HomeMy WebLinkAboutStaff Comments Grffil1544 CITY OF COLLEGE STATION Planning e'r Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM April 4, 2005 TO: Britt Rice Electric L.P. via fax 693.9785 FROM: Molly Hitchcock, Staff Planner SUBJECT: AUDIO VIDEO (SP) - Site Plan My apologies--comments were inadvertently sent out on Friday. I am resending the fax with the final comments (Nonresidential Architectural Standards review was added). Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached Easement Dedication Sheet and required documents (please allow 4 weeks to process). Please note that the Easement Dedication Sheet and necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call Molly Hitchcock or Josh Norton at 979.764.3570. Attachments: Staff review comments cc: GJ Partners LTD via fax 696.5775 CSC Engineering & Environmental Consultants, Inc. via fax 778.0820 Cumpton &Associates, Inc. via fax 492.5197 Case file #05-041 Home of Texas A&M University (11111111114111 CITY OF COLLEGE STATION Planning e'r Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM April 22, 2005 TO: Britt Rice Electric LP, via fax 693.5775 FROM: Bridgette George, Assistant Development Manager SUBJECT: AUDIO VIDEO (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review and approval: Six (6) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (please submit additional copies to be stamped for your records). Two (2) revised site plans; One (1) landscaping plan; and One (1) revised grading plan. If there are comments that you are not addressing with the revised plans, please attach a letter explaining the details. If you have any questions or need additional information, please call Molly Hitchcock or Josh Norton at 764-3570. Attachments: Staff review comments cc: GJ Partners LTD, via fax 696.5775 ✓ CSC Engineering & Environmental Consultants, Inc., Via fax 778.0820 v Case file #05-00500041 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 2 Project: AUDIO VIDEO (SP) - 05-00500041 PLANNING 1. Shrubs used to screen parking must be a minimum of 3 feet above the parking lot pavement elevation. Please indicate this on the landscaping plan. 2. The buffer for the rear facade requires a fence or wall. Please describe what will be used on the landscaping plan. 3. Please show required bicycle parking. 4. NOTE: Building materials and color samples will be required before Building Permit. Reviewed by : Molly Hitchcock Date: April 19, 2005 ENGINEERING 1. (C-7) Add inlet protection to the inlets located between Audio Video and David Gardner's (Contact Donnie Willis, City of CS Drainage Inspector at 764-6375. 2. FYI: Sheet C-2 appears to be the old sheet and needs to be replaced by Sheet SP-1? Reviewed by: Josh Norton Date: April 21, 2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 2 of 2 1 ' t4c, e6.$‘--1 /f76;s' r tir I . Griffill511114 CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM April 4, 2005 TO: Britt Rice Electric L.P. via fax 693.9785 FROM: Molly Hitchcock, Staff Planner SUBJECT: AUDIO VIDEO (SP) - Site Plan My apologies--comments were inadvertently sent out on Friday. I am resending the fax with the final comments (Nonresidential Architectural Standards review was added). Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached Easement Dedication Sheet and required documents (please allow 4 weeks to process). Please note that the Easement Dedication Sheet and necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call Molly Hitchcock or Josh Norton at 979.764.3570. Attachments: Staff review comments cc: GJ Partners LTD via fax 696.5775 CSC Engineering & Environmental Consultants, Inc. via fax 778.0820 Cumpton &Associates, Inc. via fax Case file #05-041 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: AUDIO VIDEO (SP) — 05-041 PLANNING 1. In addition to C-1 zoning, the property has OV Corridor Overlay zoning. Please show both zoning designations on the site plan. 2. In the title block, please include: • "Site Plan for Audio Video" • "University Park Ph. II Lots 3A and 3F Block V" • "1.83 acres" 3. The owner of the property should be the same on the application as on the site plan. 9. The front setback is 40 feet (OV requirement). The current building is grandfathered. Please remove the 25 foot setback that is shown. 5. Please identify the zoning of abutting parcels. 6. In the future, if an item on the site plan checklist does not apply to the project, please do not check it off, but write "N/A". 7. Please identify the ROW width for University. 8. The parking space dimensions are off for spaces 37-41. 9. Wheelstops may not be used for 18-ft. parking stalls (spaces 16 and 20). 10. Please provide details on the dumpster enclosure. 11. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. Reviewed by: Molly Hitchcock Date: March 29, 2005 LANDSCAPING/STREETSCAPING/BUFFER 1. The landscaping and site plans should be using the same base plan (the layout has not been updated on the landscaping plan). 2. In addition to what has been shown, the landscaping plan should include: topographic and final grading information adequate to identify and properly specify planting for areas needing slope protection; the location of existing and proposed utilities and all easements on or adjacent to the lot; and an indication of adjacent land uses. 3. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. 4. Streetscaping is not required along the access easement. Please adjust the linear feet used in the streetscape point and tree calculations. 5. Please correct the cedar elm count. 6. Please state that each trunk of a crepe myrtle will be at lease 1.25-inch caliper. 7. Parking areas are required to be screened from the right-of-way along 100% of the street frontage. At a minimum, plantings, berms, and/or structural elements used must be a minimum of 3 feet above the parking lot pavement elevation. If shrubbery is used, at least 50% must be evergreen. 8. Irrigation is required. Please address this issue. 9. NOTE: Signage will not be approved through the site/landscaping plan, but will be reviewed when a building (signage) permit is applied for. Reviewed by: Molly Hitchcock Date: March 29, 2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 2 of 4 NONRESIDENTIAL ARCHITECTURAL STANDARDS 1. The western elevation is proposing 80% EIFS. It is limited to 75%. 2. Please provide color samples before Building Permit. 3. Painted steel panel siding and galvanized steel is allowed on the rear façade if it can not be seen from a right-of-way and if a buffer is applied. Please ensure the buffer is shown on the landscaping plan. 4. Please show required bicycle parking. Reviewed by : Molly Hitchcock Date: April 4, 2005 ENGINEERING 1. Submit Development Permit application with required supporting documentation (drainage report, water design report "fire flow", erosion protection, grading plan, etc.) 2. Illustrate all existing easements (access, utility, gas company, etc.) 3. Show the slope of the proposed 6" sanitary sewer service line (3" to 6" line = 1/8 slope required). 4. Verify "Existing 8" Sewer Line", showing 10" line. Is "Existing 6" Sewer Line" State Farm's service line? 5. The water demand shown on the site plan supports using a .75" meter not a 2" meter, please explain. 6. Depict location of irrigation meter. 7. Platted University Park not State Farm? Reviewed by: Josh Norton (764-6221) Date: April 1, 2005 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of IMC conduit for riser poles. 3. Developer to furnish and install 2 —4" PVC conduits from transformer location to power pole/property line. 4. Developer to intercept existing 4" PVC conduits and extend to transformer Location. 8. Developer pours transformer pad(s) per city specs and design. 9. Transformer must be located behind west bldg. line. Contact Sam Weido with CSU at 979-764-6314 prior to final placement of transformer. 10. Developer provides digital AutoCAD 14 version of plat and/or site plan. 11. email to sweidocstx.qov 12. Developer provides load data for project. 13. Developer provides temporary blanket easement for construction purposes. 14. Developer provides easements for electric infrastructure as installed for electric lines Reviewed by: Sam Weido Date: 3-31-05 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 4 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 4 of 4 s- LI- ( 411: CITY OF COLLEGE STATION Planning ea Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM April 1, 2005 TO: Britt Rice Electric L.P. via fax 693.9785 FROM: Bridgette George, Development Coordinator SUBJECT: AUDIO VIDEO (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached Easement Dedication Sheet and required documents (please allow 4 weeks to process). Please note that the Easement Dedication Sheet and necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call Molly Hitchcock or Josh Norton at 979.764.3570. Attachments: Staff review comments cc: GJ Partners LTD via fax 696.5775 ✓ CSC Engineering & Environmental Consultants, Inc. via fax 778.0820 'r' Cumpton &Associates, Inc. via fax 492.5197 77 q-- 1 d y Case file #05-041 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: AUDIO VIDEO (SP) — 05-041 PLANNING 1. In addition to C-1 zoning, the property has OV Corridor Overlay zoning. Please show both zoning designations on the site plan. 2. In the title block, please include: • "Site Plan for Audio Video" • "University Park Ph. II Lots 3A and 3F Block V" • "1.83 acres" 3. The owner of the property should be the same on the application as on the site plan. 4. The front setback is 40 feet (OV requirement). The current building is grandfathered. Please remove the 25 foot setback that is shown. 5. Please identify the zoning of abutting parcels. 6. In the future, if an item on the site plan checklist does not apply to the project, please do not check it off, but write "N/A". 7. Please identify the ROW width for University. 8. The parking space dimensions are off for spaces 37-41. 9. Wheelstops may not be used for 18-ft. parking stalls (spaces 16 and 20). 10. Please provide details on the dumpster enclosure. 11. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. Reviewed by: Molly Hitchcock Date: March 29, 2005 LANDSCAPING/STREETSCAPING/BUFFER 1. The landscaping and site plans should be using the same base plan (the layout has not been updated on the landscaping plan). 2. In addition to what has been shown, the landscaping plan should include: topographic and final grading information adequate to identify and properly specify planting for areas needing slope protection; the location of existing and proposed utilities and all easements on or adjacent to the lot; and an indication of adjacent land uses. 3. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. 4. Streetscaping is not required along the access easement. Please adjust the linear feet used in the streetscape point and tree calculations. 5. Please correct the cedar elm count. 6. Please state that each trunk of a crepe myrtle will be at lease 1.25-inch caliper. 7. Parking areas are required to be screened from the right-of-way along 100% of the street frontage. At a minimum, plantings, berms, and/or structural elements used must be a minimum of 3 feet above the parking lot pavement elevation. If shrubbery is used, at least 50% must be evergreen. 8. Irrigation is required. Please address this issue. 9. NOTE: Signage will not be approved through the site/landscaping plan, but will be reviewed when a building (signage) permit is applied for. Reviewed by: Molly Hitchcock Date: March 29, 2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 2 of 3 • ENGINEERING 1. Submit Development Permit application with required supporting documentation (drainage report, water design report "fire flow", erosion protection, grading plan, etc.) 2. Illustrate all existing easements (access, utility, gas company, etc.) 3. Show the slope of the proposed 6" sanitary sewer service line (3" to 6" line = 1/8 slope required). 4. Verify "Existing 8" Sewer Line", showing 10" line. Is "Existing 6" Sewer Line" State Farm's service line? 5. The water demand shown on the site plan supports using a .75" meter not a 2" meter, please explain. 6. Depict location of irrigation meter. 7. Platted University Park not State Farm? Reviewed by: Josh Norton (764-6221) Date: April 1, 2005 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of IMC conduit for riser poles. 3. Developer to furnish and install 2—4" PVC conduits from transformer location to power pole/property line. 4. Developer to intercept existing 4" PVC conduits and extend to transformer Location. 8. Developer pours transformer pad(s) per city specs and design. 9. Transformer must be located behind west bldg. line. Contact Sam Weido with CSU at 979-764-6314 prior to final placement of transformer. 10. Developer provides digital AutoCAD 14 version of plat and/or site plan. 11. email to sweido@cstx.gov 12. Developer provides load data for project. 13. Developer provides temporary blanket easement for construction purposes. 14. Developer provides easements for electric infrastructure as installed for electric lines Reviewed by: Sam Weido Date: 3-31-05 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 3 (..*ffill1151114 CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM April 4, 2005 TO: Britt Rice Electric L.P. via fax 693.9785 FROM: Molly Hitchcock, Staff Planner SUBJECT: AUDIO VIDEO (SP) - Site Plan My apologies--comments were inadvertently sent out on Friday. I am resending the fax with the final comments (Nonresidential Architectural Standards review was added). Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached Easement Dedication Sheet and required documents (please allow 4 weeks to process). Please note that the Easement Dedication Sheet and necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call Molly Hitchcock or Josh Norton at 979.764.3570. Attachments: Staff review comments cc: GJ Partners LTD via fax 696.5775 CSC Engineering & Environmental Consultants, Inc. via fax 778.0820 Cumpton &Associates, Inc. via fax 492.5197 Case file #05-041 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: AUDIO VIDEO (SP) —05-041 PLANNING 1. In addition to C-1 zoning, the property has OV Corridor Overlay zoning. Please show both zoning designations on the site plan. 2. In the title block, please include: • "Site Plan for Audio Video" • "University Park Ph. II Lots 3A and 3F Block V" • "1.83 acres" 3. The owner of the property should be the same on the application as on the site plan. 4. The front setback is 40 feet (OV requirement). The current building is grandfathered. Please remove the 25 foot setback that is shown. 5. Please identify the zoning of abutting parcels. 6. In the future, if an item on the site plan checklist does not apply to the project, please do not check it off, but write "N/A". 7. Please identify the ROW width for University. 8. The parking space dimensions are off for spaces 37-41. 9. Wheelstops may not be used for 18-ft. parking stalls (spaces 16 and 20). 10. Please provide details on the dumpster enclosure. 11. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. Reviewed by: Molly Hitchcock Date: March 29, 2005 LANDSCAPING/STREETSCAPING/BUFFER 1. The landscaping and site plans should be using the same base plan (the layout has not been updated on the landscaping plan). 2. In addition to what has been shown, the landscaping plan should include: topographic and final grading information adequate to identify and properly specify planting for areas needing slope protection; the location of existing and proposed utilities and all easements on or adjacent to the lot; and an indication of adjacent land uses. 3. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. 4. Streetscaping is not required along the access easement. Please adjust the linear feet used in the streetscape point and tree calculations. 5. Please correct the cedar elm count. 6. Please state that each trunk of a crepe myrtle will be at lease 1.25-inch caliper. 7. Parking areas are required to be screened from the right-of-way along 100% of the street frontage. At a minimum, plantings, berms, and/or structural elements used must be a minimum of 3 feet above the parking lot pavement elevation. If shrubbery is used, at least 50% must be evergreen. 8. Irrigation is required. Please address this issue. 9. NOTE: Signage will not be approved through the site/landscaping plan, but will be reviewed when a building (signage) permit is applied for. Reviewed by: Molly Hitchcock Date: March 29, 2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 2 of 4 NONRESIDENTIAL ARCHITECTURAL STANDARDS 1. The western elevation is proposing 80% EIFS. It is limited to 75%. 2. Please provide color samples before Building Permit. 3. Painted steel panel siding and galvanized steel is allowed on the rear façade if it can not be seen from a right-of-way and if a buffer is applied. Please ensure the buffer is shown on the landscaping plan. 4. Please show required bicycle parking. Reviewed by : Molly Hitchcock Date: April 4, 2005 `C.. L,C.4I6L GINEERING 1. ubmit Development Permit applic ion with required supporting documentation drainage repo , water design report "fire flow", erosion protection, grading plan, etc.) C � '' mac. lustre all existing easements (access, utility, gas company, etc.) -- � J( cl. J Show the slope of the proposed 6" sanitary sewer service line (3" to 6" line 1/8 slope required). C) Verify "Existing 8" Sewer Line", showing 10" line. Is "Existing 6" Sewer Line" State Farm's service line? (,^.),tf /,„, /,,e---The water demand shown on the site plan supports using a .75" meter hot a 2" meter, lease explain. kfrII:)Depict location of irrigation meter. r� J f L.,7!Platted University Park not State Farm? A Reviewed by: Josh Norton (764-6221) Date: April 1, 2005 : .-t I 2-2 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of IMC conduit for riser poles. 3. Developer to furnish and install 2—4" PVC conduits from transformer location to power pole/property line. 4. Developer to intercept existing 4" PVC conduits and extend to transformer Location. 8. Developer pours transformer pad(s) per city specs and design. 9. Transformer must be located behind west bldg. line. Contact Sam Weido with CSU at 979-764-6314 prior to final placement of transformer. 10. Developer provides digital AutoCAD 14 version of plat and/or site plan. 11. email to sweido( cstx.gov 12. Developer provides load data for project. 13. Developer provides temporary blanket easement for construction purposes. 14. Developer provides easements for electric infrastructure as installed for electric lines Reviewed by: Sam Weido Date: 3-31-05 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 4 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 4 of 4 w Grff1151111111 CITY OF COLLEGE STATION Planning&Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM April 4, 2005 TO: Britt Rice Electric L.P. via fax 693.9785 FROM: Molly Hitchcock, Staff Planner SUBJECT: AUDIO VIDEO (SP) - Site Plan My apologies--comments were inadvertently sent out on Friday. I am resending the fax with the final comments (Nonresidential Architectural Standards review was added). Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached Easement Dedication Sheet and required documents (please allow 4 weeks to process). Please note that the Easement Dedication Sheet and necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call Molly Hitchcock or Josh Norton at 979.764.3570. Attachments: Staff review comments cc: GJ Partners LTD via fax 696.5775 CSC Engineering & Environmental Consultants, Inc. via fax 778.0820 Cumpton &Associates, Inc. via fax 492.5197 Case file#05-041 Home of Texas A&M University • E • 4 NONRESIDENTIAL ARCHITECTURAL STANDARDS 1. The western elevation is proposing 80% EIFS. It is limited to 75%. 2. Please provide color samples before Building Permit. 3. Painted steel panel siding and galvanized steel is allowed on the rear facade if it can not be seen from a right-of-way and if a buffer is applied. Please ensure the buffer is shown on the landscaping plan. 4. Please show required bicycle parking. Reviewed by : Molly Hitchcock Date: April 4, 2005 ENGINEERING 1. Submit Development Permit application with required supporting documentation (drainage deport, water design report "fire flow", erosion protection, grading plan, etc.) Illustrate all existing easements (access, utility, gas company, etc.) 3. Show the slope of the proposed 6" sanitary sewer service line (3" to 6" line = 1/8 slope required). S.4r..Verify "Existing 8" Sewer Line", showing 10" line. Is "Existing 6" Sewer Line" State Farm's rvice line? .J The water demand shown on the site plan supports using a .75" meter not a 2" meter, ,..C4ase explain. D:pict location of irrigation meter. Platted University Park not State Farm? Reviewed by: Josh Norton (764-6221) Date: April 1, 2005 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of IMC conduit for riser poles. 3. Developer to furnish and install 2—4" PVC conduits from transformer location to power pole/property line. 4. Developer to intercept existing 4" PVC conduits and extend to transformer Location. 8. Developer pours transformer pad(s) per city specs and design. 9. Transformer must be located behind west bldg. line. Contact Sam Weido with CSU at 979-764-6314 prior to final placement of transformer. 10. Developer provides digital AutoCAD 14 version of plat and/or site plan. 11. email to sweido(&.cstx.gov 12. Developer provides load data for project. 13. Developer provides temporary blanket easement for construction purposes. 14. Developer provides easements for electric infrastructure as installed for electric lines Reviewed by: Sam Weido Date: 3-31-05 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 4 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 4 of 4 STAFF REVIEW COMMENTS NO. 1 Project: AUDIO VIDEO (SP) —05-041 PLANNING ul! In addition to C-1 zoning, the property has OV Corridor Overlay zoning. Please show both zoning designations on the site plan. 2. In the title block, please include: • "Site Plan for Audio Video" • "University Park Ph. II Lots 3A and 3F Block V" • "1.83 acres" 3. The owner of the property should be the same on the application as on the site plan. 4. The front setback is 40 feet (OV requirement). The current building is grandfathered. Please remove the 25 foot setback that is shown. 5. Please identify the zoning of abutting parcels. 6. In the future, if an item on the site plan checklist does not apply to the project, please do not check it off, but write "N/A". 7. Please identify the ROW width for University. 8. The parking space dimensions are off for spaces 37-41. 9. Wheelstops may not be used for 18-ft. parking stalls (spaces 16 and 20). 10. Please provide details on the dumpster enclosure. 11. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right-of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. Reviewed by: Molly Hitchcock Date: March 29, 2005 LANDSCAPING/STREETSCAPING/BUFFER 1. The landscaping and site plans should be using the same base plan (the layout has not been updated on the landscaping plan). 2. In addition to what has been shown, the landscaping plan should include: topographic and final grading information adequate to identify and properly specify planting for areas needing slope protection; the location of existing and proposed utilities and all easements on or adjacent to the lot; and an indication of adjacent land uses. 3. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. 4. Streetscaping is not required along the access easement. Please adjust the linear feet used in the streetscape point and tree calculations. 5. Please correct the cedar elm count. 6. Please state that each trunk of a crepe myrtle will be at lease 1.25-inch caliper. 7. Parking areas are required to be screened from the right-of-way along 100% of the street frontage. At a minimum, plantings, berms, and/or structural elements used must be a minimum of 3 feet above the parking lot pavement elevation. If shrubbery is used, at least 50% must be evergreen. 8. Irrigation is required. Please address this issue. 9. NOTE: Signage will not be approved through the site/landscaping plan, but will be reviewed when a building (signage) permit is applied for. Reviewed by: Molly Hitchcock Date: March 29, 2005 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 2 of 4