HomeMy WebLinkAboutStaff Comments CITY OF COLLEGE STATION `j DEVELOPMENT SERVICES `� 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM April 7, 2003 TO: Michael Tomchesson, Via fax 8476" FROM: Bridgette George, Assistant Development Manager SUBJECT: QUICKER STICKER (SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review and approval of the construction plans: Six (6) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached; Two (2) revised site; and One (1) landscaping plan. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. Attachments: Staff review comments cc: Christian A. Galindo Via fax 846-8868 Bo Miles, Dominion Construction, Via fax 696.5045 Case file #03-00500080 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: QUICKER STICKER (SP) – 03-00500080 PLANNING J1. Please be aware that the plat will need to be filed prior to site plan approval. 2. At the end of every parking row, a 180-sq.ft.end island is required. Parking space "19" does not have the 180-sq.ft. between the parking space and the building. ./3. Please provide flood plain information stating whether or not the subject property is within the 100-year flood plain referencing F.E.M.A. 4. Provide and label building setback lines. —5. Identify the irrigation meter. J 6. Please re-mark existing fire lanes on the private access. 7. All paved areas must be curbed. It appears that you are not showing any curbs along the front of the proposed addition, or the paved area on the northeast end of the building. / 8. Please be aware for buffering and signage purpose lots 2R-A & 2R-B are being considered as one Building Plot. For this building plot you will be allowed one free standing sign. Reviewed by: Jennifer Reeves Date: 04-02-03 SANITATION 1. Site plan needs to show a proposed 12 by 12 foot dumpster pad to be built when the 2250 S.F. addition is added. Reviewed by: Pete Caler Date: 04-03-03 ENGINEERING 1. Do the water and sewer demands provided on the site plan include the future addition? 2. Show the size of all water and sewer lines existing and proposed. 3. Your proposed water service lines cross private property. The access easement does not include utilities. You will need to obtain permission from that land owner (letter is sufficient) to cross the property where you are showing, or set your meter and run the service line through the utility easement at the southern corner of the access easement. Reviewed by: Carol Cotter Date: 04-02-03 NOTE: Any changes made to the plans,that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 2 of 3 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of#4 rigid conduit for riser poles. Developer installs first 10'. City installs remainder. 3. Developer pours transformer pad(s) per city specs and design. 4. Developer installs pull boxes as per city specs and design.(pull boxes provided by the city. 5. Developer provides digital AutoCAD 2000i version of plat and/or site plan. email to rbolinci.colleqe-station.tx.us 6. Developer provides load data for project. 7. Developer provides temporary blanket easement for construction purposes. 8. Developer provides easements for electric infrastructure as installed for electric lines (including street lights). Reviewed by: Ronnie Bolin Date: 4-2-03 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans,that have not been requested by the City of College Station, must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. Page 3 of 3 CITY OF COLLEGE STATION ‘jDEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM April 21, 2003 TO: Michael Tomchesson, Via fax 847.8987 FROM: Bridgette George, Assistant Development Manager SUBJECT: QUICKER STICKER (SP) - Site Plan Staff reviewed the above-mentioned revised site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review and approval of the plans: Six (6) revised site plans. If you have any questions or need additional information, please call Carol Cotter at 764-3570. Attachments: Staff review comments cc: Christian A. Galindo Via fax 846-8868 Bo Miles, Via fax 696.5045 Case file #03-00500080 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 2 Project: QUICKER STICKER (SP) - 03-00500080 PLANNING 1. No Comment. Reviewed by: Jennifer Reeves Date: 04-21-03 ENGINEERING 1. The 2-inch water service line will need to be designated a public line, and the meters will have to be located on your property. Please route water line to your property line and set meters there. 2. Given that the two water service lines are each 1-inch lines, and the irrigation has yet to be sized, is the 2-inch line sufficient for your water needs? Reviewed by: Carol Cotter Date: April 15, 2003 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 2 of 2