HomeMy WebLinkAbout27 Development Permit 316 Ponderosa Place II F2 F3. ' ·. SITE DRAINAGE REPORT PONDEROSA PLACE, SECTION TWO TRACTS "F-2" AND "F-3" JUNE 27, 1995 PREPARED FOR : Rock Pra irie , LTD . PREPARED BY : M .L. Hammons, P .E . 1700 Kyle South , Suite 240 College Station , TX 77840 ( 409)696-1444 .. PROJECT DESCRIPTION Construction of retail facilities, including an auto oil & lube service, a dry cleaning servic e and a self-serve car wash . The proposed facility is to be situated in Tract "F" of the Ponderosa Place Subdivis ion , Section Two and is located in the northwest quadrant of the intersection of Rock Pra irie Road and State Highway 6 , also identified as Texas Avenue South (See Appendix #1 , "Area Map"). Proposed improvements will occupy ·tracts "F-2" and "F-3". The development is to be a common driveway/common parking retail trade area among the three separate businesses and in conjunction with the Exxon facil it y located on the adjacent tract "F-4". The facilities proposed in this project will include buildings with combined "footprint" are as of approximately 4,600 square feet. Stormwater detention facilities are presently located on tract "F-2" to provide stormwater run-off control requirements for tracts "F-1", "F-2", "F-3" and "F-4". This proposal includes modification of the detention facility , but the drainage control function will be continuously operative during the modification . STORMWATER CONTROL The development site (tracts "F-2" and "F-3"), addressed herein , is an in tegral part of the storm drainage system that was designed and implemented in 1993 by Victoria Bank and Trust. There is no proposal, herein, to change or modify the watershed run -off patt e rn s or to change the degree of run-off attenuation or the discharge routing . Th i s propos al provides strict adherence to the original drainage plan , even though the stormwater drainage and detention facilities will be modified to enlarge the land area available for retail facilities development. Changes to accomplish land area usage improvements are to be accomplished by : 1. Deeper detention pond (5 .0' vs 3.0') 2. Vertical concrete pond walls -vs -sloped earth walls The original plan, as followed herein, was prepared and submitted by B.J . Kling. A partial reproduction of the report is included herein as Attachment I. Further, the plan was updated in February, 1995 to include the Exxon development of tract "F-4". A p artial reproduction of the updated report is included herein as Attachment 11. According to Attachment I, page 2 , first paragraph , "the detention pond has been designed to attenuate enough peak run-off for the full development of the site , incl ud ing the two tracts to be sold at a later time ." Since the land to be used in this development 1 . ; . I ' '' is a part of the "tracts to be sold at a later time", no additional stormwater ma na ge m K .t facilities are required . Therefore , the objective of th is report is to show adhe rence t o the conditions of the original analysis , thus maintain ing the performan c e inte grit y of the system as it was originally designed and approved . Essential factors for adherence include : 1. Acceptance and discharge of sto r mw~ter run -off fro m adja ce nt t ra cts. 2 . Proper drainage routing (direct d ischarge -vs -detention ) fro m tr acts "F -2" and "F-3". 3 . Detention volume capacity of at least 17 , 9 3 8 ft ( 100 year sto r m ev ent). 4. Discharge outflows to closely match the original sto r m ev en t de si g n . DRAINAGE AREAS Neither this development site , nor any of the upstream drainage areas are w it h i n the 100 year flood plain . (See Appendix #2 , "FIRM flood p lain map"). As reported in the tract "F-4" update , a small portion of the "F-4" tract (E xxo n ) d rai n s directly to tract "F-3" (this site). As shown by grading plan (See App en d ix #3 , "G rad in g Plan") all incoming surface flow will flow i nto the detention pond . Also , all tract "F-1" (Victoria Bank & Trust) stormwater run -off, w ith det en t io n pond destination, flows onto the paved access easement along the west side of t ra ct s "F -4 ", "F-3" and "F-2" as originally planned . As provided by this development pla n , All of t h at inflow then flows into the detention pond via surface flow or via the proposed un d erg ro u '.1d collection and transfer system . Therefore , acceptance and r un -off from ad j a cen t tr act s is not modified and is in compliance with the original plan . All Rock Prairie, Ltd. site generated stormwater run-off eithe r flows d i rectly t o t h e street (or paved private access) or into the detention pond (See Appendix #4 , "S ite r un -off flow plan"). As the plan shows , a 0 .176 acre perimeter area drains directly to street flow an d the 0 .908 acre mid section of the site drains to the detention pond. Therefore , d r ai n a ge from tracts "F-2" and "F-3" a re properly included in the dete nt ion po nd colle cti o n sy stem and comply with the original storm drainage plan . As shown by the grad ing plan , (Append ix #3) a detention pond is to be c o nst r u ct ed on tract "F-2". The original drainage plan in cludes a detention pond on this t r a c t , b ut is larger in area . According to Attachment I, page 3 , 1st pa ragraph , the orig i nal p o nd provides volumes of 14 , 131 ft 3 for the 2 5 year storm and 17 , 9 38 ft 3 for th e 100 year 2 storm. This proposal is to increase the depth and reduce the surface area of th e pond while maintaining or exceeding the originally planned storage volumes . The de pth a nd surface areas of the redesigned pond are tabulated thus: ELEVATION AREA 301.8 0 302.0 2150 sf 302 .3 3680 sf 303.0 3800 sf 304 .0 4170 sf 305.0 4580 sf 306 .0 5430 sf 306 .3 5780 sf 306 .8 6330 sf VOLUME 0 140 ft 3 940 ft 3 3550 ft 3 7530 ft3 11 , 910 ft 3 16, 910 ft 3 18,590 ft 3 21 ,620 ft 3 (Discharge i nvert) (100 year volume ) (Ultimate volume ) Therefore, originally planned detention volume requirements have been met . Detention pond discharge is presently controlled by a discharge structure located as shown by Appendix #3 and as detailed by Append ix #5 (Detention disc harge str uct u r2) Discharge structure modifications to accomplish a deeper storage facility in clude : 1. Raising the overflow level from 306.0 to 306.3 , by extending the top of the concrete structure with brick and epoxy grout mix . 2 . Lowering the f low control orifice from elevation 303 .0 to 301 .8 . The size a nd/or shape of the orifice will be adjusted to prov ide flows properly metered (according to original plan) at the 10 , 25 and 100 year storm eve nts . Discharge flows as shown by Attachment I, page 3, (and the target flows fo r redesi gn) are : 25 year ..... . 100 year .... . 4 .00 cfs 4 .82 cfs Flow control integrity will thereby be attained . DRAINAGE VOLUME In order to remain in full compliance with the original stormwater control pl an , the actual run-off for each contributing area must not exceed the originally calcu lated run -off . Since the area and the intensity of the rainfall event used in the Rational Method of cal cul ati o n is identical, the only variable is the C-factor . The o riginal run -off calc u lations w ere b as ed on a "C-factor of 0 .78". (See Appendix #6 , "C -factor Confir mation") 3 '. The composite "C-factor" for tracts "F-2" and "F -3" is 0 .777 ; thus in full compliance . C factor has been calculated thus : CONCLUSIONS Impervious Areas C = 0 .90 Buildings Paving Walkways Etc. Other Areas C = 0 .35 Landscaping Lawn Run-off area F2DA - 1 Run-off area F2DA - 2 5 ,310 sf@ 0.90 2 ,335 sf@ 0 .35 31 ,313 sf@ 0 .90 8 ,262 sf@ 0 .35 47 ,220 sf@ C = 0 .777 Since tracts "F-2" and "F-3" have been included in the original ordinance comliant stor m drainage plan for the tracts that were then (1993) Victoria Bank and Trust land , prope r storm drainage for tracts "F-2" and "F-3" must comply with the design perameters of the originally designed and approved plan . All drainage inflows from adjacent tracts , an d all site generated drainage flows have been accommodated . Detention storage vo lume s have been maintained or exceeded and all metered discharge rates have been maintained. Accordingly, as provided in the original plan , "no impact is expect ed to downstream landowners from this development". 4 CERTIFICATION I hereby certify that this drainage analysis and the fac ilities des ign result ing the refro m was prepared by me (or under my supervision) and that the plan has been devised for compliance with the City of College Station Drainage Policy and Design Stand ard s and for adherence to the original V ictoria Bank and Trust area dra inage plan of Septem ber 1993. M . L. Hammons Registered Professional Eng ineer State of Texas #25308 5 .. , ,,. '· ,. APPENDICES #1 Area Map #2 FIRM Flood Plain Map (Copy) #3 Site Grading Plan #4 Site Run-Off Flow Pattern Sketch #5 Detention Discharge Structure Drawing #6 C-Factor Confirmation ATTACHMENTS Original Victoria Bank and Trust Drainage Analysis and Plan (Copy) II 1995 Updated Plan (Copy) VICINITY MAP I Z f--D Ck'.~ D --i Z I NTS 1 If" I I I i 3 / A Bra zos Co unt y U nin c orp o ra t ed Areas 4 8 1195 ZONE X ~ . /) · / Ci t y of Co ll ege St ati o n 4 800 83 C0 C it y of College Station 480083 ·. \ ON WATER LINE AND DEPTH J VERIF IED ~· / / Ji 1 I I I I ·~1 ~ N j ! / . . d . J.. .d , -l , .. --.. .d GRATE INLET-NEENAH R-1879-A9G OR EQUAL Ei CIRCULAR OPE NIN G IN FA CE OF BOX FL IN ELEY 303 .00 --_ 14 ·--.. --4 . --·-t· .. TOP ELEY .306.00 #3 REINFORCING 8.A.~S AT l 5° O.C.8.W., 7 CLEAR 15" RCP @ 0. 757. D£T£/\ITJON POND OlJTLD WORKS DETAJL NOT TO SCALE A ppi:::: N 0 I x $ 5 ---,--------r--1 310 • 06 /19 /95 18:05 '0'409 846 8252 KLHiG EN GR KLING ENGINEERING & SURVEYING TELECOPIER COVER SHEET (Ef:faxcover) Please deliver the following pages to: Name: J<~ \k""'~'-o&- Firm: _______________________ _ Fax Number: ~Cl_o -~S \ From:----...S~~~-1~ .......... ~~~T ________ _ Kling Engineering & Surveying 4103 South Texas Ave .• Suite 212 Bryan, Texas 77902 Phone: (4091846-6212 Fax: (4091846 -8252 We are transmitting page(s), including this cover letter from our fax number listed above. If any pages are missing or incomplete, please contact sender. Regarding: ~a..-''cl\ ~ t..WRJ ~..\----l~"-'>-U b-.O-lQ [41001 O"'\ ~Le~ t= -~ -Q.St-\-\ A.t_fu.' · .~f\h ~~O~I\ ~"lr, ~@-\~:a <,C-81\~i"'"' ~~~~[1,.J)m~,\: ']) /\ \ _.,_ .1-·l5>1-~~ l~ tD~\.t'1 ~Let ui. \--\ \ ·~ UcDk~~ 'f-1.. D·~L\:}~ ~T~~ o.<4l kr °'"'& \J'd-Q..~ ~ Co~l?~o~ ,, C \ 7-. Q ,!'( l ~ • 1. I I I I I I I I I I I il I , I .I I I Drainage Report for Victoria Bank and Trust -College Station Branch Robert Stevenson Survey, A-54 College Station, Brazos County, Texas September 8, 1993 GENERAL LOCATION & DESCRIPTION The proposed site location is Tract F of Ponderosa Place, Section Two, 3.81 Acres, which is located at the intersection of Rock Prairie Road and State Highway No. 6 . The tract is bounded by Tract A and Tract E of the beforementioned subdivision to the north, the frontage road for Highway 6 to the east, Rock Prairie Road to the south and Longmire Drive to the west. The tract is currently vacant and is covered entirely by grass. Proposed improvements consist of subdividing the tract into three separate tracts, the largest of which will consist of an approximately 5700 square foot bank with 65 parking spaces and a 9 lane drive-thru facility. The remaining two tracts are to be developed after being sold and platted at a later date. DRAINAGE BASINS & SUB-BASINS Two primary studies have been performed on Carter's Creek and its tributaries. The first is a study performed by the Federal Emergency Management Agency in July, 1992, titled Flood Insurance Study -Brazos County. Texas and Incorporated Areas. The purpose of this report was to investigate the existence and severity of flood hazards for Brazos County and to aid in the administration of the National Flood Insurance Act of 1968 and the Flood Disaster Protection Act of 1973. The second study is the Stormwater Management Plan. Phase III, performed by Walton and Associates -Consulting Engineers, Inc. contracted with the City of College Station in 1987. The purpose of this study was to gain knowledge of the existing and future drainage conditions in the City and to identify flood problems and flood prone areas. The site is located on a ridge line dividing the Bee Creek drainage basin, Lick Creek drainage basin and the Foxfire Tributary to Carter's Creek drainage basin. The site itself mostly drains into the Foxfire Tributary's basin, thus the tributary is the primary drainageway. Secondary drainageways include a series of culverts and open ditches along Highway 6 until the flow reaches the tributary. (See Appendix 1: "General Location Map"). The site is not within the 100 year flood plain according to the Flood Insurance Rate Map for College Station, Texas. (See Appendix 2: "Flood Plain Map"). Almost all offsite runoff is intercepted by the curb and gutter systems along Longmire and Rock Prairie Road which leads into two curb inlets that discharge into the right-of-way of Highway 6. The runoff then proceeds down an open ditch until it reaches Lick Creek. Runoff from Tract A drains over the 5 foot retaining wall and down the property line, more or less, into the curb and gutter parking lot and drives of Tract F. From here, runoff enters the frontage road and proceeds into an open ditch and ultimately into the Foxfire Tributary. Victoria Bank and Trust -Drainage Report Page 2 DRAINAGE DESIGN CRITERIA/FACILITY DESIGN Because of the increase in peak runoff expected from this development detention will be provided for development of the entire site . That is, the detention pond has been designed to attenuate enough peak runoff for the full development of the site, including the two tracts to be sold at a later time. The pond will be located at the north corner of the tract and will discharge into the right-of-way of Highway 6. Currently runoff drains onto the frontage road as sheet flow. After development, it will become concentrated flow, therefore, the pond outlet will be discharged across the frontage road through a 15" R.C.P culvert to be constructed. Due to topography and the flowline elevation of the curb inlet at the Rock Prairie Road intersection, the existing storm sewer system cannot be utilized . The design storm used is the 25 year event, though the 10 year and 100 year storms were investigated. The Rational Method was used to calculate peak runoffs and the Modified Rational Method was used to estimate detention storage volume requirements. A runoff coefficient of 0 .35 was used for pre-development conditions ·while a runoff coefficient of 0.90 was used for post-development impervious areas and 0 .50 for post-development landscaped areas. This yielded a pre-development peak runoff of Q25 = 13.18 cfs and a post-development peak runoff of Q25 = 29 .38 cfs and thus a required attenuation of 16.20 cfs. Because of topography, Reserve Tract "A" will not be required to drain into the detention pond. All i nflow into the pond will be from the bank's tract and Reserve Tract "B". Therefore, the tract can be divided into two drainage areas: Drainage Area #1 is captured by the detention pond and Drainage Area #2 bypasses the pond. DA #1 contributes Qi 5 = 20.15 cfs and DA #2 contributes Q25 = 9.23 cfs . (See Appendix 3: "Drainage Area Maps"). This requires the 16 .20 cfs attenuation be taken from DA #1 and thus the maximum outflow of the pond to be 3 .95 cfs. Most drainage will be sheet flow, curb and gutter, and open channel flow, although one portion of the drive and parking lot will be storm sewered with three grate inlets and a 15" R.C.P. The parking lot will have two curb breaks located at the south end of the tract with 6: 1 side sloped swales leading to a main interceptor channel. The 15" storm sewer will daylight near the middle of this channel while the drive-thru lanes will drain to a curb break with a 6: 1 side sloped swale leading to the north end of the channel. The interceptor channel itself will have 6: 1 side slopes , 0. 98 % channel slope, maximum water depth of 1. 0 ft, and a velocity of 3.6 fps. The interceptor channel then leads into the detention pond, which will have a maximum volume of approximately 23,000 ft3 and varies in elevation 303.0 to 306 .5 . The outlet works will be an 8" orifice in a concrete box with the orifice flow line at elevation 303.0 and a grate inlet at the top of the box with an elevation of 306.0. The box then leads to a 15" R .C.P. on a 0. 75 % grade that will be bored beneath the frontage road and daylight in an area between the southbound exit ramp and the turnaround exit ramp for Highway 6 . The turnaround exit ramp currently has an 18" R.C.P. culvert beneath it and has sufficient capacity for the pond's discharge. The ditch section between the proposed 15" and existing 18" pipe will require regrading with a minimum slope of 0.8 % . It is anticipated that at such time as the frontage road is converted to one-way traffic, the turnaround exit ramp will be removed and the ditch section can then be i mproved to obtain more positive drainage. ! i. i I f I t I I I I .I ·I. Victoria Bank and Trust -Drainage Report Page 3 This design provides for a water surface elevation in the pond of 305. 78, peak outflow of 4.00 c f s, and a storage volume of 14,131 ft3 for the 25 year storm. The 100 year storm will have a water surface elevation of 306.10, peak outflow of 4.82 cfs , and a storage volume of 17,938 ft3 . .. CONCLUSIONS Peak runoff after development increases by 16.2 cfs for the 25 year event and 19.12 cfs for the 100 year event. The Detention Pond will bring post-development, 25 year peak runoffs down to their pre-development conditions and will bring post-development, 100 year peak runoffs down from 34 .68 cfs to 15. 71 cfs, an increase of 0.15 cfs from pre-development conditions. Since the site currently drains into the Highway 6 right-of-way and ultimately into the same ditch section that the detention pond discharges into, and peak runoffs have been attenuated , no impact is expected to downstream landowners from this development. "I hereby certify that this report (plan) for the drainage design of Victoria Bank & Trust - College Station Branch was prepared by me (or under my supervision) in accordance with the provisions of the City of College Station Drainage Policy and Design Standards for the owners thereof." - I I I . I I I V1 '-f o rt <A L >'"'" L ·~ in-'--· A r-ec... ... ? I rt/l AcrO:> ~10-.. 8.~3 71,., Q -= J l . i?Y c 1 ~ 10 f _, /. o.c.? ~ 15. J)b d-::. , Vo>+-yp,,,efop~ 11: >.ct7..Ac.- ~,o = B.b:> ~l(K),; /I, b ~ Q,0 -=-t6.'7l J-s Oz.:;-: z.q, "'Jct; r Q,Ct? ~ 3~ • b~ ~r~ £/(;v ~ 3o t/ 305" '50b so 7 30& 3()0 ~ 0 1 0 5 '21 ~r; '-1 2.:-I S f:7V)J0 LJ3J( Cul f e..· :.-{""v:: ,·crv 1 [ • A ~ I. 'LO ~7... Q,o~l\o .... "" '3,'i/ Qz.;; ::;. 3,c,5 O.o-= )1, ~"{ Qis1 Z0.15 C:,(() = '2.3 .'7°l Q,0-;. 0.0 7 Qi>~ <1,'2..'3 QIOC>-;. ) 01'0~ I. ! ' DRAINAGE REPORT FOR EXXON EXPRESS HWY 6 & ROCK PRAIRIE ROAD Rqbert Stevenson Survey, A-54 College Station, Texas February 22, 1995 DEVELOPED BY: Exxon Express -Hwy 6 c/o Ray Hansen 730 N. Rosemary Bryan, TX 77802 ( 409) 846-7861 PREPARED BY: Kling Engineering & Surveying 4103 Texas Avenue, Suite 212 Bryan, TX 77802 (409) 846-6212 Drainage Report for Exxon Express -Hwy 6 & Rock Prairie Road Robert Stevenson Survey, A-54 College Station, Brazos County, TeJ1,as February 20, 1995 GENERAL LOCATION & DESCRIPTION The proposed site location is Tract "F-4", Resubdivision of Ponderosa Place, Section Two, "Tract F", (hereafter referred to as Tract "F-4 ") located at the intersection of Rock Prairie Road and State Highway No. 6. The tract is bounded by Tract "F-3" of the beforementioned subdivision to the northwest , the frontage road for Highway 6 to the northeast, Rock Prairie Road to the southeast and Tract "F-1" of the beforementioned subdivision to the southwest (See Appendix 3: "Resubdivision plat of Ponderosa Place Section II Tract F). The tract is currently vacant and is covered entirely by grass. Proposed improvements consist of constructing a 3869 square foot Exxon Express Convenience Store, 8 covered gas pumping islands, 38 parking spaces, and installing 2 -12,000 gallon and 1 -8000 gallon underground storage tanks. DRAINAGE BASINS & SUB-BASINS Two primary studies have been performed on Carter's Creek and its tributaries . The first is a study performed by the Federal Emergency Management Agency in July, 1992, titled Eloo.d Insurance Study -Brazos County, Texas and Incorporated Areas. The purpose of this report was to investigate the existence and severity of flood hazards for Brazos County and to aid in the administration of the National Flood Insurance Act of 1968 and the Flood Disaster Protection Act of 1973 . The second study is the Stormwater Management Plan, Phase III, performed by Walton and Associates -Consulting Engineers, Inc. contracted with the City of College Station in 1987. The purpose of this study was to gain knowledge of the existing and future drainage conditions in the City and to identify flood problems and flood prone areas . The subject tract was formerly a portion of the 3.81 acre Tract "F" of Ponderosa Place Section Two (hereafter referred to .as Tract "F"), which has since been subdivided into Tracts Fl, / F2, F3, & F4. A drainage analysis was performed and a drainage report prepared for Tract "F" V in regards to the construction of the Victoria Bank & Trust, College Station Branch which is now built and situated on Tract "F-1". The Tract "F" study provided a detention pond that was designed to attenuate enough peak runoff for the full development of Tract F (see Victoria Bank & Trust Drainage Report Dated September 13 , 1993). Subsequently, runoff for the resubdivision Tracts F-1, F-2, F-3 & F-4 has been attenuated as well. Therefore, no detention is needed for Tract F-4. ' ' ' I I I I I I I I I I I I I. I. I Exxon Express -Hwy 6 & Rock Prairie Road Drainage Report Page 2 .. -. -. ............. · .. ;..; .... ~11.J The site is located on a ridge line dividing the Bee Creek drainage basin, Lick Creek drainage basin and the Foxfire Tributary to Carter's Creek drainage basin. The site itself mostly drains into the Foxfire Tributary's basin , thus the tributary · is the primary drainageway . Secondary drainageways include a series of culverts and open ditches along Highway 6 until the flow reaches the Foxfire Tributary. (See Appendix 1: "General Location Map"). The site is not within the 100 year flood plain according to the Flood Insurance Rate Map for College Station, Texas. (See Appendix 2: "Flood Plain Map"). Almost all off-site runoff is intercepted by two fackties. The first being the curb and ·gutter system along Rock Prairie Road which leads into two curb inlets that discharge into the right-of-way of Highway 6, runoff then proceeds down an open ditch until it reaches Lick Creek. The second is an open ditch that runs parallel to the east line of Tract "F-1" and discharges into the detention pond on Tract "F-2" which is metered out into the Highway 6 right-of-way and proceeds to the Foxfire Tributary. Currently, the majority of the runoff from the subject tract sheet flows into the gutters along Highway 6 frontage road, proceeds to an open ditch, and then ultimately into the Foxfire Tributary. A portion of the tract sheet flows into the curb and gutter systems along Rock Prairie Road, then follows the discharge pattern that flows into Lick Creek as mentioned earlier (See Appendix 5: "Hydrologic Calculations -Rational Method). ·DRAINAGE DESIGN CRITERIA/FACILITY DESIGN Because of the detention requirements for Tract "F" have been met, no detention for Tract "F-4" is required. In the previous study performed by Kling Engineering, Tract "F" was divided into Drainage Area #1 and Drainage Area #2. DA #1 is captured by the detention pond and DA lfl, which contains Tract "F-4", bypasses the pond . (Reference Appendix 3 of the Victoria Bank & Trust Drainage Report Dated September 13 , 1993). To show that the detention requirements for Tract "F" have been met, the design storm for the 25 year return period will be used, even though the 10 year and 100 year storm were also investigated . The Rational Method was used to calculate peak runoff. A runoff coefficient of 0.35 was used for pre-development conditions while a runoff coefficient of 0.90 was used for post-development and impervious areas and 0.35 for post-development landscaped areas. This yielded a pre-development runoff of Q25 = 13.18 cfs. The detention pond outlet peak flow is 4.00 cfs for the 25 year storm, leaving 13.18 cfs -4.00 cfs = 9.18 cfs of allowable direct runoff from the site. The development site for Tract "F-4" can be divided into five drainage areas: Drainage Area #1 flows into the detention pond while Drainage Area lfl, #3, #4, and #5 contribute to direct runoff (See Appendix 4: "Drainage Area Map"). The collective runoff of DA #2, DA #3, DA #4, and DA #5 for the 25 year storm is 6.31 cfs which is substantially less than the 9.18 cfs allowable. Therefore, the detention requirements are in compliance with city ordinances . The results for all the storm events are tabulated below: I ' ' Ill • • • • '. • • Exxon Express -Hwy 6 & Rock Prairie Road Drainage Report Page 3 Storm return period 10 25 100 Pre-Dev. Q Tract F (cfs) 11.54 / 13 .18 ./ 15.56 / Det Pond outfl<ry (cfs) 3.84 4.00 / 4.82 / Allowable direct runoff 7.70 / 9.18 10.74 / Post-Dev Tract 11 F-4 11 (cfs) (sum~ #2 ... DA #4) 5.53. 6.31 / 7.44 / Most drainage will be sheet flow, curb and gutter, and open channel flow. The site will have three concrete flumes, two of which discharge at the right-of-way of Highway 6 and one that discharges into the .gutter of Rock Prairie Road . DA #1 has a Q 25 of 3.64 cfs that discharges through the proposed driveway into the detention pond. DA #2 has a Q25 of 2.13 cfs that discharges through the proposed Highway 6 entrance into the Highway 6 frontage road curb and gutter system and ultimately into the Foxfire Tributary. DA #3 has a Q25 of 1.29 cfs that discharges through a concrete flume onto Highway 6 frontage and ultimately into the Foxfire Tributary. DA #4 has a Q25 of 2.38 cfs that discharges through a concrete flume into the curb and gutter system on Rock Prairie Road and ultimately into Lick Creek. DA #5 has a Q25 of 0.51 cfs that discharges through a concrete flume onto the Highway 6 frontage road and ultimately into the Foxfire Tributary . CONCLUSIONS A detention pond for Tract 11 F 11 of Ponderosa Place Sectio Two has been designed to attenuate runoff for the full development of the tract. Tract 11 F-4" Resubdivisio f Ponderosa Place Section Two is a subsidiary of Tract 11 F 11 mentioned above. The sum of the peak out w of the detention pond and the direct runoff from Tract 11 F-4 11 is substantially less than the pre-developed runoff for Tract 11 F 11 • Therefore detention is not required for Tract 11 F-4 II and no impact to upstream or downstream landowners is expected. 11 1 hereby certify that this report (plan) for the drainage design of Exxon Express -Hwy 6 & Rock Prairie Road was prepared by me (or under my supervision) in accordance with the provisions of the City of College Station Drainage Policy and Design Standards for the owners thereof. 11 I I I I B i I .. II II Ill , • I Exxon Express -Hwy 6 & Rock Prairi e Road Drainage Report Page 4 REFERENCES Stormwater Management Plan, Phase Il: Drainage Policy and Design Standards, City of College Station , Ordinance No. 1728 , prepared by : Walton & Associates , October, 1987 . Stormwater Management Plan, Phase III: Drainage System Analysis, City of College Station , prepared by: Walton & Associates, August , 1986 . APPENDICES 1) 2) 3) 4) 5) General Location Map Flood Plain Map -Commun ity No. 480083, Panel No. 0182 Effective Date : July 2 , 1992 Resubdivision Plat of Ponderosa Place Section II, Tract F Drainage Area Map I Grading Plan -Prepared by Kling Engineering & Surveying Hydrologic Calculations -Rational Method • lr.cs95-0lb :\exxon .rpt II J ............-: ..-e: ' . s 60". •Stf' w .. 21~.52 . ~ . 11,,_7''1.? . tinUTY fAS£M£NT --..,-_.,...,,..,.., Arr.rlT-...., .. ti 6 45.}B VOL 1 ~-4 'PC. 217 _mo~ Of 28 ' TRAC: '. T . ~-·,,,. F-2'" . --.: I ACCESS ESl.IT . . . ' t" •• ::· . 0 .543. ACRES. DETENTION F AGILITY ., ;.--: . _:-:.. .. , F~ 1"· :RES · ·- ., . ..... -:"' ' ·. '\: . - ; ~· ' . . ··~. iRIE . ROAD rv 80'• R. 0. W. .-· . .-, .. , < '', ...... · Ct./RVE. . DEL TA •. ··' ... ·.··:_,;,, ........ ., •. -_:1·_6~46'!8." · .. :;;_::.'jp:/":~· -· .•-.; _·,:~:7·;~i . so·oo ·od'. · RADIUS 599.26 «2 5 .00 . I .. I t: '··I 8 ·l ~-::~ -.. ' . . J ,.._ .. l .. -~· !;:·.· •I ; "· i /2" 1 ~~f'No "-'(; u:; N'-fT22 ;!. 2.J:ss · 1 /'t' t.R.. ·ffiD . ' ·,_ ~-f.. ,. ... ~- :~ . _·:: ·25.00 ~ .. ~>~::" ... . ·:-· . . . . .. ~ (/) (/) WW a: a: :3 :3 a: 00~ • (/) (/) _J <Ill LO U:: I I I I (/) (/) (/) ·1-1-1- IWWW IWWW :III I (/) (/) (/) :888 ..-f".\IN I I I ) <O ,... ,... )(')(')(') l ~ C\I .... ) y 9 9 ) <? (") <? I ~ I .... w -~ u l r I I I ;J,-,,r, :;.. {!'. '/! :tv ( ir::i ,. , 1. 1 r d , X ___ o_z.._.;' _"'_3_. &,_il-_c._~_J _)( a,o. , C,-::.o .ro ;4q:.. C .e>ifac ),.,..!'~ ['./?,,-.'-, c; .. c .3:."(o.o +) + o.cio(c.13) -o. o.77 0 .17 c D • 7 ;, ') { ~ I 1...) +-D . 9 C ( 0 . 'l. 't l D . ""'·· '/· C.71 !/. -c .c '> """r - 0 . V5 ( C . 1.' -z.. ) -+ D 9 C> ( 0 · 0 S ) c., '.:-·-----.. -· . --c . 7.j. O c ] Q 10 -=-5. 5?.; c ~s <..:. A !loc..Vc.....b I e.. Gz,-:..{o.)f cH .C:: Allcw .... lol~ Oi c<>:.. {.y4 cf'S < A llow4 Lie (!,_I'= o .'J o '>j? frJ • ~ 0 I -f"u m'.:Y/I''./ 1J,.hf/ Ho y1 ''7r (_s-_f_J _"l_s_'5_1_""' -~0_(/_) { rf 'N f I · ·"0 l I I II _-I I/ _J J f./d