HomeMy WebLinkAbout2025-4646 - Ordinance - 11/13/2025ORDINANCE NO.2025-4646
AN ORDINANCE AMENDING CHAPTER 103, "BUILDINGS AND BUILDING
REGULATIONS," ARTICLE III, "TECHNICAL CODES," DIVISION 2 "BUILDING
CODES" AND DIVISION 3 ELECTRICAL CODE, OF THE CODE OF ORDINANCES OF
THE CITY OF COLLEGE STATION, TEXAS, BY AMENDING CERTAIN SECTIONS
RELATING TO BUILDING REGULATIONS; PROVIDING A SEVERABILITY CLAUSE;
DECLARING A PENALTY; AND PROVIDING AN EFFECTIVE DATE.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF COLLEGE STATION,
TEXAS:
PART 1: That Chapter 103, "Buildings and Building Regulations," Article III, "Technical
Codes," Division 2 "Building Codes" and Division 3 `Electrical Code" of the Code of
Ordinances of the City of College Station, Texas, be amended as set out in Exhibit "A" and
Exhibit "B" attached hereto and made a part of this Ordinance for all purposes.
PART 2: If any provision of this Ordinance or its application to any person or circumstances is
held invalid or unconstitutional, the invalidity or unconstitutionality does not affect other
provisions or application of this Ordinance or the Code of Ordinances of the City of College
Station, Texas, that can be given effect without the invalid or unconstitutional provision or
application, and to this end the provisions of this Ordinance are severable.
PART 3: That any person, corporation, organization, government, governmental subdivision or
agency, business trust, estate, trust, partnership, association and any other legal entity violating
any of the provisions of this Ordinance shall be deemed guilty of a misdemeanor, and upon
conviction thereof shall be punishable by a fine of not less than twenty five dollars ($25.00) and
not more than five hundred dollars ($500.00) or more than two thousand dollars ($2,000) for a
violation of fire safety, zoning, or public health and sanitation ordinances, other than the dumping
of refuse. Each day such violation shall continue or be permitted to continue, shall be deemed a
separate offense.
PART 4: This Ordinance is a penal ordinance and becomes effective January 1, 2026.
ORDINANCE NO. 2025-4646
Page 2 of 50
PASSED, ADOPTED and APPROVED this 13TH day of November 2025.
ATTES : APPRO�'
City Secretary MayorV
APPROVED:
VA�� PWrA.c.(.(.
City Attorney
ORDINANCE NO. 2025-4646
Page 3 of 50
EXHIBIT A
That Chapter 103, "Buildings and Building Regulations," Article III, "Technical Codes," Division 2
"Building Codes" is hereby amended to read as follows:
Sec. 103-131. — International Building Code adopted.
A booklet entitled 'International Building Code 2024 Edition' as amended and as hereafter may be
amended, at least one (1) copy of which is on file in the office of the Building Official of the City of
College Station, Texas, is hereby adopted and designated as the Building Code of the City of College
Station, Texas. In addition, Appendix D of the 2024 International Building Code is hereby adopted.
Sec. 103-132. — International Building Code amended.
The above referenced International Building Code is hereby amended as follows:
Section 105 (Permits) is amended by adding Section 105.1.3 to read as follows:
105.1.3 Registration of Contractors.
It shall be the duty of every individual who makes contracts to construct, enlarge,
alter, repair, move, demolish, or change the occupancy of a building or structure, or
to erect, install enlarge, alter, repair, remove, convert or replace any electrical, gas,
mechanical, or plumbing system, the installation of which is regulated by this code,
or to cause any such work to be done, and every individual making such contracts
and subletting the same or any part thereof, to first register with the Building Official,
giving full name, residence, name and place of business, and in case of removal
from one place to another to have made corresponding change to the Building
Official.
Exception: Homeowner permits as provided per local amendment by added
Section R105.2.4, International Residential Code.
Plumbing Contractors - Plumbing contractors shall be licensed as prescribed by the
State of Texas and shall register their license with the City of College Station before
a plumbing permit is issued by the City.
Air Conditioning, Refrigeration and Heating Contractors - Air Conditioning,
Refrigeration and Heating Contractors shall be licensed by the State of Texas and
shall register their license with the City of College Station before a mechanical
permit is issued by the City.
Licensed Irri,2ators - Irrigation Contractors shall be licensed Irrigators by the State
of Texas shall register their license with the City of College Station before a lawn
irrigation permit is issued by the City.
Electrical Contractors - Electrical Contractors shall be licensed by the State shall
register their license with the City of College Station before an electrical permit is
issued by the City.
Electrical Sian Contractors — Electrical Sign Contractors shall be licensed by the
State shall register their license with the City of College Station before a permit is
issued.
Before any license is registered with the City, the applicant shall have adequate
ORDINANCE NO. 2025-4646
Page 4 of 50
insurance coverage for general liability as provided for by State law for the
respective trade.
2. Section 105.2 (Work exempt from permit) is amended by deleting item #2 under
"Building" and replacing with the following:
"2. Fences of wood, chain link, or similar material, and less than eight feet in height,
and walls of brick, stone, concrete, or similar material, and less than six feet in
height, shall not be construed to be a structure, nor shall they require a building
permit.
3. Section 105.2 (Work exempt from permit) is amended by adding the
following under "Electrical":
Replacing Fuses: No permit shall be required for replacing fuses of like
rating.
Replacing Flush or Snap Switches: No permit shall be required for
replacing flush or snap switches, receptacles, lamp sockets, the installation
of lamps, or minor repairs on permanently connected electrical appliances.
Conveying Signals: No permit shall be required for the installation,
maintenance or alteration of wiring, poles and down guys, apparatus,
devices, appliances or equipment for telegraph, telephone, signal service or
central station protective service used in conveying signals or intelligence,
except where electrical work is done on the primary side of the source of
power at a voltage over 50 volts and of more than 500 watts.
Wiring by Electric Public Service Company: No permit shall be required
for the installation, maintenance or alteration of electric wiring, apparatus
devices, appliances or equipment to be installed by an electric public service
company for the use of such company in the generation, transmission,
distribution, sale or utilization of electrical energy. However, an electric
public service company shall not do any wiring on a customer's distribution
system, including metering equipment wherever located and transformer
vaults in which customer's transformers are located, nor shall any of its em-
ployees do any work other than done for said company as hereinbefore
provided for by virtue of this exception.
Temporary Wiring: No permit shall be required for the installation of
temporary wiring, apparatus, devices, appliances or equipment used by a
recognized electrical training school or college.
Railway Crossing Signal Devices: No permit shall be required for the
installation and maintenance of railway crossing signal devices, when such
is performed by due authority of the railroad and in accordance with the
standards of the American Railroad Association, and in collaboration with
and approval of the Department of Public Services of the City of College
Station.
4. Section 107.1(General) is amended to include the following at the end of the section
and before the exception: "The design professional shall be an architect or engineer
legally registered and in compliance under the laws of Texas and shall affix his
official seal to the construction documents for the following:
1. All group A, E and I occupancies.
2. Building and structures three or more stories in height
ORDINANCE NO. 2025-4646 Page 5 of 50
3. Buildings and structures 5,000 square feet or more
in total area Exception: "Group R-3 buildings,
Regardless of size"
5. Section 109.4 (Work commencing before permit issuance) is amended by
deleting the existing text in its entirety and replacing it with the following:
"Any person who commences any work on a building, structure electrical, gas,
mechanical or plumbing system before obtaining the necessary permits shall be
subject to a penalty of 100% of the usual fee in addition to the required permit fees."
6. Section 109.6 (Refunds) is amended by deleting the existing text in its entirety
and replacing it with the following:
"The City Manager or his designee is authorized to establish a refund policy."
7. Section [A] 110.3.1 (Footing and foundation inspection) is amended by adding
the following to the end of said section:
"The Building Official shall have the authority to require a form survey to verify
building setbacks. Such survey shall be provided to the Building Official prior to
placement of concrete and prepared by a surveyor licensed to perform work in the
State of Texas."
Section 110.3.6 (Lath and gypsum board inspection) is amended
by deleting the section in its entirety.
9. Section 111.2 (Certificate issued) is amended by deleting items number 4, 5, 7, 10,
and 11.
10. Section 113 (Means of Appeals) is amended by deleting the section in its entirety.
11. Section 116.1 (Unsafe Conditions) is amended by deleting the sentence, "Unsafe
structures shall be taken down and removed or made safe, as the building official
deems necessary and as provided for in this section." and replacing it with the
following: "Unsafe structures shall be taken down, removed or made safe as
provided for in Section 1 (C), Chapter 3, Code of Ordinances."
12. Section 202 (Definitions) is amended by adding "Porte-Cocheres"
1. A passageway through a building or screen wall designed to let vehicles pass
from street to an interior courtyard.
2. A roofed structure extending from the entrance of a building over an adjacent
driveway and sheltering those getting in or out of vehicles.
13. Section 202 (Definitions) is amended by deleting the Townhouse definition and
replacing it with the following:
"Townhouse. A single-family dwelling unit constructed in a group of attached units
separated by property lines in which each unit extend from foundation to roof and
with open space on at least two sides."
14. Section 303.4 (Assembly Group A-3) is amended by adding "tutorial services".
15. Section 502.1 (Address identification) is amended by deleting the existing text
in its entirety and replacing it with the following:
ORDINANCE NO. 2025-4646
Page 6 of 50
"502.1 Address identification. An official address, assigned by the Building
Official or his designee, shall be provided and placed pursuant to this section in
such a position as to be clearly visible from the public street or roadway fronting
the property. Addresses placed pursuant to this section shall be a minimum four (4)
inches in height and stroke of minimum one-half (1/2) inch, composed of a durable
material and of a color that provides a contrast to the background itself. The official
address shall be placed a minimum of thirty-six (36) inches and a maximum of
thirty (30) feet in height measured from the ground level. Buildings or structures
located more than fifty (50) feet from the street curb shall have an official address
at least five (5) inches in height. Durable materials used for the official address shall
include, but not be limited to, wood, plastic, metal, weather resistant paint, weather
resistant vinyl, or weather resistant material designed for outside use on a glass
surface. For single family residences, the requirement of this section may be met
by providing a minimum of two (2) inch high numbers on both sides of a U. S.
mailbox located near the curb in front of the house, or a freestanding structure with
numbers at least four (4) inches in height.
A building complex composed of multiple structures or dwellings shall have an
official suite or unit number assigned to each building, suite or tenant as well as a
street address number. If there is sufficient street frontage, each building, suite or
tenant may also be assigned an official street address number. The official street
address number of each structure must be prominently posted on the building so that
it is visible from the nearest public street or designated fire lane. Each number
designated by the Building Official, or his designee, for each individual suite or
unit must be conspicuously posted on each suite or unit.
Commercial buildings with side or rear access in addition to the main entrance,
shall also display the business name and official address on each side or rear door
with characters at least two (2) inches in height. Residential structures which
provide for rear vehicular access from a dedicated public alley, street or designated
fire lane shall conspicuously post an official address at least two
(2) inches in height so that it is visible from the public alley, street or designated fire
lane.
The owner or manager of a building complex, which contains an enclosed shopping
mall, shall submit to the Fire Official four (4) copies of diagrams acceptable to the
Fire Marshal of the entire complex, indicating the location and number of each
business. When a change in a business name or location is made, the owner or
manager shall so advise the Fire Marshal in writing of the change.
When required by the Fire Code Official, address numbers shall be provided in
additional approved locations to facilitate emergency response."
16. Table 803.13 (Interior Wall And Ceiling Finish Requirements by Occupancy) is
amended by deleting the existing text in footnote "d" and replacing it with the
following:
"Class A interior finish material shall be required in all areas of all assembly
occupancies, whether sprinklered or not, except as provided for in notes e and f
below."
17. Section 902.1.2 (Marking on access doors). Is amended by replacing 2 inches with
4 inches.
ORDINANCE NO. 2025-4646 Page 7 of 50
18. Section 903.1 (General) is amended by adding the following text at the end
of said section: "For the purpose of this section, the term "fire area" shall be
replaced with "building area."
19. Section 903.2 (Where Required) is amended by adding the following text at the
end of the section:
In addition to the requirements of this section, an automatic sprinkler system
shall be provided throughout all new buildings and structures as follows:
Where the total building area exceeds 12,000 square feet in area.
2. Where the height exceeds two stories, regardless of area.
20. Section 903.2.1.6 (Assembly Occupancies on Roofs) is amended
by deleting the exception in its entirety.
21. Section 903.2.3 (Group E) is amended by deleting the exception in its entirety.
And adding item "4" to read as follows: Group E, day care facilities, as defined in
Section 203.4.2 of the International Fire Code
22. Section 903.2.4 (Group F-1) is amended by deleting items "2" and "3."
23. Section 903.2.4.2 (Group F-1 distilled spirits) is amended to add: An automatic
sprinkler system shall be provided throughout a Group F-1 fire area used for the
manufacture of distilled spirits involving more than 120 gallons of distilled
spirits (>16% alcohol) in the fire area at anv one time
24. Section 903.2.7 (Group M) No. 2 is amended by replacing "three stories above
grade" with "two stories in height" and by deleting No. 3 in its entirety.
25. Section 903.2.9 (Group S-1) is amended by replacing "three stories above grade"
with "two stories above grade" in item "2" and by replacing "24,000 square feet"
with "12,000 square feet" in item "3."
26. Section 903.2.9.3 (Group S-1 Distilled spirits or wine) is amended to add: An
automatic sprinkler system shall be provided throughout a Group F-1 fire area
used for the manufacture of distilled spirits involving more than 120 gallons of
distilled spirits (>16% alcohol) in the fire area at anv one time.
27. Section 903.2.10 (Group S-2 Parking Garages) is amended by deleting the
exception in its entirety.
28. Section 903.2.11.7 is added:
ORDINANCE NO. 2025-4646
Page 8 of 50
Section 903.2.11.7 Buildings over 12,000 sq. ft. An automatic sprinkler system
shall be installed throughout all buildings over 12,000 sq. ft. and greater, and in all
existing buildings that are enlarged to be 12,000 sq. ft. or greater, and in buildings
greater than 12,000 sq. ft. which are enlarged. For the purpose of this provision,
fire walls, fire barriers, or horizontal assemblies shall not define separate buildings.
29. Section 903.2.13 (Porte-cocheres). All porte-cocheres shall be protected with fire
sprinklers.
Exception: Porte-cocheres of non-combustible construction or a distance of 10 foot
or greater.
30. Section 903.3.1.1.1 (Exempt locations) is amended by deleting item number 4.
31. Section 903.3.1.2.2 (Corridors and balconies in the means of egress) is amended as
follows:
903.3.1.2.2 (Corridors and balconies in the means of egress). Sprinkler protection
shall be provided in all corridors and for all balconies in the means of egress.
32. Section 903.3.1.2.3 (Attics). is amended by deleting items 3.4 and 4.5
33. Section 904.3.5, (Monitoring). is amended by deleting the section and replacing it
with:
904.3.5 (Monitoring). All automatic fire extinguishing system shall be monitored
with a system in accordance with NFPA 72.
34. Section 905.1, (General). is amended by adding Section 905.1.1, Safety factor, as
follows:
905.1.1 (Safety factor). All standpipe systems with the exception of manual
standpipes shall be designed with a minimum safety factor of 5 PSI or 10% of
required pressure (whichever is greater) taken at the source for the hydraulically
most demanding system and/or outlet.
35. Section 905.4, (Location of Class I standpipe hose connections), is amended as
follows with all other code text to remain as written:
905.4 (Location of Class I standpipe hose connections). Class I standpipe hose
connections shall be provided in all of the following locations:
1. In every required interior exit stairway, a hose connection shall be provided
for each story above and below grade plane. Hose connections shall be
located at [the main] an intermediate [floor] landing between stories unless
otherwise approved by the fire code official.
36. Section 906.1 (Where required) is amended by deleting exception 1 and 2 all
others remain the same.
37. Section 907.2.1 (Group A) is amended by adding the following section:
ORDINANCE NO. 2025-4646
Page 9 of 50
907.2.1.3 Group A-2. An automatic alarm system shall be provided for fire
areas containing Group A-2 occupancies that have an occupant load of 100
or more.
38. Section 907.2.7.1.1, (Occupant notification). is repealed in its entirety.
39. Section 907.2.8.2, (Automatic smoke detection system), is hereby amended to read
as follows:
907.2.8.2 (Automatic smoke detection system). An automatic smoke detection
system that activates the occupant notification system in accordance with Section
907.5 shall be installed throughout all interior corridors serving sleeping units.
The automatic smoke detection system requirement is met only by the installation
of smoke or beam detectors whenever possible. If environmental conditions do
not allow the installation of smoke detectors, fire alarm heat detectors may be
used on a limited basis when approved by the fire code official.
Exception: An automatic smoke detection system is not required in buildings
that do not have interior corridors serving sleeping units and where each
sleeping unit has a means of egress door opening directly to an exit or to an
exterior exit access that leads directly to an exit.
Exception: An automatic smoke detection system is not required in buildings
that do not have interior corridors serving sleeping units and where each
sleeping unit has a means of egress door opening directly to an exit or to an
exterior exit access that leads directly to an exit.
40. Section 907.2.13.2 (Fire department communication system) is deleted in its
entirety
41. Section 907.2.13.1.2, (Duct smoke detection), is amended to read as
follows:
907.2.13.1.2 (Duct smoke detection). Duct smoke detectors complying with
Section 907.3.1 shall be located in accordance with the NFPA 90A: Standard for the
Installation of Air -Conditioning and Ventilating Systems or as follows:
1. In the main return air and exhaust air plenum of each air-conditioning system
having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s).
Such detectors shall be located in a serviceable area downstream of the last duct
inlet.
2. At each connection to a vertical duct or riser serving two or more stories from a
return air duct or plenum of an air-conditioning system. In Group R-1 and R-2
occupancies, a smoke detector is allowed to be used in each return air riser
carrying not more than 5,000 cfm (2.4 m3/s) and serving not more than 10 air -
inlet openings.
42. Section 907.2, (Where required - new buildings and structures), is amended by
ORDINANCE NO. 2025-4646
Page 10 of 50
adding Section 907.2.24, Fire alarm systems for property protection, to read as
follows:
907.2.24 (Fire alarm systems for property protection). Fire alarm systems
dedicated solely to the protection of property are permitted to be installed in
facilities where a fire alarm system is not required by other sections of this code
or the International Building Code provided the following conditions are met:
1. Any and all automatic detection is installed, located and maintained in
accordance with the requirements of NFPA 72 and a documentation cabinet as
required by NFPA 72 is provided and installed.
2. The installed system is monitored by a supervising station which provides
remote and central station service.
3.One manual means of activation is installed in an approved location
4. Where the fire alarm system control unit is located in an area that is not
readily accessible to response personnel, a remote fire alarm system
annunciator panel is installed.
43. Section 907.2, (Where Required) — is amended by adding Section 907.2.25, Fire
alarm systems for property protection, to read as follows:
907.2.25.1 (Group R-4) Fire alarm systems and smoke alarms shall be installed in
Group R-4 occupancies as required in Sections 907.2.10.1 through 907.2.10.3.
Section 907.2.10.1 Manual fire alarm system. A manual fire alarm system that
activates the occupant notification system in accordance with Section 907.5 shall
be installed in Group R-4 occupancies.
Exceptions:
1. A manual fire alarm system is not required in buildings not more than two
stories in height where all individual sleeping units and contiguous attic and
crawl spaces to those units are separated from each other and public or common
areas by not less than 1-hour fire partitions and each individual sleeping unit has
an exit directly to a public way, egress court or yard.
2. Manual fire alarm boxes are not required throughout the building where all of the
following conditions are met:
2.1. The building is equipped throughout with an automatic
sprinkler system installed in accordance with Section
903.3.1.1 or 903.3.1.2.
2.2. The notification appliances will activate upon sprinkler water flow.
2.3. Not fewer than one manual fire alarm box is installed at an
approved location.
3. Manual fire alarm boxes in resident or patient sleeping areas shall not be required
ORDINANCE NO. 2025-4646
Page 11 of 50
at exits where located at all nurses' control stations or other constantly attended
staff locations, provided such stations are visible and continuously accessible and
that the distances of travel required in Section 907.4.2.1 are not exceeded.
907.2.25.2 (Automatic smoke detection system). An automatic smoke detection
system that activates the occupant notification system in accordance with Section
907.5 shall be installed in corridors, waiting areas open to corridors and habitable
spaces other than sleeping units and kitchens.
Exceptions:
1. Smoke detection in habitable spaces is not required where the facility is equipped
throughout with an automatic sprinkler system installed in accordance with
Section 903.3.1.1.
2. An automatic smoke detection system is not required in buildings that do not
have interior corridors serving sleeping units and where each sleeping unit has a
means of egress door opening directly to an exit or to an exterior exit access that
leads directly to an exit.
907.2.25.3 (Smoke alarms). Single- and multiple -station smoke alarms shall be
installed in accordance with Section 907.2.11.
44. Section 907.3.1, (Duct smoke detectors), is amended to read as follows:
907.3.1(Duct smoke detectors). Smoke detectors installed in ducts shall be listed for
the air velocity, temperature and humidity present in the duct. Duct smoke detectors
shall be connected to the building's fire alarm control unit where a fire alarm system
is required by Section 907.2. Activation of a duct smoke detector shall initiate a
visible and audible supervisory signal at a Central monitoring station and shall
perform the intended fire safety function in accordance with this code, NFPA 90A:
Standard for the Installation of Air -Conditioning and Ventilating Systems and the
International Mechanical Code. In facilities that are required to be monitored by a
supervising station, duct smoke detectors shall report only as a supervisory signal
and not as a fire alarm. They shall not be used as a substitute for required open area
detection. 2021 International Building- Related Code.
Exceptions:
1. In occupancies not required to be equipped with a fire alarm system,
actuation of a smoke detector shall activate a visible and an audible signal in
an approved location. Smoke detector trouble conditions shall activate a
visible or audible signal in an approved location and shall be identified as air
duct detector trouble.
2. For fire alarm systems which cannot be programmed for supervisory
signals, duct detectors shall be allowed to activate the alarm signal.
45. Section 907.3., (Fire safety functions), is amended by adding 907.3.5, Fire
alarm systems - emergency control, as follows:
907.3.5 (Fire alarm systems - emergency control). At a minimum, the following
ORDINANCE NO. 2025-4646
Page 12 of 50
functions, where provided, shall be activated by the fire alarm system:
Elevator capture and control in accordance with ASME/ANSI A17.1b,
Safety Code for Elevators and Escalators.
2. Release of automatic door closures and hold open devices
3. Stairwell and/or elevator shaft pressurization.
4. Smoke management and/or smoke control systems.
5. Initiation of automatic fire extinguishing equipment.
6. Emergency lighting control.
7. Unlocking of doors.
8. Emergency shutoff of gas and fuel supplies that may be hazardous
provided the continuation of service is not essential to the
preservation of life.
9. Emergency shutoff of audio systems for sound reinforcement or
entertainment (i.e. music systems, systems for announcement and broadcast
which are separate from public address systems) provided that such systems
are not used to issue emergency instructions.
10. Emergency shutoff of systems used for the creation of displays or
special effects (i.e. lighting effects, laser light shows, projection
equipment).
46. Section 907.4.2.1, (Location), is amended to add the Exception to read as follows:
907.4.2.1 (Location). Manual fire alarm boxes shall be located not more than 5
feet (1524 mm) from the entrance to each exit. In buildings not protected by an
automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2,
additional manual fire alarm boxes shall be located so that the distance of
travel to the nearest box does not exceed 200 feet (60 960 mm).
Exception: Where construction of the building prohibits the proper installation of a
pull station (e.g. glass walls, interior brick or rock walls), a pull station shall be
allowed to be located in the normal path of egress, where approved by the Fire
Marshal or designee.
47. Section 907.5.1.1, (Presignal feature), is amended to read as follows:
907.5.1.1 (Presignal feature and positive alarm sequences). A presignal feature or
Positive Alarm Sequence as defined in NFPA 72 shall not be installed unless
approved by the fire code official. Request to use a presignal feature or a Positive
Alarm Sequence must be submitted in writing to the Fire Marshal and approval
granted before installation. Where a presignal feature or Positive Alarm Sequence
is provided, a signal shall be annunciated at a constantly attended location approved
ORDINANCE NO. 2025-4646
Page 13 of 50
by the fire code official, so that occupant notification can be activated in 2021
International Building- Related Codes the event of fire or other emergency. When
approved by the fire code official, the presignal feature or Positive Alarm Sequence
shall be implemented in accordance with the requirements of NFPA 72.
48. Section 907.5.2.3, (Visible alarms), is amended by adding a subsection
907.5.2.3.4, Group R-2 sleeping areas, and Section 907.5.2.3.5, Combination
devices, to read as follows:
907.5.2.3.4 (Group R-2 sleeping areas). Living rooms in Group R-2
occupancies shall have audible notification appliances that meet the sleeping area
audible requirements of NFPA 72, Chapter 18, Section 18.4.5, and Subsection
18.4.5.1. When such units are required to be equipped with visible notification
for the hearing impaired or when such units are designated as accessible in
accordance with ICC/ANSI A117.1, combination audible and visible notification
appliances that meet both the sleeping area audible requirements of NFPA 72,
Chapter 18, Section 18.4.5, Subsection 18.4.5.1 and the effective intensity
settings of NFPA 72, Chapter 18.5.5.7.2 shall be installed.
907.5.2.3.5 (Combination devices). Combination 120 VAC single or multiple -
station smoke detectors with an onboard visible notification appliance if utilized
to meet the requirements of Section 907.2.11, will not be given credit for
meeting the visible alarm notification requirements of Section 907.5.2.3.3 if
these devices do not have the capability of supplying backup power for the
visible notification appliance portion of the device. Should such devices be
utilized to comply with Section 907.2.11, the visible appliance side of the device
shall flash in synchronization with the notification appliances required in the
unit.
49. Section 907.6.3, (Initiating device identification), is amended to read as follows
with exceptions to remain as written:
907.6.3 (Initiating device identification). The fire alarm system shall identify the
specific initiating device address, location, device type, and floor level where
applicable and status including indication of normal, alarm, trouble and
supervisory status, to the fire alarm panel, annunciator panel and to the
supervising station as appropriate.
50. Section 907.5.2.3.1 (Public Use Areas and Common Use Areas) is amended
by deleting the exception and adding Section 907.5.2.3.1.1 to read as
follows:
Section 907.5.2.3.1.1 (Employee Work Areas). Where a fire alarm and
detection system is required, employee work areas shall be provided with
devices that provide audible and visible alarm notification.
51. Section 912.2.1, (Visible location), is amended by adding the following sentence
to the end of that section to read as follows:
912.2.1 (Visible location). Fire department connections shall be located on the
ORDINANCE NO. 2025-4646
Page 14 of 50
street side of buildings or facing approved fire apparatus access roads, fully
visible and recognizable from the street, fire apparatus access road or nearest
point of fire department vehicle access or as otherwise approved by the fire code
official. The fire department connection shall be identified by a sign installed
above the connection with the letters "FDC" not less than 6 inches high and
mounted at least 3 feet above the FDC to the bottom edge of the sign unless
approved by the fire code official and if multiple FDC's a sign identifying the
corresponding riser.
52. Section 912.2.2, (Existing buildings), is amended to read as follows:
912.2.2 (Existing buildings). On existing buildings, wherever the fire department
connection is not visible to approaching fire apparatus, the fire department
connection shall be indicated by an approved sign mounted on the street front or
on the side of the building. Such sign shall have the letters "FDC" not less than 6
inches (152 mm) high and words in letters not less than 2 inches (51 mm) high or
an arrow to indicate the location. Signs shall be mounted no lower than 7 feet
from grade to the bottom edge of the sign and are subject to the approval of the
fire code official.
53. Section 912.2 (Location), is amended to add the following:
Section 912.2.3 (Distance). Fire department connection shall not be located
further than 100 feet from the fire hydrant measured by lay of hose from the
engine.
54. Section 912.4.1, (Locking fire department connection caps), is amended to read as
follows:
912.4.1 (Locking fire department connection caps). Locking caps are required on
all fire department connections for water -based fire protection systems including
but not limited to FDC's and standpipes.
55. Section 912, (Fire Department Connections), is amended by adding Section
912.7, Location and type, as follows:
912.7 (Location and type). Sprinkler system and standpipe fire department hose
connections shall be as follows:
1. Within 40 feet of a public street, approved fire lane, or access roadway
2. Within 100 feet of an approved fire hydrant measured per hose lay.
3. All structures are required to have a five inch "Storz" connection.
a. Where provided, the five inch "Storz" inlet shall be installed at a
30-degree angle pointing down.
i. Exception: NFPA 13R system requiring less than 250 gpm.
4. Minimum of two feet above finished grade and a maximum of four feet
above finished grade for standard inlets and minimum of 30 inches at
lowest point above finished grade and maximum of four feet above
ORDINANCE NO. 2025-4646 Page 15 of 50
finished grade for the five inch "Storz" inlet.
5. Freestanding FDCs shall be installed a minimum of one foot and a
maximum of seven feet from the gutter face of the curb.
6. The Fire Code Official shall approve the location of freestanding
fire department connections. Freestanding FDCs must be physically
protected against impact per the requirements of Section 312 or
other approved means.
7. Fire department connections for H occupancies shall be freestanding,
remote and located as determined by the fire code official.
8. Fire department connections for systems protecting fuel storage
tanks shall be freestanding, remote and located as determined by
the fire code official.
56. Section 1004.5.1 (Increased occupant load) is amended by deleting the section in
its entirety.
57. Section 1004.9 (Posting of occupant load) is amended by adding the following
text to the end of said section:
"For the purposes of this section, the occupant load shall be the number of
occupants computed at the rate of one occupant per unit of area as prescribed in
Table 1004.5."
58. Section 1612.3 (Establishment of flood hazard areas) is amended by inserting
"Brazos County" for name of jurisdiction and "July 2, 1992 or February 9, 2000"
for the date of issuance.
59. Section 1907 (Slab -on -ground) is amended by adding Section 1907.1.1 to read as
follows:
"Section 1907.1.1 Minimum foundation standard. All slabs -on -grade with turned -
down footings shall comply with the Minimum Foundation Standard as shown in
figure 1."
ORDINANCE NO. 2025-4646
Page 16 of 50
Figure 1
/s 8ARS
a 16' o,C.
— 5-1/2'
�
-• T-....� �f
7 7/2'
4OR6 \fir \f\�� \ti\� OR6 E
6 IL POLY BARS / c �� WSVAPOR f !
HARRIER 3 ry �f
3" SPRRUPS
/3 HARS 948- CC. 'i 1
4 go. W`U 024' O.C.
414' 4' w OR 6 ga. WWM 978, O.C.
INTERIOR BEAM EXTERIOR REAM
Bar Min, Lap. Min. Radius
Size Inches of &ends
/ is /I 13 12" 15116 " 1
.... \\ #4 12" 1-114"
/A. /i / #5 15" 1-91116"_�
6" min. #6 20" 2-1f ¢"
I #7 26" 2-5/8"
INTERIOR SLAB DROP 1 18 35" 3"
GENERAL NOTES:
1 , Exterior beam shall extend a minimum of 6 'inches into undisturbed soil or fill
which is compacted to 95% Standard Proctor (ASTM D 698) within (±) 23 of optimum
moisture content. All fill material shall have a Plasticity Index (P.1.) between 5 and 18,
2. Interior beams that exceed 60 ft. in length must be a min_ of 30' deep.
3. Maximum beam spacing shall be 15 feet and shall be continuous over the length
or width of the foundati n.
4. Steel to be set to clear are earth minimum 3", wood or steel forms
by 1-1/2".
5. Minimum concrete specified compression strength shall be 3000 psi 0 28 days.
6. Masonry fireplace footings shall be a minimum of 30" deep with 2 mats of
#5*s 0 12" O.C. both ways.
7. These minimum standards shall apply -to oil foundations.
Exceptions:
A. Foundations for ternporary buildins and permanent buildings not exceeding one
story in height and 406 sg
quore feet in area.
B. Foundations designed by an Architect registered in the State of Texas or a
civil/structural Engineer registered in the State of Texas and approved for use
by the Building Official_
8. All foundations designed by an Architect or Engineer shall be installed as designed.
Revisions and exceptions must be submitted in writing by the Architect or Engineer
and approved by the Building Official.
9. Reinforcing steei shall be grade 60 (grade 40 allowed for stirrups only).
1 All deformations shall meet ASTM A515,
Imo. DESMpnin i °ATIs �i$, CITY OF COLLEGE STATION
I I (WBUILDING DIVISION
MINIMUM FOUNDATION STANDARDS
I I A�
3-48
Rev. 061136
1. APPENDIX D (FIRE DISTRICTS) is hereby adopted.
ORDINANCE NO. 2025-4646
Page 17 of 50
Sec. 103-133. - Fire limits.
The fire district referenced in any code or ordinance adopted by the City shall be construed to be the
following described area.
1. Beginning at the south corner of Farm Highway No. 60 and Old Highway No. 6, Block 8
Boyett Addition;
Thence northeast along center of Farm Highway No. 60 through Blocks 8,1, and 2 to east
corner of Tauber Street and Farm Highway No. 60;
Thence northwest approximately 189 feet;
Thence southwest to east corner of Block 1, Lot 21, to corner of Main and Patricia Streets;
Thence northwest approximately 50 feet;
Thence southwest approximately 190 feet which includes Lots 21 to 26 inclusive, also
Block 1, Boyett Addition;
Thence northwest approximately 150 feet to the Church Avenue;
Thence southwest approximately 52 feet to Patricia Street which includes Lots 18 to 27
and 28, Block 1, Boyett Addition;
Thence southwest on Patricia Street to Old Highway No. 6;
Thence southeast approximately 200 feet along center of Old Highway No. 6 to the place
of beginning.
2. Save and except the area described as follows:
Beginning at the intersection of the northwest right-of-way line of the University Drive
and the northeast right-of-way line of Boyett Street;
Thence northwest along the northeast right-of-way line of Boyett Street to the southeast
right-of-way line of Patricia Street;
Thence northeast along the southeast right-of-way line of Patricia Street approximately
235 feet;
Thence southeast through Lot. No. 11, Block No. 1, Boyett addition, 25 feet from and
parallel to the line between Lot No. 11 and Lot No. 12 to the northwest right-of-way line
of University Drive;
Thence southwest along the northwest right-of-way line of University Drive to the place
of beginning and being all of Lot No. 13, all of Lot No. 12, and the southwest 25 feet of
Lot No. 11, Block No. 1, Boyett Addition.
ORDINANCE NO. 2025-4646
Page 18 of 50
3. Beginning at the corner of George Bush Drive and Montclair Street, Block 8, West Park
Addition;
Thence southwest along centerline to Highlands Street, which includes Lots 1 to 13
inclusive;
Thence southeast along centerline of Highlands Street, 100 feet to alley;
Thence northeast to east corner of Lot No. 1, Block No. 8, Montclair Avenue;
Thence northwest 100 feet to place of beginning.
ORDINANCE NO. 2025-4646 Page 19 of 50
Sec. 103-134. — Amendments to the International Residential Code.
The International Residential Code adopted by reference in Section 101.4, 2024 International
Building Code, is hereby amended as follows:
1. Section R102.4 (Referenced codes and standards) is amended by adding the following to
said section:
"Any reference to the ICC Electrical Code shall mean the National Electrical Code, as
adopted and amended by the City of College Station."
(Reason: The City of College Station has adopted the National Electrical Code to
regulate electrical installations.)
2. Section R105.2 (Work exempt from permit) is amended by deleting number one under
"Building" and replacing it with the following:
"1. One detached accessory structure per residential lot, provided the floor area does not
exceed 120 square feet and the structure complies with an of the following:
a. The accessory structure is not located in a surface drainage easement.
b. The accessory structure is not permanently affixed to the ground.
c. The accessory structure is located in the rear yard.
d. The accessory structure is not provided with utilities (sewer, water, gas or
electricity).
(Reason: this amendment allows a small accessory structure without utilities in the
rear yard. Area restriction is consistent with language in the IBC.)
3. Section R105.2 (Work exempt from permit) is amended by deleting number ten under
"Building" and replacing with the following:
"10. Uncovered decks, patios or other raised floor surfaces located not more
than 30 inches above adjacent grade and are not attached to a dwelling."
(Reason: Guardrail provisions become effective on decks, porches or other raised
surfaces that are located more than 30 inches from adjacent grade.)
4. Section R105.2.4 is added to read as follows:
"R105.2.4 Homeowner permit. A property owner may obtain a building permit to
perform work on a building owned and occupied by him as his homestead without
registering with the City as a contractor. However, work involving the electrical,
plumbing and mechanical systems must be permitted and installedby licensed
contractors."
Reason: Allows a homeowner to obtain a building permit for work on his
omestead.)
5. Section R106.3.1 (Approval of construction documents) is amended by deleting
the last sentence in said section.
(Reason: The last sentence requires one set of construction documents be returned to
the applicant and kept at the site during construction. It is not consistent with local
practice to require two sets of construction documents, returning one set to the
applicant, for-1 & 2 family dwellings.)
6. Section RI 08.5. (Refunds) is amended by deleting the text in said section and replacing it
with the following:
"The City Manager or his designee is authorized to establish a refund policy."
(Reason: A refund policy for permit fees already exists. This amendment also
makes the fee refund requirement consistent with the other I -Codes)
7. Section R109.1.1 (Foundation Inspection) is amended by adding the following to the end
of said section:
ORDINANCE NO. 2025-4646
Page 20 of 50
"The Building Official shall have the authority to require a form survey to verify
building setbacks. Such survey shall be provided to the Building Official prior to
placement of concrete and prepared by a surveyor licensed to perform work in the State
of Texas."
(Reason: Gives the building official the authority to require a form survey when
building placement is critical. A survey would likely be required for zero lot line
construction and instances where the building is located on or near the building
setback line on one or more sides.)
8. Section R112 (Means of Appeals) is amended by deleting the section in its entirety.
Reason: The City has already provided for the establishment of the Construction
Board of Adjustments and Appeals in Section 1(A), Chapter 3, College Station
Code of Ordinances.)
9. Section R202 (Definitions) is also amended by adding the following definitions:
Air Gap, Irrigation System. A complete physical separation between the free flowing
discharge end of a potable water supply pipeline and an open or non -pressure receiving
vessel.
Atmospheric Vacuum Breaker. An assembly containing an air inlet valve, a check seat,
and an air inlet port. The flow of water into the body causes the air inlet valve to close the
air inlet port. When the flow of water stops the air inlet valve falls and forms a check
against back-siphonage. At the same time it opens the air inlet port allowing air to enter
and satisfy the vacuum. Also known as an Atmospheric Vacuum Breaker Back-
Siphonage Prevention Assembly.
Backflow Prevention, Irrigation System. The mechanical prevention of reverse flow, or
back siphonage, of nonpotable water from an irrigation system into the potable water
source.
Backflow Prevention Assembly. Any assembly used to prevent backflow into a potable
water system. The type of assembly used is based on the existing or potential degree of
health hazard and backflow condition.
Completion of Irrigation System Installation. When the landscape irrigation system
has been installed, all minimum standards met, all tests performed, and the irrigator is
satisfied that the system is operating correctly.
Consulting, Irrigation System. The act of providing advice, guidance, review or
recommendations related to landscape irrigation systems.
Cross -Connection. An actual or potential connection between a potable water source
and an irrigation system that may contain contaminates or pollutants or any source of
water that has been treated to a lesser degree in the treatment process.
Design, Irrigation System. The act of determining the various elements of a landscape
irrigation system that will include, but not be limited to, elements such as collecting site
specific information, defining the scope of the project, defining plant watering needs,
selecting and laying out emission devices, locating system components, conducting
hydraulics calculations, identifying any local regulatory requirements, or scheduling
irrigation work at a site. Completion of the various components will result in an irrigation
plan.
Design Pressure, Irrigation System. The pressure that is required for an emission
device to operate properly. Design pressure is calculated by adding the operating
pressure necessary at an emission device to the total of all pressure losses accumulated
from an emission device to the water source.
Double Check Valve. An assembly that is composed of two independently acting,
approved check valves, including tightly closed resilient seated shutoff valves attached at
each end of the assembly and fitted with properly located resilient seated test cocks. Also
ORDINANCE NO. 2025-4646
Page 21 of 50
known as a Double Check Valve Backflow Prevention Assembly.
Emission Device. Any device that is contained within an irrigation system and that is
used to apply water. Common emission devices in an irrigation system include, but are
not limited to, spray and rotary sprinkler heads, and drip irrigation emitters.
Employed, Irrigation Systems. Engaged or hired to provide consulting services or
perform any activity relating to the sale, design, installation, maintenance, alteration,
repair, or service to irrigation systems. A person is employed if that person is in an
employer -employee relationship as defined by Internal Revenue Code, 26 United States
Code Service, §3212(d) based on the behavioral control, financial control, and the type of
relationship involved in performing employment related tasks.
Head -to -Head Spacing, Irrigation System. The spacing of spray or rotary heads equal
to the manufacturer's published radius of the head.
Health Hazard, Irrigation System. A cross -connection or potential cross -connection with
an irrigation system that involves any substance that may, if introduced into the potable
water supply, cause death or illness, spread disease, or have a high probability of
causing such effects.
Hydraulics. The science of dynamic and static water; the mathematical computation of
determining pressure losses and pressure requirements of an irrigation system.
Installer, Irrigation System. A person who actually connects an irrigation system to a
private or public raw or potable water supply system or any water supply, who is licensed
according to Title 30, Texas Administrative Code, Chapter 30 (relating to Occupational
Licenses and Registrations).
Irrigation Inspector. A person who inspects irrigation systems and performs other
enforcement duties for a municipality or water district as an employee or as a contractor
and is required to be licensed under Title 30, Texas Administrative Code, Chapter 30
(relating to Occupational Licenses and Registrations).
Irrigation Plan. A scaled drawing of a landscape irrigation system which lists required
information, the scope of the project, and represents the changes made in the installation
of the irrigation system.
Irrigation Services. Selling, designing, installing, maintaining, altering, repairing,
servicing, permitting, providing consulting services regarding, or connecting an irrigation
system to a water supply.
Irrigation System. An assembly of component parts, including the backflow device and
all equipment downstream, that is permanently installed for the controlled distribution and
conservation of water to irrigate any type of landscape vegetation in any location, and/or
to reduce dust or control erosion. This term does not include a system that is used on or
by an agricultural operation as defined by Texas Agricultural Code, §251.002.
Irrigation Technician. A person who works under the supervision of a licensed irrigator
to install, maintain, alter, repair, service or supervise installation of an irrigation system,
including the connection of such system in or to a private or public, raw or potable water
supply system or any water supply, and who is required to be licensed under Title 30,
Texas Administrative Code, Chapter 30 (relating to Occupational Licenses and
Registrations).
Irrigation Zone. A subdivision of an irrigation system with a matched precipitation rate
based on plant material type (such as turf, shrubs, or trees), microclimate factors (such
as sun/shade ratio), topographic features (such as slope) and soil conditions (such as
sand, loam, clay, or combination) or for hydrological control.
Irrigator. A person who sells, designs, offers consultations regarding, installs, maintains,
alters, repairs, services or supervises the installation of an irrigation system, including the
connection of such system to a private or public, raw or potable water supply system or
ORDINANCE NO. 2025-4646
Page 22 of 50
any water supply, and who is required to be licensed under Title 30, Texas Administrative
Code, Chapter 30.
Irrigator -in -Charge. The irrigator responsible for all irrigation work performed by an
exempt business owner, including, but not limited to obtaining permits, developing design
plans, supervising the work of other irrigators or irrigation technicians, and installing,
selling, maintaining, altering, repairing, or servicing a landscape irrigation system.
Landscape Irrigation. The science of applying the necessary amount of water to
promote or sustain healthy growth of plant material or turf.
Irrigation License. An occupational license that is issued by the Texas Commission on
Environmental Quality under Title 30, Texas Administrative Code, Chapter 30 to an
individual that authorizes the individual to engage in an activity that is covered by Title 30,
Texas Administrative Code, Chapter 30.
Mainline, Irrigation System. A pipe within an irrigation system that delivers water from
the water source to the individual zone valves.
Maintenance Checklist, Irrigation System. A document made available to the irrigation
system's owner or owner's representative that contains information regarding the
operation and maintenance of the irrigation system, including, but not limited to: checking
and repairing the irrigation system, setting the automatic controller, checking the rain or
moisture sensor, cleaning filters, pruning grass and plants away from irrigation emitters,
using and operating the irrigation system, the precipitation rates of each irrigation zone
within the system, any water conservation measures currently in effect from the water
purveyor, the name of the water purveyor, a suggested seasonal or monthly watering
schedule based on current evapotranspiration data for the geographic region, and the
minimum water requirements for the plant material in each zone based on the soil type
and plant material where the system is installed.
Major Maintenance, Alteration, Repair, or Service (Irrigation System). Any activity
that involves opening to the atmosphere the irrigation main line at any point prior to the
discharge side of any irrigation zone control valve. This includes, but is not limited to,
repairing or connecting into a main supply pipe, replacing a zone control valve, or
repairing a zone control valve in a manner that opens the system to the atmosphere.
Master Valve, Irrigation System. A remote control valve located after the backflow
prevention device that controls the flow of water to the irrigation system mainline.
Matched Precipitation Rate. The condition in which all sprinkler heads within an
irrigation zone apply water at the same rate.
New Installation, Irrigation System. An irrigation system installed at a location where
one did not previously exist .
Pass -through Contract. A written contract between a contractor or builder and a
licensed irrigator or exempt business owner to perform part or all of the irrigation services
relating to an irrigation system.
Pressure Vacuum Breaker. An assembly containing an independently operating
internally loaded check valve and an independently operating loaded air inlet valve
located on the discharge side of the check valve. Also known as a Pressure Vacuum
Breaker Back-siphonage Prevention Assembly.
Reclaimed Water. Domestic or municipal wastewater which has been treated to a quality
suitable for beneficial use, such as landscape irrigation.
Records of Landscape Irrigation Activities. The irrigation plans, contracts, warranty
information, invoices, copies of permits, and other documents that relate to the
installation, maintenance, alteration, repair, or service of a landscape irrigation system.
Reduced Pressure Principle Backflow Prevention Assembly. An assembly containing
two independently acting approved check valves together with a hydraulically operating
ORDINANCE NO. 2025-4646
Page 23 of 50
mechanically independent pressure differential relief valve located between the two
check valves and below the first check valve.
Static Water Pressure. The pressure of water when it is not moving.
Supervision, Landscape Irrigation. The on-the-job oversight and direction by a
licensed irrigator who is fulfilling his or her professional responsibility to the client and/or
employer in compliance with local or state requirements. Also a licensed installer working
under the direction of a licensed irrigator or an irrigation technician who is working under
the direction of a licensed irrigator to install, maintain, alter, repair or service an irrigation
system.
Water Conservation, Irrigation System. The design, installation, service, and operation
of an irrigation system in a manner that prevents the waste of water, promotes the most
efficient use of water, and applies the least amount of water that is required to maintain
healthy individual plant material or turf, reduce dust, and control erosion.
Zone Flow. A measurement, in gallons per minute or gallons per hour, of the actual flow
of water through a zone valve, calculated by individually opening each zone valve and
obtaining a valid reading after the pressure has stabilized. For design purposes, the zone
flow is the total flow of all nozzles in the zone at a specific pressure.
Zone Valve, Irrigation System. An automatic valve that controls a single zone of a
landscape irrigation system.
10. Section R302.1 (Exterior walls) is amended by deleting the existing text and replacing it
with the following:
R302.1 Exterior walls. Exterior walls with a fire separation distance less than 3 feet shall
have not less than a one hour fire -resistive rating with exposure from both sides. The above
provisions shall not apply to walls which are perpendicular to the line used to determine the
fire separation distance.
Exception: Tool and storage sheds, playhouses and similar structures exempted from
permits by Section R105.2 are not required to provide wall protection based on location on
the lot.
Projections. Projections may extend beyond the exterior wall on zero lot line construction.
Projections shall be constructed from non-combustible material on the underside and may
allow manufactured perforated soffit material installed for attic ventilation. The soffit may
project a maximum of 18 inches, excluding non-combustible gutters, over the adjacent
property line.
Exception: Tool and storage sheds, playhouses and similar structures exempted from
permits by Section R 105.2 shall not extend over the lot line in zero lot line construction.
Combustibles in maintenance easement. The construction of any structure utilizing
combustible material or the storage of combustible material is prohibited within the
maintenance easement. The term "maintenance easement" is defined in Article 11 of the
UDO.
Exception: A wood fence may be installed in the maintenance easement.
(Reason: Provides for protected overhangs on "zero lot line" construction.)
11. Section R302.5.1 Opening protection; change to read as follows:
R302.5.1 Opening protection. Openings from a private garage directly into a room used
for sleeping purposes shall not -be permitted. Other openings between the garage and
dwelling unit shall be equipped with solid wood doors not less than 1-3/8 inches (3g mm)
ORDINANCE NO. 2025-4646
Page 24 of 50
in thickness, solid or honeycomb -core steel doors not less than 1-3/8 inches (35 mm) thick,
or 20-minute fire -rated doors.
(Reason: Absence of data linking self -closing devices to increased safety. Self -
closing devices often fail to close the door entirely.)
12. Section R302.6 (Dwelling -unit garage fire separation) is amended by adding the following
exception:
"Exception: One unprotected attic access opening, not exceeding 30 inches by 54
inches in size, is allowed per garage."
13. Section R320.5 (Continuity) is amended by deleting the following text in said section:
"Handrail ends shall be returned or shall terminate in newel posts or safety terminals."
(Reason: It is not consistent with local practice to require handrails to be returned in
residential construction.)
14. Section R309 (Automatic Fire Sprinkler Systems) is amended by deleting the section in
its entirety.
(Reason: State Law passed stating that municipalities could not require an automatic
fire sprinkler system to be installed in one -and -two family dwellings.)
15. Section R305.2 (Chemical termiticide treatment) is amended by adding the following to
the end of said section:
"The method of application and contractor hired to apply the chemicals shall submit to
the Building Department when applying for the Building Permit, and verification of the
application turned in prior to issuance of the Certificate of Occupancy."
(Reason: This will allow the Building Department to verify that the structure has
been treated for termites.)
16. Section R308.1 (Address Identification) is amended by deleting the existing text in its
entirety and replacing it with the following:
"Premises identification shall comply with Section 502.1, International Building Code,
as amended."
(Reason: The IBC, as amended, provides a detailed standard for premises
identification)
17. Section R306.2.1 (Elevation requirements) is amended by deleting the existing text, save
the exception, and replacing it with the following:
1. Buildings and structures shall have the lowest floors elevated in accordance with the
City of College Station Code of Ordinances, Chapter 13 (Flood Hazard Protection)
and the City of College Station Drainage Policy and Design Standards (refer to
Section II.D).
ORDINANCE NO. 2025-4646
Page 25 of 50
2. In areas of shallow flooding (AO Zones), buildings and structures shall have the
lowest floor (including basement) elevated above the highest adjacent grade as the
depth number specified in feet on the Flood Insurance Rate Maps, or at least 2 feet
if a depth number is not specified, plus the additional footage requirements in the
City of College Station Code of Ordinances, Chapter 13 (Flood Hazard Protection)
and the City of College Station Drainage Policy and Design Standards (refer to
Section II.D).
3. Basement floors that are below grade on all sides shall be elevated in accordance
with the City of College Station Code of Ordinances, Chapter 13 (Flood Hazard
Protection) and the City of College Station Drainage Policy and Design Standards
(refer to Section II.D).
(Reason: The revised language eliminates potential conflicts between the IRC and
the City's Floodplain Ordinance.)
18. Section 328.1.1; add to read as follows:
Section 328.1.1 Adjacency to Structural Foundation. Depth of the swimming pool and
spa shall maintain a ratio of 1:1 from the nearest building foundation or footing of a
retaining wall.
Exception: A sealed engineered design drawing of the proposed new structure shall
be submitted for approval.
(Reason: To clarify specific distances for pools and spas.)
19. Section R403.1.3.3 (Slabs -on -ground with turned -down footings) is amended by deleting
the existing text and replacing it with the following to read as follows:
"All slabs -on -ground with turned -down footings shall comply with the minimum
foundation standard in Section 1907.2, International Building Code."
(Reason: Section 1907.2, IBC, references the minimum foundation standard
specifically developed for use in this area.)
20. Chapter 11 (Energy Efficiency) is amended by deleting this chapter in its entirety and
replacing it with the following.
"One -and -two family dwellings shall comply with the 2024 International Energy
Conservation Code as amended."
(Reason: The International Energy Conservation Code and Chapter 11 read the
same, and the State Energy Lab recommended amendments to the International
Energy Conservation Code. So to keep from amending both parts we deleted
Chapter 11.)
21. Section M1305.1.2; change to read as follows:
M1305.1.2 Appliances in attics. Attics containing appliances shall be provided ... {bulk
ORDINANCE NO. 2025-4646
Page 26 of 50
of paragraph unchanged} ... side of the appliance. The clear access opening dimensions
shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), and large enough
to allow removal of the largest appliance. As a minimum, for access to the attic space,
provide one of the following:
1. A permanent stair.
2. A pull down stair with a minimum 300 lb (136 kg) capacity.
3. An access door from an upper floor level.
Exceptions:
1. The passageway and level service space are not required where the appliance is
capable of being serviced and removed through the required opening with the
approval of the code official.
2. Where the passageway is unobstructed and not less than 6 feet (1829 mm) high
and 22 inches (559 mm) wide for its entire length, the passageway shall be not
greater than 50 feet (15,250 mm) in length.
(Reason: To provide a safe means of accessibility to appliances in attics and to allow for
different types of construction limitations
22. Section M1411.9 (Condensate disposal) is amended by deleting the existing text and
replacing with the following:
"Condensate from all cooling coils or evaporators shall be conveyed from the drain pan
outlet to the sanitary sewer system, if available. The condensate drain shall be connected
to the sanitary sewer system in a manner approved by the code official.
Exception: When a sanitary sewer system is not available on the premises, or connection
thereto is not practical, the condensate shall discharge into an approved french drain."
(Reason: This amendment provides more specific requirements for the method of
condensate disposal.)
23. Section M1501.1 (Outdoor discharge) is amended by deleting the last sentence in said
section.
(Reason: It is common local practice to run the exhaust vents to the soffit and ridge
vent to eliminate another roof penetration.)
24. Section M1505.2 (Recirculation of air) is amended by deleting the second sentence in
said section, and replacing it with the following:
"Exhaust air from bathrooms and toilet rooms shall discharge directly to the outdoors or
the vent termination shall be unobstructed and within 6 inches of the soffit vent or ridge
vent."
(Reason: This amendment provides specific requirements if the exhaust air is to
discharge in the attic, and will remain consistent with common local practice.)
ORDINANCE NO. 2025-4646
Page 27 of 50
25. Section G2408.3 (Private garages) is amended by deleting the section in its entirety.
(Reason: It is not consistent with local practice to require appliances located in
private garages to be installed 6 feet above the floor.)
26. Section G2417.1.2 (Repairs and additions) is amended by deleting the existing text in its
entirety and replacing it with the following:
"In the event repairs or additions are made after the pressure test, the affected piping
shall be tested. If approved by the code official minor repairs and additions are not
required to be pressure tested provided the woik is inspected and connections are tested
with a noncorrosive leak -detecting fluid or other leak detecting methods."
(Reason: As written, the code would allow gas pipe repairs and additions to be
tested with a soapsolution. This amendment provides the code official with the
discretion to require a pressure test if deemed appropriate. This amendment is also
consistent with a similar amendment to the IFGC.)
27. Section G2417.4 (Test pressure measurement) is amended by deleting the existing text in
its entirety and replacing it with the following:
"Test pressure measurement shall comply with Section 406.4, 2024 International Fuel
Gas Code, as amended."
(Reason: This amendment provides for the use of the more accurate diaphragm
gauge for gas tests on systems operating at 5 psi or less.)
28. Section G2417.4.1 (Test pressure) is amended by deleting the existing text in its entirety
and replacing it with the following:
"Test pressure shall comply with Section 406.4.1, 2024 International Fuel Gas Code, as
amended."
(Reason: This amendment provides for an elevated standard for gas pressure tests. It
is also consistent with pressure test amendments from previous code editions.)
29. Section P2503.8 (Inspection and testing of backflow prevention devices) is amended by
deleting the section in its entirety and replacing with the following:
"Inspection and testing of backflow prevention devices shall comply with Section 312.10,
2024 International Plumbing Code, as amended."
(_Reason: Consistent with City Council's direction concerning backflow prevention
devices.)
30. P2804.6.1 (Requirements for discharge pipe) is amended by deleting the text in number
five and replacing it with the following:
"Discharge to an indirect waste receptor or to the outdoors."
(Reason: This removes the language that allows the discharge pipe to terminate to
the pan serving the water heater.)
31. Section P2902.5.3 (Lawn irrigation systems) is amended by deleting the existing text in
its entirety and replacing it with the following:
"P2902.5.3 Lawn Irrigation Systems
ORDINANCE NO. 2025-4646
Page 28 of 50
P2902.5.3.1 Valid License Required. Any person who connects an irrigation system to
the water supply within the city or the city's extraterritorial jurisdiction, commonly
referred to as the ETJ, must hold a valid license, as defined by Title 30, Texas
Administrative Code, Chapter 30 and required by Chapter 1903 of the Texas
Occupations Code, or as defined by Chapter 365, Title 22 of the Texas Administrative
Code and required by Chapter 1301 of the Texas Occupations Code.
Exception: A property owner is not required to be licensed in accordance with Texas
Occupations Code, Title 12, §1903.002(c)(1) if he or she is performing irrigation work
in a building or on a premises owned or occupied by the person as the person's home. A
home or property owner who installs an irrigation system must meet the standards
contained in Title 30, Texas Administrative Code, Chapter 344 regarding spacing, water
pressure, spraying water over impervious materials, rain or moisture shut-off devices or
other technology, backflow prevention and isolation valves. See Texas Occupations
Code § 1903.002 for other exemptions to the licensing requirement.
P2902.5.3.2 Permit Required. Any person installing an irrigation system within the
territorial limits or extraterritorial jurisdiction of the city is required to obtain a permit
from the city prior to beginning work on the irrigation system. A completed irrigation
permit application and irrigation plan must be a submitted to the city and approved
before a permit will be issued by the city. The irrigation plan must be in compliance
with the requirements of this section.
Exceptions:
1. An irrigation system that is an on -site sewage disposal system, as defined by
Section
366.002, Health and Safety Code; or
2. An irrigation system used on or by an agricultural operation as defined by
Section 251.002, Agriculture Code; or
3. An irrigation system connected to a groundwater well used by a property owner
strictly for domestic use.
P2902.5.3.3 Backflow Prevention Methods and Devices. Any irrigation system that is
connected to the potable water supply must be connected through a backflow prevention
method approved by the Texas Commission on Environmental Quality (TCEQ). The
backflow prevention device must be approved by the Foundation for Cross -Connection
Control and Hydraulic Research, the University of Southern California, the
International Plumbing Code, or any other laboratory that has equivalent capabilities for
both the laboratory and field evaluation of backflow prevention assemblies. The
backflow prevention device must be installed in accordance with the laboratory
approval standards or if the approval does not include specific installation information,
the manufacturer's current published recommendations. If conditions that present a
health hazard exist, one of the following methods must be used to prevent backflow;
1. An air gap may be used if:
a) there is an unobstructed physical separation; and
b) the distance from the lowest point of the water supply outlet to the flood
rim of the
fixture or assembly into which the outlet discharges is at least one inch or
twice the diameter of the water supply outlet, whichever is greater.
ORDINANCE NO. 2025-4646
Page 29 of 50
2. Reduced pressure principle backflow prevention assemblies may be used if:
a) the device is installed at a minimum of 12 inches above ground in a
location that will
ensure that the assembly will not be submerged; and
b) drainage is provided for any water that may be discharged through the
assembly relief valve.
3. Atmospheric vacuum breakers may only be used as replacements on existing
systems utilizing atmospheric vacuum breakers if:
a) no back -pressure will be present;
b) there are no shutoff valves downstream from the atmospheric vacuum
breaker;
c) the device is installed at a minimum of six inches above any downstream
piping
and the highest downstream opening. Pop-up sprinklers are measured
from the retracted position from the top of the sprinkler;
d) there is no continuous pressure on the supply side of the atmospheric
vacuum breaker for more than 12 hours in any 24-hour period; and
e) a separate atmospheric vacuum breaker is installed on the discharge side
of each irrigation control valve, between the valve and all the emission
devices that the valve
controls.
4. Pressure vacuum breakers may be used if:
a) no back -pressure condition will occur; and
b) the device is installed at a minimum of 12 inches above any downstream
piping and the highest downstream opening. Pop-up sprinklers are
measured from the retracted position from the top of the sprinkler.
All backflow prevention devices used in applications designated as health hazards must
be tested upon installation and annually thereafter.
If there are no conditions that present a health hazard, double check valve backflow
prevention assemblies may be used to prevent backflow if the device is tested upon
installation and test cocks are used for testing only. A double check valve may be
installed below ground i£
1. the double check valve assembly is installed in a vault or other approved
enclosure that which is constructed of a durable material. The vault or
enclosure shall either be of solid (waterproof) construction with an integral
bottom or bottomless to facilitate drainage. If the vault or enclosure is
bottomless, a minimum of four (4) inches of washed gravel shall be installed
below the assembly. The washed gravel shall have a diameter of between 3/8
inch and 3/4 inch (inclusive);
2. the test cocks are plugged with a non-ferrous material (brass, plastic, etc.)
except when the double check valve is being tested;
3. the test cock plugs are threaded, water -tight, and made of non-ferrous
material;
4. a y-type strainer is installed on the inlet side of the double check valve;
5. a minimum clearance of three (3) inches is provided between any fill
material and the bottom of the double check valve to allow space for testing
and repair; and
6. a minimum clearance of four (4) inches is provided on the sides of the double check
valve to test and repair the double check valve. If an existing irrigation system
ORDINANCE NO. 2025-4646
Page 30 of 50
without a backflow-prevention assembly requires major maintenance, alteration,
repair, or service, the system must be connected to the potable water supply through
an approved, properly installed backflow prevention method before any major
maintenance, alteration, repair, or service is performed. If an irrigation system is
connected to a potable water supply through a double check valve, pressure vacuum
breaker, or reduced pressure principle backflow assembly and includes an automatic
master valve on the system, the automatic master valve must be installed on the
discharge side of the backflow prevention assembly. The irrigator shall ensure the
backflow prevention device is tested by a licensed Backflow Prevention Assembly
Tester prior to being placed in service. The tester must be registered with the City of
College Station and the test results must be provided to the local water purveyor and
the irrigation system's owner or owner's representative within ten business days of
testing of the backflow prevention device.
P2902.5.3.4 Specific Conditions and Cross -Connection Control. Before any chemical
is added to an irrigation system connected to the potable water supply, the irrigation
system must be connected through a reduced pressure principle backflow prevention
assembly or air gap.
Connection of any additional water source to an irrigation system that is connected to
The potable water supply can only be done if the irrigation system is connected to the
Potable water supply through a reduced -pressure principle backflow prevention
assembly or an air gap.
Irrigation system components with chemical additives induced by aspiration, injection,
Or emission system connected to any potable water supply must be connected through a
reduced pressure principle backflow device.
If an irrigation system is designed or installed on a property that is served by an on -site
sewage facility, as defined in Title 30, Texas Administrative Code, Chapter 285, then:
1. all irrigation piping and valves must meet the separation distances from the On -
Site
Sewage Facilities system as required for a private water line in Title 30, Texas
Administrative Code, Section 285.91(10);
2. any connections using a private or public potable water source that is not the
city's potable water system must be connected to the water source through a
reduced pressure principle backflow prevention assembly as defined in Title 30,
Texas Administrative
Code, Section 344.50; and
3. any water from the irrigation system that is applied to the surface of the area
utilized by the On -Site Sewage Facility system must be controlled on a separate
irrigation zone or zones so as to allow complete control of any irrigation to that
area so that there will not be excess water that would prevent the On -Site
Sewage Facilities system from operatin effectively.
P2902.5.3.5 Water Conservation. All irrigation systems shall be designed, installed,
maintained, altered, repaired, serviced, and operated in a manner that will promote
water conservation as defined in the Definitions section of this ordinance.
P2902.5.3.6 Irrigation Plan Design. An irrigator shall prepare an irrigation plan for each
site where a new irrigation system will be installed. A paper or electronic copy of the
irrigation plan must be on the job site at all times during the installation of the irrigation
system. A drawing showing the actual installation of the system is due to each irrigation
ORDINANCE NO. 2025-4646
Page 31 of 50
system owner after all new irrigation system installations. During the installation of the
irrigation system, variances from the original plan may be authorized by the licensed
irrigator if the variance from the plan does not:
1. diminish the operational integrity of the irrigation system;
2. violate any requirements of this ordinance; and
3. go unnoted in red on the irrigation plan.
The irrigation plan must include complete coverage of the area to be irrigated. If a
system does not provide complete coverage of the area to be irrigated, it must be noted
on the irrigation plan.
All irrigation plans used for construction must be drawn to scale. The plan must include,
at a minimum, the following information:
1. the irrigator's seal, signature, and date of signing;
2. all major physical features and the boundaries of the areas to be watered;
3. a North arrow;
4. a legend;
5. the zone flow measurement for each zone;
6. location and type of each:
a) controller; and
b) sensor (for example, but not limited to, rain, moisture, wind, flow, or
freeze);
7. location, type, and size of each:
a) water source, such as, but not limited to a water meter and point(s) of
connection;
b) backflow prevention device;
c) water emission device, including, but not limited to, spray heads, rotary
sprinkler heads, quick -couplers, bubblers, drip, or micro -sprays;
d) valve, including but not limited to, zone valves, master valves, and
isolation
valves;
e) pressure regulation component; and
f) main line and lateral piping.
8. the scale used; and
9. the design pressure.
P2902.5.3.7 Design and Installation. No irrigation design or installation shall require the
use of any component, including the water meter, in a way which exceeds the
manufacturer's published performance limitations for the component.
P2902.5.3.7.1 Spacing. The maximum spacing between emission devices must not
exceed the manufacturer's published radius or spacing of the device(s). The radius or
spacing is determined by referring to the manufacturer's published specifications for a
specific emission device at a specific operating pressure. New irrigation systems shall
not utilize above -ground spray emission devices in landscapes that are less than 48
inches not including the impervious surfaces in either length or width and which contain
impervious pedestrian or vehicular traffic surfaces along two or more perimeters. If
pop-up sprays or rotary sprinkler heads are used in a new irrigation system, the sprinkler
heads must direct flow away from any adjacent surface and shall not be installed closer
than four inches from a hardscape, such as, but not limited to, a building foundation,
fence, concrete, asphalt, pavers, or stones set with mortar.
Exception:
ORDINANCE NO. 2025-4646
Page 32 of 50
Narrow paved walkways, jogging paths, golf cart paths or other small areas located in
cemeteries, parks, golf courses or other public areas if the runoff drains into a
landscaped area.
P2902.5.3.7.2 Water Pressure. Emission devices must be installed to operate at the
minimum and not above the maximum sprinkler head pressure as published by the
manufacturer for the nozzle and head spacing that is used. Methods to achieve the water
pressure requirements include, but are not limited to, flow control valves, a pressure
regulator, or pressure compensating spray heads.
P2902.5.3.7.3 Piping. Piping in irrigation systems must be designed and installed so that
The flow of water in the pipe will not exceed a velocity of five feet per second for
polyvinyl chloride (PVC) pipe.
P2902.5.3.7.4 Irrigation Zones. Irrigation systems shall have separate zones based on
Plant material type, microclimate factors, topographic features, soil conditions, and
hydrological requirements.
P2902.5.3.7.5 Matched Precipitation Rate. Zones must be designed and installed so that
all of the emission devices in that zone irrigate at the same precipitation rate.
P2902.5.3.7.6 Impervious Surfaces. Irrigation systems shall not spray water over
surfaces made of concrete, asphalt, brick, wood, stones set with mortar, or any other
impervious material, such as, but not limited to, walls, fences, sidewalks, streets, etc.
P2902.5.3.7.7 Master Valve. When provided, a master valve shall be installed on the
discharge side of the backflow prevention device on all new installations.
P2902.5.3.7.8 PVC Pipe Primer Solvent. All new irrigation systems that are installed
Using PVC pipe and fittings shall be primed with a colored primer prior to applying the
PVC cement in accordance with the International Plumbing Code (Section 605).
P2902.5.3.7.9 Rain or Moisture Sensor. All new automatically controlled irrigation
Systems must include sensors or other technology designed to inhibit or interrupt
operation of the irrigation system during periods of moisture or rainfall. Rain or
moisture shut-off technology must be installed according to the manufacturer's
published recommendations. Repairs to existing automatic irrigation systems that
require replacement of an existing controller must include a sensor or other technology
designed to inhibit or interrupt operation of the irrigation system during periods of
moisture or rainfall.
P2902.5.3.7.10 Isolation Valve. All new irrigation systems must include an isolation
valve between the water meter and the backflow prevention device.
P2902.5.3.7.11 Depth Coverage of Piping. Piping in all irrigation systems must be
Installed according to the manufacturer's published specifications for depth coverage of
piping. If the manufacturer has not published specifications for depth coverage of
piping, the piping must be installed to provide minimum depth coverage of six inches of
select backfill, between the top of the pipe and the natural grade of the topsoil. All
portions of the irrigation system that fail to meet this standard must be noted on the
ORDINANCE NO. 2025-4646
Page 33 of 50
irrigation plan. If the area being irrigated has rock at a depth of six inches or less, select
backfill may be mounded over the pipe. Mounding must be noted on the irrigation plan
and discussed with the irrigation system owner or owner's representative to address any
safety issues. If a utility, man-made structure or roots create an unavoidable obstacle,
which makes the six-inch depth coverage requirement impractical, the piping shall be
installed to provide a minimum of two inches of select backfill between the top of the
pipe and the natural grade of the topsoil. All trenches and holes created during
installation of an irrigation system must be backfilled and compacted to the
original grade.
P2902.5.3.7.12 Irrigation System Wiring. Underground electrical wiring used to
connect an automatic controller to any electrical component of the irrigation system
must be listed by Underwriters Laboratories as acceptable for burial underground.
Electrical wiring that connects any electrical components of an irrigation system must
be sized according to the manufacturer's recommendation. Electrical wire splices which
may be exposed to moisture must be waterproof as certified by the wire splice
manufacturer. Underground electrical wiring that connects an automatic controller to
any electrical component of the irrigation system must be buried with a minimum of six
inches of select backfill.
P2902.5.3.7.13 Irrigation System Water. Water contained within the piping of an
Irrigation system is deemed to be non -potable. No drinking or domestic water usage,
such as, but not limited to, filling swimming pools or decorative fountains, shall be
connected to an irrigation system. If a hose bib (an outdoor water faucet that has hose
threads on the spout) is connected to an irrigation system for the purpose of providing
supplemental water to an area, the hose bib must be installed using a quick coupler key
on a quick coupler installed in a covered purple valve box and the hose bib and any
hoses connected to the bib must be labeled "non potable, not safe for drinking." An
isolation valve must be installed upstream of a quick coupler connecting a hose bib to
.an irrigation system.
P2902.5.3.7.14 Licensed Person On Site During Installation. Beginning January 1,
2010, either a licensed irrigator or a licensed irrigation technician shall be on -site at all
times while the landscape irrigation system is being installed. When an irrigator is not
onsite, the irrigator shall be responsible for ensuring that a licensed irrigation technician
is on -site to supervise the installation of the irrigation system.
P2902.5.3.8 Completion of Irrigation System Installation. Upon completion of the
Irrigation system, the irrigator or irrigation technician who provided supervision for the
on -site installation shall be required to complete the following four items:
1. a final walk through with the irrigation system's owner or the owner's
representative to explain the operation of the system;
2. The maintenance checklist on which the irrigator or irrigation technician shall
obtain the signature of the irrigation system's owner or owner's representative
and shall sign, date, and seal the checklist. If the irrigation system's owner or
owner's representative is unwilling or unable to sign the maintenance checklist,
the irrigator shall note the time and date of the refusal on the irrigation system's
owner or owner's representative's signature line. The irrigation system owner or
owner's representative will be given the original maintenance
checklist and a duplicate copy of the maintenance checklist shall be maintained
ORDINANCE NO. 2025-4646 Page 34 of 50
by the irrigator.
The items on the maintenance checklist shall include but are not limited to:
a) the manufacturer's manual for the automatic controller, if the system is
automatic;
b) a seasonal (spring, summer, fall, winter) watering schedule based on
either
current/real time evapotranspiration or monthly historical reference
evapotranspiration (historical ET) data, monthly effective rainfall
estimates, plant landscape coefficient factors, and site factors;
c) a list of components, such as the nozzle, or pump filters, and other such
components;
that require maintenance and the recommended frequency for the
service; and
d) the statement, "This irrigation system has been installed in accordance
with all
applicable state and local laws, ordinances, rules, regulations or orders. I
have tested the system and determined that it has been installed
according to the Irrigation Plan and is properly adjusted for the most
efficient application of water at this time."
3. A permanent sticker which contains the irrigator's name, license number,
company name, telephone number and the dates of the warranty period shall be
affixed to each automatic controller installed by the irrigator or irrigation
technician. If the irrigation system is manual, the sticker shall be affixed to the
original maintenance checklist. The information contained on the sticker must be
printed with waterproof ink and include:
4. The irrigation plan indicating the actual installation of the system must be
provided to the irrigation system's owner or owner representative.
P2902.5.3.9 Maintenance, Alteration, Repair, or Service of Irrigation Systems. The
licensed irrigator is responsible for all work that the irrigator performed during the
maintenance, alteration, repair, or service of an irrigation system during the warranty
period. The irrigator or business owner is not responsible for the professional
negligence of any other irrigator who subsequently conducts any irrigation service on
the same irrigation system.
All trenches and holes created during the maintenance, alteration, repair, or service of
an irrigation system must be returned to the original grade with compacted select
backfill.
Colored PVC pipe primer solvent must be used on all pipes and fittings used in the
maintenance, alteration, repair, or service of an irrigation system in accordance with the
adopted International Plumbing Code (Section 605).
When maintenance, alteration, repair or service of an irrigation system involves
excavation work at the water meter or backflow prevention device, an isolation valve
shall be installed, if an isolation valve is not present.
P2902.5.3.10 Reclaimed Water. Reclaimed water may be utilized in landscape irrigation
systems if:
1. there is no direct contact with edible crops, unless the crop is pasteurized before
consumption;
2. the irrigation system does not spray water across property lines that do not
belong to
ORDINANCE NO. 2025-4646
Page 35 of 50
the irrigation system's owner;
3. the irrigation system is installed using purple components;
4. the domestic potable water line is connected using an air gap or a reduced
pressure
principle backflow prevention device, in accordance with §290.47(i) of this title
(relating to Appendices);
5. a minimum of an eight inch by eight inch sign is prominently posted on/in the
area that is being irrigated, that reads, "RECLAIMED WATER — DO NOT
DRINK"; and
6. backflow prevention on the reclaimed water supply line shall be provided in
accordance with the regulations of the city's water provider.
P2902.5.3.11 Advertisement Requirements. All vehicles used in the performance of
irrigation installation, maintenance, alteration, repair, or service must display the
irrigator's license number in the form of "LI " in a contrasting color of block
letters at least two inches high, on both sides of the vehicle.
All forms of written and electronic advertisements for irrigation services must display
the irrigator's license number in the form of "LI ." Any form of
advertisement, including business cards, and estimates which displays an entity's or
individual's name other than that of the licensed irrigator must also display the name of
the licensed irrigator and the licensed irrigator's license number. Trailers that advertise
irrigation services must display the irrigator's license number.
The name, mailing address, and telephone number of the commission must be
prominently displayed on a legible sign and displayed in plain view for the purpose of
addressing complaints at the permanent structure where irrigation business is primarily
conducted and irrigation records are kept.
P2902.5.3.12 Contracts. All contracts to install an irrigation system must be in writing
and signed by each party and must specify the irrigator's name, license number,
business address, current business telephone numbers, the date that each party signed
the agreement, the total agreed price, and must contain the statement, "Irrigation in
Texas is regulated by the Texas Commission on Environmental Quality (TCEQ), MC-
178, P.O. Box 13087, Austin, Texas 78711-3087. TCEQ's website is: www.
tceq.state.tx.us."
All contracts must include the irrigator's seal, signature, and date.
All written estimates, proposals, bids, and invoices relating to the installation or repair
of an irrigation system(s) must include the irrigator's name, license number, business
address, current business telephone number(s), and the statement: "Irrigation in Texas is
regulated by the Texas Commission On Environmental Quality (TCEQ) (MC-178), P.O.
Box 13087, Austin, Texas 78711-3087. TCEQ's web site is: www.tceq.state.tx.us."
An individual who agrees by contract to provide irrigation services as defined in
§344.30 of this title (relating to License Required) shall hold an irrigator license issued
under Title 30, Texas Administrative Code, Chapter 30 (relating to Occupational
Licenses and Registrations) unless the contract is a pass -through contract as defined in
§344.1(36) of this title (relating to Definitions). If a pass -through contract includes
irrigation services, then the irrigation portion of the contract can only be performed by a
licensed irrigator. If an irrigator installs a system pursuant to a pass -through contract,
the irrigator shall still be responsible for providing the irrigation system's owner or
through contract, the irrigator shall still be responsible for providing the irrigation
system's owner or owner's representative a copy of the warranty and all other
ORDINANCE NO. 2025-4646
Page 36 of 50
documents required under this chapter. A pass -through contract must identify by name
and license number the irrigator that will perform the work and must provide a
mechanism for contacting the irrigator for irrigation system warranty work.
The contract must include the dates that the warranty is valid.
P2902.5.3.13 Warranties for Irrigation Systems. On all installations of new irrigation
systems, an irrigator shall present the irrigation system's owner or owner's
representative with a written warranty covering materials and labor furnished in the new
installation of the irrigation system. The irrigator shall be responsible for adhering to
terms of the warranty. If the irrigator's warranty is less than the manufacturer's warranty
for the system components, then the irrigator shall provide the irrigation system's owner
or the owner's representative with applicable information regarding the manufacturer's
warranty period.
The warranty must include the irrigator's seal, signature, and date. If the warranty is part
of an irrigator's contract, a separate warranty document is not required.
An irrigator's written warranty on new irrigation systems must specify the irrigator's
name, business address, and business telephone number(s), must contain the signature
of the irrigation system's owner or owner's representative confirming receipt of the
warranty and must include the statement: "Irrigation in Texas is regulated by the Texas
Commission on Environmental Quality (TCEQ), MC-178, P.O. Box 130897, Austin,
Texas 78711-3087. TCEQ's website is: www.tceq.state.tx.us."
On all maintenance, alterations, repairs, or service to existing irrigation systems, an
irrigator shall present the irrigation system's owner or owner's representative a written
document that identifies the materials furnished in the maintenance, alteration, repair, or
service. If a warranty is provided, the irrigator shall abide by the terms. The warranty
document must include the irrigator's name and business contact information.
P2902.5.3.14 Duties and Responsibilities of City Irrigation Inspectors. A licensed
irrigation inspector or plumbing inspector shall enforce the ordinance of the city, and
shall be responsible for:
1. verifying that the appropriate permits have been obtained for an irrigation
system and
that the irrigator and installer or irrigation technician, if applicable, are licensed;
2. inspecting the irrigation system;
3. determining that the irrigation system complies with the requirements of this
section;
4. determining that the appropriate backflow prevention device was installed and
tested;
5. investigating complaints related to irrigation system installation, maintenance,
alteration, repairs, or service of an irrigation system and advertisement of
irrigation services; and
6. maintaining inspection records according to this section."
32. Section P2906.5 (Water -distribution pipe.) is amended by adding the following text to
the end of the section:
"Inaccessible water distribution iping under slabs shall be copper (minimum type K) or
cross -linked polyethylene (PEX tubing all installed without joints or connections.
Materials subject to corrosion shall be protected when exposed to concrete or corrosive
soils."
ORDINANCE NO. 2025-4646
Page 37 of 50
(Reason: This amendment provides an elevated standard for water distribution piping
installed under concrete slabs. It is also consistent with the International Plumbing
Code.)
33. Section 2906.10 (Cross -linked polyethylene plastic (PEX)) is amended by adding
P2906.10.3 to read as follows:
"P2906.10.3. Sleeving. When a sleeve is provided for cross -linked polyethylene (PEX)
plastic piping or tubing installed under concrete slabs the annular space between the
piping or tubing and the sleeve must be caulked, foamed, or otherwise sealed to prevent
the entrance of termiticide."
(Reason: This amendment provides added protection from liquid chemical
termiticides that may enter the void between the sleeve and piping/tubing.)
34. Section P3002.2. (Building sewer) is amended by adding P3002.2.1 to read as follows:
"P3002.2.1 Depth of building sewer. Building sewer pipe shall be installed with a
minimum of twelve (12) inches of cover. Where conditions prohibit the required amount
of cover, cast iron pipe with approved joints may be used unless other means of
protecting the pipe is provided as approved by the Building Official."
(Reason: When field conditions do not allow at least 12 inches of ground cover over
a sewer line, cast iron pipe provides an equivalent level of protection. This
amendment is also consistent with provisions in the International Plumbing Code.)
35. Section E3401.1 (applicability) is amended by deleting the section in its entirety and
replacing with the following:
"Electrical installations shall comply with the National Electrical Code, as adopted and
amended by the City of College Station."
(Reason: The City has adopted the National Electrical Code to regulate electrical
installations. This amendment also makes the IRC consistent with state law.)
Sec. 103-135. — Amendments to the International Fuel Gas Code.
The International Fuel Gas Code adopted by reference in Section 101.4.1, 2024 International
ORDINANCE NO. 2025-4646
Page 38 of 50
Building Code is hereby amended as follows:
1. Section 102.8 (Referenced codes and standards) is amended by adding the
following exception:
"Exception: Any reference to the ICC Electrical Code shall mean the National
Electrical Code, as adopted and amended by the City of College Station."
2. Section 105.3(Application for permit) is amended by deleting the text in said section
and replacing it with the following:
"The code official may require a permit application for work regulated by this
code."
3. Section 108.2(Schedule of permit fees) is amended by deleting the section in its
entirety.
4. Section 108.6 (.Refunds) is amended by deleting the text in said section and
replacing it with the following:
"The City Manager or his designee is authorized to establish a refund policy."
Section 112 (Means of Appeal) is amended by deleting the section in its entirety.
6. Section 305.5 (Private garages) is amended by deleting the section in its entirety.
7. Section 406.1.2 (Repairs and additions) is amended by deleting the existing
text in its entirety and replacing it with the following:
"In the event repairs or additions are made after the pressure test, the affected piping
shall be tested. If approved by the code official, minor repairs and additions are not
required to be pressure tested provided the work is inspected and connections are
tested with a noncorrosive leak -detecting fluid or other leak detecting methods.
Section 406.4 (Test pressure measurement) is amended by adding the following to
the end of said section:
`For gas systems with a working pressure up to and including five (5) psi., a
diaphragm gauge utilizing a dial with a minimum diameter of three and one-half
inches (3 1/z"), a set hand, 2/10 pound incrementation and a pressure range not more
than twenty (20) psi shall be acceptable. A mechanical spring gauge is only
acceptable for use on gas systems requiring a pressure test of more than 20 psig.'
9. Section 406.4.1 (Test pressure) is amended by deleting the existing text in its
entirety and replacing it with the following:
`The test pressure to be used shall be no less than twice the proposed maximum
working pressure, but no less than five (5) psig, irrespective of design pressure.'
10. Section 406.4.2 (Test duration) is amended by deleting the existing text in its
entirety and replacing it with the following:
"Gas piping systems shall withstand the required.pressure test for a period of not less
than ten (10) minutes without showing any drop in pressure."
Sec. 103-136. — Amendments to the International Mechanical Code.
ORDINANCE NO. 2025-4646
Page 39 of 50
The International Mechanical Code adopted by reference in Section 101.4.2, 2024 International
Building Code is hereby amended as follows:
1. Section 102.8 (Referenced codes and standards) is amended by adding the
following exception:
`Exception: Any reference to the ICC Electrical Code shall mean the
National Electrical Code, as adopted and amended by the City of College
Station.'
2. Section 105.3 (Application for permit) is amended by deleting the text in
said section and replacing it with the following:
`The code official may require a permit application for work regulated by
this code.'
3. Section 108.2 (Schedule of permit fees) is amended by deleting the section
in its entirety.
4. Section 108.6 (Refunds) is amended by deleting the text in said section and
replacing it with the following:
"The City Manager or his designee is authorized to establish a refund
policy.'
5. Section 115.4 (Failure to comply) is amended by adding the following at the
end of said section:
`Fines shall be not less than twenty-five ($25.00) and not more than two -
thousand ($2,000.00)'
6. Section 112 (Means of Appeal) is amended by deleting the section in its
entirety.
7. Section 304.7 (Private garages) is amended by deleting the section in its
entirety.
8. Section 1109.2.5 (Refrigerant pipe shafts) is amended by adding the
following exception:
"4. Where the design is in compliance with Ashrae 15 — 2024 Section
9.12.1.5.1 (Shaft alternative)"
Sec. 103-137. —Amendments to the International Plumbing Code.
The International Plumbing Code adopted by reference in Section 101.4.3, 2024 International
ORDINANCE NO. 2025-4646
Page 40 of 50
Building Code is hereby amended as follows:
Section 102.8 (Referenced codes and standards) is amended by adding the
following exception:
`Exception: Any reference to the ICC Electrical Code shall mean the National
Electrical Code, as adopted and amended by the City of College Station.'
(Reason: The City of College Station has adopted the National Electrical Code to regulate
electrical installations.)
2. Section 105.3 (Application for permit) is amended by deleting the text in said
section and replacing it with the following:
`The code official may require a permit application for work regulated by this code.'
(Reason: The code as written, requires a written application for plumbing permits. This
amendment provides the flexibility of making written permit applications optional.)
3. Section 108.2 (Schedule of permit fees) is amended by deleting this section in its
entirety.
(Reason: The City currently has a permit fee schedule that has been adopted by resolution.)
4. Section 108.6 (Refunds) is amended by deleting the text in said section and
replacing it with the following:
`The City Manager or designee is authorized to establish a refund policy.'
(Reason: A refund policy for permit fees already exists. This amendment also makes the
IPC fee refund requirement consistent with section 109.6, 2024 IBC.)
5. Section 115.4 (Failure to comply) is amended by adding the following sentence:
`Fines shall be not less than twenty-five ($25.00) and not more than two thousand
($2,000.00)'
(Reason: The amounts above are consistent with the fines as outlined in the adopting
ordinance for violations.)
6. Section 112 (Means of Appeal) is amended by deleting the section in its entirety.
(Reason: The City already provided for the establishment of the Construction Board of
Adjustments and Appeals)
7. Section 305.4.1 (Sewer depth) is amended by inserting "twelve
(12)" in both blanks and adding the following sentence to the end of said section.
`Where conditions prohibit the required amount of cover, cast iron pipe with
approved joints may be used unless other means of protecting the pipe is provided
as approved by the Building Official.'
ORDINANCE NO. 2025-4646
Page 41 of 50
(Reason: When field conditions do not allow at least 12 inches of ground cover over a
sewer line, cast iron pipe is provided as approved by the Building Official.)
8. Section 312.1 (Required tests) is amended by deleting the following text from said
section:
`, for piping systems other than plastic, by'
(Reason: This change allows an air test for plastic piping systems — a common practice on
job sites without access to water.)
9. Section 312.2 (Drainage and vent water test) is amended by deleting said section in
its entirety and replacing with the following:
`312.2 Drainage water test. A water test shall be applied to the drainage system
either in its entirety or in sections. If applied to the entire system, all openings in the
piping shall be tightly closed, except the highest opening, and the system shall be
filled with water to the point of overflow. If the system is tested in sections, each
opening shall be tightly plugged except the highest opening of the section under test,
and each section shall be tested with not less than a 5-foot head of water. This
pressure shall be held for at least 15 minutes. The drainage system shall then be
tight at all points.'
(Reason: This change omits any reference to pressure testing the vent system. It is not a
common practice in this area to require a pressure test on the vent system.)
10. Section 312.3 (Drainage and vent air test) is amended by deleting said
section in its entirety and replacing with the following:
`312.3 Drainage air test. An air test shall be applied to the drainage piping by
forcing air into the system until there is uniform gauge pressure of 5 pounds per
square inch (psi) or sufficient to balance a 10-inch column of mercury. This
pressure shall be held for a test period of at least 15 minutes. Any adjustment to the
test pressure required because of changes in ambient temperature or the seating of
gaskets shall be made prior to the beginning of the test period.'
(Reason: This change omits any reference to pressure testing the vent system. It is not
common practice in this area to require a pressure test on the vent system.)
11. Section 312.7(Gravity sewer test) is amended by replacing "I 0-foot" with
"5-foot".
(Reason: This change makes for uniform testing methods of DWV and gravity sewer
piping.)
12. Section 312.11(Inspection and testing of backflow prevention assemblies.) is
amended by deleting said section in its entirety and replacing with the following:
`312.10 Inspection and testing of backflow prevention assemblies. Upon initial
ORDINANCE NO. 2025-4646
Page 42 of 50
installation, an inspection shall be made of all backflow prevention devices and
assemblies to determine whether they are operable. Testing of all backflow
prevention devices and assemblies shall be in accordance with Chapter 11, Section
10, Subsection F, of the Code of Ordinances, City of College Station, Texas."
(Reason: Consistent with City Council's direction concerning backflow prevention
devices.)
13. Section 410.4 (Substitution) is amended by deleting the last sentence in said
section and replacing it with the following:
"Small occupancies with an occupant load of less than 50 the required drinking
water can be provided by means of bottled water dispenser in lieu of a drinking
fountain device."
(Reason: This change allows bottled water dispensers to be used in place of drinking
fountains.)
14. Section 606 (Installation of the Building Water Distribution System) is
amended by adding section 606.8 to read as follows:
`606.7 Sleeved cross -polyethylene piping or tubing. `When a sleeve is provided for
cross -linked polyethylene (PEX) plastic piping or tubing installed under concrete
slabs the annular space between the piping or tubing and the sleeve must be caulked,
foamed, or otherwise sealed to prevent the entrance of termiticide.'
(Reason: This amendment provides added protection from liquid chemical termiticides that
may enter the void between the sleeve and piping /tubing.)
15. Section 608.17.5 (Connections to lawn irrigation systems) is amended by
deleting the first sentence in said section and replacing it with the following:
`The potable water supply to lawn irrigation systems shall be protected against
backflow by an atmospheric vacuum breaker, a pressure vacuum breaker assembly,
a reduced pressure principle backflow prevention assembly or a double check.'
(Reason: Consistent with City Council's direction concerning backflow prevention
devices.)
16. Section 701.2 (Connection to sewer required) is amended by deleting the
section in its entirety and replacing with the following:
`701.2 Connection to sewer required. Every building in which plumbing fixtures
are installed and all premises having sanitary drainage piping shall be connected to
an approved sewer. Private sewage systems must comply with City of College
Station's Code of Ordinances. All private sewage disposal systems must comply
with the latest adopted standards of the Texas Commission on Environmental
Quality and be installed under the direction of the Brazos County Health
Department. The installer shall be licensed by the Texas Commission on
Environmental Quality.'
ORDINANCE NO. 2025-4646
Page 43 of 50
(Reason: This change requires private sewer system installations — treatment plants, septic
systems, etc. — to comply with state and county health department rules.)"
17. Section 1003.3.5 (Hydromechanical grease interceptors, fats, oils and
greases disposal systems and automatic grease removal devices) is amended by
deleting the first sentence in said section:
(Reason: College Station Code of Ordinances contains detailed provisions for sizing grease
interceptors.)
Sec. 103-138. — Amendments to the International Property Maintenance Code.
The International Property Maintenance Code adopted by reference in Section 101.4.4, 2024
ORDINANCE NO. 2025-4646 Page 44 of 50
International Building Code is hereby amended as follows:
1. Section 102.8 (Referenced codes and standards) is amended by adding the following
exception:
`Exception: Any reference to the ICC Electrical Code shall mean the National
Electrical Code, as adopted and amended by the City of College Station.'
(Reason: The City of College Station has adopted the National Electrical Code to regulate
electrical installations.)
2. Section 106 (Means of Appeal) is amended by deleting the section in its entirety.
(Reason: College Station Code of Ordinances provides for the Construction Board of
Adjustments and Appeals.)
3. Section 109 (Unsafe Structures and Equipment) is amended by deleting the section
in its entirety.
(Reason: College Station Code of Ordinances contains detailed provisions concerning
dangerous structures, written in compliance with State law.)
4. Section 109.4 (Notice) is amended by deleting the section in its entirety.
(Reason: College Station Code of Ordinances contains detailed provisions concerning
notices, written in compliance with State law.)
5. Section 110 (Emergency Measures) is amended by deleting the section in its
entirety.
(Reason: College Station Code of Ordinances contains detailed provisions concerning
emergency measures, written to comply with State law.)
6. Section I I I (Demolition) is amended by deleting the section in its entirety.
(Reason: College Station Code of Ordinances contains detailed provisions concerning the
demolition and/or repair of substandard structures, written to comply with State law.)
7. Section 302.4 (Weeds) is amended by deleting the section in its entirety.
(Reason: Code enforcement has requirements concerning the height of weeds/grass and is
responsible for enforcement.)
8. Section 304.3 (Premises identification) is amended by deleting the text in said
section and replacing it with the following:
`Premises identification shall be in compliance with Section 502.1, 2024
International Building Code as amended.'
(Reason: The City has detailed addressing standard adopted by Section 502.1, IBC.)
ORDINANCE NO. 2025-4646
Page 45 of 50
9. Section 304.14 (Insect screens) is amended by deleting the existing text and
replacing it with the following:
`Every door, window, and other outside opening required for ventilation of habitable
rooms, food preparation areas, food service areas or any other areas where products
to be included or utilized in food for human consumption are processed,
manufactured, packaged or stored, shall be supplied with approved tightly fitting
screens of not less than 16 mesh per inch (16 mesh per 25mm) and every swinging
door shall have a self -closing device in good working condition.
Exceptions:
1. Screens shall not be required where other approved means, such as air curtains or
insect repellant fans, are employed.
2. Screens shall not be required for windows and doors enclosing habitable spaces
that contain central heating and air conditioning equipment that provide mechanical
ventilation.'
(Reason: The new text requires screens year round and provides for an additional exception
allowing screens to be omitted on homes with central air and heat.)
10. Section 602.3 (Heat supply) is amended by adding the following dates in the blanks
provided:
`l October in first blank and 30 April in second blank'
(Reason: The specified dates should cover the time of year that heat is needed in this
geographic area)
11. Section 602.4 (Occupiable work space) is amended by adding the following dates in
the blanks provided:
`l October in first blank and 30 April in second blank'
(Reason: The specified dates should cover the time of year that heat is needed in this
geographic area)
12. Section 602.4 (Occupiable work spaces) is amended by adding the following
exception:
`3. Warehouse, storage rooms and similar areas that are not occupied on a constant
basis.'
(Reason: The added exception allows warehouses, storage rooms, and similar work areas
that are not occupied on a constant basis to be unheated.) "
13. Appendix A (Boarding Standard) is hereby adopted.
ORDINANCE NO. 2025-4646
Page 46 of 50
(Reason: The appendix provides the minimum specifications for boarding up a structure.
This can be utilized by a jurisdiction to set a consistent boarding quality standard.)
Sec. 103-139. — Amendments to the International Energy Conservation Code.
The International Energy Conservation Code adopted by reference in Section 101.4.6, 2024
International Building Code, is hereby amended as follows:
ORDINANCE NO. 2025-4646
Page 47 of 50
1. Section C&R102.4(Referenced codes and standards) is amended by adding the
following to said section:
"Any reference to the ICC Electrical Code shall mean the National Electrical Code,
as adopted and amended by the City of College Station."
2. Section C&R109 (Means of Appeals) is amended by deleting the section in its
entirety.
3. Section C402.6 (Air leakage- building thermal envelope) is amended by adding an
exception:
"Exception: The air leakage — thermal envelope shall be considered acceptable when
the items listed in Table R402.5.1.1, applicable to the method of construction, are
field verified. Where required by the code official, an approved third party,
independent from the installer, shall inspect and approve the thermal envelope and
insulation installation."
4. Section R401.3 (Certificate) is amended by deleting the existing text from said
section and inserting:
"The certificate shall list the types and efficiencies of heating, cooling and service
water heating equipment. Where a gas -fired unvented room heater, electric furnace,
or baseboard electric heater is installed in the residence, the certificate shall list
"gas -fired unvented room heater," "electric furnace" or "baseboard electric heater."
as appropriate. An efficiency shall not be listed for gas -fired unvented room
heaters, electric furnaces or electric baseboard heaters."
5. Section R402.5.1.2 (Air Leakage Testing) is amended by adding an exception:
"Exception: Building envelope tightness and insulation installation shall be
considered acceptable when the items listed in Table R402.5.1.1, applicable to the
method of construction, are field verified. Where required by the code official, an
approved third -party independent from the installer, shall inspect and approve the
air barrier and insulation installation."
6. Section R402.5.5 (Air -Sealed Electrical and communication outlet boxes. Is
amended by adding the following to the end of the section:
"On -site sealing of boxes is acceptable, when using approved sealant materials"
7. Section R403.3.3 (Ductwork located outside conditioned space) is amended by
adding the following to the end of the section:
"Supply and return air ducts in unconditioned spaces may have an insulation R-
Value of 6 when installed in conjunction with an air conditioner having a minimum
SEER rating of 16."
8. Section R403.3.7 (Duct System Testing) is amended by adding an additional
exception below said section:
ORDINANCE NO. 2025-4646
Page 48 of 50
Exception: 5. Duct tightness shall be considered acceptable when the items listed
below, applicable to the method of construction, are field verified:
Connections:
a. Seal core to collar with UL listed mastic or at least 2 wraps of UL
181 listed tape.
b. Secure connection with mechanical clamp placed over the core and
tape.
c. Pull jacket and insulation back over core. Use a mechanical clamp,
two wraps of UL 181 listed tape or UL listed mastic to secure
insulation.
Splices
a. Butt two cores together on a 4" length metal sleeve.
b. Secure core and sleeve with UL listed mastic or two wraps of UL
181 listed tape
C. Secure connection with 2 clamps placed over the taped core ends.
d. Pull jacket and insulation back over core. Use two wraps of UL
181 listed tape or UL listed mastic to secure insulation.
9. Section R403 (Systems) is amended by adding R403.14 to read as follows:
"403.14 Heating equipment. Electrical resistance heat may be used as the primary
source of heating for residential use not exceeding five hundred (500) square feet in
area."
10. Section R404.2 (Interior Lighting Controls) Is amended by deleting this section in
its entirety.
11. Section R406.6 (Verification by approved agency) is amended by replacing the
existing text with:
"The Code Official may require verification of compliance with Section R406 be
completed by an approved third party."
ORDINANCE NO. 2025-4646
Page 49 of 50
EXHIBIT B
That Chapter 103, "Buildings and Building Regulations," Article I1I, "Technical Codes," Division 3
"Electrical Code" is hereby amended to read as follows:
Sec. 103-162. — National Electrical Code adopted.
A booklet entitled `National Electrical Code 2023 Edition' as amended and as hereafter may be
amended, at least one (1) copy of which is on file in the office of the Building Official of the City
of College Station, Texas, is hereby adopted and designated as the Electrical Code of College
Station, Texas.
Sec. 103-163. — Amendments to the National Electrical Code.
Section 210.23 (B) 15- and 20- Ampere Branch Circuits. It shall also be amended
to include the following sentence after said section:
"However, a circuit shall not serve more than ten openings."
2. Section 210.52 (B) Small Appliances shall be amended by adding the following
subsection:
"(4) Separate Circuit Required. A separate circuit is required for each refrigerator,
deep freeze, dishwasher, disposal, trash compactor or any other load exceeding six
(6) amperes."
3. Section 210.52 (C) Countertops And Work Surfaces shall be amended to include
after the words `...with 210.52 (C) (1) through (C) (3). the following sentence:
"However, a separate circuit is required for microwave ovens or any other counter top
appliance with a load exceeding six (6) amperes."
4. Section 210.52 (F) Laundry Areas. Shall be amended to include after the words'. .
. for the installation of laundry equipment.' the following sentence:
"However, a separate circuit is required for a washing machine or any other laundry
appliance with a load exceeding six (6) amperes."
Section 210.52(1) One -Family and Two -Family Dwelling. Shall be amended by
adding the following subsection:
"(J) Other Locations. A separate circuit is required for each well pump or other
outdoor loads exceeding six (6) amperes."
6. Article 230 Services. Shall be amended by adding the following section:
"230.11 Meter Mounting Heights. Individual meters shall be mounted at a height
not greater than 5'-6" or less than 4'-6" above finished grade, measured to the center
line of the meter base. Meter packs shall be mounted with its horizontal centerline
not greater than 4'-6" or less than 4'-0" above finished grade."
"Exception: Meters and meter packs may be mounted at a different height by special
permission of the Building Official or his designee when special conditions make the
installation at the above heights impractical. "
7. Section 230.70 General shall be amended by adding the following subsection:
"(D) Service Disconnecting Means for Commercial Buildings and Structures. For
commercial buildings and structures, the service disconnecting means shall be
installed on the outside of the building or structure. A power operated disconnect
switch (shunt trip) is permitted for service disconnects rafed 1000 amps or more. All
shunt trip disconnecting means shall be of the maintained contact type in an approved,
lockable enclosure. All service disconnects shall be clearly marked in a permanent
manner.
ORDINANCE NO. 2025-4646
Page 50 of 50
Exception: A power operated disconnect switch (shunt trip) may be allowed on
service disconnects rated less than 1000 amps, if the applicant requests an exception
from the Electrical Division and Building Official and satisfies the official that one of
the following criteria has been met.
(a) A power operated disconnect switch (shunt trip) may be used for a service
disconnect rated less than 1000 amps when the building or structure is served
by a single transformer and the transformer is not anticipated to be used for
multiple services; or
(b) A power operated disconnect switch (shunt trip) may be used for a service
disconnect rated less than 1000 amps on an existing building or structure when
space is not available to mount an external disconnect.
(Reason: This was an existing amendment that was changed to require a
maintained contact type, shunt trip.
Article 230 Services. Shall be amended by adding the following section:
"230.70 (E) Outside Disconnect Locking Device. Factory installed key operated
lock shall have an alternate locking mechanism approved by the local jurisdiction."
(Reason: This amendment gives the City of College Station Electrical Department the
ability to lock the electrical service panel in the case of an emergency or delinquent
bill.)
9. Section 230.71 (A) General shall be amended to include the following sentence after
said section:
"Any multi -tenant building larger than 5,000 square feet shall have a service
disconnect."
Reason: This amendment was added to help correct the problem with multi -tenant
ease centers having too many means of disconnect.)