STAFF REVIEW COMMENTS NO. 2
Project: TEXAS ROADHOUSE (SP) - 08-00500084
PLANNING
1. No Comments.
Reviewed by: Jennifer Prochazka, Senior Planner, AICP and Lauren Hovde, Staff Planner
Date: May 23, 2008
3455 Salt Creek Lane
Suite 100
Arlington Heights, IL 60005
t: 847 788 9200
f: 847 788 9536
GreenbergFarraw ATLANTA
NEW YORK
CHICAGO
LOS ANGELES
BOSTON
DALLAS
NEW JERSEY
ST.PETERSBURG
May 15,2008
To Ms. Lauren Hovde Project Texas Roadhouse College Station,TX
City of College Station
1101 Texas Avenue Project# 20080091.5
College Station,TX 77842 Re Plan Review Comments Response
t: 979.764.3570
Dear Ms. Hovde:
In regard to the proposed Texas Roadhouse restaurant in College Station,Texas and the Plan Review submitted to you,we
have received your memorandum,via facsimile on April 21,2008, and we offer the following responses:
Planning:
Comment 1 Please submit a NRA(Non-Residential Architectural)application.
Response 1 Please refer to attached,completed NRA Application.
Comment 2 Please submit a revised site plan showing where the existing landscape is being replaced.
Response 2 Refer to Note on Revised Site Plan.
Comment 3 The square footage of the addition needs to be added to the site plan/revised landscape plan.
Response 3 Refer to Square Footage on the Revised Site Plan.
Comment 4 Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view
or isolated so as not to be visible from any public right-of-way or residential district within 150'of the subject
lot,measured from a point five feet above grade. Such screening shall be coordinated with the building
architecture and scale to maintain a unified appearance.
Response 4 No Landscape Revision required at this time.
Comment 5 Please note that any changes made to the plans,that have not been requested by the City of College
Station, must be explained in your next transmittal letter and"bubbled"on your plans. Any additional
changes on these plans that the City has not been made aware of will constitute a completely new review.
Response 5 No additional changes have been incorporated.
•
City of College Station
Plan Review Comments
May 15, 2008
Page 2 of 2
Landscaping/Streetscapinq/Buffer:
Comment 1 Provide a general rule that 100%coverage of groundcover,decorative paving,decorative rock(not loose),
or a perennial grass is required in parking lot islands,swales and drainage areas,the parking lot setback,
rights-of-way, and adjacent property disturbed during construction.
Response 1 Please refer to Note on Revised Site Plan.
We trust that our response has sufficiently answered your comment; if however,you need more information, please do not
hesitate to contact me at 847.788.9200,ext.232, or iwehmevert greenbergfarrow.com. Thank you.
Sincerely,
oc,kk..7-0_,1,1 fh.12-le-A.....,
Julie T.Wehmeyer,AIA
Project Manager
JTW/rrg
cc: Kerni Smith,Texas Roadhouse(w/attach.via email)
Mike Laur,Texas Roadhouse(w/attach.via email)
David Banet,Texas Roadhouse(w/attach.via email)
Angelina Robinson, GF TX(w/attach.via email)
Susan Nelson-Kougias, GF IL(w/attach.via email)
P:\20081200800915\999 General Correspondence1200800915 Plan Review Response Ltr.to City of College Station,TX 2008-05-15A.doc
City of College Station
Requirements for Electric Service:
All electric service will be provided underground.
• Electric department personnel have the discretion to provide overhead service if
deemed appropriated.
Developer I Owner is responsible for providing and installing at developers cost:
• Conduits per Electrical Divisions spec and design.
• 30 ft. of rigid conduit for riser poles (install first 10 ft. city will install remainder)
provide weatherhead if secondary riser.
• Concrete transformer pads for commercial and apartment complex projects per city
specs and design.
• Concrete junction box pads per city specs and design.
• Subsurface pull boxes per city spec and design (pull boxes supplied by City).
• Street lighting per city spec and design.
• CT can on building if necessary per city spec and design.
Developer/ Owner needs to provide the City of College Station Electric Division with:
• Plat and/or site plan
• Digital (Autocad version) of plat and/or site plan.
E-mail to jreeves@ci.coiiege-station.tx.us
• Electric load data for project (need ASAP transformer delivery is currently 20 to
26 weeks)
• Temporary Blanket easement (see attached form, fill out and return with necessary
paperwork).
• Upon completion of project surveyed sealed meets & bounds descriptive
easements are necessary to release temporary blanket easement.
Electric service will not be energized unless easement form is on file in our
legal department.
12-15-99
Date
City of College Station Contacts:
Public Utilities Department Tony Michalsky
Electrical Division Electric T&D Superintendent, 409-764-3438
P.O. Box 9960 e-mail—tmichals@ci.college-station.tx.us
College Station, Texas Jennifer Reeves
fax#409-764-3452 Electric Planning/Project Assistant, 409-764-3502
e-mial—jreeves@ci.college-station.tx.us
RE: ELECTRICAL SERIVCE REQUEST
We the undersign hereby request electric service for:
Business Name
Location
Owner's Name
Contact Person Phone #
Fax# E-mail
Estimated Date Construction Begins
Estimated Construction Completion Date
Anticipated Date Permanent Service Required
THIS IS NOT A REQUEST FOR METER INSTALLATION
Return by MAIL OR FAX
Thank You
CITY OF COLLEGE STATION
PLANNING DIVISION
POST OFFICE BOX 99601101 TEXAS AVENUE
COLLEGE STATION,TEXAS 77842-9960
COLLEGE STATION TELEPHONE:(409)764-3570
MEMORANDUM
January 10, 2000
TO: Bob Cornett, Via fax (606) 276.2Q L'70 I
i C
FROM: Bridgette George, Asst. Development Coordinato '`..
SUBJECT: Texas Roadhouse - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information for plan approval and distribution:
Six (6) sets of civils with the revised site and landscaping plans attached;
and,
Three (3) revised site and landscaping plans only.
If there are comments that you are not addressing with the revised site plan, please
attach a letter explaining the details. If you have any questions or need additional
information, please call me at 764-3570.
Attachments: Staff review comments
cc: Sheila Brown, Via fax (502) 327-4689
Delmar Baronhead I, Ltd., Via fax (972) 233-1501
Case file #99-439
STAFF REVIEW COMMENTS
No. 2
Project: Texas Roadhouse Site Plan #99-439
,--->1. In the paving notes on SP-1, notes 4 & 5 need to comply with the City's Fire
Lane marking requirements.
'� 2. Recalculate the landscape/streetscape point requirements. All existing trees
will need to be barricaded, but the point status will be non-protected (35 pts
ea) due to previous damage caused while clearing the site. Please include
point status for all new plantings provided in the landscape requirement (plant
list). The streetscape total point requirement is 1650. This includes the 1-
canopy tree/25 feet of frontage plus an additional 300-points/50 feet of
frontage. Provide approximately 7 more (4" min. caliper) canopy trees added
to this site. The project must expend 50% of its point total on canopy trees.
This is derived from 50% of the landscape total requirement (1100 pts) plus
the streetscape total point requirement (1670 pts), for a total of 2750 points
towards canopy trees. (Note: 2 non-canopy trees can be substituted for 1
canopy tree.)
A. The City's requires a 20 feet site triangle at driveways with no obstructions
between the heights of 2.5 and 9 feet.
,,( Provide a fire hydrant on the northwest corner of the site and include the
construction drawings. You will not be able to use the existing location near
University Drive because it will not meet the City's Fire Protection Ordinance
requirement. An approved fire hydrant location shall be in place before the
fire department will allow combustibles on site.
\ Reviewed by: Scott Hester Date: 1-10-00
� 4 , , ti, f)i ft, C,,.#oy etr.k.
`i L t kt t.}o,_. "\ .0 ,, ":;• ..A./ . `1 o- t)
f' e if n 0.(1---, .. a:y t 1 .e• L.7 r;1 F
Staff Review Comments Page 1 of 1
CITY OF COLLEGE STATION
j PLANNING DIVISION
POST OFFICE BOX 9960 1101 TEXAS AVENUE
COLLEGE STATION,TEXAS 77842-9960
COLLEGE STATION TELEPHONE (409)764-3570
MEMORANDUM
January 27, 2000
TO: Bob Cornett, Via fax (606) 276-2901
I,
',01
FROM: Bridgette George, Asst. Development Coordinator •
SUBJECT: Texas Roadhouse - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address
the attached comments and submit the following information for further staff review and
for the plans to be stamped approved and distributed:
Six (6) revised site and landscaping plans;
Six (6) plan and profiles from the waterline to the fire hydrant and backflow
preventer at the building where the FDC is located; and,
$100 processing fee for the next round of three (3) staff reviews;
If there are comments that you are not addressing with the revised site plan, please
attach a letter explaining the details. If you have any questions or need additional
information, please call me at 764-3570.
Attachments: Staff review comments
cc: Sheila Brown. Via fax (502) 327-4689
Delmar Baronhead I, Ltd. Via fax (972) 233-1501
Case file #99-439
STAFF REVIEW COMMENTS
No. 3
Project: Texas Roadhouse Site Plan #99-439
/1. In the paving notes on SP-1, also amend the text in notes 4 and 5 regarding
the 8" fire lane stripe.
—h> 2. Provide barricading for all the existing trees that are to be included in the
streetscape points requirement. Only 16 of the 20 existing trees depicted on
the landscape plan are barricaded.
/3. PLANT LIST: Remove the statement at the bottom of the Plant List. This list
is the official landscape list approved by the city unless you request to amend
it. Also, Item "E" in the plant lists shows a quantity of 80 with 800 points. The
drawing depicts a quantity of 90 and should show 900 points.
/4. LANDSCAPE REQUIREMENTS: Amend the total points for the new non-
canopy trees plantings from 2520 to 2620, and the total landscape new
planting points from 4620 to 4720. Also, Amend the total points provided for
new and existing from 5320 to 5420.
Reviewed by: Scott Hester Date: 1-24-00
Staff Review Comments Page 1 of 1
Bridetteeorge:::..e_RRe ». .... - . .....-......:................................. - .... - ...............:........................................---......:........,............
......:::9Geo NewDevelopment ListPage 1
From: Tony Michalsky
To: Bridgette George
Date: 8/30/99 7:55AM
Subject: Re: New Development List
Sorry I'm late with these.
Super B Subdivision (99-312)
No Comments
Lake View Acres (99-243)
There is an existing overhead electrical line that crosses this property to provide service to a residence
besides the U-haul property. Easement will need to be provided to cover existing line. If line needs to
be relocated, we will work with property owner on relocation.
Ismaili Jamatkhana&Center(99-438)
Developer installs electrical conduit per city specs and design.
(There is an electrical J-box existing at the Edelweiss Ave. & Rock Pr Rd intersection and at the property
line of the commercial lot show on site plan. Service will be provide from these two locations. Conduit
will need to be installed from the J-box to the proposed transformer location and then carried to the J-box
by the commercial lot.)
Developer pour transformer pad per city specs.
Developer will need to provide easements to cover electical infrastructure as installed.
Need electrical load data.
Super Trac Convenience Store and Gas Station (99-719)
Developer installs conduit per city spec and design.
Developer pours transformer pad per city specs.
Need electrical load data.
Developer provides easements to cover electrical infrastructure as installed.
Proposed electric service location must be in the same location unless building is seperated by
necessary firewall.
Would like to discuss possible relocation of transformer.
Electrical service will be provide from the existing power line along the Hwy 158 right of way.
Christ United Methodist Church (99-438)
No Comment
Texas Road House Restaurant(99-439)
• Developer installs conduit per city spec and design.
Proposed transformer location is okay.
Metering will be located on transfomer, service from transformer to building by developer.
Need electric load data.
Developer provides easements to cover electrical infrastructure as installed.
Wal-Mart Seasonal Box Addition (99-440)
No comments
>>> Bridgette George 08/24/99 11:33AM >>>
GOOD MORNING! Attached is the list of new development for this week.
Thank you!
Bridgette George :o)
Asst. Development Coordinator
MEMORANDUM
September 1, 1999
TO: '-"Sheila Brown, Via fax (502) 327-4689
FROM: Bridgette George, Asst. Development Coordinat. jJ
SUBJECT: Texas Roadhouse - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address
the comments and submit the following information for further staff review:
Three (3) complete sets of building construction documents for the
proposed development with the revised site and landscaping plans
attached; and,
The attached redlined site plan with staff comments.
I am still waiting to receive the civil construction documents from the engineer who is
reviewing those. There may be additional comments that will need to be addressed
concerning grading, drainage, and utilities. As soon as I receive those I will forward
those to you.
If there are comments that you are not addressing with the revised site plan, please
attach a letter explaining the details. If you have any questions or need additional
information, please call me at 764-3570.
Attachments: Redlined site plans
Staff review comments
cc: vbelmar Baronhead I, Ltd., Via fax (972) 233-1501
✓The Roberts Group, Via fax (606) 276-2901
Case file #99-439
boa 4'-/ 3 ,
STAFF REVIEW COMMENTS
No. 1
Project: Texas Roadhouse Restaurant #99-439
;1. Who will construct the roadway within this 30-foot access and utility
easement? Will it be installed before the development of this site? Will the
roadway extend to the intersection of University Drive and Glenhaven? The
City will not issue a C.O. until this roadway is complete to provide access to
your site.
-,1 2. The City has approved the 20-foot utility easement along University Drive,
but the waterline location has not been approved. Your site plan should
reflect the approved civil plans.
-3. The off-street parking requirement is 1 per 65 sq. feet (97 spaces). Also give
the dimensions to each section of the parking spaces.
- 4. Several parking end islands are not the required 180 square feet. The
property line should evenly divide the two end islands on the southeast and
southwest corners of the property for the perimeter parking facing University
Drive. There is an additional 180 square feet required for every 15 interior
parking spaces (4 total). Provide 2 additional interior islands for this site.
5. Provide water meter locations and place them in a utility easement. (Note:
the proposed electrical meter and gas meter locations at the building appear
to be reversed.)
-6. FDC locations shall be placed on the site plan.
/7` Show fire lane(s) on the site plan.
V8. The existing fire hydrant located on the southwest corner of proposed site is
a proposed location by a private contractor and has not been approved by
the City. If this proposed location is approved, you will need to provide an
additional fire hydrant on the proposed site. The City has not approved the
waterline location adjacent to University Drive. It may be located on the north
side of the proposed development within the 30-foot Access and Utility
Easement. The existing fire hydrant as shown will not be at this location if the
waterline is relocated to the north of your site. If the waterline does stay at
this location along University Drive you will not be able to use this existing
fire hydrant location due to the City's Fire Protection Ordinance requirement
(Chapter 6, Section 603, 603.1.36). A fire hydrant will need to be placed on
site (suggest the NW corner near the 30' Access & Utility Easement) for use
by the Fire Department, and to meet the City Fire Protection Ordinance
requirement. An approved fire hydrant location shall be in place before the
fire department will allow combustibles on site.
Staff Review Comments Page 1 of 2
9. Provide wheel stops in the parking areas on the east and west property lines
2 feet from the edge of pavement to prevent the overhang of vehicles onto
the adjacent properties. Also, a 6-inch raised curb shall be required around
the entire perimeter of the lot. In this case, you may use knockdown curbing
that can be removed in the event that future parking area on the adjacent
property is installed.
4. 10.Recalculate the street tree points for the streetscape requirement. Will these
existing trees along University Drive meet the streetscape point requirement
since they are now under non-protected status? All existing trees will need
to be barricaded, but the point status will be non-protected due to previous
damage caused while clearing the site.
- 11.Provide screening for the parking lot on the south side of your site facing
University Drive.
,>12.Recalculate the new planting points for landscaping requirement.
413.The city will need to approve the materials used for the retaining wall prior to
installation.
-- 14.Chose one of the detail options from the zoning ordinance.
Note: The engineering comments will follow upon completion of their review.
Reviewed by: Scott Hester Date: 8-31-99
Staff Review Comments Page 2 of 2
Ar, STATION
COLLEGE P. 0. Box 9960 • 1101 Texas Avenue • College Station, TX 77842
Tel: 409 764 3500
MEMORANDUM
TO: Sheila C. Brown, Texas Roadhouse
Via fax #(502) 426-3274 ,
FROM: Natalie Ruiz, Development "s o.i i : ,.7 / i3 'J
DATE: Wednesday, February 23, 2000
RE: Building permit issuance for Texas Roadhouse in College Station.
This week, staff received revised site plans along with the waterline plans for the Texas
Roadhouse restaurant to be constructed on University Drive. A building permit will be issued
for the restaurant once the following items are submitted:
Punchlist for Building Permit
An estimate of the proposed waterline sealed by a registered professional
engineer.
Building permit fee in the amount of$1,380.
If you have any questions about the items listed above or need additional information pertaining
to issuance of a building permit, please contact me at (409) 764-3570 or e-mail me at
"nruiz@ci.collc«c-station.tx.us". Thank you.
cc: ase file 1199-439
Lance Simms, Building Official
Home of Texas A&M University
MEMORANDUM
February 14, 2000
TO: Bob Cornett, Via fax (606) 276-2901
FROM: Bridgette George, Asst. Development Coordinator
SUBJECT: Texas Roadhouse - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address
the attached comments and submit the following information for further staff review and
for the plans to be stamped approved and distributed:
Six (6) revised site and landscaping plans;
Six (6) plan and profiles from the waterline to the fire hydrant and backflow
preventer at the building where the FDC is located; and,
$100 processing fee for the next round of three (3) staff reviews;
If there are comments that you are not addressing with the revised site plan, please
attach a letter explaining the details. If you have any questions or need additional
information, please call me at 764-3570.
Attachments: Staff review comments
cc: Sheila Brown, Via fax (502) 327-4689
Delmar Baronhead I, Ltd. Via fax (972) 233-1501
Case file #99-439
•
I;
COLLEGE STATION
(t_ P. O. Box 9960 • 1101 Texas Avenue • College Station, TX 77842
Tel: 409 764 3500
MEMORANDUM
TO: Sheila C. Brown, Texas Roadhouse
Via fax #(502) 426-3274
FROM: Natalie Ruiz, Development Coord.)at., 111TI
DATE: Friday, February 18, 2000
RE: Building permit issuance for Texas Roadhouse in College Station.
This week, staff received revised site plans along with the waterline plans for the Texas
Roadhouse restaurant to be constructed on University Drive. A building permit will be issued
for the restaurant once the following items are submitted:
Punchlist for Building Permit
Four (4) copies of the revised waterline plans. (The only staff review
comment is to note the mechanical joint at the 90°bend.)
_ Seven (7) copies of the revised site plan package. (The only staff review
comments that need to be addressed are on the landscape plan. Several of the
existing trees that are presently accruing points (non-protected 35 pts. ea.)
towards the landscape/streetscape point requirement will not be counted due
to the intrusion of the pavement into the new barricaded areas. Also, you will
need to recalculate the landscape/streetscape points due to the removal of the
nine trees, which reduces the streetscape points by 385 points. In addition, in
the Landscape Notes (sheet LA-1) you should add a note #10 that explains the
definition of a barricaded area: Barricade area for existing trees: An area
protected throughout construction and extending in a radius of 1 foot per
caliper inch of tree diameter from every protected tree that prevents intrusion
by construction equipment, vehicles and people.)
Site plan review fee of $100. (This fee was required with the last round of
site plan reviews and was not submitted.)
_ Building Permit application. Submit the completed application. Once the
application is received, staff will determine the total amount of building
permit fees.
Home of Texas A&M University
Memo to Sheila Brown
Texas Roadhouse
Case#99-439
Page 2 of 2
Punchlist for Building Permit(cont.):
_ An estimate of the proposed waterline sealed by a registered professional
engineer.
_ Water and sanitary sewer tap fees in the amount of$2,100.
6" sanitary sewer tap - $100 inspection fee (the developer is
responsible for the making of the tap according to the City
specifications and is subject to City inspection).
_ 1"water tap (irrigation) - $500; and,
_ 2"water tap (domestic) - $1500.
Temporary electric pole fee in the amount of$45.
Application for a Contractor's License. Your contractor will be required to
submit the completed application along with the $54 application and
processing fee prior to issuance of a building permit.
If you have any questions about the items listed above or need additional information pertaining
to issuance of a building permit, please contact me at (409) 764-3570 or e-mail me at
"nruiz@ci.college-station.tx.us". Thank you.
Attachments: Building Permit Application
Contractor's License Application
cc: Case file#99-439
Lance Simms, Building Official
CITY OF COLLEGE STATION
APPLICATION FOR CONTRACTOR LICENSE
Type of Contractor.
Applicant Name:
Company Name:
Company Address:
City: State: Zip:
Phone: Mobile:
Pager _ Other
List any persons authorized to apply for permits or inspections other than the applicant:
I hereby make application to the City of College Station for a Contractor's License. I certify that
the above statements are true and correct. I understand that the application fee of 550.00 and the
processing fee of $4.00 is non-refundable. I further understand that the provision of false
information on this application may result in the revocation of this license by the City of College
Station.
Signature of Applicant Date:
Official Use Only
State License Number. Exp.Date
City License Number Exp.Date
Issued by:
L..i....96
To: Bridgette George
From: Ted Mayo �.
CC: Sabine McCully
Date: 02/23/00
Re: OAKWOOD CUSTOM HOMES COMMERCIAL SITE PLAN Drainage Submittal Review
I have reviewed the submittal of 02-17-2000 by Hester Engineering Corporation and all of my concerns
relative to drainage have been addressed.
•Page 1
STAFF REVIEW COMMNETS
No. 4
Project: TEXAS ROAD HOUSE RESTAURANT (SP) (99-120)
1. Several of the existing trees that are presently accruing points (non-protected
35 pts. ea.) towards the landscape/streetscape point requirement will not be
counted due to the intrusion of the pavement into the new barricaded areas.
Also, you will need to recalculate the landscape/streetscape points due to the
removal of the nine trees points, which reduces the streetscape points by 385
points. In addition, in the Landscape Notes (sheet LA-1) you should add a
note #10 that explains the definition of for a barricaded area:
Barricade area for existing trees: An area protected throughout
construction and extending in a radius of 1 foot per caliper inch of tree
diameter from every protected tree that prevents intrusion by construction
equipment, vehicles, and people.
Reviewed by: SCOTT HESTER Date: 18-Feb-00
Staff Review Comments Page 1 of 1