Special Notes and Comments
PROVIDE ATTIC ACCESS WITHIN MAX 50' OF APPLIANCES
IF PASSAGEWAY IS UNOBSTRUCTED AND NOT LESS THAN 6' HIGH AND
22" WIDE FOR ITS ENTIRE LENGTH PER SECTION 306.3, 2012 IMC.
*** ATTIC ACCESS DOOR LOCATED WITHIN A SPACE OF CONDITIONED
AIR SHALL BE INSULATED EQUALIVENT TO THE REQUIRED R -VALUE OF
THE SURROUNDING WALL (R-13)OR CEILING (R-38) TO COMPLY WITH
2012 INTERNATIONAL ENERGY CONSERVATION CODE.
*** Shall advertise only the name of, uses of, or goods or
services available within the building, or tenant lease
space, to which the banner is attached.
Shall be mounted parallel to the face of the building.
Shall not be cantilevered away from the structure.
Shall not extend more than one foot from any exterior
building face, mansard, awning, or canopy.
Shall not obstruct any window, door, stairway, or other
opening intended for ingress, EGRESS, or for needed
ventilation or light.
Shall not be attached to any tree, fence, or public utility
pole.
** PROVIDE COMBUSTION AIR: FOR GAS-FIRED APPLIANCES PER
SECTION 304 OF THE 2012 INTERNATIONAL FUEL GAS CODE; FOR
OTHER FUELS TO COMPLY WITH CHAPTER 7 OF THE 2012 IMC.
*** INSTALL EMERGENCY LIGHTING IN ALL COMMON AREAS,
CORRIDORS, EGRESS PATHS, AND EXTERIOR 'EXIT DISCHARGE'
LANDING AREAS AT EACH EXIT DOOR TO COMPLY WITH SECTION
1006.3 OF 2012 IBC.
*** INSTALL EXIT SIGNS IN LOCATIONS AND ILLUMINATED PER
SECTION 1011 OF THE 2012 IBC. SEE BUILDING CODES AND NOTES
ON CITY STAMPED APPROVED BUILDING PLANS FOR EXIT SIGN
LOCATIONS. GROUP R-1 (HOTELS)SHALL ALSO HAVE FLOOR -LEVEL
EXIT SIGNS IN ALL AREAS SERVING GUESTROOMS, SECTION 1011.2.
*** PROVIDE EXTERIOR LANDING (60" X 60" FOR ACCESSIBILITY)
LEVEL WITH THE INTERIOR FLOOR AT EACH REQUIRED EXIT DOOR.
** SUBMIT FIRE ALARM PLANS WITH PRODUCT DATA SHEETS - DESIGN
AND INSTALL AS PER NFPA 72
NO WORK SHALL START UNTIL PLANS HAVE BEEN REVIEWED AND
APPROVED BY LOCAL FIRE MARSHAL'S OFFICE, (979)764-3705.
** PROVIDE FIRE EXTINGUISHERS) - VERIFY LOCATION AND
PLACEMENT WITH THE FIRE MARSHALL'S OFFICE (MIN. 2A10BC)
*** PROVIDE FIRE -RATED DOORS & WINDOWS WHEN INSTALLED
WITHIN FIRE -RATED WALL ASSEMBLIES TO COMPLY WITH TABLES
716.3, 716.5, & 716.6 OF 2012 IBC.
** SUBMIT FIRE SPRINKLER PLANS AND CALCULATIONS FOR REVIEW
----------------------------------------------------_