K I Consulting Engineers
July 18, 2005
Ms. Lindsay Boyer
Project Manager
City of College Station
P.O. Box 9960
College Station, Texas 77842
Re: R &S Leasing
College Station Professional Building Two
PK Job No. 52805 - 291
Dear Mrs. Boyer:
Enclosed please find the following:
979 - 731 -8000, 979- 731 -1500 (Fax)
www.pkengineering.com
1. One (1) complete set of the revised site plan.
2. One (1) 11 X 17 Grading and Erosion Plan.
3. One (1) copy of the Fire Flow Calculations for flow
hydrant number N -101.
4. One (1) copy of the drainage report
5. Easement dedication sheet
The following items are addressed:
PLANNING (Lindsay Boyer)
✓1. The north arrow is correct on the Key map.
✓2. The date of submittal has been added electronically.
13. The rear building setback has been changed from 25' to
15'
-4. Bicycle parking facilities have been added at the
front of the building.
5. The driveway throat depth has been dimensioned and
meets the 55' requirement.
--6. Dimensions for the opposite right and left driveways
have been added.
S: \2005 \52805 -291 R &S- medical \CS -02 -site review 1 responsedoc \� — V s
Brenham • Bryan • Rosenberg ��
, Ms. Lindsay Boyer
July 18, 2005
Page 2
�7. The proposed parking ties in directly to the existing
parking lot to extend the existing parking rows.
/ 8. The end islands on the east side of the rear parking
rows have been enlarged to meet the 180 sf
requirement.
✓ 9. A 2,268 sf island has been added to the rear parking
to meet the parking requirements.
10. The square footage has been noted on the building, the
medical clinics square footage will be less than
20,000 sf.
/11. Site plans have been provided. The off -site parking
areas have been shown on the site plan and are no
further away than 250 feet from the site.
-12. Curbing to be removed has been marked with an "X ".
13. A shared access agreement for the neighboring lots
will be provided.
14. The fire lane on the east side of the building has
been widened to 26'.
15. Screening details have been added.
:f16. Building elevation and material samples will be
provided for review prior to the issuance of a
building permit.
LANDSCAPING /STREETSCAPING /BUFFER (Lindsay Boyer)
1. The parking screening has been extended into the end
islands.
2. The parking will be 100% screened as required.
3. OK, Noted on City Site Plan
4. OK, Noted on City Site Plan
ENGINEERING (Josh Norton
1. Sewer and Water demands have been added to the Utility
Plan.
2. The meters are located within the 10' Public Utility
Easement along the west property line.
The fire flow report is enclosed.
The drainage report is enclosed.
5. The connection to the existing 8" water main has been
changed to a tapping sleeve and valve.
6. An RPBA will be provided for each of the fire and
domestic water lines going into the building.
7. The fire lane continues around the building with the
adjacent property's fire lane.
v ,8-. 7 OK, thanks.
• Ms. Lindsay Boyer
July 18, 2005
Page 3
ELECTRICAL (Ronnie Bolin
1. OK, Noted on Utility Plan.
2. OK, Conduits shall be furnished and installed as required
by the City.
3. OK, Noted on Utility Plan.
4. The drawing will be e- mailed.
5. The load data will be shown on the MEP plans.
6. The blanket Easement Dedication Sheet is attached.
7. OK, easements will be provided as needed.
8. OK, thanks.
MISCELLANEOUS
1. OK, Noted on City Site Plan.
2. OK, Noted on City Site Plan.
Very Truly Yours,
Steve E. Duncan, P.E.
sed @pkengineeing.com
SED /dj w
Enclosures
Cc: Leon Williamson
Walt Schoenvogel
N
Pledger Kalkomey, Inc.
K I Consulting Engineers
October 24, 2005
Ms. Lindsay Boyer
Project Manager
City of College Station
P.O. Box 9960
College Station, Texas 77842
Re: R &S Leasing
College Station Professional Building Two
PK Job No. 52805 -291
Dear Mrs. Boyer:
0-
7020 Coyote Run
Bryan, Texas 77808
979- 731 -8000, 979 - 731 -1500 (Fax)
www.pkengineering.comll - - l 3
Enclosed please find the following per your July 26, 2005 memo:
1. Eight (8) complete sets of the revised site plan (2
The following items are addressed:
PLANNING (Lindsay Boyer)
1. All supporting documentation required for the easement
dedication sheet will be provided prior to the
issuance of a Building Permit.
2. The plans have been corrected to show that the curbing
will be removed.
3. The building height is now below thirty feet (30')
tall and the twenty -six foot (26 fire lane is no
longer applicable.
4. The access agreement is attached.
5. The landscape legend has been corrected.
5:\2005 \52805 -291 R &S- medical \CS -03 -site review 2 respon .doc
Brenham • Bryan • Rosenberg
additional sets
to be stamped for our records)
2.
Two (2)
copies of sheet C.1 - City Site Plan
3.
One (1)
11 X 17
copy of sheet C.3 - Grading Plan.
4.
One (1)
copy of
the revised drainage report
5.
One (1)
copy of
the Easement Agreement for Reciprocal
Access,
Parking,
Drainage and Detention.
The following items are addressed:
PLANNING (Lindsay Boyer)
1. All supporting documentation required for the easement
dedication sheet will be provided prior to the
issuance of a Building Permit.
2. The plans have been corrected to show that the curbing
will be removed.
3. The building height is now below thirty feet (30')
tall and the twenty -six foot (26 fire lane is no
longer applicable.
4. The access agreement is attached.
5. The landscape legend has been corrected.
5:\2005 \52805 -291 R &S- medical \CS -03 -site review 2 respon .doc
Brenham • Bryan • Rosenberg
Ms. Lindsay Boyer
October 24, 2005
Page 2
ENGINEERING
(Josh Norton)
/The
system creates a flow of 7,527 gpm as shown by the
calculations in the fire flow report.
✓2r The
meter size has been removed and will be shown with
the
building plans.
The
sanitary sewer slope has been changed to 1% minimum.
LA
thanks.
5. Drainage Report:
U,e�e certification sheet has been updated and re-
located to the cover.
b. The contours on the west end have been revised.
c. The existing slope at the west end of the pond
shall remain; existing contours have been changed
to a lighter shade.
d. A detail of the retaining wall has been added.
e. The flow line elevation and size of the existing
pipe outlet structure has been labeled.
f. The outfall discharges into a concrete flume on
the adjacent property which then connects to the
cul -de -sac located on Longleaf Circle.
g. The contours have been revised to show no offsite
improvements on the adjacent property to the
east.
h. A detail of the concrete headwall and outlet
structure has been added.
i. The drainage agreement for the adjoining
properties is as defined in the Ponderosa Place -
Tract B drainage report and the attached Easement
Agreement.
j. Maintenance responsibilities are defined in the
attached Easement Agreement.
k. A 2.5' wide curbed channel has been added to
improve the outlet structure and prevent future
erosion.
Ms. Lindsay Boyer
October 24, 2005
Page 3
ADDITION CHANGES:
The water and electrical utilities have been
relocated to the East side of the building due to
changes within the building required by the MEP
engineer. Since the new fire line connection is
located at the end of the existing eight inch (8 ")
main line, an 8" x 6" cross is used in lieu of a
tapping sleeve and valve. The electrical utilities
will be installed per City requirements.
Very Truly Yours,
4v P.E.
sed@pkengineeing.com
SED /djw
Enclosures
cc: Leon Williamson
Walt Schoenvogel
Pledger Kalkomey, Inc.
es
7020 Coyote Run
Bryan, Texas 77808 J9
\A.-
Consulting Engineers
December 5, 2005
Ms. Lindsay Boyer
Project Manager
City of College Station
P.O. Box 9960
College Station, Texas 77842
Re: R &S Leasing
College Station Professional Building Two
PK Job No. 52805 -291
Dear Mrs. Boyer:
979 - 731 -8000, 979 - 731 -1500 (Fax)
www. pkengineering. corn
Enclosed please find the following per your October 28, 2005
memo:
1.
$200 processing
fee.
2.
Eight (8)
complete
sets of the
revised site plan (2
additional
sets
to be stamped
for our records)
3.
Three (3)
copies
of sheet C.1
- City Site Plan.
4.
One (1) 11
X 17
copy of sheet
C.3 - Grading Plan.
The following items are addressed:
PLANNING /ENGINEERING (Lindsay Boyer /Josh Norton)
A hydrant and valve was added and the Plan /Profile and
�gineers cost estimate are attached.
1,2! The existing hydrant is aligned toward Rock Prairie Rd.;
a cross will be put in and the existing hydrant will be
C32 econnected.
he easement dedication information will be submitted
L' rior to the issuance of the Development Permit.
n easement has been shown and will be dedicated up to
within 5 -ft of the building.
�he sanitary sewer line has been labeled as SDR 26 ASTM
D3034.
\ \Snap 121731 \share 1\2005 \52805 -291 R &S- medical \CS -03 -site review 3 response. doc
Brenham • Bryan • Rosenberg
Ms. Lindsay Boyer
October 24, 2005
Page 2
✓6. The flow line elevation of the sewer service has been
labeled, it is located 30" above the flow line of the
existing manhole and a drop connection will not be
required.
7. The irrigation system note is located on sheet C.l - City
Site Plan.
ADDITIONAL CHANGES:
a. The building was shifted toward the east to allow
room for the second floor extension.
b. The drive on the East side of the building was
shifted away from the building to make room for the
building's mechanical equipment. This resulted in
the loss of two (2) parking spaces at the connection
to the Ponderosa Place parking lot and the addition
of four (4) parking spaces in the lot behind the
building. The landscape and Parking analysis have
been adjusted to account for the net change of two
(2) additional parking spaces.
Very Truly Yours,
4eve E. ncan, P.E.
sed @pkengineeing.com
SED /djw
Enclosures
cc: Leon Williamson
Walt Schoenvogel
P = Pledger Kalkomey, Inc.
K Consulting Engineers
June 27, 2005
Ms. Bridgette George
City of College Station
P.O. Box 9960
College Station, Texas 77842
Re: R &S Leasing
College Station Professional Building Two
PK Job No. 52805 -291
Dear Mrs. George,
Enclosed please find the following:
! � - t 1 - >
7020 Coyote Run r�-7 rvg
Bryan, Texas 77808 ,
7A
979 - 731 -8000, 979 - 731 -1500 (Fax)
www.pkengineering.com
U
1. Site Plan Application
2. Site Plan Checklist
3. Payment in the amount of $1000.00 for the $200.00
Application Fee, $200.00 Development Permit
Application Fee and $600.00 Public Infrastructure
Inspection Fee.
4. Eleven (11) copies of the Site Plan dated today.
Very Truly Yours,
_ . Duncan, P.E.
sed @pkengineeing.com
SED /dj w
Enclosures
Cc: Leon Williamson
Walt Schoenvogel
S: \2005 \52805 -291 R &S- medical \CS -01 -site pla .doc