Application Number . . . . . 12-00001227 e 8/11/14
----------------------------------------------------------------------------
Special Notes and Comments
WATER CLOSET SHALL BE 18" FROM SIDE WALL. PROVIDE MINIMUM
60" WIDE X 56" DEEP CLEARANCE FOR ACCESSIBLE WATER CLOSET
AND ALSO A 60" TURNING DIAMETER CIRCLE CLEARANCE.
*** HANDRAILS SHALL COMPLY WITH SECTION 1012 OF THE 2012
IBC. HANDRAIL HEIGHT SHALL BE MOUNTED BETWEEN 34"-38" ABOVE
STAIR TREAD NOSINGS AND FINISH RAMP WALKING SURFACE. PROVIDE
HANDRAILS ON BOTH SIDES AND HANDRAIL EXTENSIONS AT THE TOP &
BOTTOM OF EACH FLIGHT OF STAIRS OR RAMPS.
*** PROVIDE PROTECTION FOR EXIT DOORS & REQUIRED EGRESS
PATH, STRUCTURES, DUMPSTER ENCLOSURES, MECHANICAL, PLUMBING,
AND ELECTRICAL EQUIPMENT FROM IMPACT OR BLOCKED BY
AUTOMOBILES.
*** SEE GENERAL INSPECTION CHECKLIST FOR COMMERCIAL,
MULTI -FAMILY, AND/OR MIXED OCCUPANCY BUILDINGS. INSPECTION
CHECKLIST AVAILABLE AT PLANNING & DEVELOPMENT SERVICES, CITY
HALL, CITY OF COLLEGE STATION. (1101 TEXAS AVENUE)
*** PROVIDE A KNOX BOX FOR FIRE DEPARTMENT ACCESS. A KEY
FOR EACH SHELL BUILDING DOOR AND/OR TENANT ENTRY DOOR IS
REQUIRED. CONTACT FIRE MARSHAL'S OFFICE (979)764-3705.
** REQUIRED EMERGENCY EXIT DOORS SHALL BE OPERABLE FROM THE
INSIDE WITHOUT THE USE OF KEY, TOOL, OR SPECIAL
KNOWLEDGE/EFFORT. STOREFRONT EXIT DOORS WITHOUT A
THUMB -LATCH REQUIRE STATEMENT "DOOR MUST REMAIN UNLOCKED
WHEN BUILDING IS OCCUPIED" ON THE DOOR WITH 1 INCH LETTERS.
WITHOUT THE USE OF A KEY,TOOL OR SPECIAL KNOWLEDGE/EFFORT
*** INTERIOR LIGHTING SHALL MEET THE CONTROLS AND WATTAGE
LIMIT REQUIREMENTS OF CHAPTER 4 OF THE 2012 INTERNATIONAL
ENERGY CONSERVATION CODE.
*** PROVIDE LIGHTING REDUCTION CONTROLS (ABLE TO REDUCE
ROOM/AREA LIGHTING BY AT LEAST 50 PERCENT)IN EACH ROOM WITH
MORE THAN ONE LIGHT FIXTURE PER SECTION C405.2.1.2 OF IECC.
*** PROVIDE AUTOMATIC TIME SWITCH CONTROLS AND OCCUPANCY
SENSORS PER SECTIONS C405.2.2.1 & C405.2.2.2 OF IECC.
** All roof and ground -mounted mechanical equipment shall be
sreened from view or isolated so as not to be visible from
any public right-of-wa or residential district within 150
feet of the subject lot, measured from a point five feet
above grade. Such screening shall be coordinated with the
building architecture and scale to maintain a unified
appearance. Acceptable methods of screening rooftop
equipment may include, but are not limited to encasement,
parapet walls, or partition screens.
-----------------
BUILDING DEPT REPRESENTATIVE: 'Aff