conducted and irrigation records are kept.
P2902.5.3.12 Contracts. All contracts to install an irrigation system must be in
writing and signed by each party and must specify the irrigator's name, license
number, business address, current business telephone numbers, the date that each
party signed the agreement, the total agreed price, and must contain the statement,
"Irrigation in Texas is regulated by the Texas Commission on Environmental
Quality (TCEQ), MC-178, P.O. Box 13087, Austin, Texas 78711-3087. TCEQ's
website is: www. tceq.state.tx.us." All contracts must include the irrigator's seal,
signature, and date. All written estimates, proposals, bids, and invoices relating to
the installation or repair of an irrigation system(s) must include the irrigator's name,
license number, business address, current business telephone number(s), and the
statement: "Irrigation in Texas is regulated by the Texas Commission On
Environmental Quality (TCEQ) (MC-178), P.O. Box 13087, Austin, Texas 78711-
3087. TCEQ's web site is: www.tceq.state.tx.us." An individual who agrees by
contract to provide irrigation services as defined in §344.30 of this title (relating to
License Required) shall hold an irrigator license issued under Title 30, Texas
Administrative Code, Chapter 30 (relating to Occupational Licenses and
Registrations) unless the contract is a pass-through contract as defined in
ORDINANCE NO. 2022-4352 Page 40 of 54
§344.1(36) of this title (relating to Definitions). If a pass-through contract includes
irrigation services, then the irrigation portion of the contract can only be performed
by a licensed irrigator. If an irrigator installs a system pursuant to a pass-through
contract, the irrigator shall still be responsible for providing the irrigation system's
owner or through contract, the irrigator shall still be responsible for providing the
irrigation system's owner or owner's representative a copy of the warranty and all
other documents required under this chapter. A pass-through contract must identify
by name and license number the irrigator that will perform the work and must
provide a mechanism for contacting the irrigator for irrigation system warranty
work. The contract must include the dates that the warranty is valid.
P2902.5.3.13 Warranties for Irrigation Systems. On all installations of new
irrigation systems, an irrigator shall present the irrigation system's owner or owner's
representative with a written warranty covering materials and labor furnished in the
new installation of the irrigation system. The irrigator shall be responsible for
adhering to terms of the warranty. If the irrigator's warranty is less than the
manufacturer's warranty for the system components, then the irrigator shall provide
the irrigation system's owner or the owner's representative with applicable
information regarding the manufacturer's warranty period. The warranty must
include the irrigator's seal, signature, and date. If the warranty is part of an
irrigator's contract, a separate warranty document is not required. An irrigator's
written warranty on new irrigation systems must specify the irrigator's name,
business address, and business telephone number(s), must contain the signature of
the irrigation system's owner or owner's representative confirming receipt of the
warranty and must include the statement: "Irrigation in Texas is regulated by the
Texas Commission on Environmental Quality (TCEQ), MC-178, P.O. Box 130897,
Austin, Texas 78711-3087. TCEQ's website is: www.tceq.state.tx.us." On all
maintenance, alterations, repairs, or service to existing irrigation systems, an
irrigator shall present the irrigation system's owner or owner's representative a
written document that identifies the materials furnished in the maintenance,
alteration, repair, or service. If a warranty is provided, the irrigator shall abide by
the terms. The warranty document must include the irrigator's name and business
contact information.
P2902.5.3.14 Duties and Responsibilities of City Irrigation Inspectors. A licensed
irrigation inspector or plumbing inspector shall enforce the ordinance of the city,
and shall be responsible for:
(1) verifying that the appropriate permits have been obtained for an irrigation
system and that the irrigator and installer or irrigation technician, if applicable, are
licensed;
(2) inspecting the irrigation system;
(3) determining that the irrigation system complies with the requirements of this
section;
(4) determining that the appropriate backflow prevention device was installed and
tested;
ORDINANCE NO. 2022-4352 Page 41 of 54
(5) investigating complaints related to irrigation system installation, maintenance,
alteration, repairs, or service of an irrigation system and advertisement of irrigation
services; and
(6) maintaining inspection records according to this section.”
32. Table P2906.4 (Water service pipe) is amended by deleting the following materials:
“Acrylonitrile butadiene styrene (ABS) plastic pipe
Asbestos-cement pipe
Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe
Polyethylene (PE) plastic pipe
Polyethylene (PE) plastic tubing”
33. Table P2906.5 (Water distribution pipe) is amended by deleting the following materials:
“Polyethylene/aluminum/polyethylene (PE-AL-PE) composite pipe”
34. Section P2906.5 (Water-distribution pipe.) is amended by adding the following text to
the end of the section:
“Inaccessible water distribution piping under slabs shall be copper (minimum type K)
or cross-linked polyethylene (PEX) tubing all installed without joints or connections.
Materials subject to corrosion shall be protected when exposed to concrete or corrosive
soils.”
35. Section 2906.10 (Cross-linked polyethylene plastic (PEX)) is amended by adding
P2906.10.3 to read as follows:
“P2906.10.3. Sleeving. When a sleeve is provided for cross-linked polyethylene (PEX)
plastic piping or tubing installed under concrete slabs the annular space between the
piping or tubing and the sleeve must be caulked, foamed, or otherwise sealed to prevent
the entrance of termiticide.”
36. Section P3002.2. (Building sewer) is amended by adding P3002.2.1 to read as follows:
“P3002.2.1 Depth of building sewer. Building sewer pipe shall be installed with a
minimum of twelve (12) inches of cover. Where conditions prohibit the required amount
of cover, cast iron pipe with approved joints may be used unless other means of
protecting the pipe is provided as approved by the Building Official.”
37. Section E3401.1 (applicability) is amended by deleting the section in its entirety and
replacing with the following:
“Electrical installations shall comply with the National Electrical Code, as adopted and
amended by the City of College Station.”
ORDINANCE NO. 2022-4352 Page 42 of 54
Sec. 103-135. – Amendments to the International Fuel Gas Code.
The International Fuel Gas Code adopted by reference in Section 101.4.1, 2021 International
Building Code is hereby amended as follows:
1. Section 102.8 (Referenced codes and standards) is amended by adding the
following exception:
“Exception: Any reference to the ICC Electrical Code shall mean the National Electrical
Code, as adopted and amended by the City of College Station.”
2. Section 106.3 (Application for permit) is amended by deleting the text in said section
and replacing it with the following:
“The code official may require a permit application for work regulated by this code.”
3. Section 109.2 (Schedule of permit fees) is amended by deleting the section in its
entirety.
4. Section 109.6 (Refunds) is amended by deleting the text in said section and replacing it
with the following:
“The City Manager or his designee is authorized to establish a refund policy.”
5. Section 113 (Means of Appeal) is amended by deleting the section in its entirety.
6. Section 305.5 (Private garages) is amended by deleting the section in its entirety.
7. Section 403.3.3 (Copper and copper alloy) is amended by deleting the section in its
entirety.
8. Section 403.4.3 (Copper and copper alloy tubing) is amended by deleting the section in
its entirety.
9. Section 406.1.2 (Repairs and additions) is amended by deleting the existing text in its
entirety and replacing it with the following:
“In the event repairs or additions are made after the pressure test, the affected piping
shall be tested. If approved by the code official, minor repairs and additions are not
required to be pressure tested provided the work is inspected and connections are tested
with a noncorrosive leak-detecting fluid or other leak detecting methods.
10. Section 406.4 (Test pressure measurement) is amended by adding the following to the
end of said section:
‘For gas systems with a working pressure up to and including five (5) psi., a diaphragm
gauge utilizing a dial with a minimum diameter of three and one-half inches (3 ½”), a
ORDINANCE NO. 2022-4352 Page 43 of 54
set hand, 2/10 pound incrementation and a pressure range not more than twenty (20) psi
shall be acceptable. A mechanical spring gauge is only acceptable for use on gas
systems requiring a pressure test of more than 20 psig.’
11. Section 406.4.1 (Test pressure) is amended by deleting the existing text in its entirety
and replacing it with the following:
‘The test pressure to be used shall be no less than twice the proposed maximum
working pressure, but no less than five (5) psig, irrespective of design pressure.’
12. Section 406.4.2 (Test duration) is amended by deleting the existing text in its entirety
and replacing it with the following:
“Gas piping systems shall withstand the required pressure test for a period of not less
than ten (10) minutes without showing any drop in pressure.”
ORDINANCE NO. 2022-4352 Page 44 of 54
Sec. 103-136. – Amendments to the International Mechanical Code.
The International Mechanical Code adopted by reference in Section 101.4.2, 2021 International
Building Code is hereby amended as follows:
1. Section 102.8 (Referenced codes and standards) is amended by adding the following
exception:
‘Exception: Any reference to the ICC Electrical Code shall mean the National Electrical
Code, as adopted and amended by the City of College Station.
2. Section 106.3 (Application for permit) is amended by deleting the text in said section
and replacing it with the following:
‘The code official may require a permit application for work regulated by this code.’
3. Section 109.2 (Schedule of permit fees) is amended by deleting the section in its
entirety.
4. Section 109.6 (Refunds) is amended by deleting the text in said section and replacing it
with the following:
“The City Manager or his designee is authorized to establish a refund policy.”
5. Section 113.4 (Failure to comply) is amended by adding the following at the end of said
section:
“Fines shall be not less than twenty-five ($25.00) and not more than two-thousand
($2,000.00).”
6. Section 114 (Means of Appeal) is amended by deleting the section in its entirety.
7. Section 304.7 (Private garages) is amended by deleting the section in its entirety.
8. Section 507.6.1 (Capture and containment test) is amended by deleting the section in its
entirety.
ORDINANCE NO. 2022-4352 Page 45 of 54
Sec. 103-137. – Amendments to the International Plumbing Code.
The International Plumbing Code adopted by reference in Section 101.4.3, 2021 International
Building Code is hereby amended as follows:
1. Section 102.8 (Referenced codes and standards) is amended by adding the following
exception:
‘Exception: Any reference to the ICC Electrical Code shall mean the National Electrical
Code, as adopted and amended by the City of College Station.’
2. Section 106.3 (Application for permit) is amended by deleting the text in said section
and replacing it with the following:
“The code official may require a permit application for work regulated by this code.”
3. Section 109.2 (Schedule of permit fees) is amended by deleting this section in its
entirety.
4. Section 109.5 (Refunds) is amended by deleting the text in said section and replacing it
with the following:
“The City Manager or designee is authorized to establish a refund policy.”
5. Section 113.4 (Failure to comply) is amended by inserting the following amounts in the
blanks provided at the end of said section:
“Fines shall be not less than twenty-five ($25.00) and not more than two- thousand
($2,000.00)”
6. Section 114 (Means of Appeal) is amended by deleting the section in its entirety.
7. Section 305.4.1 (Sewer depth) is amended by inserting “twelve (12)” in both blanks and
adding the following sentence to the end of said section.
“Where conditions prohibit the required amount of cover, cast iron pipe with approved
joints may be used unless other means of protecting the pipe is provided as approved by
the Building Official.”
8. Section 312.1 (Required tests) is amended by deleting the following text from said
section:
“, for piping systems other than plastic, by”
9. Section 312.2 (Drainage and vent water test) is amended by deleting said section in its
entirety and replacing with the following:
ORDINANCE NO. 2022-4352 Page 46 of 54
“312.2 Drainage water test. A water test shall be applied to the drainage system either
in its entirety or in sections. If applied to the entire system, all openings in the piping
shall be tightly closed, except the highest opening, and the system shall be filled with
water to the point of overflow. If the system is tested in sections, each opening shall be
tightly plugged except the highest opening of the section under test, and each section
shall be tested with not less than a 5-foot head of water. This pressure shall be held for
at least 15 minutes. The drainage system shall then be tight at all points.”
10. Section 312.3 (Drainage and vent air test) is amended by deleting said section in its
entirety and replacing with the following:
“312.3 Drainage air test. An air test shall be applied to the drainage piping by forcing
air into the system until there is uniform gauge pressure of 5 pounds per square inch
(psi) or sufficient to balance a 10-inch column of mercury. This pressure shall be held
for a test period of at least 15 minutes. Any adjustment to the test pressure required
because of changes in ambient temperature or the seating of gaskets shall be made prior
to the beginning of the test period.?”
11. Section 312.6 (Gravity sewer test) is amended by replacing “10-foot” with “5-foot”.
12. Section 312.10 (Inspection and testing of backflow prevention assemblies.) is amended
by deleting said section in its entirety and replacing with the following:
“312.10 Inspection and testing of backflow prevention assemblies. Upon initial
installation, an inspection shall be made of all backflow prevention devices and
assemblies to determine whether they are operable. Testing of all backflow prevention
devices and assemblies shall be in accordance with Chapter 11, Section 10, Subsection
F, of the Code of Ordinances, City of College Station, Texas.”
13. Section 410.4 (Substitution) is amended by deleting the last sentence in said section and
replacing it with the following:
“Where bottle water dispensers are provided in other occupancies, drinking fountains
shall not be required.”
14. Table 605.3 (Water Service Pipe) is amended by deleting the following materials:
Acrylonitrile butadiene styrene (ABS) plastic pipe
Polyethylene (PE) plastic pipe
Polyethylene (PE) plastic tubing
Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe
15. Section 606 (Installation of the Building Water Distribution System) is amended by
adding section 606.7 to read as follows:
ORDINANCE NO. 2022-4352 Page 47 of 54
“606.7 Materials below slab. Water distribution piping installed under concrete slabs
shall be copper (minimum type K), cross-link polyethylene (PEX) tubing, or cross-
linked polyethylene/aluminum/ polyethylene (PEX-AL-PEX) pipe, all installed without
joints or connections. Materials subject to corrosion shall be protected when exposed
to concrete or corrosive soils.”
16. Section 606 (Installation of the Building Water Distribution System) is amended by
adding section 606.8 to read as follows:
“606.8 Sleeved cross-polyethylene piping or tubing. ‘When a sleeve is provided for
cross-linked polyethylene (PEX) plastic piping or tubing installed under concrete slabs
the annular space between the piping or tubing and the sleeve must be caulked, foamed,
or otherwise sealed to prevent the entrance of termiticide.”
17. Section 608.17.5 (Connections to lawn irrigation systems) is amended by deleting the
first sentence in said section and replacing it with the following:
“The potable water supply to lawn irrigation systems shall be protected against backflow
by an atmospheric vacuum breaker, a pressure vacuum breaker assembly, a reduced
pressure principle backflow prevention assembly or a double check.”
18. Section 701.2 (Connection to sewer required) is amended by deleting the section in its
entirety and replacing with the following:
“701.2 Connection to sewer required. Every building in which plumbing fixtures are
installed and all premises having sanitary drainage piping shall be connected to an
approved sewer. Private sewage systems must comply with City of College Station’s
Code of Ordinances. All private sewage disposal systems must comply with the latest
adopted standards of the Texas Commission on Environmental Quality and be installed
under the direction of the Brazos County Health Department. The installer shall be
licensed by the Texas Commission on Environmental Quality.”
19. Section 1003.3.5 (Hydromechanical grease interceptors, fats, oils and greases disposal
systems and automatic grease removal devices) is amended by deleting the first sentence
in said section.
ORDINANCE NO. 2022-4352 Page 48 of 54
Sec. 103-138. – Amendments to the International Property Maintenance Code.
The International Property Maintenance Code adopted by reference in Section 101.4.4, 2021
International Building Code is hereby amended as follows:
1. Section 102.7 (Referenced codes and standards) is amended by adding the following
exception:
“Exception: Any reference to the ICC Electrical Code shall mean the National
Electrical Code, as adopted and amended by the City of College Station.”
2. Section 107 (Means of Appeals) is amended by deleting the section in its entirety.
3. Section 111 (Unsafe Structures and Equipment) is amended by deleting the section in
its entirety.
4. Section 111.4 (Notice) is amended by deleting the section in its entirety.
5. Section 112 (Emergency Measures) is amended by deleting the section in its entirety.
6. Section 113 (Demolition) is amended by deleting the section in its entirety.
7. Section 302.4 (Weeds) is amended by deleting the section in its entirety.
8. Section 304.3 (Premises identification) is amended by deleting the text in said section
and replacing it with the following:
“Premises identification shall be in compliance with Section 502.1, 2021 International
Building Code as amended.”
9. Section 304.14 (Insect screens) is amended by deleting the existing text and replacing
it with the following:
“Every door, window, and other outside opening required for ventilation of habitable
rooms, food preparation areas, food service areas or any other areas where products to
be included or utilized in food for human consumption are processed, manufactured,
packaged or stored, shall be supplied with approved tightly fitting screens of not less
than 16 mesh per inch (16 mesh per 25mm) and every swinging door shall have a self-
closing device in good working condition.”
Exceptions:
1. Screens shall not be required where other approved means, such as air curtains or
Insect repellant fans, are employed.
ORDINANCE NO. 2022-4352 Page 49 of 54
2. Screens shall not be required for windows and doors enclosing habitabl e spaces that
contain central heating and air conditioning equipment that provide mechanical
ventilation.’
10. Section 602.3 (Heat supply) is amended by adding the following dates in the blanks
provided:
“1 October in first blank and 30 April in second blank”
11. Section 602.4 (Occupiable work spaces) is amended by adding the following dates in
the blanks provided:
“1 October in first blank and 30 April in second blank”
12. Section 602.4 (Occupiable work spaces) is amended by adding the following exception:
“3. Warehouse, storage rooms and similar areas that are not occupied on a constant
basis.”
13. Appendix A (Boarding Standard) is hereby adopted.
ORDINANCE NO. 2022-4352 Page 50 of 54
Sec. 103-139. – Amendments to the International Energy Conservation Code.
The International Energy Conservation Code adopted by reference in Section 101.4.6, 20 21
International Building Code, is hereby amended as follows:
1. Section C&R108.1 (Referenced codes and standards) is amended by adding the
following to said section:
“Any reference to the ICC Electrical Code shall mean the National Electrical Code, as
adopted and amended by the City of College Station.”
2. Section C&R110 (Board of Appeals) is amended by deleting the section in its entirety.
3. Section C402.5 (Air leakage-thermal envelope (Mandatory)) is amended by adding an
exception:
“Exception: The air leakage – thermal envelope shall be considered acceptable when
the items listed in Table R402.4.1.1, applicable to the method of construction, are field
verified. Where required by the code official, an approved third party, independent from
the installer, shall inspect and approve the thermal envelope and insulation installation.”
4. Section R401.3 (Certificate) is amended by deleting the existing text from said section:
“The certificate shall list the types and efficiencies of heating, cooling and service water
heating equipment. Where a gas-fired unvented room heater, electric furnace, or
baseboard electric heater is installed in the residence, the certificate shall list “gas-fired
unvented room heater,” “electric furnace” or “baseboard electric heater.” as appropriate.
An efficiency shall not be listed for gas-fired unvented room heaters, electric furnaces
or electric baseboard heaters.”
5. Section R402.4.1.2 (Testing) is amended by adding an exception:
“Exception: Building envelope tightness and insulation installation shall be considered
acceptable when the items listed in Table R402.4.1.1, applicable to the method of
construction, are field verified. Where required by the code official, an approved third
party independent from the installer, shall inspect and approve the air barrier and
insulation installation.”
6. Section R402.4.6 (Electrical and communication outlet boxes (air-sealed boxes). Is
amended by adding the following to the end of the section:
“On-site sealing of boxes is acceptable, when using approved sealant materials”
7. Section R403.3.1 (Ducts located outside conditioned space) is amended by adding the
following to the end of the section:
ORDINANCE NO. 2022-4352 Page 51 of 54
“Supply and return air ducts in unconditioned spaces may have an insulation R-Value
of 6 when installed in conjunction with an air conditioner having a minimum SEER
rating of 16.”
8. Section R403.3.5 (Duct Testing) is amended by adding an additional exception below
said section:
Exception: 2. Duct tightness shall be considered acceptable when the items listed
below, applicable to the method of construction, are field verified:
Connections:
a. Seal core to collar with UL listed mastic or at least 2 wraps of UL
181 listed tape.
b. Secure connection with mechanical clamp placed over the core and
tape.
c. Pull jacket and insulation back over core. Use a mechanical clamp,
two wraps of UL 181 listed tape or UL listed mastic to secure
insulation.
Splices:
a. Butt two cores together on a 4” length metal sleeve.
b. Secure core and sleeve with UL listed mastic or two wraps of UL
181 listed tape
c. Secure connection with 2 clamps placed over the taped core ends.
d. Pull jacket and insulation back over core. Use two wraps of UL 181
listed tape or UL listed mastic to secure insulation.
9. Section R403 (Systems) is amended by adding R403.13 to read as follows:
“403.13 Heating equipment. Electrical resistance heat may be used as the primary
source of heating for residential use not exceeding five hundred (500) square feet in
area.”
10. Section R404.2 (Interior Lighting Controls) Is amended by deleting this section in its
entirety.
11. Section R406.5 (Verification by approved agency) is amended by replacing the existing
text with:
“The Code Official may require verification of compliance with Section R406 be
completed by an approved third party.”
ORDINANCE NO. 2022-4352 Page 52 of 54
EXHIBIT B
That Chapter 103, “Building Regulations,” Article III, “Technical Codes,” Division 3 “Electrical
Code” is hereby amended to read as follows:
Sec. 103-162. – National Electrical Code adopted.
A booklet entitled ‘National Electrical Code 2020 Edition’ as amended and as hereafter may be
amended, at least one (1) copy of which is on file in the office of the Building Official of the City
of College Station, Texas, is hereby adopted and designated as the Electrical Code of College
Station, Texas.
Sec. 103-163. – Amendments to the National Electrical Code.
1. Section 210.23 (A) 15- and 20- Ampere Branch Circuits. Shall be amended to delete
the reference to 15 ampere branch circuits. It shall also be amended to include the
following sentence after said section:
“However, a circuit of twenty (20) amperes shall not serve more than ten openings.”
2. Table 210.24 Summary of Branch-Circuit Requirements shall be amended by
placing an asterisk next to all 14 AWG conductors indicated in the table and by adding
this footnote at the bottom of the table:
“ special note: Except for fixture wires in UL or other listed fixtures, no conductor of a
size smaller than 12 AWG solid copper is allowed in branch circuit wiring.”
3. Section 210.52 (B) Small Appliances shall be amended by adding the following
subsection:
“(4) Separate Circuit Required. A separate circuit is required for each refrigerator,
deep freeze, dishwasher, disposal, trash compactor or any other load exceeding six (6)
amperes.”
4. Section 210.52 (C) Countertops And Work Surfaces shall be amended to include after
the words ‘…with 210.52 (C) (1) through (C) (5). the following sentence:
“However, a separate circuit is required for microwave ovens or any other counter top
appliance with a load exceeding six (6) amperes.”
5. Section 210.52 (F) Laundry Areas. Shall be amended to include after the words '. . .
for the installation of laundry equipment.' the following sentence:
“However, a separate circuit is required for a washing machine or any other laundry
appliance with a load exceeding six (6) amperes.”
ORDINANCE NO. 2022-4352 Page 53 of 54
6. Section 210.52 One-Family and Two-Family Dwelling. Shall be amended by adding
the following subsection:
“(J) Other Locations. A separate circuit is required for each well pump or other outdoor
loads exceeding six (6) amperes.”
7. Article 230 Services. Shall be amended by adding the following section:
“230.11 Meter Mounting Heights. Individual meters shall be mounted at a height not
greater than 5'-6” or less than 4'-6" above finished grade, measured to the center line of
the meter base. Meter packs shall be mounted with its horizontal centerline not greater
than 4'-6” or less than 4'-0" above finished grade.”
“Exception: Meters and meter packs may be mounted at a different height by special
permission of the Building Official or his designee when special conditions make the
installation at the above heights impractical. “
8. Section 230.70 General shall be amended by adding the following subsection:
“(D) Service Disconnecting Means for Commercial Buildings and Structures. For
commercial buildings and structures, the service disconnecting means shall be installed
on the outside of the building or structure. A power operated disconnect switch (shunt
trip) is permitted for service disconnects rated 1000 amps or more. All shunt trip
disconnecting means shall be of the maintained contact type in an approved, lockable
enclosure. All service disconnects shall be clearly marked in a permanent manner.
Exception: A power operated disconnect switch (shunt trip) may be allowed on service
disconnects rated less than 1000 amps, if the applicant requests an exception from the
Electrical Division and Building Official and satisfies the official that one of the
following criteria has been met.
(a) A power operated disconnect switch (shunt trip) may be used for a service
disconnect rated less than 1000 amps when the building or structure is served by
a single transformer and the transformer is not anticipated to be used for multiple
services; or
(b) A power operated disconnect switch (shunt trip) may be used for a service
disconnect rated less than 1000 amps on an existing building or structure when
space is not available to mount an external disconnect.
9. Article 230 Services. Shall be amended by adding the following section:
“230.70 (E) Outside Disconnect Locking Device. Factory installed key operated lock
shall have an alternate locking mechanism approved by the local jurisdiction.”
ORDINANCE NO. 2022-4352 Page 54 of 54
10. Section 230.71 (A) General shall be amended to include the following sentence after
said section:
“Any multi-tenant building larger than 5,000 square feet shall have a service
disconnect.”
11. Section 250.52 (A) (5) Rod and Pipe Electrodes shall be amended by deleting the
section in its entirety and replacing with the following:
“Rod and Pipe Electrodes. Rod and pipe electrodes shall not be less than eight (8) feet
in length, not less than 5/8” in diameter and shall be copper coated.”
12. Section 310.3 (B) Conductor Material shall be amended by adding the following
Exception:
“Exception: Aluminum and copper-clad aluminum is not allowed in branch circuits.”
13. Section 320.12 Uses Not Permitted shall be amended by deleting the section in its
entirety and replacing with the following:
“Uses Not Permitted. Type AC cable shall not be permitted in commercial buildings
as a wiring method.”
14. Section 334.12 (A) Types NM and NMC. Shall be amended to include the following
subsection:
“(11) In educational occupancies as defined by the City’s “adopted building code.”