CONSTRUCTION BOARD OF ADJUSTMENTS AND APPEALS
Case Number Q</ UCri
Name of Applicant Acrofit Gymnastics, Inc. —
1501 FM 2818 Ste. 106
Mailing Address
College Station, TX 77840 —
(409) 696-1234
Telephone Number
Name of Property Owner James M. Griffin d/b/a College Stat;nn BusivaPg Center
1501 FM 2818
Mailing Address
College Station, TX 77840
(409) 764-8223
Telephone Number
LOCATION OF PROPERTY
Address 1501 FM 2818, Suite 106. 107, tnR 1n9 —
Lot ,9-. Block /a- Subdivision So VtW vU
Description if Applicable Approximately 7,500 gross square feet used as
gymnastics training facility —
Action Requested Motion - That, after review of applicable ordinances, regulations,
and building codes, and the facts and circumstances Surrounding the applicants
facilities expansion, particularly the proximity of fire hydrants, exit capacity
of the facilities, occupancy level of the facilities, clear span interior space
of facilities - s. - • ' - - - - " " = - " • '
a variance and waiver with regard to the installation of overhead sprinkler system.
Current Zoning of Subject Land
Applicable Ordinance Section —
COMPLETE THE FOLLOWING FOR A VARIANCE REQUEST
The following specific variation from the ordinance is requested.
Deletion and waiver of requirement for overhead sprinkd;er system.
This variance is necessary due to the following special conditions.
See attached correspondence with attachments.
The following alternatives to the requested variance are possible.
Limit sprinkler system to only Class C areas of Group A assembly area
This variance will not be contrary to the public interest by virtue of the following
facts: See attarhed rnrrPspnnAanr_p with attachments.
The facts stated by me in this application are true and correct to the best of my knowledge.
Acrofit Gymnastics, Inc.
By: P49a4—
May 26, 1994
Bill Connatser
Applicant Date
05/23/94 1tv:2B 'Lr4u9 540 0702 BALM t nralA, --
ACROFIT GYMNASTICS, INC.
1501 FM 2818 Suite 106
College Station, Texas 77840
409-696-1234
May 23, 1994
City of College Station
1101 S Texas Avenue
Collage Station, Texas 77840
RE: ACROFIT Gymnastics Building Permit
Dear Sirs,
Please allow this to serve as our Letter of Intent regarding ACROFIT Gymnastics's
pending building permit. ACROFIT will permit the remodeling work with the City of
College Station through J,L. Derby Construction with all plans shown, including a fire
protection sprinkler system. ACROFIT and J.L. Derby Construction offer this plan to
the City pending a variance hearing with the Construction Board of Adjustments and
Appeals regarding the necessity of a 'sprinkled system".
ACROFIT request a temporary electrical hook-up from the City of College Station to
aid in Its remodeling efforts.
ACROFIT has contracted with Standard Automatic Fire Enterprises, Inc. of College
Station to design and install a fire protection sprinkler system pending the outcome ome
said variance hearing. ACROFIT will also supply the necessary Civil Engineering
ork
performed in this regard. ACROFIT will at the earliest date, but no later than June 9.
1994, supply the City of College Station with a complete set of remodeling plans
including all necessary or required engineering specifications on the fire protection
sprinkler system. It is our understanding that should ACROFIT receive the variance
waiver at such hearing, the designed fire protection sprinkler system will not be
needed and the remainder of the building permit will stand as designed.
It is our understanding that should ACROFIT not receive the variance waiver at such
hearing,installation of the fire protection sprinkler system will begin within two weeks
of said hearing. Standard Automatic Fire Enterprises. Inc. estimates the installation
time for the fire protection sprinkler system could be completed within 3 to 4 weeks
from beginning of installation.
Sine rely,
STANDARD AUTOMATIC FIRE ENTERPRISES, INC
Bil� ' P.O.Box, 10408
Co-Owner Oonner natser COLLEGE STATION,TEXAS 77842-0408
Co
• s I Gy via . Al
J / •
II A eirgigii
Jo •' S even R. Rians
Villir
J . . • Construction Co. StangEg otic Fire Enterprises
PRESIDENT •
05-25-1994 02:46PM FROM John Robertson TO 1776623951 P.07
• g ACROFIT GYMNASTICS
1501 FM 2818 Suite 106
College Station, Texas 77840
409-696-1234
Mr George Spain
Mr. David Moore
City Of College Station
RE: ACROFIT Gymnastics Building Permit
Dear Sirs,
Recently through John L. Derby Construction Company, ACROFIT Gymnastics applied
for a permit to expand its College Station gym to a total of 7,500 square feet. It is
our understanding that the building permit was delayed since ACROFIT's business
classification was considered by the City of College Station as an "Assembly"
business. The city recommended the installation of a fire sprinkler system to meet the
Assembly building codes.
ACROFIT is proud of our record of providing and maintaining a safe environment for
our students to learn and work. We ask for your consideration of the following facts
as you review our existing building plan:
1 . Number of People: ACROFIT averages approximately 35 to 40 students,
coaches and parents during our busiest instruction hours. Once, in the last eighteen
months, a special event drew approximately 60 people.
Section 404.2.1 defines "Small Assembly" as places of public assembly with
or without a legitimate stage having a capacity of 100 or more persons but having a
capacity less than designated for Large Assembly. By doubling our lease space,
ACROFIT cannot "double" our student numbers. The 35 to 40 average mentioned
above, will be maintained.
2. Location Existing fire hydrants: There ae presently two existing fire
hydrants located within 100 feet of the lease space. The back parking lot has a fire
hydrant within 60 feet of the back exit door and the front parking lot has a fire
hydrant within 100 feet of the front exit doors.
3. Existing exit doors_ The 7500 feet lease space has a total of six door exits
at this time. (four doors existing the front and two doors exiting the back wall)
4. Equipment layout: The layout of the gym equipment creates an "open" air
atmosphere within the gym whereby there are no barriers to block the exit path of our
students or parents in case of an emergency.
:�.. LJ-1JJY vL�Yui i fRul i Junrl muurrLSUrl IU If (bbe-Y7D1 I .lJb
ACROFIT
Page 2
5. Equipment type: The fire rated gymnastics equipment utilized by
ACROFIT meets and surpasses the special fire codes for the State of California. A
copy of these specifications are included for you review.
6. Rebuilding of dividing wall: Upon ACROFIT's abandonment of the 7500
lease space, ACROFIT would be willing to contract with the City of College Station
to replace the two hour fire wall separating the two existing spaces being demolished
at
this time.
We are attempting to complete this construction by June 1, so we may begin
our scheduled activities with the school break. We appreciate your prompt
consideration of these facts as you review our permit further. Should you have any
questions, I may be reached during the day at 846-4545.
Respectively Submitted,
Bill Connatser
Co-Owner
ACROFIT Gymnastics
I .. _.. L i
05-25-1994 02:47PM FROM John Robertson TO 1776623951 P.09
05/11/94 11:06 V515 386 4566 . AAI ®005
FOAM
TYPICAL P_RnPFRTIfS
• Standard Test .jest111110 XJ-1200
Density, !b/cu. tt. ASTM-D-3S7S 2, 0 z 10%
Tensile Strength, PSI .ASTM-D-412- 34. 7
Elongation, % ASTM-D.-412 102.
Tear Resistance, lb/in ASTM-D-412 11 . 0
Compression Strength, PSI AS1'6-0-3575 •
10% Deflection 2. 5
25X• Deflection 5 _ 4.
40% Deflection 9.5
S0% Defteotion • 13. 6
•
Compression Set, 74 AS2t-D-357S
S0% Deflection <20.
Thermal Stability, % AST1•i-0-3575 • • • •
(24 hrs Q 158' F) <-0. 5
Thermal Conductivity ASTM-C-177
BTU, inch/sq. f t. , hour,' F 0. 25
water Absorption - ASTM-D-3575 ,<0. 07
( lb/sq. ft. (Skived) •
Working Temperature' Range PPP-C-1752 '-65-F to 2.10.F •
CJ..,cJ-177,4 tic.,- frl I rf- u11 Junn RuJerLsun IU 1 f rC70G..J �l r to
05/11/84 11:54 0 515 700 4555 Ml IJUU 4
, @)
NYLON MESE
• Product Series: •
11
T92 DN Date: I3lL9 •_ .—•
..
•
Product .Dere„ : ' Athletic Fabric in..plain weave using .025" dia. vinyl-
coated 1000'deo. polyester core yarn ,
phySicsl Properties yap FILL -
TYPICAL .
• Construction, ends/in D3775 12 ^ 1Z
Tensile Strength, lb . D1682 245 2_
(1 inch strip)
Tear Strength, lb D1117-14 _ 70 •
7a
(Trapezoidal)
Stretch, Z D3107 4.5 4.5
(27 lb/in/i5 mit)
Set. % D3107 2.0 2.0
(0 1b/in/15•116r) -
Shrinkage.� Z -
P7.- (120°C110 alm) -
Abrasion Resistance 1)3884 Ho 'exposure of core_Yarn
. (U18/1 kg/500 cycles) 11.3
N Weight. oz/yd' 1)3776 •Me ,
i 1 2knamc Strength. lb .D3787 300+
`i Weatherability, 800 hrs G53
Appearance
Trace discolosrtion _
Tensile Retention, ZGreater than 9bl
Flammability per State of California Fire Code Bulletin 117 --'Class 1
Aft4.rflame, "sec Does not iKnite
'Afterglow. •sec • -----
Chaz Length, in
Mildew Re.,iatance 021 -
' Zone of Zahibition. mm8
Fungal Growth, % None
. Immediately clean soiled fabric with detergent/water/bleach solution followed
'• by thorough rinse with clean Vater. Do nor use dry. cleaning fluid or other
chemical cleaning agents not recommended t
I i- This information is furninhad for reference purposes only-
VJJ-GJ-177N YJG•4 f r'I I r r ui i Junri muuerLSUrI I U i f (OOGJ:7J1 r . 11
OS/11/94 11:05 $515 386 4566 AAI 0 003
•
•
la
1802 VINYL
TARP 18
Flame Resistant Tarp Fabric
3PECIFICATIONS
Base - Type Nylon
Weight 5.0 ozisq.yd.
Finished Coated Weight 2
Method 5041 19.0 - 1 ozJsd.Yd.
Tongue Tear
Method 5134 80180 lbs,
8'x 10'sample size
Grab Tensile
Method 5100 350/300 lbs.
Strip Tensile
Method 5102 275r225 tbs./in.
Adhesion(minimum)
Method 5970 10 tbolo.
liydrostatic Reslst.snce
Method 5512 300 psi
Cold Crack
MIL-C-20696C LTC Pass-40.F.
Para 4.4.6LTA Pass-67-F.
, Flame Re:istoncc &elf edinguishing
Method 5903 FR within 5 seconds
Roll Width 61.25'
Specifics Size 110 yds
We bereve Ut1s ln(cyrnslion is tilt best curtenU j reaktbe cal the&tie - it is orrered
■t 2 poeslble helpft!wppast.on M e><peri'rtenttitn you may care b un4etmkc wan
rime Nees. it is subleci to revision iso erJdlirot knowledge and experience are
golneti. We rn4kr no pvarentee or results and assume no obGpet,on cc labllty
whstLoewer N orxnresi rt wttn this informetitn,
3+7/94
05-25-1994 02:40PM FROM John Robertson TO 1776623:351 P. 12
05/11/84 11:04 ' 51S 386 4566 MI
140z VINYL
PRV 1410W 61" LEATHERLIKE TECHNICAL DATA SKEET
FED METHOD' TEST RESULT
FABRIC WIDTH 61"
ROLL LENGTH ( in yds)-4- 100
5041 FABRIC WEIGHT 13 . 0--
(ounces per sq/yd) 15. 0
5970 ADHESION ( lbs/2" ) 25
5134 TEAR RESISTANCE WARP 75
FILL 75
5100.1 TENSILE WARP 245
- (4" grab/lbs )
FILL 235
5304.1 TENSILE BEFORE ABRASION %CARP 180
(1" strip in 1bs)
FILL 170
5304.1 TENSILE AFTER ABRASION WARP 175
(1" strip in lbs)
FILL 155
5512 HYDROSTATIC 425
RESISTANCE (psi )
5903 FLAME SECONDS (2 .0
RETARDANCE
CHAR LENGTH (6 .0
5874 COLD TEMPERATURE -40 F
RESISTANCE
" METHOD NUMBERS REFER TO FEDERAL STANDARD6 191-A
TEXTILE TEST METHODS.
+ ROLL LENGTHS INDICATED ARE NOMINAL AND MAY VARY_
EACH ROLL MAY CONTAIN UP TO THEEE PIECES
(NO PIECE WILL HE SHORTER THAN SEVEN YARDS) .
NOTE: THIS TECHNICAL DATA IS BASED ON
•
AND U .S. GOVERNMENT TEST METHODS AND IS ACCURATE
TO THE BEST OF OUR KNOWLEDGE AT THE TIME OF
PRINTING. SINGLE VALUES SHOULD NOT BE INTERPRETED
AS A SPECIFICATION WITHOUT CONSULTING
05-25-1994 02:40PM FROM John Robertson
, TO 1776623951 P. 13
�1_/
STANDARD AUTOMATIC .
FIRE ENTERPRISES, INC. SAFE inc.
Fire Sprinkler Systems Specialists , Texas License No. SCR-0322
•
' 5-17-84
,J. L: DERBY CONSTRUCTION •
1501 FM 2818 SUITE*
• ' 'COLLEGE.STATION,TEXAS 77840
(409) 896-0588
RE: ACROFIT GYM .
. 1501 FM 2818 SUITE#
COLLEGE STATION, TEXAS 77840
•
• ATTN: JOHN DERBY • .
THIS IS A PROPOSAL TO PROVIDE- TURN KEY RE.PROTECTION SYSTEM FOR THE
ABOVE REFERENCED PPQJE`CT„WEI HAVE LISTE6�lHE-SCOPE OF THE BID FOR YOUR
CONVENIENCE. , i_ •t. '% l , l 1` ��1 ,..�.'`�.
-All WORK [ j� ',`;: '`.
TO BE IN FULL ACCORDANCE f . N.F.O A. #13, AND THE CITY OF COLLEGE
STATION, TEXAS FIRE MARSHAL. // j
-WET PIPE, HYDRAULICALL'V CALCULATED F R N ORDINARY HAZARD GROUP 1
OCCUPANCY. (NOTE: ALTHOUGH THIS IS A LIGH1 HAZARD OCCUPANCY, ALL
LEASE SPACES MUST BE ESI NED T' ACCOMObATE UTURE TENNANTS.
-WORK TO START AT AW E T T CONN CTION TO I NG CITY WATER LINE. THIS
INCLUDES A TAPPING SLEEVE, APPI G VALVE, P0 AY BOX AND FEE.
-APPROXIMATELY 54 LF OF CL1l S 200 -900 PVC 1IRELINE WITH SAND BEDDING &
CONCRETE THRUST BLOCKS BEHIND ALL FITTINGS INCLUDING TAPPING SLEEVE.
-COMPACTION OF DITCHLINE. ! I. . i .. -•\ 1 ' 1
•
• -RISER ENTRY POINT ON OIJTSIOE OF TrirPIPt WILL BE INSULATED AND REC-
EIVE AN ALUMINUM JACKET. (INOLDDfYOUR REQUEST)
-RISER WILL INCLUDE A 4”DOUBLE=CFBAFLOW ASSEMBLY WITH OS&Y VALVES
-OS&Y VALVES WILL HAVE TAMPER SWITCHES ON THEM.
-RISER WILL HAVE AN ALARM VALVE, RETARD CHAMBER, TRIM, MAIN DRAIN, WATER
MOTOR GONG, FLOW SWITCH, SPARE HEAD(3OX,WRENCH AND SPARE HEADS.
-ALL SIGNS AND HYDRAULIC INFORMATION WILL BE POSTED AT RISER.
-PIPE TO BE BLACK STEEL, SCH:,10 FOR 2-1/2'1&LARGER, SCH, 40 FOR 1"TO 2"PIPE,
-FITTINGS TO BE SCREWED, 12SLE3 CAST IRON FOR 1"-2•"AND 300#GROOVED FOR 2-1/2"
AND LARGER. OUTLETS OFF MAINS TO BE SHOP.WI~LDED, 300#FITTINGS.
-ALL PIPE TO BE HYDROSTATICALLY TESTED AT 200 PSI FOR A 2 HOUR DURATION. THE
TEST FEE HAS BEEN INCLUDED.
-WE HAVE ALSO INCLUDED THE FIRE ALARM MONITORING PANEL, DIGITAL DIALER TO
MONITORING AGENCY.(INCLUDED AS PER YOUR REQUEST.)
SPECIFICALLY EXCLUDED FROM THE PROPOSAL gRE THE FOLLOWING:
-PROFESSIONAL CIVIL ENGINEERS PLAN AND PROFILE. (ESTIMATED COST$1,000.00)
-SAW CUT, REMOVAL, REPAIR, PATCH OR HAUL AWAY DEBRI OF CONCRETE PAVING,
-PAINTING OR PRIMING OF SPRINKLER PIPE, FITTINGS, HANGERS OR DEVICES.
-ADEQUATE HEAT MUST BE PROVIDED BY OWNER TO INSURE SPRINKLER PIPE IS
NOT SUBJECTED TO FREEZING, INSULATION AND OR HEAT TRACE ARE NOT INCLUDED
WITHIN THIS PROPOSAL OR APPROVED METHODS OF HEAT PROTECTION.
P.O. Box 10408 • College Station; Texas 771142-0408 • (409) • Fax (409)7
UMER
690-0301 690-6741
bS-d5-i 4 Od:4'JF M bRUI1 John Robertson IU 1'r'rbb2.3 51 P. 14
13
•
•
•
PAG�f12
•
$17,964.00 FURNISHED AND INSTALLED,FOB JOBSITE,ALL TAXES/REMODEL TAXES
HAVE BEEN INCLUDED,
WE THANK YOU FOR THE OPPORTUNITY TO QUOTE YOUR FIRE PROTECTION PROJECT.
SHOULD YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO CALL.
•
• TRULY, '
ST07/4...410.4;t1
IANS
PRESIDENT
O
O Cu
ISI
I— V)
0 </ I
Lc) J
N
3
W
IMI ' in IiI
W
o.1 N
z Ia o
LL_
WW " O
Zg
a8 Lf)
ca UtZCU
v a
4 O
vQ 1
o O
$ O
O
In
N
0
CO
\ \
,/ , _ -;439-A__ ...... A — II
--7-7=-4-
A /
. 0
*a
,...k
,_.
Q3 v,
i z I
- o E
C.-),\"--
-0
_ c.)
\L,....
Ni
1 0 i
i\j
• - _
a<>' ' i ---1:•'; acti;Z,;,...1 ill-07/4,1-1"°• /
Rimt* dt'Ardid
0 •\ \
ozz /WA_4m4 A41°'..
q7. 5
g53. 5
CONSTRUCTION BOARD OF ADJUSTMENTS AND APPEALS
STAFF REPORT
Case Number: 94-007
Applicant: Acrofit Gymnastics, Inc.
1501 FM 2818 Ste. 106
College Station, TX 77840
Telephone: (409) 696-1234
Property Owner: College Station Business Center
1501 FM 2818
College Station, TX 77840
Attn: James Griffin
Telephone: (409) 764-8223
Location of Property: 1501 FM 2818, Ste. 106-109
Description of Property: Lot 2, Block 2 in the Southwood 26 Subdivision
Zoning of Property: C-2, Commercial - Industrial
Action Requested: Deletion and waiver of requirement for overhead sprinkler system or re-
classification designation of occupancy.
Applicable Ordinances: Ordinance 1919 in Section 901.8.7 of the adopted 1991 edition of
the Standard Building Code.
Staff Comments: Minimum occupancy content is based upon the size of the building and the
actual maximum amount of persons at any given time. This occupancy content is not allowed to be
increased above the calculated level of occupancy load.
Educational occupancies above the 12th grade are classified as business occupancies, also
buildings used for assembly purposes with less than 100 persons are classified as Group B Business
occupancies. The hundred person allowance is dependent upon the occupant content allowable for
the total gross square footage of the building for that given occupancy. Group E occupancies usage
are for the building use or any portion by six or more persons at any one time for educational
purposes through the 12th grade for the dissemination of knowledge or giving of an instructional
nature. Gathering of 100 or more persons in one room or given area shall be classified as a Group A
Assembly occupancy.
Occupancy content is listed below for the possible following occupancy classifications:
Occupant Load
Group A Assembly 7111 square feet 15 net 474
Group B Business 7612 square feet 100 gross 77
Group E Educational 7111 square feet 50 net 142
Should this building be classified as educational or business then the fire wall separation would
be required at both intersecting walls to remain intact separating the occupancies. Fire wall
separations are (4) four hour rated walls. This separation allows the Acrofit gymnasium to be treated
as a building within a building complex. Tenant separation between all other occupancies of this
complex are required.
It is the expressed opinion by other professional Building Officials, Standard Building Code
and myself that the most definable classification for this proposed occupancy is as a Small Assembly.
Existing local Building Code amendment 1919, Section 901.8.6 is the prohibitory document which
disallows this occupancy from not having to be sprinkled. As described in the diagram, it is shown
that the Acrofit occupancy is enclosed within the fire walls on both end walls. As a Small Assembly
occupancy, Table 400 of the Standard Building Code allows 12,000 square feet and applicable area
modifications to be calculated for the total unsprinklered area.
Calculations are as follows for a Small Assembly classification:
As per Section 402.3.2
402.3.3
I=4/3 [100 (F/P - .25)]
I= 1.33 X 28.3 = 37.68% Increase over unsprinklered area of Table 400 allowance
12,000 square feet
X 37.68%
4,522 square feet
+12,000
16,522 square feet
402.4.4 If sloped ramps were present then an extra 50% of unsprinklered area above
the previous modification allowances are applicable as per Table 400
12,000 square feet
X 50%
6,000 square feet
+ 16,522 square feet
22,522 square feet Total allowed floor space without requiring to be sprinkled
Twenty- two thousand five hundred and seventeen square feet could be allowed without sprinkling as
per Standard Building Code with applicable area modifications included. I would ask the Board to
consider the variance of the local amendment which requires sprinklering, instead of providing for the
variance of another occupancy classification. Our Building Code is a widely used and accepted model
which has proven through the years to be an effective and demonstrative document for providing
safety to both property and life.
CONSTRUCTION BOARD OF ADJUSTMENTS AND APPEALS
STAFF REPORT
Case Number: 94-007
Applicant: Acrofit Gymnastics, Inc.
1501 FM 2818 Ste. 106
College Station, TX 77840
Telephone: (409) 696-1234
Property Owner: College Station Business Center
1501 FM 2818
College Station, TX 77840
Attn: James Griffin
Telephone: (409) 764-8223
Location of Property: 1501 FM 2818, Ste. 106-109
Description of Property: Lot 2, Block 2 in the Southwood 26
Subdivision
Zoning of Property: C-2, Commercial - Industrial
Action Requested: Deletion and waiver of requirement for overhead sprinkler system.
Applicable Ordinances: Ordinance 1919 in Section 901.8.7 of the adopted 1991
edition of the Standard Building Code.
Staff Comments: Section 901.8.7 of the College Station Building Code local
amendments require that an approved sprinkler system be provided in all structures when
the total building area exceeds fifteen thousand (15,000) square feet. Section 901.8.6
requires a sprinkler system for Group A Assembly occupancies (except churches) when
the total square footage exceeds five thousand (5,000) square feet. The applicant states
35-40 occupants are an average occupant content. Occupant content and load is
calculated from the building size not from the amount using the structure. Re-
construction was presumably initiated without a building permit being issued.
Total door dimensioned width is adequate to egress occupants for emergency
conditions.
36" X 6 = 216/.2 = 1080 occupant egress
7111 square feet net =474 occupant load
15
App!: Acro fit Gymnastics, Inc.
M. Griffin
Phone: (409764--8223
1601 J 1611 2711 2717 Owner: James Address: 1501 FM 2818
STATE HWY 6 - TEXAS AVE 0
NOT TO SCALE
2702
G'�
11//411* Ir G�
21p11601
• p LONGMIRE DR 4® 2a zalz f*C>� igi
c
001 2009 2011 2013
�� P ����// 04 7006 n; 2070
4/0
r �UEll
imill
111111P2011
V j101
HILLTOP DR ii*
V .p,-rBvi, ." ,
20 0
wiz- 0 illik
\\ tik6 :.:.
CT 11
404
! iii
g -
1909 S i
DlliNli
-S a rte;
SOUTHWOOD
\ DR s - $ s scii
SL._
W
® 7107 11IX7 Sill
(.4 Building Division
City of College Station, Texas
94-007
CASE NUMBER:
CONSTRUCTION BOARD OF ACTION REQUESTED: Variance
ADJUSTMENTS AND APPEALS
LEGAL NOTICE
DATE TO BE PUBLISHED: MONDAY, June 6, 1994
BILL TO: The City of College Station
P. O. Box 9960
College Station, TX 77842
NOTICE OF PUBLIC HEARING
The College Station Construction Board of Adjustments and Appeals will hold a public hearing to
consider a variance request by Acrofit Gymnastics, Inc. for the following property:
Lot 2 Block 12 in the Southwood 26 Subdivision, zoned C-2, Commercial-Industrial
The hearing will be held in the Council Room of the College Station City Hall, 1101 Texas
Avenue at 4:00 p.m. meeting of the Board on Tuesday, June 7, 1994.
Any request for sign interpretive services must be made 48 hours before the meeting. To make
arrangements call (409) 764-3547 or(TDD) 1-800-735-2989.
For additional information, please contact me at (409) 764-3743.
Susan Macdonald
Building Technician
CITY OF COLLEGE STATION
•
C\I41 Post Office Box 9960 1101 Texas Avenue
College Station,Texas 77842-9960
(409)764-3500
June 2, 1994
College Station Business Center
1501 FM 2818
College Station, TX 77845
Attn: James Griffin
Dear Sirs,
The Construction Board of Adjustments and Appeals will meet on Tuesday, June 7, 1994
at 4:00 p.m. in the City of College Station Council Chambers to hear the variance request.
for case number 94-007, located at Lots 2, Block 12 in the Southwood 26 Subdivision. If
you have any question, please call me at(409)764-3743.
itv
S. cerely, ��/� /
�! '/ / I • / / / 1
Susan Macdonald
Building Technician
Home of Texas A&M University
O__ CITY OF COLLEGE STATION
Post Office Box 9960 1101 Texas Avenue
College Station,Texas 77842-9960
(409)764-3500
June 2, 1994
Acrofit Gymnastics, Inc.
1501 FM 2818 #106
College Station, TX 77845
Dear Sirs,
The Construction Board of Adjustments and Appeals will meet on Tuesday, June 7, 1994
at 4:00 p.m. in the City of College Station Council Chambers to hear your variance
request., case number 94-007, located at Lots 2, Block 12 in the Southwood 26
Subdivision. If you have any question, please call me at (409)764-3743.
Sinerely,
/:)46Mfrk
Susan Macdonald
Building Technician
Home of Texas A&M University
•
LEGAL NOTICE
DATE TO BE PUBLISHED: MONDAY, May 30, 1994
BILL TO: The City of College Station
P. O. Box 9960
College Station, TX 77842
NOTICE OF PUBLIC HEARING
The College Station Construction Board of Adjustments and Appeals will hold a public hearing to
consider a variance request by Acrofit Gymnastics, Inc. for the following property:
Lot 2 Block 12 in the Southwood 26 Subdivision, zoned C-2, Commercial-Industrial
The hearing will be held in the Council Room of the College Station City Hall, 1101 Texas
Avenue at 4:00 p.m. meeting of the Board on Tuesday, May 31, 1994.
Any request for sign interpretive services must be made 48 hours before the meeting. To make
arrangements call (409) 764-3547 or(TDD) 1-800-735-2989.
For additional information, please contact me at (409) 764-3743.
Susan Macdonald
Building Technician
•
(1"61 CITY OF COLLEGE STATION
Post Office Box 9960 1101 Texas Avenue
College Station,Texas 77842-9960
(409) 7643500
May 27, 1994
Acrofit Gymnastics, Inc.
1501 FM 2818 #106
College Station, TX 77845
Dear Sirs,
The Construction Board of Adjustments and Appeals will meet on Tuesday, May 31, 1994
at 4:00 p.m. in the City of College Station Council Chambers to hear your variance
request, case number 94-007, located at Lot 2, Block 12 in the Southwood 26
Subdivision. If you have any question, please call me at (409)764-3743.
Sincerely,
( AVAd- /Vd- C'
Susan Macdonald
Building Technician
Home of Texas A&M University
•
�•� CITY OF COLLEGE STATION
Post Office Box 9960 1101 Texas Avenue
College Station,Texas 77842-9960
(409) 764-3500
May 27, 1994
College Station Business Center
1501 FM 2818
College Station, TX 77845
Attn: James Griffin
Dear Mr. Griffin,
The Construction Board of Adjustments and Appeals will meet on Tuesday, May 31, 1994
at 4:00 p.m. in the City of College Station Council Chambers to hear the variance request
for case number 94-007, located at Lot 2, Block 12 in the Southwood 26 Subdivision. If
you have any question, please call me at (409)764-3743.
Sincerely,
4a104( -74/6Za&7M-e#'(--'
Susan Macdonald
Building Technician
Home of Texas A&M University