Loading...
HomeMy WebLinkAboutStaff Comments • (frffill1111111111 CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM June 27, 2005 TO: Marcela Matiz, via fax 713-468-7693 FROM: Jennifer Prochazka, Project Manager SUBJECT: TEXAS PAVILION RETAIL CENTER (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: $200 processing fee for the next round of three (3) staff reviews; and, Six (6) complete sets of construction documents (not building plans) for the proposed development with the revised site and landscaping plans attached. Two (2) revised site One (1) landscaping plan If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me or Josh Norton at 764-3570. Attachments: Staff review comments cc: James Chang, via email jchanqaibclawfirm.com Ned Sager, via fax 713-468-7693 Case file #05-00500064 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 3 Project: TEXAS PAVILION RETAIL CENTER (SP) - 05-00500064 PLANNING 1. There have been changes made to the plan that were not asked for by the City and have not been specifically called to our attention. Please note that any changes not specifically requested by the City should be bubbled or called out in some other way. 2. In response to your comments regarding fire lanes: proposing a fire lane off-site may require additional off-site work, which will require permission from the adjacent property owner. Do you have any information on the existing pavement in the areas you are showing to be fire lane? 3. The response sheet from Windrose states that no asphalt paving is proposed, however it is still shown on the STM site plan. Please coordinate the two plans. If it is proposed, please provide a detail. 4. All end islands must be a minimum of 180 square feet. (Repeat Comment) Several of the islands that you have not dimensioned do not meet this minimum requirement. Several of your end islands are now reduced in size to below the minimum. Also, you have reduced the drive aisle width (please note 23' is required...on your first submittal you had 22'-11.5", you now have 22'-3"). Your parking is also now encroaching into the 15' parking setback. Have you made any other changes to the plan that staff has not asked for? 5. It is our understanding that Windrose is now working with the Chase Bank company to include some minor site changes. Please submit those changes with the next submittal. As a reminder, any changes not specifically requested by the City should be bubbled or called out in some other way. Please call me to discuss these comments and to let me know of any other changes made to the plan that I am not aware of. Reviewed by: Jennifer Prochazka Date: June 27, 2005 ENGINEERING 1. The fire hydrant and fire hydrant line will require an easement to be dedicated by separate instrument, for the areas which are not already covered by a PUE. Reviewed by: Josh Norton Date: June 21, 2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 2 of 2 (7.1,111111111111'4111111111111 CITY OF COLLEGE STATION Planning e' Development Services 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM July 18, 2005 / TO: Marcela Matiz, via fax 713-468-7693 r FROM: Bridgette George, Asst. Development Manager SUBJECT: TEXAS PAVILION RETAIL CENTER (SP) Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: Six (6) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached Two (2) revised site One (1) landscaping plan One (1) 11x17 grading and erosion control plan Easement Dedication Sheet and required documents If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. Attachments: Staff review comments cc: James Chang, via email ichanq(a�ibc wfirm.com Ned Sager, via fax 713-468-7693 V Case file #05-00500064 Home of Texas A&M University STAFF REVIEW COMMENTS No. 4 Project: TEXAS PAVILION RETAIL CENTER (SP) - 05-00500064 ENGINEERING The follow comments are a result from changes to the site plan since our last review. 1. The sanitary sewer service which serves the proposed 5,931 SF retail building must at least be at a 1% slope. 2. The irrigation meter will require a backflow preventer, please depict. However the domestic water line feeding the proposed retail building will not require a backflow preventer. 3. You may consider locating the proposed bank's water meters back towards the retail building as to straighten the domestic line feeding the building. 4. Please provide plan and profile detail for the two fire hydrant lines. 5. Further review of the private utilities: meter sizing, line sizing, etc, will be done by the CoCS building department. 6. To process the easement dedication you need to fill out an easement dedication application and meet all of its requirements. These applications may be downloaded from our web site under development applications. I will hold on to the metes and bounds, and exhibit as they are a part of the application. 7. Due to the extension of public infrastructure with the fire hydrants, an additional $600 for inspections will be required before the development permit will be issued. Please feel free to contact me if you have any further questions. Reviewed by: Josh Norton Date: July 14, 2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 2 05-4.4 . b-goco- keAgr4t) A_._.__ 0D :00 STM &Associate. stm architects and associates,1.1.c. dba STM & ASSOCIATES ,r uC tn. CITY OF COLLEGE STATION PLAN EXAMINING CORRECTIONS-PROJECT#-00500064 ADDRESS: 2000 TEXAS AVENUE, 77840 JENNIFER PROCHAZKA PLANING COMMENTS 1. Is all off-site fire lane"proposed" .... alb) omit-mon , ? �} SI 11 p`1\0j Y Y uuck il Please re: Due to there Is not any record about existing fire lanes close to the property, we ares u f proposing a new one as noted on the Site plan a-1.0. J 7 0.X.. X You are only showing fire lanes at the rear of Please re: A new fire lane was added at the front of the building as noted on the Site plan a-1.0. 0.,X Thank you for providing the pavement details. Please specify, .... Please re: Civil plans. 1 r 1 I r i 4. Thank you for providing the square footages of the parking ... 1 ase re:Site plan A-1.0. 5. Please be sure all setbacks are shown at the correct .... Please re:Site plan a-1-0. t)i , c\The parking space in the southwest corner of the property .... Please re:Site plan a-1-0. 0',•. Thank you for providing the survey to show how you area affecting .... Please re:Site plan a-1-0. 0/ Thank you for the information that you have provided regarding interior islands .... ' ease re: The information has been removed as noted on the Site plan A-1.0. 9. The rear elevation is not meeting the requirements of.... Please re:Building elevation A-4-0. 04tPlease provide the inside dimension of the dumpster enclosure .... lease re:Dumpster minimum dimensions are12'x12'wla12'clear opening inside the gates as noted on the details sheet A-1.2 8705 Katy Freeway,Suite 202•Houston,Texas 77024•Ph:713-468-7557•Fax:713-068-7693 STM &Associates stm architects and associates,t.i.c. dba STM & ASSOCIATES O"`. Please provide information of how the dumpster enclosure will be treated .... Please re: Dumpster's finish exterior wall surface w/block filler&E.I.F.S.finish to match color building.12 ga.metal plate for dumpster door spot welded to tubular steel frame painted to match color building as noted on the details sheet A-1.2 Ofr )2. On sheet C7 Erosion control plan, it looks as if you are proposing .... P ease re:Civil plans. CpX. The transformer is not showing as screened. Please show how it will be screened .... Please re:The transformer will be screened by landscape as note on landscaping plans L-1-0. and L-2. rte, Please provide a temporary blanket easement for construction purposes. /Please re: Easement dedication sheet and all the documents required were submitted with the last review on June 6—2005 as you requested. JOSH NORTON ENGINEERING COMMENTS 1. Fire hydrants must be located where the fir truck can pull .... Please re: Civil plans. 2. Meters are still located in TXDOT ROW. Please re: Civil plans. If you have any question about the answers above please call me. Ph: 713-468-7557 Fax: 713-468-7693 Marcela Matiz stm&associates 8705 Katy Freeway,Suite 202•Houston,Texas 77024•Ph:713-468-7557•Fax:713-468-7693 Av Winarose Land Services, Inc — 10675 Richmond Ave, Bldg 7 �'� '' Houston, Texas 77042 !Y ` E Phone(713)458-2281 Fax(713)461-1151 '� ,% Professional Surveying & Engineering Services s ENGINEERING COMMENTS: 1. Revised. Fire Hydrant location revised per conversation with Josh Norton. 2. Revised PLANNING COMMENTS: " 3. Revised,no asphalt paving proposed. `- 14 ', • -6-Y\ Gte 5. Revised. i,\0c9pOUA-- 1 Revised. (*ffill511411111 CITY OF COLLEGE STATION Planning dr Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM May 2, 2005 TO: Marcela Matiz, via fax 713-468-7693 FROM: Jennifer Prochazka, Staff Planner SUBJECT: TEXAS PAVILION RETAIL CENTER(SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: Revised site, civil, and landscaping plans. Easement Dedication Sheet and required documents. Please note that the Easement Dedication Sheet and the necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: James Chang, via email jchanq ibclawfirm.com Ned Sager, via fax 713-468-7693 Case file #05-00500064 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: TEXAS PAVILION RETAIL CENTER(SP) —05-00500064 PLANNING 1. Please provide the following additional information in the title block of ALL sheets: address, legal description, owner name, developer name, and total site area. 2. The vicinity map on several of the sheets is incorrect. 3. All plans need to match. For instance, only one plan is showing the alternative curb placement for the required bicycle facilities. 4. Total site area on application and landscape plan do not match. Please clarify. 5. Please provide the ownership and current zoning of this tract and all adjacent tracts on the site plan. 6. Please show property lines only as they currently exist. This property is not currently divided. Also, the ROW for the Texas Avenue widening project has been acquired; please reflect this as the current property line. 7. Please provide ALL setbacks on the site plan. 8. Please provide an existing survey so that staff can determine what modifications are proposed to the surrounding parking areas and insure general parking and landscaping compliance. 9. Please provide required and provided parking synopsis on the site plan. 10. Parking space in southwest corner of property is only 14 feet in length, and must be a minimum of 18'. 11.ALL parking spaces must be at least 18' in length (if a 2' overhang is provided). The spaces shown facing Texas Avenue do not meet this requirement. 12. Please show locations of all fire lanes on site and the fire lanes that they connect to off site. 13. If the property is not located within a floodplain, please provide a note stating this with the confirming FEMA/FIRM map number. 14. Anything 'existing' on site must meet current standards or will need to be replaced since this is a complete redevelopment of the site. This includes pavement. 15. Please provide a pavement detail. 16. All curbing is required to be monolithic. 17. For every 15 interior parking spaces you are required to provide a 180 square foot interior island somewhere within the interior parking area. If the end islands (in the interior of the site) exceed their required square footage, the additional square footage can be applied to the interior island requirement. If you wish for the additional square footage of your end islands to count toward your interior island requirement, please provide the square footage of these end islands. 18. Please show location of fire hydrant on the site plan. 19. The dumpster enclosure needs to have a 12ft. opening (inside width) in order to house a FEL container. The dumpster needs a 12' clear opening for service. 20. Please provide information on how the dumpster enclosure will be treated or screened. Will it be painted? Are there gates? 21. Is note 126 shown in the right place on the site plan? Will that whole area be 'asphalt impregnated expansion joint material?" 22. Please remove any key notes that do not have a corresponding location on the plan. 23. Please label transformer and other mechanical equipment. 24. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 2 of 4 residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. 25. FYI: Any proposed pedestrian access to TxDOT right-of-way shall be coordinated with current Texas Avenue widening project. Appropriate data will be required for any future permits @ this site. Reviewed by: Jennifer Prochazka Date: April 25, 2005 LANDSCAPING/STREETSCAPING/BUFFER 1. Total site area on application and landscape plan do not match. Please clarify. 2. All proposed landscaping must be located on site. Please do not show any off-site landscaping, including existing. 3. Is any landscaping being removed or replaced on existing properties (ie: with parking island modifications)? 4. Proposed landscape should be evenly dispersed. Why is there no landscaping proposed around the bank building? 5. All landscape counting toward the required points for this site must be located on site. 6. Please remove landscaping shown on this site that is being removed with new construction (ie: in parking areas). 7. Please use different symbols for different species. Dwarf species cannot be used for required screening. 8. The 'African Iris' is not considered to be a shrub. 9. The way you have determined the number of streetscape trees that are required is correct. However, the way that you have calculated the additional streetscape point requirement is incorrect. To calculate the streetscape points required, you only need to add an additional 300 points for every 50 linear feet of frontage, you do not need to add in required points for street trees. Reviewed by: Jennifer Prochazka Date: April 25, 2005 ENGINEERING 1. Provide contours for area. 2. Indicate location of fire lanes. 3. Water service lines will need to be Type K Copper. 4. Water demands indicated only allow for a .75" meter. 5. Water and Irrigation meters must be located in easement or ROW. 6. FYI: Due to the Texas Ave. Widening/Utility Project currently under construction, the City's Public Works department is currently reviewing the utility plan for the Texas Pavillion Project; we will return these additional comments ASAP. 7. Sewer service lines require a cleanout every 100ft. 8. Verify slope of sewer service line to Bank. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 4 9. Please indicate the name of the plat/legal description of this site 10. Development Permit Application will require standard supporting documentation (drainage report, water report, sewer report, erosion control plan, etc.) Reviewed by: Josh Norton Date: April 21, 2005 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of IMC conduit for riser poles. 3. Developer pours transformer pad(s) per city specs and design. 4. Developer installs pull boxes as per city specs and design.(pull boxes 5. provided by the city). 6. Developer provides digital AutoCAD 2000 version of plat and/or site plan. 7. email to sweido(c�cstx.gov 8. Developer provides load data for project. 9. Developer provides temporary blanket easement for construction purposes. 11. Developer provides easements for electric infrastructure as installed for electric lines (including street lights). 12. To discuss any of the above electrical comments, please contact Sam Weido at 979.764.6314. Reviewed by: Sam Weido Date: 4-28-05 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 4 of 4 CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM May 2, 2005 TO: Marcela Matiz, via fax 713-468-7693 FROM: Jennifer Prochazka, Staff Planner SUBJECT: TEXAS PAVILION RETAIL CENTER(SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: Revised site, civil, and landscaping plans. Easement Dedication Sheet and required documents. Please note that the Easement Dedication Sheet and the necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: James Chang, via email ichanq( ibclawfirm.com Ned Sager, via fax 713-468-7693 Case file #05-00500064 Home of Texas A&M University I< d-WrI,CUIA-Q rekcyd ri cam,,( kY ch J J\ii,,t't STAFF REVIEW COMMENTS NO. 1 ,ANI?:\U:\ /� Project: TEXAS PAVILION RETAIL CENTER(SP) - 05-00500064 Vr \Yr‘ ‘1\ , ti Itututif, nutt i bop ( 7 .4i, ;\ PLANNING/ / IPlease pro de the followir(g additional jhformation in the tie block of ALL sheets: address, 4' va /legal descri tion, owner n me, developer name, and total tte area. The vicinity map on several of the sheets is incorrect. All plans need to match. For instance, only one plan is showing the alternative curb placement for the required bicycle facilities. Total site area on application and landscape plan do not match. Please clarify. lease provide the ownership and current zoning of this tract and all adjacent tracts on the ciP site plan. . Please show property lines only as they currently exist. This property is not currently divided. Also, the ROW for the Texas Avenue widening project has been acquired; please ( Ak reflect this as the current property line. 'y ^� ease provide ALL setbacks on the site plan. '`(�. Sh-CAP e COTTeCt y ttaf (-Lej4 . 9.. Please provide an existing survey so that staff can determine what modiffeations are proposed to the surrounding parking areas and insure neral parking and landscaping compliance. h0 1.c• 1t - C1 -6-k-5 tie. . . „.- r pAiic-v- x . -( amo cA . I?lease provide required and provided parking synopsis on the site plan. U 0 Parking space in outhwe t corner of property is only 14 feet in length, and must be a )ninimum of 18'. li,f. ALL parking spaces ust be at least 18' in length (if a 2' overhang is provided). The spaces shown facing Texas Avenue do not meet this requirement. .fir? (A(\.eS a -lease show locations of all fire lanes on site and the fire lanes that they connect to off site. (7(1 ' .�. If the property is not located within a floodplain, please provide a note stating this with the CL* r a( : onfirming FEMA/FIRM map number. hK w c),0 -W. Anything 'existing' on site must meet current standards or will need to be replaced since this al (Attl '. is a complete redevelopment of the sit-q., This includes pav men,t. 7 1 1 14745. ,lease provide a pavement detail. -'Au-4.1 S s p c A, 1914 O( • DII curbing is required to be monolithic.WL r f W1T/. For every 15 interior parking spaces you are required to provide a 180 square foot interior tisland somewhere within the interior parking area. If the end islands (in the interior of the Novtozykl- site) exceed their required square footage, the additional square footage can be applied to the interior island requirement. If you wish for the additional square footage of your end islands to count toward your inter r island�^r�quirement, please provide the square footage ,„ dr, of these end islands. ( (A � O -eaa t3L Vld J 2 7 1 ease show location of fire hydrant on the site plan. - q 2;nlisirde t�ll/t.eSUJI/IAJThedumpsterenclosureneedstohavea12ft. opening width) in order tto�-,house a . .' FEL container. The dumpster needs a 12' clear opening for service. -- ate_ ' jUT[,f"LQ 20 Please provide information on how the dumpster enclosure^ri,ll be treated or screened. Will J t be painted? Are there gates? -CA - 0 G{- Pfl' i not {021 Is note 126 shown in the right place on the site plan? Will that whole area be 'asphalt ft144Ppregnated expansion joint material?" ease remove any key notes that do not have a corresponding location on the plan. Please label transformer and other mechanical equipment. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or I NOTE: Any changes made to the plans,that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. N =tLn1AS LkA4 h&.r✓k yt Vic. v le_a % G -a) residential district within 150' of the subject lot, measured from a point five feet above ade. Such screening shall be coordinated with the building architecture and scale to aintain a unified appearance. . FYI: Any proposed pedestrian access to TxDOT right-of-way shall be coordinated with current Texas Avenue widening project. Appropriate data will be required for any future permits @ this site. Reviewed by: Jennifer Prochazka Date: April 25, 2005 L IDSCAPING/STREETSCAPING/BUFFER rr��/. otal site area on application and landscape plan do not match. Please clarify. II proposed landscaping must be located on site. Please do not show any off-site andscaping, including existing. 3/ Is any landscaping being removed or replaced on existing properties (ie: with parking island modifications)? N d -5 U- -tu 51.A 4/Proposed landscape should be�enly�dispersed. CL-qty is there nAondscaping proposed� around the ban build] G��" V �! All landscape coupOW (LW ing owar a re•tre porn 'or is si e must be located on site. IVPlease remove landscaping shown on this site that is being removed with new construction V}ie: in parking areas). Y/. Please use different symbols for different species. Dwarf species cannot be used for /required screening. ,8: The 'African Iris' is not considered to be a shrub. VJAYIA)-64 4! The way you have determined the number of streetscape trees that are required is correct. However, the way that you have calculated the additional streetscape point requirement is incorrect. To calculate the streetscape points required, you only need to add an additional 300 points for every 50 linear feet of frontage, you do not need to add in required points for street trees. Reviewed by: Jennifer Prochazka Date: April 25, 2005 ENGINEERING 1. Provide contours for area. 2. Indicate location of fire lanes. 3. Water service lines will need to be Type K Copper. 4. Water demands indicated only allow for a .75" meter. 5. Water and Irrigation meters must be located in easement or ROW. 6. FYI: Due to the Texas Ave. Widening/Utility Project currently under construction, the City's Public Works department is currently reviewing the utility plan for the Texas Pavillion Project; we will return these additional comments ASAP. 7. Sewer service lines require a cleanout every 100ft. 8. Verify slope of sewer service line to Bank. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 4 9. Please indicate the name of the plat/legal description of this site 10. Development Permit Application will require standard supporting documentation (drainage report, water report, sewer report, erosion control plan, etc.) Reviewed by: Josh Norton Date: April 21, 2005 ELECTRICAL t. Developer installs conduit per city specs and design. 2. Developer provides 30' of IMC conduit for riser poles. 3. Developer pours transformer pad(s) per city specs and design. 4. Developer installs pull boxes as per city specs and design.(pull boxes 2. provided by the city). (1. Developer provides digital AutoCAD 2000 version of plat and/or site plan. 7. email to sweido(c�cstx.gov fig Developer provides load data for project. 9. Developer provides temporary blanket easement for construction purposes. 11. Developer provides easements for electric infrastructure as installed for electric lines (including street lights). 12. To discuss any of the above electrical comments, please contact Sam Weido at 979.764.6314. Reviewed by: Sam Weido Date: 4-28-05 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 4 of 4 • (*riff15114 CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM June 13, 2005 TO: Marcela Matiz, via fax 713-468-7693 FROM: Jennifer Prochazka, Staff Planner SUBJECT: TEXAS PAVILION RETAIL CENTER(SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached. One (1) 11x17 grading and erosion control plan Easement Dedication Sheet and required documents. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me or Josh Norton at 764-3570. Attachments: Staff review comments cc: James Chang, via email ichangaibc wfirm.com Ned Sager, via fax 713-468-7693 Case file#05-00500064 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 2 Project: TEXAS PAVILION RETAIL CENTER (SP) - 05-00500064 PLANNING 1. Is all off-site fire lane "proposed?" Is none of it existing? 2. You are only showing fire lanes at the rear of this site. How do you propose to access the fire hydrants or the main entrances to the buildings? Depending on how your fire lanes are reconfigured, you may need to re-work some of your end islands to achieve the required turning radii. Also, you are showing parking spaces in front of your hydrants. This is not permitted. 3. Thank you for providing the pavement details. Please specify where each type (light, medium, heavy) is to be used. All dumpster approaches (not just in front of the dumpster, but the entire route) and all fire lanes must be a minimum of 6". All other concrete pavement must be a minimum of 5". #4 bars at 18" o.c. is required at all times. Please provide additional detail for what you have labeled at "asphalt paving." 4. Thank you for providing the square footages of the parking islands. All end islands must be a minimum of 180 square feet. 5. Please be sure that all setbacks are shown at the correct distance. The side street setback (from Holleman) is 15 feet. 6. The parking space in the southwest corner of the property is only 14 feet in length. All parking spaces in this area must be a minimum of 18 feet in length (repeat comment). 7. Thank you for providing the survey to show how you are affecting the parking off-site. Please show the dimensions of parking and drive aisles that have been reconfigured. 18 foot spaces may only be used if there is a 2' foot overhang, otherwise 20' parking spaces are required. 8. Thank you for the information that you have provided regarding interior islands. From the information I have determined that you are meeting the minimum requirements. However, please remove this information from the site plan, as it is calculated incorrectly. 9. The rear elevation (Facade D) is not meeting the requirements of 7.9.0 Building Mass and Design. A second element (for every 60') must be added in accordance with this section. 10. Please provide the inside dimensions of the dumpster (inside the bollards and inside the gates). The minimum dimensions are 12' x 12' with a 12' clear opening inside the gates. (repeat comment). This can be shown by way of a note on the plan or a detail of the enclosure. 11. Please provide information of how the dumpster enclosure will be treated or screened. Will it be painted? What are the gates made of? (repeat comment). This can be done by way of a note on the plan or a detail of the enclosure. 12. On sheet C7 Erosion Control Plan, it looks as if you are proposing a construction entrance from Holleman Drive. This location will not be permitted. Please show this entrance as connecting interior to the adjacent parking. 13. The transformer is not shown as screened. Please show how it will be screened. 14. Please provide a temporary blanket easement for construction purposes. Reviewed by: Jennifer Prochazka Date: June 10, 2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 2 of 3 ENGINEERING 1. Fire hydrants must be located where the fire truck can pull up and be within 5' of the hydrant, as well as be in a fire lane. Texas Avenue is not a possibility for truck/hydrant connection, and there can not be parking spaces between a hydrant and the truck. May consider leaving existing 6" line with hydrant to serve the proposed Bank site, as well as extending a similar line for the proposed Texas Pavilion fire hydrant. 2. Meters are still located in the TxDOT ROW and need to be relocated within an easement. 3. Please feel free to contact me if you have any questions, 979-764-6221. Reviewed by: Josh Norton Date: June 10, 2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 3 of 3 Page 1 of 1 Lindsay Boyer - Men's Warehouse Review Comments From: Lindsay Boyer To: Chris Haver Date: 5/19/2005 9:20 AM Subject: Men's Warehouse Review Comments 'Site plan has not yet been approved. n l Building square footage (6,160.5) exceeds square footage indicated on the submitted site pla (5,931). S c j- Reyyised building and site plans should reflect the same square footage. cy) s1 3(Rear elevation must be included. All facades are reviewed for compliance with non-residential architectural standards. Please provide list of building materials and any color information, indicate their placement on each elevation, and provide a table with the square footage of each material used on each elevation. Lindsay B. Boyer Staff Planner City of College Station 1101 Texas Avenue S. College Station, Texas 77840 (979) 764-3570 / (979) 764-3496 Fax lboyer@cstx.gov www.cstx.gov file://C:\Documents and Settings\lboyer\Local Settings\Temp\GW}00002.HTM 6/13/2005 STM &. Assoc late-. stm architects and associates,1.I.c. dba STM &ASSOCIATES CITY OF COLLEGE STATION PLAN EXAMINING CORRECTIONS-PROJECT#-00500064 ADDRESS: 2000 TEXAS AVENUE, 77840 JENNIFER PROCHAZKA PLANING COMMENTS 1. There have been changes made to the plan that were not..... Please re: Some changes have been made for ADA request as noted on sheet A-1.0 delta"C". 2. In response to your comments regarding fire lanes Please re: Site plan A-1.0(Fire lanes) 3. The response sheet from Windrose states that no asphalt paving is, .... Please re:The two plans have been coordinated. 4. All end islands must be a minimum of 180 sf ... Please re:Site plan A-1.0. 5. It is our understanding that Windrose is now working with the Chase .... Please re: Minor changes have been incorporated to the site according with Chase requirements as noted on sheet A-1.0.delta"D"(sidewalk around the Chase Bank and landscaping area) JOSH NORTON ENGINEERING COMMENTS 1. The fire hydrant line will require an easement to be dedicated .... Please re: Civil plans. If you have any question about the answers above please call me. Ph: 713-468-7557 Fax: 713-468-7693 Marcela Matiz stm &associates 8705 Katy Freeway,Suite 202•Houston,Texas 77024•Ph:713-468-7557•Fax:713-468-7693 .v Windrose Land Services, Inc 4779 10675 Richmond Ave, Bldg 7 Houston, Texas 77042 ` ` E Phone(713)458-2281 Fax(713)461-1151 Professional Surveying & Engineering Services s PLANNING COMMENTS: 1. Site changes for the Chase Bank have been incorporated into the civil drawings. ENGINEERING COMMENTS: 1. Recordation of 10' Public Utility Easement pending, see attached exhibit. STM R: :?sS( 4aAe STM ARCMTECTS AND ASSOCIATES,L.L.C. dba STM& ASSOCIATES Nei"S CITY OF COLLEGE STATION PLAN EXAMINING CORRECTIONS—PROJECT#-00500064 ADDRESS: 2000 TEXAS AVENUE, 77840 JENNIFER PROCHAZKA PLANING COMMENTS 1. PLEASE PROVIDE THE FOLLOWING ADDITIONAL INFORMATION IN THE TITLE BLOCK.... PLEASE RE:SITE PLAN A-1-0&ARCHITECTURAL PLANS 2. THE VICINITY MAP ON SEVERAL OF THE SHEETS IS INCORRECT PLEASE RE:CML PLANS. 3. ALL PLANS NEED TO MATCH. FOR INSTANCE, .... PLEASE RE:CML PLANS. 4. TOTAL SITE AREA ON APPLICATION AND LANDSCAPE ... PLEASE RE: LANDSCAPE PLAN. 5. PLEASE PROVIDE THE OWNERSHIP AND CURRENT ZONING .... PLEASE RE:SITE PLAN A-1-0. 6. PLEASE SHOW PROPERTY LINES ONLY AS THEY CURRENTLY .... PLEASE RE:SITE PLAN A-1-0. 7. PLEASE PROVIDE ALL SETBACK ON .... PLEASE RE:SITE PLAN A-1-0. 8. PLEASE PROVIDE AN EXISTING SURVEY .... PLEASE RE:ARCHITECTONICAL&CML PLANS. 9. PLEASE PROVIDE REQUIRED AND PROVIDED PARKING .... PLEASE RE:SITE PLAN A-1-0.(GENERAL NOTES) 10. PARKING SPACE IN SOUTHWEST CORNER OF PROPERTY .... PLEASE RE:SITE PLAN A-1-0. 11. ALL PARKING SPACES MUST BEAT LEAST 18' .... PLEASE RE:SITE PLAN A-1-0. 8705 Katy Freeway,Suite 202•Houston,Texas 77024•Ph:713-468-7557•Fax:713-468-7693 STM STM ARCHITECTS AND ASSOCIATES,L.L.C. dba STM & ASSOCIATES Nei' Sell" 12. PLEASE SHOW LOCATIONS OF ALL FIRE LANES ON SITE AND THE FIRE LINES .... PLEASE RE:SITE PLAN A-1-0. 13. IF THE PROPERTY IS NOT LOCATED WITHIN A FLOODPLAIN, PLEASE PROVIDE A .... PLEASE RE:SITE PLAN A-1-0.(GENERAL NOTES) 14. ANYTHING"EXISTING" ON SITE MUST MEET CURRENT STANDARS .... PLEASE RE:CML PLANS C3. 15. PLEASE PROVIDE A PAVEMENT DETAIL. PLEASE RE:CML PLANS C8. 16.ALL CURBING IS REQUIRED TO BE MOLITHIC. PLEASE RE:CML PLANS C8. 17. FOR EVERY 15 INTERIOR PARKING SPACES YOU ARE REQUIRED TO PROVIDE A 180 .... PLEASE RE:SITE PLAN A-1-0. 18. PLEASE SHOW LOCATION OF FIRE HYDRANT .... PLEASE RE:SITE PLAN A-1-0.8 CML PLANS. 19. THE DUMPSTER ENCLOSURE NEEDS TO HAVE 12ft .... PLEASE RE:SITE PLAN DETAILS A-1-2. 20. PLEASE PROVIDE INFORMATION ON HOW THE DUMPSTER ENCLOSURE WILL BE .... PLEASE RE: SITE PLAN DETAILS A-1-2. 21. IS NOTE 126 SHOWN IN THE RIGHT PLACE ON THE SITE? .... PLEASE RE: SITE PLAN A-1-0. 22. PLEASE REMOVE ANY KEY NOTES THAT DO NOT HAVE A .... PLEASE RE: SITE PLAN A-1-0. 23. PLEASE LABEL TRANSFORMER AND OTHER MECHANICAL .... PLEASE RE: SITE PLAN A-1-0. 24. PROVIDE A GENERAL NOTE THAT ALL ROOF AND GROUND-MOUNTED MECHANICAL .... PLEASE RE: SITE PLAN A-1-0.(GENERAL NOTES) 25. FYI: ANY PROPOSED PEDESTRIAN ACCESS TO TXDOT RIGHT-OF-WAY .... PLEASE RE: CIVIL PLANS, PLAN COORDINATED WITH PROPOSED TXDOT WIDENING. 8705 Katy Freeway,Suite 202•Houston,Texas 77024•Ph:713-468-7557•Fax:713-468-7693 _ _ STM ,. RSSC'-';'„ , STM ARCHITECTS AND ASSOCIATES,LLC. dba STM & ASSOCIATES 5 JENNIFER PROCHAZCA LANDSCAPING COMMENTS 1. TOTAL SITE AREA ON APPLICATION.... PLEASE RE: LANDSCAPE PLANS. 2. ALL PROPOSED LANDSCAPING MUST BE LOCATED ON SITE.... PLEASE RE: LANDSCAPE PLANS. 3. IF ANY LANDSCAPING BEING REMOVED OR REPLACED ON.... PLEASE RE: LANDSCAPE PLANS. 4. PROPOSED LANDSCAPING SHOULD BE EVENLY DISPERSED .... PLEASE RE: LANDSCAPE PLANS. 5. ALL LANDSCAPED COUNTING TOWARD THE REQUIRED POINTS FOR .... PLEASE RE: LANDSCAPE PLANS. 6. PLEASE REMOVE LANDSCAPING SHOWN ON THIS .... PLEASE RE: LANDSCAPE PLANS. 7. PLEASE USE DIFFERENT SYMBOLS FOR DIFFERENT SPECIES .... PLEASE RE: LANDSCAPE PLANS. 8. THE AFRICAN ARISH IS NOT CONSIDERED TO BE A SHRUB. PLEASE RE: LANDSCAPE PLANS. 9. THE WAY YOU HAVE DETERMINED THE NUMBER OF STREESCAPE TREES.... PLEASE RE: LANDSCAPE PLANS. JOSH NORTON ENGINEERING COMMENTS 1. PROVIDE CONTOURS FOR AREA. PLEASE RE: CONTOURS PROVIDED. SHEET C3 2. INDICATE LOCATION OF FIRE LANES. PLEASE RE: FIRE LANES LOCATED. 3. WATER SERVICE LINES WILL NEED TO .... PLEASE RE: CIVIL PLANS C5. 8705 Katy Freeway,Suite 202•Houston,Texas 77024•Ph:713-468-7557•Fax:713-468-7693 • STM -' SS(%r iJ C STM ARCHITECTS AND ASSOCIATES,L.L.C. dba STM &ASSOCIATES S 4. WATER DEMANDS INDICATED ONLY ALLOW .... PLEASE RE: CIVIL PLANS C5. 5. WATER AND IRRIGATION METERS MUST BE LOCATED IN .... PLEASE RE: CIVIL PLANS C5. 6. FYI: DUE TO TEXAS AVE. WIDENING/UTILITY PROJECT CURRENTLY UNDER .... PLEASE RE: COMMENTS INCORPORATED INTO PLANS. 7. SEWER SERVICE LINES REQUIRED A CLEANOUT EVERY 100FT. PLEASE RE: CIVIL PLANS C5. 8. VERIFY SLOPE OF SEWER SERVICES LINE TO BANK. PLEASE RE: CIVIL PLANS C5. 9. PLEASE INDICATE THE NAME OF THE PLAT/LEGAL DESCRIPTION .... PLEASE RE: CIVIL PLANS C3. 10. DEVELOPMENT PERMIT APPLICATION WILL REQUIRE STANDARD SUPPORTING DOC.... PLEASE RE: PROVIDED. SAM WEIDO ELECTRICAL COMMENTS 1. DEVELOPER INSTALLS CONDUIT PER CITY SPECS AND DESIGN. 2. DEVELOPER PROVIDES 30'OF IMC CONDUIT FOR RISER POLES. 3. DEVELOPER POURS TRANSFORMER PAD(S)PER CITY SPECS AND DESIGN(PULL BOXES PROVIDED BY THE CITY). 4. DEVELOPER PROVIDES DIGITAL AUTOCAD 2000 VERSION OF PLAT AND/OR SITE PLAN. EMAIL TO SWEIDOCSTX.GOV 5. DEVELOPER PROVIDES LOAD DATA FOR PROJECT 6. DEVELOPER PROVIDES TEMPORARY BLANKET EASMENT FOR CONSTRUCTION PURPOSES. 8705 Katy Freeway,Suite 202•Houston,Texas 77024•Ph:713-468-7557•Fax:713-468-7693 STM LQ..'3SS(s. ;J r STM ARCHITECTS AND ASSOCIATES,L.L.C. alis STM & ASSOCIATES 7. DEVELOPER PROVIDES EASEMENTS FOR ELECTRI INFRASTRUCTURE AS INSTALLED FOR ELECTRIC LINES(INCLUDING STREE LIGHTS). PLEASE RE:ALL ELECTRICAL COMMENTS ARE ACEPTED AS WRITTEN MISCELLANEOUS COMMENTS 1. IRRIGATION SYSTEM MUST TO BE PROTECTED BY EITHER A PRESSURE VACUUM BREAKER, A REDUCED PRESSURE PRINCIPLE BACK FLOW DEVICE, OR A DOUBLE-CHECK BACK FLOW DEVICE, AND INSTALLED AS PER CITY ORDINANCE 2394. 2. ALL BACKFLOW DEVICES MUST BE INSTALLED AND TESTED UPON INSTALLATION AS PER CITY ORDINANCE 2394. PLEASE RE:ALL MISCELLANEOUS COMMENTS ARE ACEPTED AS WRITTEN IF YOU HAVE ANY QUESTION ABOUT THE ANSWERS ABOVE PLEASE CALL ME. PH: 713-468-7557 FAX: 713-468-7693 MARCELA MATIZ STM&ASSOCIATES 8705 Katy Freeway,Suite 202•Houston,Texas 77024•Ph:713-468-7557•Fax:713-468-7693