HomeMy WebLinkAbout16 DP College Station Shopping Center Plaza 05-46 2704 Texas Ave SCITY OF C OLLEGE STATI ON
Planning d-Drodopm ent Services
SITE LEGAL DESCRIPTION:
Brandywine Subdivision
Lots 1, 3 &4 , Block 1
(College Station Shopping Plaza)
DATE OF ISSUE: 10/04/05
OWNER:
David Cotrell Investments
7505 Nightmeadow
Houston, Texas 77063
TYPE OF DEVELOPMENT:
SPECIAL CONDITIONS:
DEVELOPMENT PERMIT
PERMIT NO . 05-46
FOR AREAS OUTSIDE THE SPECIAL FLOOD HAZARD AREA
RE: CHAPTER 13 OF THE COLLEGE STATION CITY CODE
SITE ADDRESS:
2704 Texas Avenue S
DRAINAGE BASIN:
Bee Creek Trib. "A"
VALID FOR 9 MONTHS
CONTRACTOR:
Full Development Permit
All construction must be in compliance with the approved construction plans
All trees required to be protected as part of the landscape plan must be completely barricaded in accordance with Section
7.5 .E., Landscape/Streetscape Plan Requirements of the City's Unified Development Ordinance, prior to any operations of
this permit. The cleaning of equipment or materials within the drip line of any tree or group of trees that are protected and
required to remain is strictly prohibited. The disposal of any waste material such as , but not limited to, paint, oil, solvents,
asphalt, concrete , mortar, or other harmful liquids or materials within the drip line of any tree required to remain is also
prohibited .
TCEQ PHASE II RULES IN EFFECT .
The Contractor shall take all necessary precautions to prevent silt and debris from leaving the immediate construction site
in accordance with the approved erosion control plan as well as the City of College Station Drainage Policy and Design
Criteria . If it is determined the prescribed erosion control measures are ineffective to retain all sediment onsite, it is the
contractors responsibility to implement measures that will meet City, State and Federal requirements . The Owner and/or
Contractor shall assure that all disturbed areas are sodden and establishment of vegetation occurs prior to removal of any
silt fencing or hay bales used for temporary erosion control. The Owner and/or Contractor shall also insure that any
disturbed vegetation be returned to its original condition , placement and state . The Owner and/or Contractor shall be
responsible for any damage to adjacent properties, city streets or infrastructure due to heavy machinery and/or equipment
as well as erosion, siltation or sedimentation resulting from the permitted work .
In accordance with Chapter 13 of the Code of Ordinances of the City of College Station, measures shall be taken to insure
that debris from construction, erosion, and sedimentation shall not be deposited in city streets, or existing drainage
facilities .
I hereby grant this permit for development of an area outside the special flood hazard area . All development shall be in
accordance with the plans and specifications submitted to and approved by the City Engineer in the development permit
application for the above named project and all of the codes and ordinances of the City of College Station that apply.
miv~~
.--
Owner/ Agent/Contractor
ID -Ob -0~
Date
Date
$ ~-Aug 30 05 03:10p Turner Engineer Inc. 214-522-7140 p.2
.. vr
CITY OF COLLEGE. STATION
l'/.:rarmg 0-Dewl.aJm111U Sm•irtr
DEVELOPMENT PERMIT
MINIMUM SUBMllTAL REQUIREMENTS
$200 development permit fee.
$600.00 Public lnfrastructure Inspection Fee if applicable . (This fee is payable if construction of a
public waterline, sewerline, sidewalk, street or drainage facilities is involved.} _if.
Drainage and erosion control plan, with supporting Drainage Report two (2) copies ea1,;1 \.t-lo'f ~19-U>)
Notice of Intent (N.0.1.) if disturbed area is greater than 5 aaes (~ ~'A.~o)
Date of "Required PreappJicatlon Conference: _________________ _
.. (Required for areas of special flood hazard).
LEGAL DESCRIPTION Lo~ \, -;, '4-4 , ?Jlol~\ %AA1.>9'1W\t.>f. S\>B~"\S\OW
APPLICANT'S I NFORMA Tl ON {Primary Contact for the Project): -l.."'1A \l"fCtc>
Name \1'£.',\l\i.L.. ¥£.!'~fr -~~ . .JE,_:il0'2-f. AtLtHT~~ E-Mail M~AQ., ~i-J'Z@. \WA,££..
Street Address Ill\ t.\o~n\ 'a>+> llli&T \ $1>rrf.. 9aoO
City Ho\)"!,~ State _T...._j. ______ _ Zip Code 11 OQ~
Phone Number J(b 8b41\ llo"I_, Fax Number _1~~""--'8~'.._f\ .......... 5 ...... 5:.....a;J ..... ?>.__ ___ _
PROPERTY OWNER'S INFORMATION:
Name DAv\1'.> CouM.u-\t-)~,.ME.....,\2
Street Address 1-So? \!lC.i\\Y\iAOO..V
City ~\J(,lPtJ State _\._.j..::--_ __,_ __ Zip Code 110b~
Phone Number 1\2 1&'2 $05'2.. Fax Number _1~•'?_'7_?:\.-......-4 ..... S~:; ..... 7 ___ _
.A~CI llTEC"r OR ENGlNEER'S INFORMATION : M£p/~-r~Cf /o.\1L(..
Name ~iM 'fu~ &.lttu.>E.~'1--~ E-Mail _=.)_.l\!;ic..;~'-'-~~~___,;;::;e~.)f._lf=--=-·'-'U>_1"'\__._ __ _
Street Address ~400 ezt_~e:~'I O@-\\lE,
City_ .. \W.~t.Ar.! o pf\g.¥. State _...D.-"'------Zip Code :t5~
Fax Number 2. \4 S2.2. 0%1 Phone Number 2..\4-$2.'2-:JlAD
Application is hereby made for the following development specific sltei\vaterway alteratlons :
ACKNOWLEDGMENTS :
'·-~ W!ie1. hereby acknowledge or affirm that:
The information and conclus1ons contained ln the above plans and supporti
current requi rements of the City of College Station , Texas City Code, Cha t
documents comp'y with the
3 and its associated Drainage
Po licy and Design Standards.
Property Owner(s)
6113/03
--------------
?£ 1 of2
ti
~·Aug 30 05 03:10p Turner Engineer Inc. 214 -522 -7140 p.3
"
As a condition of approval of this permit application, I agree to construct the Improvements proposed in this
application according to these documents and the requirements of Chapter 13 of the College Station City
Code
Contractor
CERTIFICATIONS:
A. I, J (~ c.ertify that any nonresidential structure on or proposed to be on this site as part of this
application is design to prevent damage to the structure or Its contents as a result of flooding from
the 100-year sto
Engineer Date
B. I, I pf , certify that the finished floor elevation of the lowest floor , lnduding any basement, of any
residential stru , proposed as part of this application is at or above the base flood elevation
established i atest Federal Insurance Administration Flood Hazard Study and maps, as amended .
Engineer Date
C. I, IP, certify that the alterations or development covered by this permit shall not diminish the flood-
carrying capacity of the waterway adjoining or crossing this pennitted site and that such alterations or
development are consistent with requirements of the City of College Station City Code, Chapter 13
concerning encroachments of floodways and of floodways fringes.
Dat e
D. I, J~. do certify that the proposed alterations do not raise the level of the 100 year flood above
elevation stablished in the latest Federal Insurance Administration Flood Hazard Study.
Engineer Date
Conditions or comments as part of approval:---------------------
In accordance with Chapter 13 of the Code of Ordinances of the City of COiiege Station, measures shal l be
taken to insure that debris from construction, erosion, and sed imentation shall not be deposited In city streets,
or existing drainage facilities. All development shall be in accordance with the plans and specifications
submitted to and approved by the City Engineer for the above named project. All of the applicable codes and
ordinances of the City of College Station shall apply.
6113103 2of2
t :
..
GEOTECHNICAL ENGINEERING STUDY
College Station Shopping Plaza AdditiOns
FM 2818 and Texas Avenue
College Station, Texas
Prepared for:
DAVID COTTRELL INVESTMENTS
C/O HEIGHTS VENTURE ARCHITECTS
Houston, Texas
Prepared by:
TERRA CON
HOUSTON, TEXAS
Terracon Project No.: 92055-384
July 2005
July 19, 2005 ·lrerracon
David Cottrell Investments
c/o Mr. Mike Kravetz
Heights Venture Architects
1111 North Loop West
Houston, Texas 77008
Re: Geo technical Engineering Study
College Station Shopping Plaza Additions
FM 2818 and Texas Avenue
College Station, Texas
Terracon Project No. 92055-384
Dear Mr. Kravetz:
Consulting Engineers & Scientists
Terracon Consultants , l.nc .
11555 Clay Road, Suite 100
Houston , Texas 77043
Phone 713 .690 .8989
Fax 713 .690 .8787
www.terracon.com
Enclosed is Terracon Consultant, Inc. (Terracon) report of the geotechnical engineering study
conducted for the above referenced project in College Station, Texas. We trust that this report is
responsive to your project needs. Please contact us if you have any questions or if we can be of
further assistance.
We appreciate the opportunity to work with you on this project and look forward to providing
additional geotechnical engineering and construction materials testing services in the future.
Sincerely,
TERRA CON
Eeshani Sood, E.I.T.
Staff Engineer
~Sent r,P .E.
Senior Geote ·cal Consultant
Copies Submitted: ( 4)
Delivering Success for Clients and Employees Since 1965
More Than 70 Offices Nationwide
I .
I
I
• David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384 lrerracon
TABLE OF CONTENTS
INTRODUCTION ............................................................................... ~ .............................................. I
PROJECT DESCRIPTION ............................................................................................. ; ................. I
SCOPE OF SERVICES ............................. .-.............................................................. ~ ........................ I
SITE EXPLORATION PROCEDURES ........................................................................................... I
Field Exploration ......................................................................................................................................... 1
Laboratory Testing ............................................................................................ ; ........................................ 2
Sample Disposal. .......................................................................................................................................... 2 ·
SITE CONDITIONS .......................................................................................................................... 3
Surface Conditions .................................................................................................................. ~ ................... 3
Site Geology ..................................................... ; ........................................................................................... 3
Subsurface Conditions ................................................................................................................................ 3
Groundwater Conditions ............................................................................................................................ 4
ENGINEERING RECOMMENDATIONS ............................. -......................................................... 4
Geotechnical Considerations ................................................................................................ ; ..................... 4
Foundation System ...................................................................................................................................... 5
Drilled and Underreamed Footings ........................................................................................................... 5
Floor Slabs ................................................................................................................................................... 6
Grade Beamsffilt-Wall Panels ................................................................................................................... 7
Lateral Earth Pressures .............................................................................................................................. 8
Foundation Construction ............................................................................................................................ 8
F oundation Construction Monitoring ....................................................................................................................... 9
Earthwork .................................................................................................................................................... 9
Wet Weather Conditions ........................................................................................................................................ 10
Drainage ..................................................................................................................................................... 11
GENERAL COMMENTS .................................................................................. .-............................. 11
APPENDIX
Plan of Borings .................................................................................... A-1
Logs of Borings .............................................................. A-2 through A-7
Key to Soil Classification and Symbols ............................................... A-8
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384
INTRODUCTION
.lrerracon
This report presents the results of our geotechnical engineering study for the proposed College Station
Shopping Plaza Additions in College Station, Texas. This projec.t was authorized by Mr. David Cottrell
of David Cottrell Investments through signature of our "Agreement For Services" on July 6, 2005. The
scope of work was performed in general accordance with Terracon Proposal No. H05-440, dated July
6, 2005.
PROJECT DESCRIPTION
This project involves the proposed construction of three single-story retail/restaurant buildings and a
canopy on an ex isting retail store at a site located at the northwestern corner of the intersection of
FM 2818 and Texas Avenue in College Station, Texas , We understand that two of the buildings are
planned to range in size from approximately 7 ,000 to 8,000 square feet in size and the third building
is appreciably smaller. Our services will not address pav ement rehabilitation .
SCOPE OF SERVICES
Our s cope of work for this project consisted of:
1. Drilling test borings at selected locations within the project site to evaluate
subsurface stratigraphy and groundwater conditions.
2 . Performing geotechni cal laboratory tests on reco v ered samples to evaluate the
physical and engineering properties of the strata encountered.
3. Engineering analysis to develop design and construction recommendations with
respect to:
• Site , subgrade, and fill preparation ; and
• Foundation depth and allowable bearing pressures
SITE EXPLORATION PROCEDURES
Field Exploration
Subsurface conditions were evaluated by drilling a total of 6 test borings in the proposed building areas .
The borings B-2 and B-3 were drilled to a depth of about 25 feet each and the remaining borings to a .
depth of about 20 feet each. The three to four-inch nominal diameter borings were drilled with
continuous flight auger drilling equipment.
1
j .
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-3.84 lrerracon
The borings were drilled at the approximate locations shown on the Plan of Borings, Page A-1 of the
Appendix . The borings were located by measuring from existing/adjacent features and property
boundaries and estimating right angles without the use of surveying equipment. Boring depths were
measured from the existing ground surface at the time of our field activities.
The Logs of Borings, presenting the subsurface soil descriptions, type of sampling used, and additional
field data , are presented on Pages A-2 through A-7 of the Appendix . The Symbol Key Sheet, which
defines the terms and descriptive symbols used on the logs, is presented on Page A-8.
Soil samples were recovered using thin-walled, open-tube samplers (Shelby-tubes). All samples were
removed from samplers in the field , visuall y classified, and appropriately sealed in sample containers to
preserve their in-situ moisture contents. Pocket penetrometer tests were performed on samples of
cohesive soils in the field to serve as a general measure of consistency.
Laboratory Testing
Samples obtained during the field program were visually classified in the laboratory by a geotechnical
engineer and/or a senior technician. A testing program was conducted on selected samples , as directed
by the geotechnical engineer, to aid in classification and evaluation of engineering properties required
for analyses.
Results of the laboratory tests are presented on the Logs of Borings, located on Pages A-2 through A-7
of the Appendix, and are discussed in the following section.
Sample Disposal
All samples were returned to our laboratory in Houston, Texas . Samples not tested in the laboratory
will be stored for a period of 60 days subsequent to submittal of this report and will be discarded
after this period, unless we are notified otherwise.
2
I .
I
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384
SITE CONDITIONS
Surface Conditions
lrerracan
The boreholes are located at the existing College Station Shopping Plaza. The site is relatively lev el and
consists of existing buildings with surrounding pavement.
Site Geology
· The site for the proposed structures is located on the Yegua Formation of early to late Eocene age . The
thickness of the Yegua Formation in the general site area is about 750 to 1000 ft . The soils near the
surface are primarily clays sometimes containing silt or sand with ironstone concretions. The clays are
highly ov erconsolidated and strong with seams of lignite in some areas.
Subsurface Conditions
The particular subsurface stratigraphy, as determined from our field and laboratory programs , is shown
in detail on the Logs of Borings in the Appendix. A review of the boring logs indicates about 0 .5 to
2 inches of asphalt surface (HMAC)) then 2 to 4 inches of what appears to be compacted , re-cycled
asphalt, and about 4 to 8 inches of base material that appears to be a mixture of sand and gravel. Boring
1 revealed about one feet of fill below the pavement section but Borings 2 and 3 located near the north
end of the existing retail building show fill to depths of 8 and 11 feet. Borings 4, 5 and 6 shows fill to 4
feet depth. Below the fill soils, stiff to hard silty clay and clay soils were present to the maximum
explored depth of about 25 feet.
The fill observed at the site mainly consists of silty clay and clay soils . These soils typically exhibit low
to very high potential for volumetric changes due to moisture conditions , as indicated by the liquid
limit ranging from 36 to 87 percent with plasticity index from 18 to 54 percent. Pocket penetrometer
readings of approximately 1.0 to 4.5 tons per square foot (tsf) were recorded . An undrained shear
strength from an unconfined compressive strength test was measured to be approximately 800 to 1,900
pounds per square foot (psf). The in-situ moisture contents varied from 21 to 36 percent. Cemented
sand and clay was observed in the fill indicating lime treated soils.
3
· David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384 lrerracon
The natural silty clays and clays underlying the fill soils were encountered at depths between about 2 to
11 feet below the existing grade. These soils exhibit moderately low to very high plasticity with
measured liquid limits varying from 46 to 78 percent and plasticity indices varying from 24 to 47
percent.
Moisture conte!1ts range from 19 to 3 7 percent. Measured undrained shear strengths from unconfined
compressive strength tests varied from about 3,300 to 5,700 pounds per square foot (psf). Measured
pocket penetrometer values of the natural soils varied from 1.5 to 4.5 tons per square foot (tsf)
indicating stiff to hard soils.
Groundwater Conditions
The borings were dry augered to their completion depths in an effort to evaluate groundwater levels.
Groundwater was not observed in the borings during our field inv estigation. However, it should be
noted that groundwater conditions may fluctuate seasonally with climatic changes and should be
evaluated just prior to construction.
ENGINEERING RECOMMENDATIONS
The following recommendations are based upon the data obtained in our field and laboratory programs,
project information provided to us, and our experience with similar subsurface and site conditions.
Geotechnical Considerations
Low to very highly expansive fill and native soils are present at this site . This report provides
recommendations to remove the fill soils within the building area as well as to help mitigate the
shrinkage and expansion potential of the native clayey soils. However, even if these procedures are
followed, some movement and possible cracking in the structure should be anticipated. The severity of
cracking and other distress such as uneven floor slabs will probably increase if any modification of the
site results in excessive wetting or drying of the expansive soils . Further reduction of the risk of
distress associated with expansive soils is only feasible if the buildings were to be designed using
suspended structural slabs with the structural loads supported by drilled shafts terminated below the
active zone. Terracon can provide recommendations for a structural floor slab system, if requested.
4
l
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384
Foundation System
lrerracon
Based upon the field and laboratory data available, along with our previous experience, it is our opinion
that a foundation system consisting of drilled and underreamed footings based below the zone of
significant seasonal moisture variation would be appropriate for the proposed structures at this site .
Recommendations for drilled and underreamed footing foundations are provided below, along with
other geotechnical considerations for this project.
Drilled and Underreamed Footings
The drilled and underreamed footings should be supported in the clay soils at a depth of 14 feet below
existing grade. This depth is to place the footings below the depth of significant seasonal moisture
variation and below the fill in Boring 3. The footings placed in the building at Borings 2 and 3 should
be checked to confirm the footings are placed within the natural clay soil. The footings should be sized
for a net dead plus sustained live load bearing pressure of 8,000 psf or a net total load pressure of
12,000 psf, whichever condition governs. These allowable bearing pressures contain factors of safety of
about 3 and 2, respectively . It is our opinion that the drilled-and-underreamed footings should be
constructed with a bell to shaft ratio of 3: 1.
The footings should contain sufficient vertical reinforcing steel throughout the entire shaft length to
resist uplift (tensile) forces due to post-construction heave of the clay soils. The magnitude of uplift is
difficult to predict and will vary with in-situ moisture contents. For purposes of establishing sufficient
reinforcement to resist uplift, the uplift pressures can be approximated by using a uniform uplift
pressure of 1,500 psf over the entire perimeter of the shaft above the top of the bell. An underreamed
base to shaft ratio of about 3: 1 should provide sufficient resistance to uplift pressures caused by
expansion of the clay soils .
A minimum clearance of one bell diameter of the larger footing should be provided between the
underreams to dev elop the recommended bearing pressures and to control settlements . If a clearance of
one diameter cannot be maintained in every case, the above bearing capacities should be reduced by 20
5
I
I
l
l
!
I
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384 ·1rerracon
percent for a clearance between one-half and one bell diameters. Underreams closer than a clearance of
one half of bell diameters are not recommended.
Post construction settlements of the drilled and underreamed shafts should be one inch or less,
assuming proper construction practices are followed. Differential settlements may result from variances
in subsurface conditions, loading conditions and construction procedures, such a cleanliness of the
bearing area or flowing water in the shaft. In general, differential settlements should be on the order of
one-half of the total settlement.
Uplift pressures on the drilled and undetrearned footings will be resisted by the weight of the
foundation plus the weight of any soil directly above the . foundation. For uplift resistance, we
recommend total unit weights of about 120 pounds per cubic foot (pct) for soil and 150 pcf for
reinforced concrete be utili zed . The ultimate uplift capacity should be reduced by.an appropriate factor
of safety to compute allowable uplift capacity.
Lateral resistance of drilled footings is primarily developed by passive resistance of the soil against the
side of the footing. Due to the presence of fill and possible shrinkage cracks , the lateral resistance of
the top 4 feet of soils at the surface should be neglected. For the conditions observed, we recommend
that an allowable passive pressure of 1,200 psf be utilized for shafts placed against an undisturbed
vertical face of the in-situ soils. The allowable passive pressure contains a safety factor of about 2.
Floor Slabs
The shallow subsurface soils at this site are generally of low to high plasticity. Based upon Texas
Department ofTransportation (TxDOT) Method TEX-124-E and the information developed from our
field and laboratory programs, we have computed a value for potential vertical rise (PVR) of about two
to two-and-one-half inches for the existing subgrade conditions at the site. Based on our field
exploration, the surficial soils in the proposed building areas are expected to consist of clayey soils.
These soils possess variable strengths and consistency. To provide uniform soil conditions under the
floor slabs, and to reduce the PVR of the sub grade to about one inch or less , we recommend the floor
slabs be supported on a minimum 5-foot thick pad of properly placed and compacted select fill soils.
6
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384 lrerracon
Also, we recomm~nd that the floor slabs be raised above the final exterior grade to provide positiv e
drainage away from the building.
The fill pad should extend horizontally a f!1inimum distance of 3 feet beyond the edge of the foundation .
and be sloped to provide positiv e drainage aw ay from the building. Select fill should be used for all fill
applications in the proposed building area. Material and compaction requirements for select fill soils
are outlined in the "Earthwork" section. In addition , the near-surface subgrade soils should be
prepared as outlined in the "Earthwork" section of this report .
Grade Beams/Tilt-Wall Panels
Grade beams/tilt-walls associated with the drilled-and-underreamed footings should be designed to
span between the footings without subgrade support. Often, a vertical void of about six inches is
provided beneath the grade beams in active clayey soils such as those observed at this site. However,
recent findings indicate that the voids beneath the grade beams often fill with water, providing moisture
to the surrounding sub grade. Therefore, provided that the sub grade is prepared as outlined in the "Floor
Slabs" and "Earthwork" subsections, it is our opinion that the grade beams may be constructed
without a void at this site . However, due to the underlying clayey soils , nominal upward movement of
the grade beams may occur during moisture v ariations of the sub grade .
If construction of voids beneath the grade beams is planned, proper construction of the voids and soil
retainers is very important. If the cardboard carton system is used on this project, we recommend that
the carton form supplier provide, during the initial concrete operations , a representative to instruct the
work force on the proper installation methods for both the forms and the concrete. In addition ,
measures should be implemented to provide proper surface drainage away from the structure to reduce
the potential for water to access the voids .
For tilt-wall panels, it is our experience that the dead load on the tilt-wall panels resulting from the wall
and roofloads is generally large enough to minimize the expansion of the subsurface soil. It is also our
experience that during the placement of the panels and subsequent backfill around the panels that a
void occurs below the panels . This is due to the panels being placed on piers which normally are
7
l
I
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384 lrerracon
slightly above the subgrade. Based on the above discussion, it is our opinion that voids will not be
required under the panels.
Lateral Earth Pressures
The backfill soils adjacent to below grade walls will impose active to at-rest earth pressures against the
wall. The backfill should be compacted to 95 percent of the Standard Effort (ASTM D 698) maximum
dry density at a moisture content within 2 percent of optimum moisture content. Design lateral earth
pressures may be computed using an equivalent fluid weighing 50 pcf for dean sand backfill and 90
pcf for on-site clayey soils or select sandy clay backfill. These pressures do not include hydrostatic
pressures nor do they include surcharge forces imposed by construction or vehicular loading. The
lateral pressure produced by surcharge may be computed as 50 percent of the vertical surcharge
pressure applied as a constant pressure over the full depth of the wall. A 2-foot compacted clay soil
should be placed at the top of sand backfill to reduce the amount of infiltration of surface water.
Foundation Construction
Drilled excavations to a depth of 14 feet below existing grade will be necessary for installation of
drilled and underreamed footings for the new structures at this site. The excavations should be
performed with equipment capable of providing a relatively clean bearing area.
The presence of silty/sandy clays at the. proposed foundation bearing depths at this site may result in
S?me sloughing during pier excavation. Thus, the drilling contractor should have casing available in the
event that sloughing of the soils causes improperly formed shafts. Groundwater was not observed at
this site during drilling of the borings and is not expected to be a major concern for footings bearing at
the recommended depth. However, seepage of groundwater into the excavations is possible, and
seepage from "perched" water trapped in the near-surface soils may also occur, particularly after a
period of wet weather. To reduce the potential for water seepage into the footing excavation and to
minimize disturbance to the bearing area, we recommend that concrete and steel be placed as soon as
possible after footing excavations are completed and in no case should an excavation be left open ·
overnight. The concrete placed in the excavations should have a 6-inch slump with a plus or minus one
8
I
l
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384 ·lrerracon
inch tolerance. The bottom of each shaft excavation should be free of all loose materials and/or water,
and the bearing surface should be evaluated immediately prior to placing concrete.
It is our opinion that the underreams can be successfully constructed with a bell to shaft ratio of 3: 1 as
. described above . However , if underreams are marginally stable due to water seepage and/or the
presence of sandy seams/layers, it may be possible to successfully complete underreamed footings by
performing the sequence of construction without interruption , that is, each footing drilled ,
underreamed, and backfilled with concrete in one continuous operation. The contractor must
coordinate the operation very closely to have concrete on site at the time each footing is drilled and
underreamed so that no shaft or underream is drilled without concrete standing by, ready to be placed .
If extensive bell collapse does occur, straight shaft footings may be installed in lieu of drilled and
underreamed footings in isolated problem areas. If straight shaft footings are planned at this site,
Terracon should be contacted for additional recommendations .
Foundation Construction Monitoring
The performance of the foundation system for the proposed structure will be highly dependent upon the
quality of construction . Thus , we recommend that fill pad compaction and foundation installation be
monitored full time by an experienced Terracon soil technician under the direction of our geotechnical
engineer. During footing installation , the base of footings should be monitored to evaluate the
subgrade. We would be pleased to develop a plan for compaction and foundation installation
monitoring to be incorporated in the overall quality control program.
Earthwork
Construction areas should be stripped of all asphalt pavements , concrete curbs , vegetation, trees,
organics , loose topsoil, and other unsuitable surface materials.
Upon removal of the existing asphalt pavements, utilities and landscaped areas and after excavating so
that final sub grade elevations are achieved, the exposed sub grade should be proof rolled with a 20-ton
roller or equivalent equipment to detect weak zones in the fill subgrade. Weak areas detected during
proofrolling, as well as zones of debris and organics should be removed and replaced with soils
9
I
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384 ·.lrerracon
exhibiting similar classification , moisture content , and density as the adjacent in-situ soils. Subsequent
to proof rolling, and just prior to pl a cement of fill, the exposed subgrade should be moisture
conditioned and compacted to at least 95 percent of the Standard Effort (ASTM D 698) maximum dry
density within 2 percent of the optimum moisture content.
Proper site drainage should be maintained during construction so that ponding of surface runoff does
not occur and cause construction delays and/or inhibit site access .
Grade adjustments within the building areas should be accomplished with select fill composed of
clean , sandy clay (not a silt) with a plasticity index ranging between 10 and 20 percent. All select fill
should be placed on prepared surfaces in lifts not to exceed eight inches loose measure , with
compacted thickness not to exceed six inches. The select fill should be compacted to at least 95 percent
of the Standard Effort (ASTM D 698) maximum dry density at a moisture content within 2 percent of
optimum moisture content.
It should be noted that the near surface silty clays may present difficulties in achiev ing the proper
compaction and moisture for these soils. It may be necessary to improve these soils by one of the
techniques described in the "Wet Weather Considerations" section.
Prior to any backfilling operations, samples of the proposed borrow materials should be obtained for
laboratory moisture-density testing . The tests will pro vide a basis for evaluation of fill compaction by
m.:.place density testing. A qualified soil technician should perform sufficient in-place density tests
during the filling operations to evaluate that proper levels of compaction are being attained .
Wet Weather Considerations
Construction following wet weather periods will likely encounter difficulties due to the wet or soft
surface soils becoming a general hindrance to equipment due to rutting and pumping of the soil surface .
If the sub grade cannot be adequately compacted to minimum densities as described previously, one of
the following measures will be required : 1) removal and replacement with select fill , 2) chemical
treatment of the soil to dry and improve the stability of the sub grade , or 3) drying by natural means if
10
I
I
1
I
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384 lrerracon
the schedule allo w s . In our experience with similar soils in this area, it is our opinion that chemical
treatment is · the most efficient and effective method to increase the supporting value of wet and weak
sub grade . Chemical treatment to a depth of 24 inches or greater may be required for the wet/soft
subgrade areas .
Drainage
It is important that positive drainage be established during construction such that water will not pond
around the building areas during or following the construction period . Furthermore, the building
sub grade should be sealed against water intrusion along trenches and conduits created for utility access
·under the building.
The upper portion of utility excavations should be backfilled with properly compacted clayey soils to
minimi ze infiltration of surface water. A clay "plug" should be provided in the trench on the exterior of
the building to prev ent water from gaining access along the trench to the subgrade beneath the
structure.
All gr ades must be adjusted to provide positiv e drainage away from the structure . Where pav ing or
flatwork abuts the structure , care should be taken that the joint is properly sealed and maintained.
Roof drains should discharge on pavement or be extended away from the structure. Ideally, roof drains
'•
should discharge to storm sewers by closed pipe.
GENERAL COMMENTS
Terracon should be retained to review the final design plans and specifications so comments can be
made regarding interpretation and implementation of our geotechnical recommendations in the design
and specifications. Terracon also should be retained to provide testing and observation during
excav ation, grading, foundation and construction phases of the project.
The analysis and recommendations presented in this report are based upon the data obtained from the
borings performed at the indicated locations and from other information discussed in this report . This
11
I
I
1
David Cottrell Investments
c/o Heights Venture Architects
Terracon Project No. 92055-384 lrerracon
report does not reflect variations that may occur between borings , across the site , or due to the
modifying effects of weather. The nature and extent of such variations may not become evident until
during or after construction. If variations appear, we should be immediately notified so that further
evaluation arid supplemental recommendations can be prov ided.
The scope of services for this project does not include either specifically or by ,implication any
environmental or biological (e.g., mold , fungi , and bacteria) assessment of the site or identification or
·· prevention of pollutants , hazardous materials or conditions . If the owner is concerned about the
potenti al for such contamination or pollution , other studies should be undertaken .
This report has been prepared for the exclusive use of our client for specific application ·to the project
discussed and has been prepared in accordance with generally accepted geotechnical engineering
practices. No warranties, either express or implied, are intended or made. Site safety, excav ation
support , and de w atering requirements are the responsibility of others. In the event that changes in the
nature , design, or location of the project as outlined in this report are planned , the conclusions and
recommendations contained in this report shall not be considered v alid unless Terracon reviews the
changes and either verifies or modifies the conclusions of this report in writing.
12
' .
I
j
I
lrerracon
Consu l ti ng Eng ineers & Scientists .
APPENDIX
I
1
I
I
l
\
•B-3
0 50 100
Scale in Feet
LEGEND
SOIL
• BORING
LOCATION
~:i-di !i'-
~:i? ~--3 ~d.
lrerracon
TERRACON PROJECT NO : 92055-384
(.!) z i5 _J I " ::::!~ ::>o " CD._ i:i~ !:ii
::::!U..: l~i 8~5 ...: . ti V1 !•! C>:O 0 J e
(.!)<Xl
~g·
V1 x w
PLAN OF BORINGS
Shopping Plaza Addition
Texas Ave. and FM 2818
College Station, Texas
A-1
LOG OF BORING
PROJECT: College Station Shopping Plaz a Additions BORING NO . 8-1 FM 2818 & Texas Avenue PROJECT NO . 92055-384 College Station , Texas DATE 7-12-05
CLIENT: Heights Venture Architects SURFACE ELEVATION Existing grade
Houston , Texas
PAGE 1 of 1
FIELD DATA LABORATORY DATA DRILLING METHOD(S ):
ATTERBERG Dry Augered 0 to 20 fee t.
~ LIMITS %l ~ L w GROUNDWATER INFORMATION : ~ >< w 0:: ~ z w > ~ ::::> Borehole was dry during drilling and on completion. lU a w L (/) 0 ~ ~ ~ U5 (/) _J z ~ ~ z w -CD~ ~ 0 ~ ~ ~ 0 w ~ 0:: ~ _J 1-8u..1-m (.) ~ u., ::; 0 55 :i: E a. 0 0 ::; (3 N I=' -::::> (.) ~ (.'.) (/) CD ~:::ozu lU (/) (.) a i== i== ci (/) !:!:. :::? (/) (/) (/) (/) lU 0:: 0:: ~ en (/) ~ 0 z-5 (/) (/) z w (.'.) (/) w -(/) >-w $:~ii5uw ::::> za J: (/) _J 0 z 0:: a. ~ a~ 0 5 5 (/) 0:: z -0:: -z ~ _J a. ffi~~~ci (/) ::; a. a. ::::> a. lU (/) ::::> u., ::::> a. :::? >-::::> :::? 0:: z _J w 6 <( z:;=a.:a::g 6 0:: 0 z o~O ~ zo
:::? LL PL Pl ~ 0 a. DESCRIPTION OF STRATUM a (/) (/) a a. (.) (/) t::. u., (.) ~
PAVING: 2" Asphalt, 3" Crushed Asphalt and 8"
2-~ p 1.5 .R::ise M::it ~ri::i l
/ FILL: stiff dark g:rav CLAY
I--v Stiff to hard gray and tan CLAY P=l.5 31 69 23 46
4-,..
-li ght gray and tan 4 to 8 feet -P=4.5
5>--
-... P=4.5 30 50 24 26
81--i...
I--\ill~ Hard brown Silty CLAY ~~ P=4.5 23 98 5.7 4 0
10 -,.. ; -~"'
;"'
;
12 -; -1i1"' Iii Iii I NS ~
14 -i...lil
\illlil
19 -
16 -:: i;
i;
Iii;
\ill
18 I--flp ~45 I--i;lil -dark gray below 18 feet
,___ \illlil
20 \ill
I--Boring terminated at 20 feet.
22 --
24 --
26
._;,_
>---
"' 12
28-
m -;:::
....,
"!l. 30-(.'.)
..j N -STANDARD PENETRATION TEST RESISTANCE REMARKS : "' "' "' T -TXDOT CONE PENET RATION RESISTANCE
11Br1acan "' 0
P -POCKET PENETROMETER RESISTANCE N m
u R-PERCENTAGE OF ROCK CORE RECOVERY
al RQD -RO CK QUALITY DESIGNATION J:
A-?
!
l
LOG OF BORING
PROJECT: College Station Shopping Plaza Additions
FM 2818 & Texas Avenue BORING NO .
PROJECT NO.
B-2
92055-384 College Station, Texas
CLIENT: Heights Venture Architects
Houston , Texas
DATE
SURFACE ELEVATION
7-12-05
Existing grade
PAGE 1 of 1
FIELD DATA LABORATORY DATA DRILLING METHOD(S):
t='
\!:.
:i::
l-a._
UJ
Cl
21-~
I-" t" ..J
N t-
4--..\
I~ t'°
-..\
t"
61-..J
IV t-
-..\ I-IV t-
..J
s"-"'t"
I-v
10,__
-12-~
P=3.0
P=4.5
P=4.0
P=4.5
P=4 .5
!----+-----(~~ ::~F:<l
1-rl
1-
221-~.
18 =~~P =4 .5
20
31
36
30
31
I->-LL. !:: :::i en u z-UJ en Cl~ >-:::i ex: 0 Cl a._
91
30 82
ATIERBERG
LIMITS %l
LL PL Pl
87 33 54
UJ ex:
·~ ~ z en ~ ~ g ex: a._ 0
I-<!l en en ~ Vi
UJ z Cl
Dry Augered 0 to 25 feet.
GROUNDWATER INFORMATION :
Borehole was dry during drilling and on completion .
g; ii: 3
~ z 0 1----------------------'--'-I
u.. 8 e:. DESCRIPTION OF STRATUM
4.1 3 . 0
4.3 6 0
EA VIN G : 1. 5 fl Asphalt, 3 fl Crushed Asphalt and 8"
K"""' Material r
FILL: very stiff to hard dark gray to gray and tan
CLAY with cemented sand
Hard brown CLAY
-dark gray to gray below 18 feet
I-'/
24==~~P_=_4._5-4----l-~--l-~-l--+---jf---l---+~+-~f--~-~-~~-~-~--=--~~-~~~---;
26 1-Boring terminated at 25 feet.
...,
& 301-
REMARKS : ~ N -STANDARD PENETRATION TEST RESISTANCE
.,., T -TXDOT CONE PENETRATION RESISTANCE ~ P -POCKET PENETROMETER RESISTANCE
c::; R -PERCENTAGE OF ROCK CORE RECOVERY 11i!r1acan
~L_~R~Q~D~-~R~O~C~K~Q~U~A~Ll~T.!...!::!YD~E~Sl~G~N~AT~l~O~N~~~~~...L.~~~~~~~-~~~~~~~~....L.~~~~~~-:-~
A-3
....,
LOG OF BORING
PROJECT: College Station Shopping Plaza Additions
FM 2818 & Texas Avenue
College Station, Texas
CLIENT: Heights Venture Architects
Houston , Texas
I='
!:::,.
FIELD DATA LABORATORY DATA
ATTERBERG
LIMITS %)
>< w
0
I-~ .......... ~ >->-LL ~ ::; I-
!:: ::::> ::; (..) u
U) (..) 0 i== i== aJVi 5 U) ';) o~ o ::S ...J ::; a.. a.. rt 6 '-=-4---==--l--=-<
BORING NO .
PROJECT NO .
DATE
SURFACE ELEVATION
DRILLING METHOD(S ):
Dry Augered 0 to 25 feet.
. B-3
92055-384
7-12-05
Existing grade
PAGE 1 of 1
GROUNDWATER INFORMATION :
Borehole was dry during drilling and on completion .
:r:
l-a.. w
0 o a.. LL PL Pl DESCRIPTION OF STRATUM
----+-+----+--1----+--~--+---4--+---'-~A VIN G: 1.5'' Asphalt, 4 11 Crushed Asphalt and 4 11
1----1.-
4
\j .K~c;:p M~teri::ll r
2"-:I'" P =4 .5 FILL: firm to hard dark gray to gray Silty CLAY
,__ ...i -with slightly cemented sand pockets 2 to 4 feet 1---1---r" I'" P=3.0 36 47 22 25 -.l
4,__f...I \'"
-.l ,__IV I'"
1---+---1...i P=4. 0 2 5
5-tv ~
.___"-+---I -.l
i--1\J I'"
1----+--1 ...i P=4.5 21
8>-~I'"
>-~I'"
1----+---1N I'" P =2 .0 23
10,__ -.l
l'I l'"I ,__...i .....
12-~
,__~
1 4=~P=4 .5
16>-~
>-t/. "=&.~4 .5 33
20,__~
22,__~
99
36 18 18
104
84
1.9 15 0 -with cemented clay pockets 4 to 6 feet
0 .8 6 0 -sandy 8 to 10 feet
Hard brown CLAY
-with ferrous nodules 13 to 15 feet
4.8 4 0
,__'l
,__/111 -gray below 23 feet 24,__~~P-=-4-.5--!--1---1---!---1-+--+--+---l--+-------------:---------t
26 >-Boring terminated at 25 feet.
~a-::3~0L_,__..L.__L--1... ______ ..L.___J_-=...._j_~.J__~_,.,,,L,,---l....,,----l--L.._....L... ____________ .--______ __,
;;i; N -STANDARD PENETRATION TEST RESISTANCE ~ T-TXDOT CONE PENETRATION RESISTANCE REMARKS :
~ P -POCKET PENETROMETER RESISTANCE
u R -PERCENTAGE OF ROCK CORE RECOVERY llenacan ,
~L_~R~Q~DL-~R~O~C~K~Q~U~A~L~ITwY~D~E~S~IG~N~A~T~IO~N!.:!..... __ ~~__JL.-~~~~~~~~~~~~~~~~~1--~~~~~~-:--:
A-4
I
I
LOG OF BORING
PROJECT: College Station Shopping Plaza Additions
FM 2818 & Texas Avenue ·
CLIENT:
College Station , Texas
Heights Venture Architects
Houston, Texas
FIELD DATA LABORATORY DATA
•f='
'==-
J:
t-
Cl. w a
---!V-..i \
IV t-2----....).
1--=+---i.,...,, t-
--l
1----+---N, v t-
~ -..i
4 t-
"' ~\ill
.____.____, '
6---;
-----" l.,j
-
22-
24-
26-
281--~ l--=.:+----1
i--
;::~-1---1
P=2.75
P=3 .5
P=3 .0
P=4.5
P=4.5
25
26
t-i:: Li,
-:l (/) u r5 U; a~
>-:l a:: 0 a Cl.
24 97
ATTERBERG
LIMITS %\
LL PL Pl
46 22 24
v
"' M
"' "' a
N -STANDARD PENETRATION TEST RESISTANCE
T-TXDOT CONE PENETRATION RESISTANCE
N en P -POCKET PENETROMETER RESISTANCE
u R -PERCENTAGE OF ROCK CORE RECOVERY
5.6 4 0
REMARKS :
BORING NO .
PROJECT NO .
DATE
SURFACE ELEVATION
DRILLING METHOD(S):
Dry Augered O to 20 feet
B-4
92055-384
7-12-05
Exist ing grade
PAGE 1 of 1
GROUNDWATER INFORMATION :
Borehole was dry during drilling and on completion .
DESCRIPTION OF STRATUM
FILL: very stiff dark gray to gray Silty CLAY with
asphalt, base material ana sand pockets
Very stiff to hard light gray and tan Silty CLAY
Hard brown and tan CLAY
-dark gray below 13 feet
Boring terminated at 20 feet.
11Br1aam
~L.__~R~Q~D~-~R~O~C~K~Q~U~A~L~IT~Y~D~E~S~IG~N~A~T~IO~N!:!._~~~~~L......~~~~~~~~~~~~~~~~__JL--~~~~~~"'."""":
A-E
LOG OF BORING
PROJECT: Colle g e S ta tion Shopping Plaza Addit ions BORING NO . B-5 FM 28H~ & Texas Avenue PROJECT NO . 92055-384 College Station, Texas DAT E 7-12-05
C LIE NT: Heights Venture Architects SUR FA CE ELEVATION Existing grade
Houston , Texas
PAGE 1 of 1
FIELD DATA LABORATORY DATA DRILLING METHOD(S):
AITERBERG Dry Augered 0 to 20 feet.
~ LI MITS %1 ~ UJ GROUNDWATER INFORMATION : 1-->< UJ a:: Cf) UJ
Borehole was dry durin g drill ing and on comp letion . ~ z a > c :::i UJ UJ Cf) 0 1--1--~ Vi Cf) -' z 1--:E z UJ ~ co 1--1--0 1--:E ~ 0 UJ ~ a:: ~ -' 1-:Su. z u ~ l.L :::; 0 ;:::: r::: a.. a 0 -:::i :::; u N r:::-co \0:::::: a 'Z ~ UJ u U) :c l.L 1--<.:> U) U) u a j:: j:: 0 U) !::. ::? U) CflCflCflwa:: a:: z-ui r-a z en >-w ~~cn(.)W :::i UJ U) s U) U) z UJ 0 U) ~· za :c U) _J o za::c.. 1--a~ a ~ ~ U) a:: z --z 1---' a.. -' (.) 0 w .. U) :::; a.. a.. :::i a.. w U) :::i l.L :::i a.. 6 ::? co z 1--a.. 0 6 >-:::i z ::? a:: z -' ZO w <>: z ~a.: Ii~ a:: 0 0 1--g < 0 a.. 0 U) U) ::? 0 a.. LL PL Pl :E (.) U) l.L u~ DESCRIPTION OF STRATUM
,t AVING: 1." Asphalt, 2" Crushed Asphalt and 5" f p~i.u 22 .::i<:f' M :>i t f'ri::i l 2,__ -.i
FILL: firm to stiff dark to li ght gray and tan CLAY ~I \"
-.i
-with cemented clay at 2 feet ,__ N i"
-.i P=2 .0
4-N i"
-v Very stiff to hard gray and tan CLAY P=4.5 26 50 25 25
6-
~ -
P=4 .5 24 98 5.6 5 0 8,___
-
II" P=4 .5 24 96 3.3 8 0
10 -
-~ 12
'i
14
,___ ~P-45 -with ferro us nodul es and sandy clay seams 13
to 15 feet ,__
16
,__ ~ -
18
,____ ~ ,____ ~P-45 -dark gray below 18 feet
20
,__
-B oring terminated at 20 feet.
22 -
,____
24 -
,__
26-
-
"' 28-
~ ,__
;::: ..,
0.. 30 ,___ ~ ..; N -STANDARD PENETRATION TEST RESISTANCE REMARKS : "' (')
"' T-TXDOT CONE PENETRATION RESISTANCE 11i!nace11 "' 0
P -POCKET PENETROMETER RESISTANCE "' "' u R -PERCENTAGE OF ROCK CORE RECOVERY
m ROD -ROCK QUALITY DESIGNATION J:
A -6
I
l
"' ~
;:::
-.
0..
(!)
..;
CX)
"' "' "' 0
N m
u a:> :x:
LOG OF BORING
PROJECT: College Station Shopping Plaza Additions BORING NO. B-6 FM 2 8 18 & Texas Avenue PROJECT NO. 92055-384 College Station , Texas DATE 7-12-05
CLIENT: Heights Venture Architects SURFACE ELEVATION Existing grade
Houst on , Texas ·
PAGE 1 of 1
FIELD DATA LABORATORY DATA DRILLING METHOD(S ):
ATTERBERG Dry Augered 0 to 20 fee t.
~ LIMITS %\ ~ w GROUNDWATER INFORMATION : f-x w ct: en z w > ~ :::i Borehole was dry during drilling and on comp letion . ~ w 0 LU en 0 f-f-~ U5 en -' z f-~ z w ~
al f-f-0 f-~ ~ 0 w ~ ct:~ -' ~ LL :::; 0 ~ :i: E a.. 0 0 ti: 8LL f-m u :::; u · "' I=' al w -:::i u f-'-' (/) -::::Ozu (/) u 0 f= f= ci (/) ~ :E en rnrnrn wa: ct: z -(/) f-0 ~ Ui >-w ~!j:!iiiuw :::i w (/) 5 (/) en z w '-' (/) w· zo :i: (/) -' o z a:a.. . f-0 ~ 0 ~ ~ (/) ct: z -ct: -z f--' a.. _,uow ·· en :::; c.. a.. :::i c.. w (/) :::i LL :::l a.. 6 :::;;! alZf-c..O 6 >-:::i z :::;;! ct: z -' ZO w ci: z;::: a.: ci :i1 ct: 0 0 f-0 <i: 0 c.. 0 (/) en :::;;! 0 c.. LL PL Pl ~ u (/) t: LL u~ DESCRIPTION OF STRATUM -,P AV ING · 0 S" A-:nh::ilt ::inrl 4" R ~"" M::itP.ri::il -NI / ;,,i P=3.5 FILL : very stiff dark gray CLAY 2-tvt-;,,i -NI" -dark gray and tan below 2 feet ;,,i P=3 .0 30 62 3 1 31
4-IV t-
;,,i -v Hard gray to light gra~ and tan CLAY P=4.5 37 -with ferrous nodu es 4 to 6 feet 6-,. -P=4.5
8--
~ P=4 .5 29 88 78 3 1 47 4.4 7 0
10 -
-~ 12 --[/
14 -~""45 32
I--
16 -/ -~ 18 ~""45 -gray below 18 feet
20 --Boring terminated at 20 feet.
22 --
24 I--
-
26-
I--
281--
1--
30-
N -STANDARD PENETRATION TEST RES ISTANCE REMARKS : ' T -TXDOT CONE PENETRATION RESISTANCE 11i!r12can P -POCK ET PENETROMETER RES ISTANCE
R -PERCENTAGE OF ROCK CORE RECOVERY
ROD -ROCK QUALITY DESIGNATION
A-7
I·
KEY TO SOIL CLASSIFICATIONS AND SYMBOLS
~CLAY
[I]] SILT
[I] SAND
~GRAVEL
~ SILTY
CLAY
SOIL TYPES
vr;rn CLAYEY t:11Jl SILT
~
~
CLAYEY
SAND
CLAYEY
GRAVEL
SANDY
CLAY
SANDY
SILT
SILTY
SAND
SILTY
GRAVEL
CONSISTENCY OF COHESIVE SOILS
Penetration
Resistance
(blows per foot)
0-2
2-4
4-8
8 -15
15 -30
>30
Consistency
Very Soft
Soft
Firm
Stiff
Very Stiff
Hard
Undrained
Compressive
Strength (tsf)
·O -0 .25
0 .25 ~ 0.5
0 .5 -1 .0
1 .0 -2 .0
2 .0 -4 .0
> 4 .0
FILL
MATERIAL
ASPHALT
CONCRETE
BASE
MATERIAL
PLASTICITY OF
COHESIVE SOILS
RELATIVE DENSITY OF
COHESIONLESS SOILS
Plas ticity
Index
0-5
5 -10
10 -20
20 -40
> 40
Degree of
Plasticity
Very Low
Low
Moderate
High
Very High
Penetration
Resistance
(blows per foot)
0-4
4 -10
10 -30
·30 -50
> 50
TERMS CHARACTERIZING SOIL STRUCTURE
Relative
Density
Very Loose
Loose
Med ium Dense
Dense
Very Dense
Slickensided -having inclined planes of weakness that are slick and glossy in appearance
Fissured -containing shrinkage cracks , freq uent ly filled wit h fine sand or silt ; usually more or less vertical
lnterbedded -composed of alternate layers of different so il ty pes
Laminated -composed of thin layers of varying color and text ure
Calcareous -containing appreciable quantities of calcium carbonate
SAMPLER TYPES
I
Shelby Tube Standard Penetration Test
(SPT)
Texas Cone
Terracon
[I]
Auger Sample
A-8
. .
HEIG~TS
VJHIUR[
August 30 , 2005
City of College Station -Site Development
1101 Texas Avenue , P 2 2 ??SP
College Station, Texas 77842
RE: Response to Staff Review Comments# 1 dated June 27, 2005 and
Response to Staff Review Comments # 2 dated July 25, 2005
Please review the itemized comments below as they are numbered to correspond to Staff
Review comments.
Staff Review Comments 1 -response
PIAing
/1. The attached drawings should comprise a complete submittal (3rd review).
2. The adjacent drives are noted on Al.O. Distances are not shown because we are not
/requesting any new drives (other than the Texas Ave location) at this time.
v3 . Throat distance of 55'-0" has been met as well as the 250 ' separation distance , RE:
Al.O. Please submit thru TX-DOT for approval , (preliminary discussions with Terry
..,,{ Paholek -TX-DOT Engineer indicated no problem for approval of this drive).
~-There are no pad sites or pad buildings to be developed under this permit.
5. All impro vements shown on the attached drawings should meet current standards ,
including, but not limited to: curbing, landscape islands , end islands , dumpsters ,
drives , etc.
/((_ 7. The outdoor storage for the existing "Tractor Supply" and the proposed "We-Rent-
It" have been modified to , new 8 ' -0 " high wood fencing , honor setbacks, sized
below maximum allowable area, and factored into the parking calculation. RE:
~ Al.O & A5.4
8. Roof equipment have been screened for the building addition by a parapet wall , with
added fenc ing at the existing mechanical equipment behind the grocer. The note for
screening roof and ground-mounted equipment has been added to Al.O for any
equipment still visible on the roof of the existing structure. My field v isit indicated
/ that no additional screening is needed per the requirements.
9. Curb return radii for the proposed curb cut is shown on Al.O . The existing drive
/ radii are also shown on Al.O.
v'I 0 . Parking is entirely located on site and should meet the current standards . RE: Al.O.
11 . The entire site is one buildin lot.
2 . Parking dimensions have been shown on the site plan . RE: Al.0.
vY3 -Curb and pavement details and descriptions are shown on the attached civil
drawin gs. RE: C2 & C3.
/14. Dumpster dimensions have been increased as per current standards and enclosed
w ith painted split face emu walls with painted wood picket gate s, RE: Al.0 & A5.4.
Aug ust 30-res po nse sheet.doc
Page I of4
OAllAS
15851 Dallas Par kwa y
Suite 1060
Add ison, Tex as 7500 1
972.490.7 292 v
972. 49 0.7 444 F
11 11 tlo rth Loop \'/est
Su ile 800
Hous ton , Tex as 77008
713.869 .1103 v
713 .8695573 F
. .
HllG~TS
/ V.rnIUR~
vl5. Existing building lease lines are indicated on Al.O. The building addition is entirely
leased by the proposed "We-Rent-It " tenant.
16. For fire lane and hydrant locations , RE: C3 & CS.
17 . Building elevations with material notes are in the drawings. RE: A2.0 and the
~ attached material sample board for ease of cross-referencing.
18. Two bicycle racks have been shown on the site plan for a total of 12 available bikes
/each to be no greater than 150 ' from a building entry . RE: Al.O.
v1J Building setback lines has been corrected, RE: Al.O.
v19. For revised parking calculations, RE: Al.O.
vi I. Existing topography is best seen on the existing survey, RE: E-S. Proposed
topography is best seen on the attached grading plan, RE: C4. vn . FIRM numbers are shown on the existing survey E-S and the ALO.
. 23. Easements and utilities are on the civil drawings ,
.....-2 4 The current zoning is - , : . . ~ The overall height of the buildings is indicated on Al.O , greater detail is shown on
A2.0, A4.1 and A4.2
V 26. Signs are not a part of this permit, and will J;i e permitted separately by the Owners
Sign Vendor. RE: Al.O. AM Na f(
Landscape I Streetscaping I Buffer
1. Landscape plans we not ready at this time , but will be submitted by Friday, Sept 2,
by Bob Ruth -Landscape Architect.
Engineering
1. The property should not require replatting because there are no pad sites or other
ownership changes.
2. After site plan approval , but prior to development approval , easement
documentation , replat if necessary, and cost estimates will be submitted by the
Survey Engineer.
3. After site plan approval, but prior to development approval , the TX-DOT application
with associated drawings will be submitted by the Civil Engineer. ~There are no new connections or increased flow to the existing storm sewer system ,
RE: CS.
5. The development permit and supporting documents are attached.
6. A fire flow report can be provided if still neccessary .
Electrical
1.-10 . RE: Civil and electrical drawings.
DAU.AS
1585 1 Dalla s Par kway
Su ite 1060
Add ison , Texas 75001
97 2.4 90.7292 v
~OT 972.490.744 4 F
1.-2 . Throat distance of 55 '-0 " has been met as well as the 250 ' separation distance , H Ou$roN
RE: Al.O . Please submit thru TX-DOT for approval , (preliminary discussions with 1m Horth Loo p \'/est
Terry Paholek -TX-DOT Engineer indicated no problem for approval of this drive). Su ii e soo
Hous ton, Tex as 77008
Aug ust 30-respo nse sheet.doc
Page 2 of 4
713 .869. TI 03 V
713 .869.5573 F
.. '
Miscellaneous
1. For irrigation information, RE: Landscape drawings.
2. For backflow preventers , RE: plumbing drawings.
Staff Review Comments 2 -response
Planning
1. Hopefully , not too much additional material will be required to be submitted . Please
elaborate as clearly as possible so we may submit the correct information in a timely
manner.
2 . There are no pad sites or pad buildings to be developed under this permit.
3. The drive-thru and previously identified pad sites are no longer part of this permit
request. Future development of this area will be permitted, as required , and new L calculations will be submitted.
4. Parking spaces have been corrected, RE: Al.O .
. -. The application and fee for the Administrative a JUS ment is attached. Parking end
. ~ k islands are all a minimum of 180 s.f. (with the exception of 2 end rows being only
n . j-0.: c;.._\(}'1'-rµ 175 ~.f.). The parking setback of 1 O' along frontage property lines has been
~A fi \ 1) provided. RE: Al.O.
\Q){W v(O. Painted directional arrows have been added throughout the site to help with traffic
,, circulation identification. RE: Al.O.
v1'1. Curb return radii for the proposed curb cut is shown on Al.O . The existing drive
,,,/ radii are also shown on Al.O.
/!2. There are no pad sites or pad buildings to be developed under this permit.
13. Curb and pavement details and descriptions are shown on the attached civil
drawings . RE: C2 & C3. ~.-16. Dumpster dimensions have been increased as per current standards and enclosed
with painted split face emu walls with painted wood picket gates, RE: Al.O &
AS.4.
~.-For fire lane and hydrant locations , RE: C3 & CS.
18. Building elevations with material notes are in the drawings. RE: A2.0 and the
attached material sample board for ease of cross-referencing.
\,J-9 . Existing topography is best seen on the existing survey, RE: E-S. Proposed
topography is best seen on the attached grading plan , RE: C4.
~O . Refer to the As-Built Survey, Sheet E-S for all adjacent property information.
~The adjacent drives are noted on Al.O. Distances are not shown because we are not
requesting any new drives (other than the Texas Ave location) at this time .
--2i Throat distance of 55 '-0 " has been met as well as the 250 ' separation distance , RE:
Al.O . Please submit thru TX-DOT for approval , (preliminary discussions with Terry
/ Paholek-TX-DOT Engineer indicated no problem for approval of this drive).
V 23.-24. Easements and utilities are on the civil drawings , RE: CS.
August 30-res pon se sheet.doc
Page 3 of4
OALlAS
15851 Oollos Parkway
Suite 1060
Addison, Texas 75001
972. 490-7292 v
972.49 0.7 444 F
HOUS"fON
1111 tl orih l oop \'l est
Sui le 800
Housto n, Texas 77008
7138YIJ103 V
713.869.5573 F
--. ..
HEIGMTS
J~HIUR~
25. After site plan approval , but prior to development approval , the TX-DOT application
with associated drawings will be submitted by the Civil Engineer.
27. The overall height of the buildings is indicated on Al.O , greater detail is shown on
A2.0, A4.1 and A4.2
28. Roof equipment have been screened for the building addition by a parapet wall , with
added fencing at the existing mechanical equipment behind the grocer. The note for
screening roof and ground-mounted equipment has been added to Al.O for any
equipment still visible on the roof of the existing structure. My field visit indicated
that no additional screening is needed per the requirements .
29. The access drive has been provided for future cross access between properties . The
term eas ement is intentionally not used because that would require special recording.
If necessary, an agreement between owners can be generated.
30. Signs are not a part of this permit, and will be permitted separately by the Owners
Sign Vendor. RE: Al.O.
31. RE: reply to comment 1 of Staff Review Comments 2.
direct 281-854-6106
cell 713 299-4520
e-mail michael.kravetz@hva.cc
A ug ust 30-re s ponse sheet.doc
Page 4 of 4
DAU.AS
15851 Oollcts Par kway
Suite 1060
Add ison , Texas 75001
972.490 .7292 v
972.4 CJ0 .7 44 4 F
HOUS'fON
1111 Nort h Lo op l'l est
Sui te 800
Ho uston, Tex as 77008
713 869 .TIOJ V
713.869.5573 F