Application Number . . . . . 12-00001538 e 8/11/14
----------------------------------------------------------------------------
Sppecial Notes and Comments
22" WIDE FOR ITS ENTIRE LENGTH PER SECTION 306.3, 2012 IMC.
*** ATTIC ACCESS DOOR LOCATED WITHIN A SPACE OF CONDITIONED
AIR SHALL BE INSULATED EQUALIVENT TO THE REQUIRED R -VALUE OF
THE SURROUNDING WALL (R-13)OR CEILING (R-38) TO COMPLY WITH
2012 INTERNATIONAL ENERGY CONSERVATION CODE.
*** Shall advertise only the name of, uses of, oroods or
services available within the building, or tenant lease
space, to which the banner is attached.
Shall be mounted parallel to the face of the building.
Shall not be cantilevered away from the structure.
Shall not extend more than one foot from any exterior
building face, mansard, awning, or canopy.
Shall not obstruct any window, door, stairway, or other
opening intended for ingress, EGRESS, or for needed
ventilation or light.
Shall not be attached to any tree, fence, or public utility
pole.
** NOTE FROM WATER DEPT: DOUBLE CHECK - REDUCED PRESSURE
BACKFLOW PROTECTION ASSEMBLY REQUIRED FOR CAR WASH, POSTMIX
CARBONATER, POOL AUTO -FILL, CHEMICAL TO WATER DEVICES,
HEATING/AC UNIT WITH DIRECT CONNECTION TO WATER SUPPLY,
WATER SUPPLY LINES SERVING A 3 -STORY BUILDING OR TALLER
ABOVE GRADE, AND ALL LAWN IRRIGATION SYSTEMS.
** ALL BACKFLOW DEVICES MUST BE TESTED UPON INSTALLATION BY
A CERTIFIED TESTER REGISTERED WITH THE CITY OF COLLEGE
STATION PUBLIC UTILITIES DEPT. LAWN IRRIGATION MAY USE A
PRESSURE VACCUM BREAKER. ALL DEVICES SHALL BE INSTALLED PER
AWWA STANDARDS AND CITY'S ORD #2394.
*** PROVIDE COMBUSTION AIR: FOR GAS-FIRED APPLIANCES PER
SECTION 304 OF THE 2012 INTERNATIONAL FUEL GAS CODE; FOR
OTHER FUELS TO COMPLY WITH CHAPTER 7 OF THE 2012 IMC.
*** INSTALL EMERGENCY LIGHTING IN ALL COMMON AREAS,
CORRIDORS, EGRESS PATHS, AND EXTERIOR 'EXIT DISCHARGE'
LANDING AREAS AT EACH EXIT DOOR TO COMPLY WITH SECTION
1006.3 OF 2012 IBC.
*** INSTALL EXIT SIGNS IN LOCATIONS AND ILLUMINATED PER
SECTION 1011 OF THE 2012 IBC. SEE BUILDING CODES AND NOTES
ON CITY STAMPED APPROVED BUILDING PLANS FOR EXIT SIGN
LOCATIONS. GROUP R-1 (HOTELS)SHALL ALSO HAVE FLOOR -LEVEL
EXIT SIGNS IN ALL AREAS SERVING GUESTROOMS, SECTION 1011.2.
*** PROVIDE EXTERIOR LANDING (60" X 60" FOR ACCESSIBILITY)
LEVEL WITH THE INTERIOR FLOOR AT EACH REQUIRED EXIT DOOR.
** SUBMIT FIRE ALARM PLANS WITH PRODUCT DATA SHEETS - DESIGN
----------------------------------------------------------------------------