MEMORANDUM
May 25, 2012
TO: ML Schehin, Saddle Creek Partners, Ltd.; via email: ml @mis- development.com
FROM: Danielle Singh, Graduate Civil Engineer
SUBJECT: SADDLE CREEK PH 4 - Final Plat
ENGINEERING COMMENTS NO. 2- Construction Documents
1. Please provide an electrical layout from BTU.
2. Please ensure the area immediately downstream of the pipe 103 crossing is graded to drain.
The flow line of the pipes is lower than the ditch elevation.
3. 1 would recommend matching the existing radii at the intersection of Wild Rose Court and
Prairie Dawn Trail to provide a uniform street.
4. Please provide an engineer's estimate for the public infrastructure.
5. Please calculate the velocities in the ditch (at locations other than culvert crossings) to
determine if any additional erosion control measures are necessary.
6. HDPE will be allowed for this phase. This should not be interpreted to apply to future
phases as we try to work out specifics with the County in the ETJ.
7. Some portions of the ditches do not meet our minimum slope (0.6 %) as required by the
B /CS Unified Design Guidelines. Please address this.
Reviewed by: Danielle Singh Date: 5/24/2012
cc: Joe Salvato, The Bank & Trust; via fax: 979 - 691 -5474
Joe Schultz, Schultz Engineering, LLC; via email: joeschultz84 @verizon.net
Case file no. 12- 00500102
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be
explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have
not been pointed out to the City, will constitute a completely new review.
FROM: Danielle Singh, Graduate Civil Engineer
SUBJECT: SADDLE -..EEK PH 4 - Final Plat
ENGINEERING COMMENTS NO. 2- Construction Documents
1. Please provide an electrical layout from BTU_
2. Please ensure the area immediately downstream of the pipe 103 crossing is graded to drain.
The flow line of the pipes is lower than the ditch elevation.
3. 1 would recommend matching the existing radii at the intersection of Wild Rose Court and
Prairie Dawn Trail to provide a uniform street.
4_ Please provide an engineer's estimate for the public infrastructure.
5. Please calculate the velocities in the ditch (at locations other than culvert crossings) to
determine if any additional erosion control measures are necessary_
6. HDPE will be allowed for this phase. This should not be interpreted to apply to future
phases as we try to work out specifics with the County in the ETJ.
7, Some portions of the ditches do not meet our minimum slope (0.6 %) as required by the
B /CS Unified Design Guidelines. Please address this.
Reviewed by: Danielle Singh Date' 5/24/2012
cc: Joe Salvato, The Bank & Trust; via fax: 079- 691 -5474
Joe Schultz, Schultz Engineering, LLC; via email: joeschultz84 @verizon.net
Case file no. 12- 00500102
NOTE. Any changes made to the plans, that have not been requested by the City of College Station, must be
explained in your next transmittal letter and 'bubbled" on your plans. Any additional changes on these plans that have
not been pointed out to the City, will constitute a completely new review.
W03
GdVGNtt1S
3QOW
A0
l
TO
(S)3Jdd
8T:00:00
NOIivanQ
VLPST696
3WdN /'ON Xti_�
L1?:9T 5Z/90
3WI1`3iVG
6TTT9CfO0 Vd3S
X31
xv7
3WbN
LV :ST ZTOZ /9Z/59 3WI1
1JOd36 NOIiVOI3IZ13A NOISSIWSNa�11
(*t1
CITY OF COLLEGE STATION
Planning e5 Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
June 21, 2012 f
TO: ML Schein, Saddle Creek Partners, Ltd.; via email: ml @mis- development.com
FROM: Danielle Singh, Graduate Civil Engineer
SUBJECT: Engineering Comments No. 4 for Saddle Creek Phase 4
i
f��
Staff reviewed the above - mentioned engineering documents as requested. The following page
is a list of staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information by any Monday at 10:00 a.m. for further staff
review and approval of the plans:
One (1) set of revised construction documents.
Please note that the Development Permit Balance (Public Infrastructure Review and Inspection
Fee), will be calculated and requested once the construction documents and engineer's
estimates have been reviewed and approved.
If you have any questions or need additional information, please call Danielle Singh at
979.764.3570.
Attachments: Staff review comments
J
PC: Joe Salvato, The Bank &Trust; via fax: 979-691-5474
Joe Schultz, Schultz Engineering, LLC; via email: joeschultz84 @verizon.net`
Case File No. 12- 00500102
ENGINEERING COMMENTS NO. 4
1. A drainage easement is being shown on Sheet 2 on the north side of Prairie Dawn Trail that
was not shown on the final plat or previous set of construction plans. If the drainage
easement is necessary, please revise the plat accordingly; otherwise remove it from these
plans.
2. Please provide the electrical layout.
3. The standard water line details need to be included with your next submittal.
4. On Sheet 5 the subgrade note refers to note 3. There is no note 3.
5. Where are Lot 21 and Lot 52 getting water service from? There were no services shown on
Lariat.
6. When submitting the plans for stamping, you will need to provide 4 full sets and an 11x17
set of the grading and erosion control.
Reviewed by: Danielle Singh Date: 6/20/2012
TRANSMISSION VERIFICATION REPORT
TIME 06121/2012 09:00
NAME
FAX
TEL
SER.# COJ361119
DATE,TIME
06121 08:59
FAX NO./NAME
96915474
DURATION
00 :00 :38
PAGE(S)
02
RESULT
OK
MODE
STANDARD
ECM
CITY OF COLLEGE STATION
Planning & Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 J Pax 979.764.3496
MEMOPLANDUM
June 21, 2012
TO: Ml- Schein, Saddle Creek Partners, Ltd.; via email: ml @mis-development.com
FROM: Danielle Singh, Graduate Civil Engineer
SUBJECT: Engineering Comments No. 4 for Saddle Creek Phase 4
Staff reviewed the above - mentioned engineering documents as requested. The following page
is a list of staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information by any Monday at 10:00 a.m. for further staff
review and approval of the plans:
One (1) set of revised construction documents.
Please note that the Development Permit Balance (Public Infrastructure Review and Inspection
Fee), will be calculated and requested once the construction documents and engineer's
estimates have been reviewed and approved.
If you have any questions or need additional information, please call Danielle Singh at
Schultz Engineering, LLC
Office: 979.764.3900
Fax: 979.764.3910
June 8, 2012
Teresa Rogers
Staff Planner
City of College Station
1101 Texas Avenue
College Station, TX 77840
Re: SADDLE CREEK PH 4 Heights (FP) —12- 00500102
Dear Ms. Rogers:
Attached are 1 -24 "x36" and 13 -11 "x17" copies of the revised Final Plat and the response to staff
comments.
If you have any questions, please do not hesitate to call.
Very truly yours,
P.O. Box 11995 • College Station, Texas 77842
schultzengineeringllc.com
Schultz Engineering, LLC.
STAFF REVIEW COMMENTS NO. 1
Project: SADDLE CREEK PH 4 (FP) - 12- 00500102
PLANNING
Revise Approval of Planning and Zoning Commission to Certificate of Planning and
Zoning Commission.
Changed on the Plat.
Revise Certificate of the County Clerk to have a place for the day. Also change
"Deed Records" to "Official Records ", as this is a typo in the Unified Development
Ordinance.
Changed on the Plat.
✓3. Label and provide volume and page for 30' pipeline easement located along the
Eastern border of the plat.
There are two Pipeline easements adjacent to the eastern border, and they
have both been edited to show the volume and page.
�4. Label ownership of lots abutting Phase 4.
The ownership of the lots adjacent to phase 4 from Phases 1, 2 & 3 of
Saddle Creek have been added to the plat.
V5. Add "Lot" in front of every lot number.
This has been added to all of the lots.
V6. Add the existing subdivision limits to the Vicinity Map.
The vicinity map has been updated to show the ROW from the previous
phases of Saddle Creek.
, ,57. Please note that any changes made to the plans, that have not been requested by
the City of College Station, must be explained in your next transmittal letter and
"bubbled" on your plans. Any additional changes on these plans that the City has not
been made aware of will constitute a completely new review.
Noted.
8. Please note that you may be required to submit paid tax certificates if they are not
current prior to the filing of your plat.
Noted.
ENGINEERING COMMENTS NO. 1
/. Please tie a corner of the property to a City of College Station Monument.
The Plat has a tie to City of College Station Monument No. #143
Nv�. Construction plans are currently under review. Comments for the construction plans
will be sent separately. Any changes required may affect the final plat.
Noted.
,�3. FYI- A letter from Wellborn Special Utility District stating that they have capacity to
serve the development will be required.
Noted.
/ [:A
. It appears that Lot 28, 33 and 34 were left off the preliminary plan. Was this
intentional?
it was intentional. These lots were in the original Preliminary Plat but were
removed in the Preliminary Plat revision dated July 2010 (10 — 00500140).
5. Please provide an exhibit showing BTU's electrical layout for the development.
Noted.
ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION
1. The project location is outside CSU electric service territory. CSU will not provide
electric service to this project.
Noted.
GENERAL ELECTRICAL COMMENTS
1. To discuss any of the above electrical comments please contact Gilbert Martinez at
979.764.6255.
Noted.
SANITATION
1. Sanitation is ok with this project.
Noted.
TxDOT Comments
1. No Comment
Noted.
ENGINEERING COMMENTS NO. 2- Construction Documents
Project: SADDLE CREEK PH 4 (FP) - 12- 00500102
ENGINEERING COMMENTS NO. 2- Construction Documents
1. Please provide an electrical layout from BTU.
BTU has been contacted and their design will be forwarded once we
receive it.
2. Please ensure the area immediately downstream of the pipe 103 crossing is
graded to drain. The flow line of the pipes is lower than the ditch elevation.
Pipe 101 and Pipe 102 have been deleted. The ditches at the
intersection of Prairie Dawn Trail and Wild Rose Drive will be graded to
drain without these culverts and to tie into the existing ditches without
going downstream of this project.
3. 1 would recommend matching the existing radii at the intersection of Wild Rose
Court and Prairie Dawn Trail to provide a uniform street.
A 40' radius is now proposed for this intersection.
4. Please provide an engineer's estimate for the public infrastructure.
An engineer's estimate is attached in this submittal.
5. Please calculate the velocities in the ditch (at locations other than culvert
crossings) to determine if any additional erosion control measures are necessary.
The Drainage Report has been amended. Exhibit B and Appendix C
illustrate the velocities in the ditches.
6. HDPE will be allowed for this phase. This should not be interpreted to apply to
future phases as we try to work out specifics with the County in the ETJ.
Noted.
7. Some portions of the ditches do not meet our minimum slope (0.6 %) as required
by the B /CS Unified Design Guidelines. Please address this.
A minimum slope of 0.6% is now applied to all ditches.
PLANNING
!1. Revise the lot currently listed as Block 3, Lot 49 to be Block 3, Lot 46. For
reference, it is owned by Shawn Connelly and Bunita Eichelberger.
This Plat has been updated to show the correct owner.
1 2. Please note that you may be required to submit paid tax certificates if they are not
current prior to the filing of your plat.
Noted.
ENGINEERING COMMENTS
1. Please provide an exhibit showing BTU's electrical layout for the development. This
can be submitted with the development permit resubmittal.
BTU was contacted with the previous set of comments and we are waiting
to receive their design.
2. The development permit has not been approved. Any changes made to this may
affect the final plat.
A development permit will not be issued for this development because it is
in the ETJ.
NOTE:
• Pipe 101 & 102 were removed from the plans.
gip; • Remington Road was changed to Wild Rose Drive, by request.
Home uf7 was A6 'niver:;itp
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
June 4, 2012
TO: ML Schehin, Saddle Creek Partners, Ltd.; via email: ml @mis- development.com V -111,
FROM: Teresa Rogers, Staff Planner
SUBJECT: SADDLE CREEK PH 4 (FP) - Final Plat
Staff reviewed the above - mentioned final plat as requested. The following page is a list of staff
review comments detailing items that need to be addressed. If all comments have been
addressed and the following information submitted by any Monday at 10:00 a.m., your project
will be placed on the next available Planning and Zoning Commission meeting held in the City
Hall Council Chambers, 1101 Texas Avenue.
One (1) 24 "x36" copy of the revised final plat;
Thirteen (13) 11 "x17" copies of the revised final plat;
One (1) Mylar original of the revised final plat (required after P &Z approval); and
One (1) copy of the digital file of the final plat on diskette or e-mail to
pdsdigitalsubmittal(�i_)cstx.gov
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally filed with the City of College Station. Please note that this application will
expire in 90 days from the date of this memo, if the applicant has not provided written response
comments and revised documents to the Administrator that seek to address the staff review
comments contained herein. If all comments have not been addressed your project will not be
scheduled for a Planning & Zoning Commission meeting. Your project may be placed on a
future agenda once all the revisions have been made and the appropriate fees paid. Once your
item has been scheduled for the P &Z meeting, the agenda and staff report can be accessed at
the following web site on Monday the week of the P &Z meeting.
http://Www.cstx.gov
Please note that a Mylar original of the revised final plat will be required after P &Z approval and
prior to the filing of the plat. If you have any questions or need additional information, please call
me at 979.764.3570.
Attachments: Staff review comments
cc: Joe Salvato, The Bank & Trust; via fax 979 - 691 -5474✓
Joe Schultz, P.E., Schultz Engineering, LLC; via email: joeschultz84 @verizon.netV/
Case file no. 12- 00500102
Home of Texas A &M University
STAFF REVIEW COMMENTS NO. 2
Project: SADDLE CREEK PH 4 (FP) - 12- 00500102
PLANNING
1. Revise the lot currently listed as Block 3, Lot 49 to be Block 3, Lot 46. For reference, it is
owned by Shawn Connelly and Bunita Eichelberger.
2. Please note that you may be required to submit paid tax certificates if they are not current
prior to the filing of your plat.
Reviewed by: Teresa Rogers
Date: May 29, 2012
ENGINEERING COMMENTS
1. Please provide an exhibit showing BTU's electrical layout for the development. This can be
submitted with the development permit resubmittal.
2. The development permit has not been approved. Any changes made to this may affect the
final plat.
Reviewed by: Danielle Singh
Date: June 1, 2012
Home of Texas A &M University
TRANSMISSION VERIFICATION REPORT
TIME 06/04/2012 16:37
NAME
FAX
TEL
SER.# COJ361119
DATE,TIME
06/04 16:36
FAX NO. /NAME
96915474
DURATION
00:00:58
PAGE(S)
02
STANDARD
MODELT
ECM
�
C' J'1' ()I� CC)T.J..1 Ctrs S TATIC)N
IJosue, vs Az; a9 Uirfvr,siry"
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.35701 Fax 979.764.3496
MEMORANDUM
June 4, 2012
TO: ML. Schehin, Saddle Creek Partners, Ltd.; via email: ml@mls-development.com
FROM: Teresa Rogers, Staff Planner
SUBJECT: SADDLE CREEK PH 4 (FP) - Final Plat
Staff reviewed the above- mentioned final plat as requested. The following page is a list of staff
review comments detailing items that need to be addressed_ If all comments have been
addressed and the following information submitted by any Monday at 10:00 a.m., your project
will be placed on the next available Planning and Zoning Commission meeting held in the City
Hall Council Chambers, 1101 Texas Avenue.
One (1) 24 "x36" copy of the revised final plat;
Thirteen (13) 11 "x17' copies of the revised final plat;
One (1) Mylar original of the revised final plat (required after P &Z approval); and
One (1) copy of the digital file of the final plat on diskette or e-mail to
pdsdlgitalsubmittalAcstx qov
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally fled with the City of College Station. Please note that this application will
expire in 90 days from the date of this memo, if the applicant has not provided written response
comments and revised documents to the Administrator that seek to address the staff review
comments contained herein_ If all comments have not been addressed your project will not be
scheduled for a Planning & Zoning Commission meeting. Your project may be placed on a
fi ih ira arianrin nnra all the rpvicinniz hnva hpa?n marip and fha nnnrnnrinfa fppc nairi (Inrta vmi lr
Planning & Development Services
(*. 1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
CITE n; C01A,kG),STnT](')N Phone 979.764.3570 / Fax 979.764.3496
,, u
name °fkw ``` n�ier,ij MEMORANDUM
May 21, 2012
TO: ML Schehin, Saddle Creek Partners, Ltd.; via email: ml @mis- development.com
FROM: Teresa Rogers, Staff Planner
SUBJECT: SADDLE CREEK PH 4 - Final Plat
Staff reviewed the above - mentioned final plat as requested. The following page is a list of staff
review comments detailing items that need to be addressed. If all comments have been
addressed and the following information submitted by any Monday at 10:00 a.m., your project
will be placed on the next available Planning and Zoning Commission meeting held in the City
Hall Council Chambers, 1101 Texas Avenue.
One (1) 24 "06" copy of the revised final plat;
Thirteen (13) 11 "x17" copies of the revised final plat;
One (1) Mylar original of the revised final plat (required after P &Z approval); and
One (1) copy of the digital file of the final plat on diskette or e-mail to:
P &DS_Digital_Submittal @cstx.gov.
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally filed with the City of College Station. Please note that this application will
expire in 90 days from the date of this memo, if the applicant has not provided written response
comments and revised documents to the Administrator that seek to address the staff review
comments contained herein. If all comments have not been addressed your project will not be
scheduled for a Planning & Zoning Commission meeting. Your project may be placed on a
future agenda once all the revisions have been made and the appropriate fees paid. Once your
item has been scheduled for the P &Z meeting, the agenda and staff report can be accessed at
the following web site on Monday the week of the P &Z meeting.
http://www.cstx. pz
Please note that a Mylar original of the revised final plat will be required after P &Z approval and
prior to the filing of the plat. If you have any questions or need additional information, please call
me at 979.764.3570.
Attachments: Staff Review Comments
cc: Joe Salvato, The Bank & Trust; via fax: 979 - 691 -5474
Joe Schultz, Schultz Engineering, LLC; via email: joeschultz84 @verizon.net
Case file no. 12- 00500102
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be
explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans 3
that have not been pointed out to the City, will constitute a completely new review.
STAFF REVIEW COMMENTS NO. 1
Project: SADDLE CREEK PH 4 (FP) - 12- 00500102
PLANNING
1. Revise Approval of Planning and Zoning Commission to Certificate of Planning and
Zoning Commission.
2. Revise Certificate of the County Clerk to have a place for the day. Also change
"Deed Records" to "Official Records ", as this is a typo in the Unified Development
3
4
5
6
7
Ordinance.
Label and provide volume and page for 30' pipeline
Eastern border of the plat.
Label ownership of lots abutting Phase 4.
Add "Lot" in front of every lot number.
Add the existing subdivision limits to the Vicinity Map.
easement located along the
Please note that any changes made to the plans, that have not been requested by
the City of College Station, must be explained in your next transmittal letter and
"bubbled" on your plans. Any additional changes on these plans that the City has not
been made aware of will constitute a completely new review.
Please note that you may be required to submit paid tax certificates if they are not
current prior to the filing of your plat.
Reviewed by: Teresa Rogers Date: May 17, 2012
ENGINEERING COMMENTS NO. 1
1. Please tie a corner of the property to a City of College Station Monument.
2. Construction plans are currently under review. Comments for the construction plans
will be sent separately. Any changes required may affect the final plat.
3. FYI- A letter from Wellborn Special Utility District stating that they have capacity to
serve the development will be required.
4. It appears that Lot 28, 33 and 34 were left off the preliminary plan. Was this
intentional?
5. Please provide an exhibit showing BTU's electrical layout for the development.
Reviewed by: Danielle Singh
Date: May 21, 2012
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be
explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans
that have not been pointed out to the City, will constitute a completely new review. 2 of 3
ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION
1. The project location is outside CSU electric service territory. CSU will not provide
electric service to this project.
GENERAL ELECTRICAL COMMENTS
1. To discuss any of the above electrical comments please contact Gilbert Martinez at
979.764.6255.
Reviewed by: Gilbert Martinez Date: May 18, 2012
SANITATION
1. Sanitation is ok with this project.
Reviewed by: Wally Urrutia Date: May 16, 2012
TxDOT Comments
1. No Comment
Reviewed by: Chad Bohne Date: May 17, 2012
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be
ans
explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these p l an 3
that have not been pointed out to the City, will constitute a completely new review.
TRANSMISSION VERIFICATION REPORT
TIME 05121/2012 15:14
NAME
FAX
TEL
SER.# COJ361119
DATE,TIME
05121 15:13
FAX NO./NAME
96915474
DURATION
00:00:57
PAGE(S)
03
RESULT
OK
MODE
STANDARD
ECM
"1 Pl annin g & Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
C,Tvc7s� Ccy�.r,E.�s�;SxAx10N
Phone 979.764.35701 Fax 979.764.3496
HameofrimsA Clnitiersr.tj MEMORANDUM
May 21, 2012
TO: ML Schehin, Saddle Creek Partners, Ltd.; via email: ml@mls-development.com
FROM: Teresa Rogers, Staff Planner
SUBJECT: SADDLE CREEK PH 4 - Final Plat
Staff reviewed the above - mentioned final plat as requested. The following page is a list of staff
review comments detailing items that need to be addressed. If all comments have been
addressed and the following information submitted by any Monday at 10:00 a.m., your project
will be placed on the next available Planning and Zoning Commission meeting held in the City
Mall Council Chambers, 1101 Texas Avenue.
One (1) 24 "x36" copy of the revised final plat;
Thirteen (13) 11 "x97' copies of the revised final plat;
_ One (1) Mylar original of the revised final plat (required after P &Z approval); and
One (1) copy of the digital file of the final plat on diskette or email to:
P &DS_Digital_Submittal@a cstx.gov.
Upon receipt of the required documents for the Planning & Zoning meeting, your project will be
considered formally filed with the City of College Station. Please note that this application will
expire in 90 days from the date of this memo, if the applicant has not provided written response
comments and revised documents to the Administrator that seek to address the staff review
comments contained herein. If all comments have not been addressed your project will not be
CITY OF COIIEGE STSTION
Home of Texas A&M University'
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
May 11, 2012
TO: ML Schehin, Saddle Creek Partners, Ltd.; via email: mi(cDmis- development.com
FROM: Jason Schubert, AICP
Principal Planner
SUBJECT: SADDLE CREEK PH 4 (FP)
Thank you for the submittal of your FINAL PLAT - RESIDENTIAL application. This project will
be distributed to staff next week for their review.
cc: Joe Salvato, The Bank &Trust, via fax: 979 - 691 -5474 0— Joe Schultz, Schultz Engineering, LLC; via email: h eschultz84(cb- verizon.net
Case file no. 12- 00500102