HomeMy WebLinkAboutStaff Comments 0 (irff"544 CITY OF COT J.FGE STATION Planning d'Development Services LP ,° 1101 Texas Avenue, P.O. Box 9960 (k� 5 College Station, Texas 77842 �1 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM August 29, 2005 TO: Rabon Metcalf, P.E. via fax to 979-690-0329 FROM: Trey Fletcher, Project Manager SUBJECT: KM Custom Homes Office Building-Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a Nst of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: 17 One(1) revised site and landscaping plan. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Baker&Carnes Investments, LLC • 230 Southwest Parkway East, Suite 106, College Station, TX 77840 Kenny Melesky, KM Custom Homes via fax to 979-846-5589 Case fie 105-00500147 STAFF REVIEW COMMENTS NO I Project: KM CUSTOM HOMES-OFFICE BLDG (SP)—05-00500147 /PLANNING ,/North side setback shows 7.5' but building separation only 12'. 142(Discrepancies exist among the replat (2001), proposed site plan and previously approved site plan for TC Homes regarding location of interior lot lines and dimensions. v, Site plan shows 7.5-foot rear building setback; 15 feet is required. ' 4(Provide bike rack capable of storing a minimum of four(4) bicycles per Section 7.9.F. Parting requirements: 9 spaces are required for each lot for a total of 27 required spaces. This was also indicated on the previously approved, phased site plan in 2002. . . _ •,. . i e ,o a •, • (,3ll vide building nktene ncicolor samPts and binding elevations in conjunction with site plan or prior to building permit approval to fulfill Section 7.9 of the UDO. Reviewed by: Trey Fletcher Date: 8-26-2005 LANiDSCAPING/STREETSCAPING/BUFFER 0/To receive barricaded points for existing trees they must be barricaded one foot per caliper inch. A barricade detail must be provided. Barricades must be in place prior to any activity on the property. Reviewed by: Trey Fletcher Date: 8-26-2005 ENGINEERING 1. Engineering is still reviewing the site plan and reports. Comments will be return in the next week. Reviewed by: Josh Norton Date: 8-29-05 FIRE 1. Reviewed by: Date: ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan email to gmartinezecstx.aov NOTE: Any climes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmitbd letter and'bubbled'on ver dans.Any additional changes on these plans that have not been palmed out to the CIV. 3. Developer provides bad data for project. 4. Developer provides temporary blanket easement for construction purposes. 5. Developer provides easements for electric infrastructure as installed for electric lines. 6. Developer will intercept existing PVC conduit at secondary pedestal and extend to building service location. 7. Service wire furnished and installed by CSU 8. To discuss any of the above electrical comments, please contact Gilbert Martinez at 979.764.6255. Reviewed by: Gilbert Martinez Date: 08-23-05 MISCELLANEOUS 1. Irrigation system must be protected by a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans,that have not been requested by the City of CoNege Station,must be explained in your next transmittal letter and"bubbled'on your plans.Any additional changes on these plans that have not been pointed out to the City. Grffil" CITY OF COLLEGE STATION Planning eir Development Services 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM August 29, 2005 TO: Rabon Metcalf, P.E. via fax to 979-690-0329 FROM: Trey Fletcher, Project Manager SUBJECT: KM Custom Homes Office Building - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised site and landscaping plan. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Baker& Carnes Investments, LLC • 230 Southwest Parkway East, Suite 106, College Station, TX 77840 Kenny Melesky, KM Custom Homes via fax to 979-846-5589 Case file #05-00500147 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: KMtUSTOM HOMES -OFFICE BLDG (SP) —05-00500147 ( . v.fir -�'`� PLANNING "' 1 � � 1. North side setback shows 7.5' but building separation only 12'. 2. Discrepancies exist among the replat (2001), proposed site plan and previously approved site plan for TC Homes regarding location of interior lot lines and dimensions. 3. Site plan shows 7.5-foot rear building setback; 15 feet is required. 4. Provide bike rack capable of storing a minimum of four (4) bicycles per Section 7.9.F. 5. Parking requirements: 9 spaces are required for each lot for a total of 27 required spaces. This was also indicated on the previously approved, phased site plan in 2002. Qfr ,. In reference to Civil Site Note No. 6, show dumpster location and screening. 7. Provide building material and color samples and building elevations in conjunction with site plan or prior to building permit approval to fulfill Section 7.9 of the UDO. Reviewed by: Trey Fletcher Date: 8-26-2005 LANDSCAPING/STREETSCAPING/BUFFER 1. To receive barricaded points for existing trees they must be barricaded one foot per caliper inch. A barricade detail must be provided. Barricades must be in place prior to any activity on the property. Reviewed by: Trey Fletcher Date: 8-26-2005 ENGINEERING 1. Engineering is still reviewing the site plan and reports. Comments will be return in the next week. Reviewed by: Josh Norton Date: 8-29-2005 FIRE 1. Repaint Fire Lane in private street. Reviewed by: Jerry Duffey Date: 8-29-2005 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan email to gmartinez@cstx.gov 3. Developer provides load data for project. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 2 of 3 4. Developer provides temporary blanket easement for construction purposes. 5. Developer provides easements for electric infrastructure as installed for electric lines. 6. Developer will intercept existing PVC conduit at secondary pedestal and extend to building service location. 7. Service wire furnished and installed by CSU 8. To discuss any of the above electrical comments, please contact Gilbert Martinez at 979.764.6255. Reviewed by: Gilbert Martinez Date: 08-23-2005 MISCELLANEOUS 1. Irrigation system must be protected by a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 3 Ckff' CITY OF COLLEGE STATION Planning e Development Services 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM September 2, 2005 TO: Rabon Metcalf, RME, Via fax 690.0329 (/ FROM: Bridgette George, Development Coordinator SUBJECT: KM CUSTOM HOMES -OFFICE BLDG (SP) Staff reviewed the above-mentioned engineering documents as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review and approval of the plans: One (1) set of revised construction documents Two (2) revised drainage reports. If you have any questions or need additional information, please call Josh Norton or myself at 764.3570. Attachments: Staff Review Comments Cc: Baker & Carnes, Interest, Inc., via fax 693.7839 I/ Case file no. 05-00500147 Home of Texas A&M University KM CUSTOM HOMES -OFFICE BLDG (SP) (05-00500147) Engineering Review Comments No. 1 1. Please submit a report explaining the functionality of the proposed water meter and 2" water line being tapped off the existing service line. Also, explain the feasibility of placing the water meter for Lot 3C. 2. Please submit a report explaining the functionality of the proposed sewer line being tapped off the existing service line. 3. Please use SDR26-ASTM D3034 for the sanitary sewer pipe material, not SCH 40. 4. Drainage Report: a. Update Table #1 b. Describe what the runoff is doing on this property, where it is going and how much c. Provide post development calcs Reviewed by: Josh Norton Date: 9-1-05 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City of College Station will constitute a completely new review. Page 2 of 2 CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM September 9, 2005 TO: Rabon Metcalf, P.E. via fax to 979-690-0329 FROM: Trey Fletcher, Project Manager SUBJECT: KM CUSTOM HOMES - OFFICE BLDG (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Six (6) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (please submit additional copies to be stamped for your records). If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. Attachments: Staff review comments cc: Baker& Carnes Investments, LLC • 230 Southwest Parkway East, Suite 106, College Station, TX 77840 Kenny Melesky, KM Custom Homes via fax to 979-846-5589 Case file#05-00500147 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 2 Project: KM CUSTOM HOMES -OFFICE BLDG (SP) - 05-00500147 PLANNING 1. Amend parking requirements table to reflect true parking requirements, being 9 per lot, based on existing, proposed and maximum allowed square footages for Lots 3A, 3B and 3C respectively. 2. Regarding the following comments (#3 and #4), per Section 7.9.D of the UDO, all buildings developed as a building plot shall have materials and colors that are similar and complement each other architecturally...All buildings shall employ architectural, site, and landscape design elements that are integrated with and common to those used on the main/primary buildings or structures on the site. These common design elements shall include building materials associated with the main/primary structure. 3. Elevations submitted denote materials used, provide samples. 4. Provide color sample for doors, eaves, vents and other painted surfaces. Reviewed by: Trey Fletcher Date: 9-9-2005 ENGINEERING 1. No comments. Reviewed by: Josh Norton Date: 9-8-2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 2 of 2