EXIT PATH SHALL NOT TRAVEL THROUGH MEETING ROOMS OR OTHER
INTERVENING ROOMS PER 2012 IBC.
*** PROVIDE EXIT SIGNS ALONG EGRESS TRAVEL PATH PER 2012
IBC.
*** EGRESS PATH THROUGH WAREHOUSE AREAS SHALL BE PERMANANTLY
MARKED ON THE FLOOR, HAVE EMERGENCY LIGHTING, AND EXIT SIGNS
TO PROVIDE AN UNOBSTRUCTED PATH TO AN EXTERIOR EXIT DOOR.
*** PROVIDE ADDRESS ON COMMERCIAL BUILDINGS -FRONT: 5"
ADDRESS NUMBERS, AND ON REAR DOOR(S): 2" HIGH ADDRESS
NUMBERS AND NAME OF BUSINESS. FOR MULTI -FAMILY RESIDENTIAL
PROVIDE DWELLING UNIT NUMBER ON FRONT DOOR AND IDENTIFY EACH
DWELLING UNIT FROM A REAR FIRE LANE. IDENTIFY MULTI -FAMILY
BUILDINGS WITH 12" BUILDING NUMBERS, VISIBLE FROM ALL
ADJACENT/NEARBY FIRE LANES. ALL NUMBERS AND LETTERS SHALL
HAVE CONTRASTING BACKGROUNDS.
*** THE TEXAS DEPARTMENT OF STATE HEALTH SERVICES REQUIRES
AN "ASBESTOS SURVEY" FOR WORK INVOLVING DEMOLITION, REMODEL,
RENOVATION TO EXISTING STRUCTURES & TENANT SPACES.
ASBESTOS SURVEY SHALL BE SUBMITTED BEFORE ANY DEMO/MATERIAL
REMOVAL WORK. FOR MORE INFORMATION ON-LINE VISIT:
htt�://www.dshs.state.tx.us/asbestos/default.shtm
OR ALL (512)834-6770 FOR MORE INFORMATION.
*** ALL UTILITIES SHALL BE SHUT-OFF AND CAPPED -OFF PRIOR TO
ANY DEMOLITION FOR SAFETY AND ENVIRONMENTAL ISSUES. SEWER
PIPES CLOSED TO PREVENT RAIN OR STORM DRAINAGE TO ENTER.
*** WHEN A BUILDING IS DEMOLISHED, THE ASSOCIATED SIGNS AND
SIGN STRUCTURES SHALL ALSO BE REMOVED, PER SECTION 7.4
SUB -SECTION Y(5) OF THE U.D.O.
*** PLATFORMS FOR MECHANICAL EQUIPMENT AND/OR ACCESS
PASSAGEWAYS WITHIN ATTICS SHALL BE ELEVATED TO ALLOW FOR
REQUIRED R-38 ATTIC INSULATION PER IECC.
*** PROVIDE ATTIC ACCESS OPENING OF MINIMUM 2011x 30" WITH A
CLEAR HEIGHT OF 30" MINIMUM HEADROOM IN THE ATTIC SPACE
ABOVE THE ACCESS OPENING. HOWEVER, ATTIC ACCESS OPENING
SHALL BE ENLARGED ENOUGH FOR THE REPLACEMENT OF THE LARGEST
PART OF THE MECHANICAL UNIT LOCATED IN THE ATTIC.
*** PROVIDE ATTIC ACCESS WITHIN 20' OF APPLIANCES;
EXCEPTION:
PROVIDE ATTIC ACCESS WITHIN MAX 50' OF APPLIANCES
IF PASSAGEWAY IS UNOBSTRUCTED AND NOT LESS THAN 6' HIGH AND