MEMORANDUM
June 27, 2005
TO: Veronica J. B. Morgan, Mitchell & Morgan, LLP, via fax 979.260.3564
FROM: Bridgette George, Development Coordinator
SUBJECT: AUTUMN CHASE (FP)
Staff reviewed the above - mentioned engineering documents as requested. The
following page is a list of staff review comments detailing items that need to be
addressed. Please address the comments and submit the following information for
further staff review and approval of the plans:
Two (2) sets of revised construction documents.
If you have any questions or need additional information, please call Carol Cotter or
myself at 979.764.3570.
Attachments: Staff Review Comments
Cc: Dan Bensimon, via fax 512.795.8431
Case file no. 05- 00500085
Home of Texas A &M University
AUTUMN CHASE (FP) (05- 00500085)
ENGINEERING REVIEW
COMMENTS No. 2
1. Gate valves are required; one less than every leg of a tee connection.
Reviewed by: Carol Cotter Date: June 27, 2005
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be
explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans
that have not been pointed out to the City of College Station will constitute a completely new review.
Page 2 of 2
ELI"
CITY OF COLLEGE STATION
Planning & Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
May 31, 2005
TO: Dan Bensimon, Via fax 512.795 -8431
FROM: Jennifer Reeves, Project Manager
SUBJECT: AUTUMN CHASE (FP)
Staff reviewed the above - mentioned engineering documents as requested. The
following page is a list of staff review comments detailing items that need to be
addressed. Please address the comments and submit the following information for
further staff review and approval of the plans:
Two (2) sets of revised construction documents and fire flow report.
If you have any questions or need additional information, please call Carol Cotter or
myself at 764.3570.
Attachments: Staff Review Comments
Cc: Veronica Morgan, PE Via Fax 979.260.3564
Case file no. 05- 00500085
Home of Texas A&M University
AUTUMN CHASE (FP) (05- 00500085)
Engineering Review
Comments No. 1
1. Provide Grading Plan.
2. Re -title Sheet 08 to Erosion Control Plan.
3. Minimum separation between water line crossing under a sewer line is 1 foot
between sewer line and encasement pipe.
4. Provide construction documents for 3 inch water mains to meter banks.
5. Use actual flow data from existing area hydrants in the fire flow analysis.
6. Show tie -in of 4" lay down curb to ground to insure that depth of water in street stays
within the ROW.
7. Is an eyebrow needed on the northwest curve of Autumn Chase Loop? Justify.
8. What are you proposing for traffic safety /circulation at the southeast intersection?
Striping? Stop signs?
9. Revise construction documents to reflect staff review comments returned on plats
regarding water and sewer lines.
Reviewed by: Carol Cotter Date: May 31, 2005
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be
explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans
that have not been pointed out to the City of College Station will constitute a completely new review.
Page 2 of 2
11 _11 (*Or"
CITY OF COLLEGE STATION
Planning 6- Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
May 31, 2005
TO: Veronica Morgan, PE Via Fax 979.260.3564
FROM: Jennifer Reeves, Project Manager
SUBJECT: AUTUMN CHASE (FP)
Staff reviewed the above - mentioned engineering documents as requested. The
following page is a list of staff review comments detailing items that need to be
addressed. Please address the comments and submit the following information for
further staff review and approval of the plans:
Two (2) sets of revised construction documents and fire flow report.
If you have any questions or need additional information, please call Carol Cotter or
myself at 764.3570.
Attachments: Staff Review Comments
Cc: Dan Bensimon, Via fax 512.795 -8431
Case file no. 05- 00500085
Home of Texas A&M University
AUTUMN CHASE (FP) (05- 00500085)
Engineering Review
Comments No. 1
1. Provide Grading Plan.
2. Re -title Sheet 08 to Erosion Control Plan.
3. Minimum separation between water line crossing under a sewer line is 1 foot
between sewer line and encasement pipe.
4. Provide construction documents for 3 inch water mains to meter banks.
5. Use actual flow data from existing area hydrants in the fire flow analysis.
6. Show tie -in of 4" lay down curb to ground to insure that depth of water in street stays
within the ROW.
7. Is an eyebrow needed on the northwest curve of Autumn Chase Loop? Justify.
8. What are you proposing for traffic safety /circulation at the southeast intersection?
Striping? Stop signs?
9. Revise construction documents to reflect staff review comments returned on plats
regarding water and sewer lines.
Reviewed by: Carol Cotter Date: May 31, 2005
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be
explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans
that have not been pointed out to the City of College Station will constitute a completely new review.
Page 2 of 2
CITY OF COLLEGE STATION
Planning 6- Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
May 25, 2005
TO: Veronica Morgan, PE Via Fax 979.260.3564
FROM: Jennifer Reeves, Project Manager
SUBJECT: AUTUMN CHASE (FP) - Final Plat
Staff reviewed the above - mentioned final plat as requested. The following page is a list of staff
review comments detailing items that need to be addressed. If all comments have been
addressed and the following information submitted by Monday, May 31, 10:00 a.m., your project
will be placed on the next available Planning and Zoning Commission meeting scheduled for
June 16th , 7:00 p.m. in the City Hall Council Chambers, 1101 Texas Avenue.
Two (2) 24 "x36" copies of the revised final plat;
Ten (10) 11 "x1 T' copies of the revised final plat;
Parkland Dedication in the amount of $ must be submitted prior to the filing of the
final plat;
One (1) Mylar original of the revised final plat; and
One (1) copy of the digital file of the final plat on diskette or e-mail to
nmanhart @cstx.gov
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally filed with the City of College Station. Please note that if all comments have
not been addressed your project will not be scheduled for a Planning & Zoning Commission
meeting. Your project may be placed on a future agenda once all the revisions have been made
and the appropriate fees paid. If you have any questions or need additional information, please
call or myself at 979.764.3570.
Attachments: Staff review comments
cc: Dan Bensimon, Via fax 512.795 -8431
Case file #05- 00500085
Home of Texas A&M University
N
STAFF REVIEW COMMENTS NO. 1
Project: AUTUMN CHASE (FP) - 05- 00500085
PLANNING /ENGINEERING
1. Provide volume and page number of "Original Plat ".
2. Submit abandonment documentation for PUEs to be abandoned. If you plan to abandon the
PUE and relocate the public sewer line near Lot 13, then the Abandonment will have to go
through Council.
3. Revise the Final Plat to reflect comments returned on Preliminary Plat.
4. Remove building set backs from the plat.
5. Provide PLIES per Subdivision Regulations 8 -1.2.
6. Construction documents and reports still under review.
Reviewed by: Jennifer Reeves /Carol Cotter Date: 05 -24 -05
ELECTRICAL
1. Developer installs conduit per city specs and design.
7. Developer provides 30' of 2" IMC conduit for riser poles.
8. Developer pours transformer pad(s) per city specs and design.
9. Developer provides easements for electric infrastructure as installed for electric lines
(including street lights). Developer provides easements on final plat per city design plan.
10. Developer installs street lights per city spec and design. (on public streets)
11. CSU will provide electric design plan for installation of conduit.
To discuss any of the above electrical comments, please contact Sam Weido at 979.764.6314.
Reviewed by: Sam Weido Date: 5 -19 -05
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.
Page 2 of 2
CITY OF COLLEGE STATION
Planning 6- Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
May 25, 2005
TO: Dan Bensimon, Via fax 512.795 -8431
FROM: Jennifer Reeves, Project Manager
SUBJECT: AUTUMN CHASE (FP) - Final Plat
Staff reviewed the above - mentioned final plat as requested. The following page is a list of staff
review comments detailing items that need to be addressed. If all comments have been
addressed and the following information submitted by Monday, May 31, 10:00 a.m., your project
will be placed on the next available Planning and Zoning Commission meeting scheduled for
June 16th , 7:00 p.m. in the City Hall Council Chambers, 1101 Texas Avenue.
Two (2) 24 "x36" copies of the revised final plat;
Ten (10) 11 "x1 T' copies of the revised final plat;
Parkland Dedication in the amount of $ must be submitted prior to the filing of the
final plat;
One (1) Mylar original of the revised final plat; and
One (1) copy of the digital file of the final plat on diskette or e-mail to
nmanhart @cstx.gov
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally filed with the City of College Station. Please note that if all comments have
not been addressed your project will not be scheduled for a Planning & Zoning Commission
meeting. Your project may be placed on a future agenda once all the revisions have been made
and the appropriate fees paid. If you have any questions or need additional information, please
call or myself at 979.764.3570.
Attachments: Staff review comments
cc: Veronica Morgan, PE Via Fax 979.260.3564
Case file #05- 00500085
Home of Texas A&M University
STAFF REVIEW COMMENTS NO. 1
Project: AUTUMN CHASE (FP) - 05- 00500085
PLANNING /ENGINEERING
1. Provide volume and page number of "Original Plat ".
2. Submit abandonment documentation for PUEs to be abandoned. If you plan to abandon the
PUE and relocate the public sewer line near Lot 13, then the Abandonment will have to go
through Council.
3. Revise the Final Plat to reflect comments returned on Preliminary Plat.
4. Remove building set backs from the plat.
5. Provide PUEs per Subdivision Regulations 8 -1.2.
6. Construction documents and reports still under review.
Reviewed by: Jennifer Reeves /Carol Cotter Date: 05 -24 -05
ELECTRICAL
1. Developer installs conduit per city specs and design.
7. Developer provides 30' of 2" IMC conduit for riser poles.
8. Developer pours transformer pad(s) per city specs and design.
9. Developer provides easements for electric infrastructure as installed for electric lines
(including street lights). Developer provides easements on final plat per city design plan.
10. Developer installs street lights per city spec and design. (on public streets)
11. CSU will provide electric design plan for installation of conduit.
To discuss any of the above electrical comments, please contact Sam Weido at 979.764.6314.
Reviewed by: Sam Weido Date: 5 -19 -05
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.
Page 2 of 2