CITY OF COLLEGE STATION
Planning er Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
September 12, 2005
TO: Mitchell and Morgan, via fax 260-3564
FROM: Lindsay Boyer, Project Manager
SUBJECT: SPRING CREEK COMMONS (PP) - Preliminary Plat
Staff reviewed the above-mentioned preliminary plat as requested. The following page is a list
of staff review comments detailing items that need to be addressed. If all comments have been
addressed and the following information submitted by Monday, September 19, 10:00 a.m., your
project will be placed on the next available Planning and Zoning Commission meeting
scheduled for October 6, 7:00 p.m. in the City Hall Council Chambers, 1101 Texas Avenue.
Two (2) 24" x 36" copies of the revised preliminary plat;
Twelve (12) 11" x 17" copies of the revised preliminary plat;
One (1) Mylar original of the revised preliminary plat; and,
One (1) copy of the digital file of the preliminary plat on diskette or e-mail to
nmanhart@cstx.gov
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally filed with the City of College Station. Please note that if all comments have
not been addressed, your project will be pulled from the scheduled Planning & Zoning
Commission agenda. Your project may be placed on a future agenda once all the revisions
have been made and the appropriate fees paid. If you have any questions or need additional
information, please call me at 979.764.3570.
Attachments: Staff review comments
cc: Quorum 6 Green, via U.S. Mail
Case file #05-00500161
Home of Texas A&M University
C\--5\'‘‘,C{4
� 5 STAFF REVIEW COMMENTS NO. 1
�\ 0 (.,(et- Project: SPRING CREEK COMMONS (PP) - 05-00500161
e
Rii✓pI vecr/
PLANNING/ENGINEERING -� CiQCk--
`j'
L:64- 1 o Park skclekA/C k- t it buk(' ti► i-.('\� No lots may be approved that do not meet minimum lot size, and unbuildable lots may not
0,)
1r be platted. Please adjust the lot size to make this lot buildable, or incorporate it into an 12.
cy adjacent lot.
r e- Lot 2, Block 2 appears unbuildable as well with the 100 ft Vegetative Buffer preserved
crC6j 7 through the lot. It was previously conditioned with the re-zoning that the buffer would need
to remain 100 ft if was not improved by underground storm sewer, in which case the buffer
could be reduced to 50 ft. This appears to be necessary to make the lot buildable and
therefore the storm extension should be noted and buffer reduced accordingly on this
preliminary plat.
As it is currently illustrated on the plat, Lakeway is located in the 100 foot buffer. According
to the conditions of the rezoning, the buffer is to remain undisturbed. Please relocate the
thoroughfare out of this buffer.
. Please provide a proposal of the building plot lines to be considered, otherwise this would
be considered one building plot.
Please note that a temporary cul-de-sac with temporary easement will need to be
constructed and granted at the northern end of each of proposed, phased extensions of
Lakeway Drive. Timing of the Site Plan parking may justify the use of the driveways as a
means of emergency vehicle circulation in lieu of a cul-de-sac.
6. Please see TxDOT's access comments below.
7. Please note that the some of the proposed easements will need to be dedicated by .
separate instruments to accommodate earlier phases.
8. FYI: Impact Fees will be required at the time of Building Permit in accordance with the
meter sizing determining the Living Unit Equivalent.
9. FYI: Conceptually, the drainage report, asserting that detention is not necessary, is
acceptable. The reasoning is that this site discharges into the primary system. Note that
the flows cannot increase on the adjacent lots and the discharge shall be to Spring Creek
and not the un-named tributary of Spring Creek to the east.
Reviewed by: Lindsay Boyer/Alan Gibbs Date: September 12, 2005
ELECTRICAL
1. Developer installs conduit per city specs and design.
2. Developer provides 30' of rigid conduit for riser poles.
3. Developer pours transformer pad(s) per city specs and design.
4. Developer installs pull boxes as per city specs and design. (pull boxes provided by the
city).
5. Developer provides digital AutoCAD 2000 version of plat and/or site plan. Email to
bread a cstx.gov
6. Developer provides load data for project.
7. Developer covers cost of relocating utility pole(s) located at proposed Lakeway Drive.
8. Developer installs conduit along proposed Lakeway Drive for future electrical facilities.
9. Developer installs street lights per city specs and design on the Lakeway Dr extension.
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review. 2 of 3
10. Developer provides easements for electric infrastructure as installed for electric lines
(including street lights).
11. To discuss any of the above electrical comments, please contact Tony Michalsky at
979.764.3438.
Reviewed by: Brent Read Date: September 9, 2005
TxDOT
1. Proposed layout indicates Access Driveway spacing would be C-C which does not account
for driveway widths. At this site the posted Speed Limit is 55 MPH which requires a spacing
of 425' between Access Drives. (see attached)
2. Total distance from the center of the existing driveway (McDonalds) north to the proposed
exit ramp is 1,514' with the north driveway (C) being 140' south of this ramp. (proposed
layout)
3. Using the proper spacing to accommodate all three (3) proposed driveways:
DT = 15'('/2McD) + 425' + 24'(A) + 425' + 30'(B) + 425' + 30'(C) = 1,374'
Dp= 452' + 450' + 472' = 1,374' (Proposed)
This is 140' south of the proposed exit ramp which is acceptable with the addition of a decel
lane. This is necessary since Driveway C is located in the merge to 1- lane area just upstream
of the exit ramp. (Same as proposed)
4. Driveway "A" shall not be constructed until the existing ramps Ca this site have been
abandoned.
5. A better solution would be to close McDonald's driveway @ the proposed turn-around &
have a shared driveway (cross-access) @ DW A located 425' from Greens Prairie Road.
With the required spacing DW C would be located approximately 430' from the exit ramp &
would probably require a shorter decel lane.
Reviewed by: Jay Page Date: September 8, 2005
BTU _ �u
1. BTU has electrical lines either on or adjacent to the subject property. Please show BTU
electric lines and the easements covering the portion of BTU's overhead facilities that lie
within the property. If there are no easements found, a 20' easement centered on the
existing lines must be granted either by plat or by separate instrument.
Reviewed by: Randy Trimble Date: September 8, 2005
NOTE: Any changes made to the plans,that have not been requested by the City of College Station, must be explained in your
next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review. 3 of 3
MEMORANDUM
To: FILE
From: Jay Page
Date: July 11, 2005
Subject: SH 6 East Frontage Rd. (0049-12-067)
North (320') of Greens Prairie Road
SPRING CREEK COMMONS
College Station,Texas
Access Driveway Permits
COMMENTS:
1) Proposed layout indicates Access Driveway spacing would be C-C which does
not account for driveway widths. At this site the posted Speed Limit is 55 MPH
which requires a spacing of 425' between Access Drives. (see attached)
2) Total distance from the center of the existing driveway (McDonalds) north to the
proposed exit ramp is 1,514' with the north driveway(C) being 140'south of
this ramp. (proposed layout)
3) Using the proper spacing to accommodate all three (3) proposed driveways:
DT = 15'(1/2McD) + 425' + 24'(A) + 425' + 30'(B) + 425' + 30'(C) = 1,374'
Dp = 452' + 450' + 472' = 1,374'(Proposed)
This is 140' south of the proposed exit ramp which is acceptable with the
addition of a decel lane. This is necessary since Driveway C is located in the
merge to 1- lane area just upstream of the exit ramp. (Same as proposed)
4) Driveway "A" shall not be constructed until the existing ramps @ this site
have been abandoned.
5) A better solution would be to close McDonald's driveway @ the proposed
turn-around & have a shared driveway (cross-access) @ DW A located 425'
from Greens Prairie Road. With the required spacing DW C would be located
approximately 430' from the exit ramp & would probably require a shorter
decel lane.
•
Gr-ffi1511111111
CITY OF COLLEGE STATION
Planning&"Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
September 12, 2005
TO: Mitchell and Morgan, via fax 260-3564
FROM: Lindsay Boyer, Project Manager
SUBJECT: SPRING CREEK COMMONS (PP) - Preliminary Plat
Staff reviewed the above-mentioned preliminary plat as requested. The following page is a list
of staff review comments detailing items that need to be addressed. If all comments have been
addressed and the following information submitted by Monday, September 19, 10:00 a.m., your
project will be placed on the next available Planning and Zoning Commission meeting
scheduled for October 6, 7:00 p.m. in the City Hall Council Chambers, 1101 Texas Avenue.
Two (2) 24" x 36" copies of the revised preliminary plat;
Twelve (12) 11" x 17" copies of the revised preliminary plat;
One (1) Mylar original of the revised preliminary plat; and,
One (1) copy of the digital file of the preliminary plat on diskette or e-mail to
nmanhart@cstx.gov
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally filed with the City of College Station. Please note that if all comments have
not been addressed, your project will be pulled from the scheduled Planning & Zoning
Commission agenda. Your project may be placed on a future agenda once all the revisions
have been made and the appropriate fees paid. If you have any questions or need additional
information, please call me at 979.764.3570.
Attachments: Staff review comments
cc: Quorum 6 Green, via U.S. Mail
Case file #05-00500161
Home of Texas A&M University
STAFF REVIEW COMMENTS NO. 1
Project: SPRING CREEK COMMONS (PP) - 05-00500161
PLANNING/ENGINEERING
1. No lots may be approved that do not meet minimum lot size, and unbuildable lots may not
be platted. Please adjust the lot size to make this lot buildable, or incorporate it into an
adjacent lot.
2. Lot 2, Block 2 appears unbuildable as well with the 100 ft Vegetative Buffer preserved
through the lot. It was previously conditioned with the re-zoning that the buffer would need
to remain 100 ft if was not improved by underground storm sewer, in which case the buffer
could be reduced to 50 ft. This appears to be necessary to make the lot buildable and
therefore the storm extension should be noted and buffer reduced accordingly on this
preliminary plat.
3. As it is currently illustrated on the plat, Lakeway is located in the 100 foot buffer. According
to the conditions of the rezoning, the buffer is to remain undisturbed. Please relocate the
thoroughfare out of this buffer.
4. Please provide a proposal of the building plot lines to be considered, otherwise this would
be considered one building plot.
5. Please note that a temporary cul-de-sac with temporary easement will need to be
constructed and granted at the northern end of each of proposed, phased extensions of
Lakeway Drive. Timing of the Site Plan parking may justify the use of the driveways as a
means of emergency vehicle circulation in lieu of a cul-de-sac.
6. Please see TxDOT's access comments below.
V7. Please note that the some of the proposed easements will need to be dedicated by
separate instruments to accommodate earlier phases.
/8. FYI: Impact Fees will be required at the time of Building Permit in accordance with the
meter sizing determining the Living Unit Equivalent.
9. FYI: Conceptually, the drainage report, asserting that detention is not necessary, is
acceptable. The reasoning is that this site discharges into the primary system. Note that
the flows cannot increase on the adjacent lots and the discharge shall be to Spring Creek
and not the un-named tributary of Spring Creek to the east.
Reviewed by: Lindsay Boyer/Alan Gibbs Date: September 12, 2005
ELECTRICAL
1. Developer installs conduit per city specs and design.
2. Developer provides 30' of rigid conduit for riser poles.
3. Developer pours transformer pad(s) per city specs and design.
4. Developer installs pull boxes as per city specs and design. (pull boxes provided by the
city).
5. Developer provides digital AutoCAD 2000 version of plat and/or site plan. Email to
breadr�cstx.gov
6. Developer provides load data for project.
7. Developer covers cost of relocating utility pole(s) located at proposed Lakeway Drive.
8. Developer installs conduit along proposed Lakeway Drive for future electrical facilities.
9. Developer installs street lights per city specs and design on the Lakeway Dr extension.
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and`bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review. 2 of 3
10. Developer provides easements for electric infrastructure as installed for electric lines
(including street lights).
11. To discuss any of the above electrical comments, please contact Tony Michalsky at
979.764.3438.
Reviewed by: Brent Read Date: September 9, 2005
TxDOT
1. Proposed layout indicates Access Driveway spacing would be C-C which does not account
for driveway widths. At this site the posted Speed Limit is 55 MPH which requires a spacing
of 425' between Access Drives. (see attached)
2. Total distance from the center of the existing driveway (McDonalds) north to the proposed
exit ramp is 1,514' with the north driveway (C) being 140' south of this ramp. (proposed
layout)
3. Using the proper spacing to accommodate all three (3) proposed driveways:
DT = 15'('/2McD) + 425' + 24'(A) + 425' + 30'(B) + 425' + 30'(C) = 1,374'
Dp= 452' + 450' + 472' = 1,374' (Proposed)
This is 140' south of the proposed exit ramp which is acceptable with the addition of a decel
lane. This is necessary since Driveway C is located in the merge to 1- lane area just upstream
of the exit ramp. (Same as proposed)
4. Driveway "A" shall not be constructed until the existing ramps Cad this site have been
abandoned.
5. A better solution would be to close McDonald's driveway @ the proposed turn-around &
have a shared driveway (cross-access) @ DW A located 425' from Greens Prairie Road.
With the required spacing DW C would be located approximately 430' from the exit ramp &
would probably require a shorter decel lane.
Reviewed by: Jay Page Date: September 8, 2005
BTU
1. BTU has electrical lines either on or adjacent to the subject property. Please show BTU
electric lines and the easements covering the portion of BTU's overhead facilities that lie
within the property. If there are no easements found, a 20' easement centered on the
existing lines must be granted either by plat or by separate instrument.
Reviewed by: Randy Trimble Date: September 8, 2005
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out
to the City,will constitute a completely new review. 3 of 3