Re: Autumn Chase Villas Drainage Addendum
Dear Alan,
05-bS
.:;;-JU-05
J'.d-0
fa~
May 16, 2005
The intent of this letter is to detail changes to the proposed drainage infrastructure
described in the Autumn Chase Villas Drainage Analysis, submitted by Mitchell & Morgan,
LLP to the City of College Station in December 2004. While none of the Cornell Street
infrastructure will be modified, the proposed layout for the Autumn Chase Villas has
changed since the last report was submitted, resulting in the need for updated drainage
design .
The new layout includes the subdividing of Lot 6, Block 2 into several smaller lots. This site
design also includes the construction of Autumn Chase Loop, which will serve as the access
route to all the lots in this portion of the Autumn Chase Subdivision. The new layout can
be seen in Exhibit( of the attached sheets . The proposed drainage system will continue to
discharge into the existing detention pond located at the east corner of the property,
adjacent to Cornell Street. The drainage design was analyzed in XP-Storm 9 .1.4 just as the
December 2004 report was.
While the configuration of the Autumn Chase subdivision has changes, the relative amount
of impervious cover has not changed significantly. Only a slight variation exists in the
postdevelopment flow into the pond between the old and new design, leaving the
conditions in the pond and downstream of the Autumn Chase subdivision largely the same,
with a slight increase upward for the new layout. The new drainage infrastructure consists
of approximately 50 LF of 30" RCP and 308 LF of 18" RCP as detailed in Exhibit C of this
addendum. Modeling of the system indicates that these pipes provide adequate
conveyance into the detention pond. In addition, the capacity of the proposed 4" rollover
curb was analyzed to determine street capacity . This was done using Manning's equation
as opposed to the gutter equations in the College Station Drainage Policy and Design
Standards (DPDS) because these equations are based on a 6" curb and Manning's was
more conservative. These calculations have been provided as Exhibit D.
The plan and profile sheet provided as Exhibit C indicates a small stub out located along on
of the interior property lines . This stub out will serve the future development of the
property by providing access to the drainage system . The property was analyzed at
estimated full development levels and as such, some drainage assumptions were made to
account for all of the flow into the detention pond. An updated drainage area map has
been provided as Exhibit B of the report. The current site configuration has only two inlets
on it ; one 5' recessed inlet at the southwest corner of the property and on 1 O' recessed
511 UNIVERSITY DRIVE EAST, SUITE 20 4 • COLLEGE STATION, TX 77840 • T 979 .260 .6 963 • F 979 .260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan .co m
inlet at the southeast corner of the property, adjacent to the detention pond . Flow from
the north end of the property will be conveyed in the streets and within the Right-of-Way
for the 100-year event. The project will continue to meet the drainage objectives of the
College Station DPDS .
If you have any questions or comments, please feel free to contact either Veronica Morgan
or myself at 260-6963 .
Sincerely,
~~ ~ty--
Terry M . Barr, E.l.T, C.F .M
Graduate Engineer
Cc: File
Dan Bensimon, Owner
"O
~
c
0
~
"S a.
E wo ..... (.) ..... (/) co -.....
,..._ Q)
C') Q)
0) .~
. Cl
0 c zw
,J:J VTUf'1 ty CH PJ ~ £
!tOD.ICN CU
& ::.. 'CAPIKJT'( CCF-S_)
2.~ fe.l:CIPf/!!.t>C>Jl, O/; CRC)SS SU '£
,., ~ "'(~J..ir-JJ>V6'S ~ovt;,J.fNES!S
.S • Lt:JN~ 1rLJDI "/!¥-.s 1-i>PIC;
0 :_ IYC.PTf-{ ( FT)
A ~£PTJ...f
,if DUTJ-/
vA-f?.'rtrlG
OF /j-::.t:J."&75 F( FOR. A lo-'r£.A-~ tNEA/T A"/IJ
o~ /);:;.. fJ.SO FT Fote A 100-rEl't'< £\IEJ.IT ,+!../{.)
t-0NI;,ITV_Ol"4~'--..$LOP6$ ~
(). '1
D.7,
tJ.C/F
I· ?..8
() l!Pn( () .::. IJ . '37 5 FT
( ((7 -}cAiC-_)
c-("CP-S
C,,C"f
". 58
7-lo/ 'l
H.ES
DEPTlf !J -=:. () •• S-D D
l {00 -)"IE~)
PAC (t:-.e'S)
13. 03
/~. zo
lb. 12.
1'6 ."'/S
TH!.O~ i~UE.s IU.PUS EJ.,J'f' o~~ S.tD€ o,:::-A c ~vi,.../"/ £.-i::> .s £C...-77oAJ
/J; D. ~75 i:r
A= ; . 11 .rct F-T
_/( s-9.1s7 r;r
()~ o.So !=T
A " -3. 93 S&FT
R=().~781=T
bt.PrJi D= 0. :175 F=T
C 10-Y€AR.)
0-6"/
IJ. 7(,
o .~e
/, 2~
'-/. I:;_
-'-{ • L.f 't
5. 05
5. 'i.3
Cc.
~ c.-CAPACrry (CPS)
n =-'1A~N1._J &o.s ~V61-/r-J c:ss
A-=: c~-.S.€CTioNitL-A~.A G r-)
R__ .;;. HYD'1!f:t-Ul-fc., leA--~'V.S c FT)
.S -= LON~ITU~l"'Al-.Sl,...of»Jt.,
(J~PTl-f fJ;; P.6 -o D
([90 -'(£.A~
t1. o~
/'<.. 0 g
13 ,-57
/'5.l:,1
Cr~
Carol Cotter
City of College Station
Planning & Development Serv ices
P.O. Box 9960
College Station, TX 77842
MITCHELL
MM
MORGAN
Re : Autumn Chase (FP) # 05-00500085
Dear Caro l,
June17,2005
We have reviewed and answered your commen t s. Please fi nd attached w ith this letter:
• Two (2) sets of rev ised construction drawin gs
• Fire Flow report
y u have any quest ions or comments, please feel free to contact us . Thank you.
Cc: File
Dan Be nsimon
511 UNIVERSITY DRIVE EAST, SUITE 204 • COLLEGE STAT ION, TX 77840 • T 979 .260.6963 • F 979 .2 60.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan.com
Carol Cotter
COCS-Development Services
P .O . Box 9960
College Station, TX 77840
MITCHELL
M M
MORGAN
R e : Autumn Ch ase (FP) -05-00500085
Dear Carol ,
June 20 , 2005
The following are our res ponses to the City 's comments for the Final Plat for Autumn Chase.
Planning/Engineering;:
Comment: Provide Grading Plan.
Answer : Contour lines have been shown around ROW 's and min FF's have been added
to the plans . These contour lines have been calculated based upon the attached
hand calculations, which were submitted, on 5116105 to Alan Gibbs with the
Autumn Chase Villas Drainage A dd endum. As you can see these are depth
calculations for the 100-year storm for each of the street grades . Since we are
using a 4" curb we calculated the allowable "Q" in the gutter with the 4" height
as well as the 6" height. Below is a chart showing the drainage area, Q 100 ,
street grade and capacity with 4" curb and 6" ROW depth. As y ou can see that
the Q l 00 is kept within the ROW if it is graded 6" above the gutter line . The
contours at ROW shown on sheet Ol are 6" above the gutter.
Ata: 1 (!lflfJ Srnu:r Srut:Tt Stuu:r
PAJ 8.2 CFS
PA2 1.39 CFS
PA3 1.96 CFS
PA4 3.3 CFS
PAS 2 .77 CFS
PA6 5 .29 CFS
PA7 4 .24
PA8 1.63 CFS
PAJO 1.44 CFS
PAll 3.45 CFS+ 1 CFS
(driveway)
PA12 .34 CFS
PA13 1.5 CFS
PA14 2 . 75 CFS-1 CFS
(driveway offsite)
<tu w1: c II' I C/IT If ! c II' I C/IT
1.28%
Off site
.78%
Gate NIA
.78%
.98%
.98%, .64%
Gate NIA
Off site
.78%
Off site
Off site
Off site
./ '' Cl IW If I/ II 6"
/)U'/ 11
5 .83 15 .67
NIA NIA
4.49 12 .08
NIA NIA
4.49 12.08
5 .05 13 .57
4 .12 11.09
NIA NIA
NIA NIA
4.49 12 .08
NIA NIA
NIA NIA
NIA NIA
511 UNIVERSITY DRIVE EAST, SUITE 204 • COLLEGE STATION, TX 77840 • T 979.260.6963 • F 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@m1tchellandmorgan.com • www.m1tchellandmorgan.com
Comment:
Answer :
Comment:
Answer:
Comment:
Answer:
Comment:
Answer:
Comment:
Answer :
Comment:
Answer:
Comment:
Answer:
Comment:
Answer :
Comment:
Answer:
Re-title Sheet 08 to Erosion Control Plan
Sheet has been re-titled.
Minimum separation between water line crossing under a sewer line is 1 foot
between sewer line and encasement pipe .
We believe we have a foot separation at these locations. If there is still a
question please let us know what water line and station where there is a
question .
Provide construction documents for 3-inch water mains to meter banks .
Plan and profiles of all 3-inch lines have been added.
Use actual flow data from existing area hydrants in the fire flow analysis
Please see attached letter.
Show tie-in of 4" lay down curb to ground to insure that depth of water in street
stays within ROW.
See answer to the first comment.
Is an eyebrow needed on the northwest curve of Autumn Chase Loop ? Justify .
No, please see attached turning radius sketch.
What are you proposing for traffic safety/circulation at the southeast
intersection? Striping? Stop signs?
We are not proposing any striping or stop signs here as the City on past projects
indicated to us that they want to handle that aspect of the project. (i .e . on
Kenny Cotton project we were required to remove our striping/signing plan for
Dartmouth).
Revise construction documents to reflect staff review comments returned on
plats regarding water and sewer lines .
The water line has been extended to the property to the west as requested .
Move HC ramp to intersection.
The ramps have been moved .
k you for your cooperation on this project. Please let us know if you have any questions.
Cc: Dan Bensimon
File
"O
&.
c:
0
~
":]
c.
E wo ,... (.)
(). ''I
D. l,.
fJ.'il'
/.. ~8
"* UTU~ ,Y CH r, ~ £
It DD~ "I DIJ
C,,C"f
" . 5"-4
7-1-1 s.. r.~
_m,_;:.. r ~~ CCJ""S_)
z.~ fel:.Cl~C~ ~/;-CR()S:S SU>
h c /'-f lr~~IJ:lfi;.S R..OV-.J.fNES!S.
.s • LDN' 1Tf)()l 1'/_"-.$.1..J)P~.
I;)·;_ IYC.PTI-{ ( FT)
()EPnf () .:::. tJ .,S-o T:>
l(DO-°)"E~)
C I (t!/:-5)
13. 03
l"f, zo
/p.a ..
Ii. "IS
iHf/Sf;,, ., ~u ES 'l't.E..PU5 E/i.I( °"I.~ Stf?.€ OF A c /e..t)&-.,/"/ E../::l .$ £C,77c>J
.. ·IJ.;StN.,.. N4A/'JIN5S A>i.b ~ 4 'tJ17'£./l. ~£.C[IPN WIT;./ A./ If /ftDL40Vli·-1'-C\I
o .6"( /). 7"
o. 'IS
/, Z!
iJ ~ D. '$75 ~r
A c ~ • 11 .sea r-r
IC~ 9. 1$'7 FT
~.:. fJ.So JCT
A c: J. 93 SCAFT
R:: (}.~7g l=T
~EPTH lJ= D. ~75 FT
C to-Y~R.)
4 . l:J..
-'1 . "t.,
~. OS
5. 41..3
~ c.-C1Jff¥rrr (CFS)
r) =-"1A:~1'} I ~ r,§ IU>~t/.t-1-~4
,Jr = e~ -.S.E:<=Ti oN"rL--A~.A G
I( .=. H'(l>~U/-fC.. ~A-01.U,S c FT)
S = /...O~ITVf>.INAl-.;sJ..,ortt.,.
/J~PTlf /J = P.6 'Q O
([tJO -'(£A~
'' · o~
/':l... 0 g
13, .S7
1'5 ~"1
(
R186 .5 '
R73 .5'
I
I
I ,
--
~ L i 4' SIDEWALK
\ ll
\ I -----------.OBl \~I
~I
I
0
I
I I
I I
I I
I I
I I
---------...-=..
180" -------
4 ' SIDEWALK l
AUTUMN CHASE LOO P :06--
I
I
I
I
I
I I
I b\ I ~
I \
11 \
-
4' SID EWALK
S:\Proj\04 58-Autumn -Chase-V ill as-N EW\0458-<:urves-justification.dwg, 06/1712005 04:42 :16 PM, 1:50
j
.I
11
I
J
I
I
I
f
' l
Ii
1/
1
Scal e :
1 i nch ,.,._._ 50 feet
\ R 155' 5 ' SIDEWALK l
;r·~'-~--~--=-=-=-=·-=~U=T=~=-~=~=C=H=AS=E=L=O=O=;
ill # R20.5 ' r~/::=--------------
"' c
0 ·.;;
·;;; .,
0::
November, 200•
Designed by: JJM
Drawn By : JUJ,CC
Checked By : VJBM
II
T.9 79 .260.6963
F.9 79 .260 .:1 564
)II l..eM:t511YOMIC [AST ...... '°' k:oucc;( SlATOt. TJI 77"
~--... ~· °""~·~ ...-..-. ............ Rl!Uft
-~ .........
-ti) -~ 0 -...J
<( -...J
0::: S:
~ lw
ti)
u ~ :::> (_)
0:::
I-<
w ~
0::: 2
LL ~
~
Of 1 Sheets
Carol Cotter
City of College Station
Planning & Development
PO Box 9960
College Station, TX 77840
MITCHELL
MM
MORGAN
RE: Fire Hydrant Test for Autumn Chase Subdivision
Dear Carol :
June 7, 2005
In December 2004 a hydrant test was run for the Autumn Chase Subdivision per your comments
on a November submittal. At that time we completed a MikeNET analysis to compare the City of
College Station water model to actual hydrant flow data . We believe that we relayed the results to
you verbally, but we do not have any written correspondence for this comment.
Please see the table below for a comparison between the results of the MikeNET analysis and the
hydrant flow data . For your convenience I have attached the flow test report to this letter .
Method Static Residual Demand
Flow Test 99.0 si 96 .0 si
Mike NET 100 .1 psi 91.3 psi
Based on the above results, we believe that the MikeNET model is a good approximation for real
flow conditions. If you have any further comments or questions please feel free to contact me .
Sin~~
Rebecca A. Riggs , EIT
Graduate Engineer
cc. file
Attachment: Hydrant Flow Test
S:\Proj\0458-Autumn -Chase-Vi llas-NE'Mdocs\0458-hydrant-test-0506 07.doc
511 UNIVERSITY DRI VE EAST. SUITE 204 • COLLEGE STATIO N. TX 77840 • T 979 260 .6963 • F 979 .260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDR OLOGY • UTILITIE S • STREETS • SITE PLANS • SUBDIVISIONS
info@m itchellan d morgan .com • www.mitch el landmorgan .com
.
-06/06/2005 08:50 FAX 979 764 34r COLLEGE STATION PUB.UTL .
(f/j.. College Station Utilities
RelL1hk, Affordable, Community Owned
1601 GRAHAM ROAD
COLLEGE STATION TEXAS 77845
Date:-23 DECEMBER 2004 {o Ull A./ Z ~ s
Number pages including cover sheet -1
Fax to: 260-3564
Attention: REBECCA
Company: MITCHELL AND MORGAN
From: Butch Willis Water Wastewater Division
Phone: 979-764-3435 Fax: 979-764-3452
FLOW TEST REPORT
Nozzle size: 2.5 inch
Location: 2316 CORNELL
Flow hydrant number: E-142
Pitot reading: 70
(GPM): 1405
Static hydrant number: E-14
Static PSI: 99
Residual PSI: 96
Iii! 001
h/7/<J~
CITY OF C OLLEGE STATI ON
Planning d-Dewloprnent &rvico
SITE LEGAL DESCRIPTION:
Autumn Chase Subdivision
Lots 1-13 , Block 3
Lots 1-6 Block 4
DATE OF ISSUE: 06/21/05
OWNER:
Dan Bensimon
5810 Tom Wooten Drive
Austin, Texas 78731
TYPE OF DEVELOPMENT:
SPECIAL CONDITIONS:
DEVELOPMENT PERMIT
PERMIT NO. 05-19B
FOR AREAS OUTSIDE THE SPECIAL FLOOD HAZARD AREA
RE : CHAPTER 13 OF THE COLLEGE STATION CITY CODE
SITE ADDRESS:
2304 Cornell Drive
DRAINAGE BASIN:
Main Bee Creek
VALID FOR 3 MONTHS
CONTRACTOR:
Full Development Permit
All construction must be in compliance with the approved construction plans
All trees required to be protected as part of the landscape plan must be completely barricaded in accordance with Section
7.5.E., Landscape/Streetscape Plan Requirements of the City's Unified Development Ordinance, prior to any operations of
this permit. The cleaning of equipment or materials within the drip line of any tree or group of trees that are protected and
required to remain is strictly prohibited . The disposal of any waste material such as , but not limited to , paint, oil , solvents,
asphalt, concrete , mortar, or other harmful liquids or materials within the drip line of any tree required to remain is also
prohibited .
****TCEQ PHASE II RULES IN EFFECT****
The Contractor shall take all necessary precautions to prevent silt and debris from leaving the immediate construction site
in accordance with the approved erosion control plan as well as the City of College Station Drainage Policy and Design
Criteria . If it is determined the prescribed erosion control measures are ineffective to retain all sediment onsite , it is the
contractors responsibility to implement measures that will meet City, State and Federal requirements . The Owner and/or
Contractor shall assure that all disturbed areas are sodden and establishment of vegetation occurs prior to removal of any
silt fencing or hay bales used for temporary erosion control. The Owner and/or Contractor shall also insure that any
disturbed vegetation be returned to its original condition, placement and state . The Owner and/or Contractor shall be
responsible for any damage to adjacent properties, city streets or infrastructure due to heavy machinery and/or equipment
as well as erosion, siltation or sedimentation resulting from the permitted work.
In accordance with Chapter 13 of the Code of Ordinances of the City of College Station, measures shall be taken to insure
that debris from construction, erosion , and sedimentation shall not be deposited in city streets , or existing drainage
facilities .
I hereby grant this permit for development of an area outside the special flood hazard area . All development shall be in
accordance with the plans and specifications submitted to and approved by the City Engineer in the development permit
application for the above named project and all of the codes and ordinances of the City of College Station that apply.
Date
Date
Item
No. Quantitv Units
1 1 LS
2 4 EA
3 1500 LF
4 4 EA
5 3000 CY
6 2293 LF
7 3033 SF
8 3033 SY
9 4040 SY
10 4875 SF
11 808 LF
12 4 EA
13 6 EA
14 3 EA
15 8 EA
16 2 EA
17 150 LF
18 889 LF
19 1 EA
20 2 EA
21 1 EA
22 3 EA
23 4 EA
24 2 EA
25 3 EA
26 7 EA
27 2 EA
28 36 LF
29 1 LF
30 1 LF
31 322 LF
32 28 LF
33 1 EA
34 1 LF
35 50 SF
36 2 EA
37 1 EA
38 1000 SY
39 10000 SY
40 LS
ENGINEERS ESTIMATE FOR
AUTUMN CHASE SUBDIVISION
Descriotion & Unit Price in Words Unit Price
GENERAUELECTRICAL ITEMS
Mobilization & Traffic Control $10 ,000 .00
Street Lighting $3,500 .00
Electrical Condu it $4 .50
Transformer Pads $400.00
ROADWAY ITEMS
Earthwork, Including Import and Export $8 .00
Tvpe Ill Curb $9 .00
2" HMAC $6 .00
6" Crushed Limestone Base $10.00
Lime Stabilized Subbase $2 .00
Concrete Sidewalk & Ramps $3 .00
SANITARY SEWER ITEMS
6" San itarv Sewer $35 .00
Sewer Manho le $2 ,300 .00
6 " Sanitary Sewer Service (< 25') $1 ,200.00
6" Sanitary Sewer Service (> 25') $1 ,800 .00
4" Sanitary Sewer Service(< 25') $900 .00
4" Sanitary Sewer Service (> 25') $1 ,200 .00
Remove Ex. Sewer Svstem $5.00
WATER LINE ITEMS
6" PVC Water Line (AWWA C909) $30 .00
Fire Hydrant $2 ,000 .00
Connect to Ex . 6" Line $500.00
6" x 90 M.J. Bend $200.00
6" x 45 M.J. Bend $200.00
6" x 22 .5 M .J . Bend $200 .00
6" x 11.25 M.J. Bend $200 .00
2" Water Service ( < 25') $800 .00
2" Water Service (> 25') $1 ,100.00
1.5" Water Service (> 25') $900.00
14" Steel Casino $40 .00
STORM DRAIN ITEMS
5' Recessed Storm Dra in Inlet $2 ,000 .00
10' Recessed Storm Drain Inlet $2 ,500.00
18" Cl Ill RCP Storm Dra in $40 .00
30" Cl Ill RCP Storm Drain $70.00
30 " x 30 Deoree RCP Bend $560 .00
30" Sloped Headwall $1,400 .00
Remove Ex. Cone Flume $4.00
30" Junction Box $1,500 .00
72" Junction Box $3 ,500.00
POLLUTION PREVENTION ITEMS
Sod in developed areas $8 .00
Hvdro Seedino in undeveloped areas $2 .00
Storm Water Pollution Prevention Implementation $4 ,000.00
Base Bid Subtotals:
Total Price
$10 ,000
$14 ,000
$6,750
$1 ,600
$24 ,000
$20 ,637
$18,198
$30 ,330
$8 ,080
$14,625
$28 ,280
$9,200
$7,200
$5,400
$7 ,200
$2,400
$750
$26 ,670
$2 ,000
$1 ,000
$200
$600
$800
$400
$2 ,400
$7,700
$1,800
$1,440
$2 ,000
$2,500
$12,880
$1 ,960
$560
$1,400
$200
$3 ,000
$3 ,500
$8 ,000
$20 ,000
$4,000
GENERAUELECTRICAL ITEMS $ 32 ,350
ROADWAY ITEMS $ 115 ,870
;' ""--J ./ """'~ •• •• 1 ~'11 STORM DRAIN ITEMS $ 28,000
~, .: ~ .......... :·. ···"I. POLLUTION PREVENTION ITEMS $ 32 ,000 ~ .. ··•···• 'B MUt1\.:ll"I~?. $ ~" :'."l'\t.I~~~ .~: .. : ·······~ ~·-· :)\······ '117689 /~'"~ Grand Total $ 313 ,660 i~~_.:.i.:..;::::..:_..,......,~~~~L.-~~~~~~-;-~~~~~~~--'~~~~~~-'-~~~~-'---'
'" ~. '9 «,"'··~ ~r I 11 0~·· .. f°GtsT~~./(}' • r ? 'J.o 0'5 ····~~.s;0N·A~ ~'tfi 1
A •... -e < ~[) ~ ,,,,_,.,, ......... I~ ..
~ Page 1 of 1
~. J
.... ,.,,
)
CITY OF COLLEGE STATION
Plan11ing c!r Development Servicu
SITE LEGAL DESCRIPTION:
Autumn Chase Subdivision
Lots 1-13, Block 3
Lots 1-6 Block 4
DATE OF ISSUE: 06/21/05
OWNER:
Dan Bensimon
5810 Tom Wooten Drive
Austin , Texas 78731
TYPE OF DEVELOPMENT:
SPECIAL CONDITIONS:
DEVELOPMENT PERMIT
PERMIT NO. 05-19A
FOR AREAS OUTSIDE THE SPECIAL FLOOD HAZARD AREA
RE: CHAPTER 13 OF THE COLLEGE STATION CITY CODE
SITE ADDRESS:
2304 Cornell Drive
DRAINAGE BASIN:
Main Bee Creek
VALID FOR 3 MONTHS
CONTRACTOR:
Clearing and Grading Permit
All construction must be in compliance with the approved construction plans
All trees required to be protected as part of the landscape plan must be completely barricaded in accordance with Section
7.5.E., Landscape/Streetscape Plan Requirements of the City's Unified Development Ordinance , prior to any operations of
this permit. The cleaning of equipment or materials within the drip line of any tree or group of trees that are protected and
required to remain is strictly prohibited . The disposal of any waste material such as, but not limited to, paint, oil , solvents,
asphalt, concrete , mortar, or other harmful liquids or materials within the drip line of any tree required to remain is also
proh ibited .
****TCEQ PHASE II RULES IN EFFECT****
The Contractor shall take all necessary precautions to prevent silt and debris from leaving the immediate construction site
in accordance with the approved erosion control plan as well as the City of College Station Drainage Policy and Design
Criteria. If it is determined the prescribed erosion control measures are ineffective to retain all sediment onsite , it is the
contractors responsibility to implement measures that will meet City, State and Federal requirements . The Owner and/or
Contractor shall assure that all disturbed areas are sodden and establishment of vegetation occurs prior to removal of any
silt fencing or hay bales used for temporary erosion control. The Owner and/or Contractor shall also insure that any
disturbed vegetation be returned to its original condition, placement and state. The Owner and/or Contractor shall be
responsible for any damage to adjacent properties, city streets or infrastructure due to heavy machinery and/or equipment
as well as erosion , siltation or sedimentation resulting from the permitted work.
In accordance with Chapter 13 of the Code of Ordinances of the City of College Station, measures shall be taken to insure
that debris from construction, erosion, and sedimentation shall not be deposited in city streets , or existing drainage
facil iti es .
I hereby grant this permit for development of an area outside the special flood hazard area. All development shall be in
accordance with the plans and specifications submitted to and approved by the City Engineer in the development permit
application for the above named project and all of the codes and ordinances of the City of College Station that apply.
06-.:::?l-OS-
Date
(o/2.3/65
Date
JUL-~8-03 MON UNIQUE STRATEGIES FAX NO. 51~7958431 P. ~
WI.I~ --·"~'U• ~"'""'*'vu~
VI' •Y~ ~..,_,..,
y t V'MVVVYV S aa& •va&&..1&.1~
·--
TCEQ Office Uge Only .,.. Notice of Intent (NOi) for Storm Water Discharges
i"" ~ As~o<:ilated with Consbuclion Activity under the
-TPDES Construction General Pennlt (TXR150000)
T~Q For help cqrnpletlng thi$ llpplt~\ion, read 1he TXR1SOOOO NOi ln,trucllons
TPDES Permil Number: TXR15•~·!..:!....•:_•~ NO
GIN Numbe r :•:_•:_•:_•'!_·~-·:_•:_••
I '-Iii (TCEQ.2002:2-lni;truciior\5).
~~~~~~~~~~~~~~~-~---~
A. Con!ltrucllon Sil• Operator ~New DNo Change customer Rererenr.e Number. CN ___ , _____ _
Name :J>an ftcn.slmov _________ • ·----~~-------~--·----
Maillng Mdtees:_!.~9.J!l.W!l_ottn PriY$ Ci\y ; Aue Do __ state:.lK.__Zip Code:lU.lL....._
Country Mailing tnrormalion (ifwlSA1$ USA) nmilory: --~-Counby Code:____ Poe\al Codo: __ _
Pliont Numb&: (51l).33§·il25 _Ext.en3lon: _____ . __ ., __ Fax tlumbar:_ _!lil21 IPS·Jfil..---·-·-
&mail Add<a$s:Ji!;>.fnslmo11~swell.ML,_,~~------·-·-·~-
TVPe ofOpernlor: 00 todivid1.1al 0 Sole Proprietorship-0.8.A. 0 Partnership D Corpora~on D Federal Govemn'leOI
0 Slate Government 0 County Govemmenl 0 City Governmanl D Other: ______ .-·---------··-----
Independent Operator? 1!J Yea 0 No Number of Employ~; l!!l O.ZO D 21-100 D 101·250 El 251-500 0 601 or higtier
Fe<11m1tTax ID: _slate Franohise Tex IO Nu~:_____ _DUNS Number: ___ _
B. Billing Address
Name:~n Bt!)iimon ------------·. . .. ·-----·~--~----------~---~-~ Mailing Addr~: ~810 To~_x.i_g~n Orln. ______ City; Auatin., __ ., __ St«le;.~ZJp COdll: 7473j __
Coontty Mailing tnlormallon (ii outtide USA) Territory:_ _Country Code; -·-~----~Poelal Code: __
c. Ptaj1tel I Sit• Information DNew 0No C!langa Regulated Eolity Refattoo11 Number: RN~-·-·-------
Name: Dan Btl\!lilmon -------------·-·---·-·-~-·-·-----~----
Melling Addreaa:.ll!D Tom Wool•!!~--~~------Clty;J.ustin Slate:.!!_ Zip CQde:_t!!ll_ __ _
Phy:\lcal M<Jren:~k2m!!J. Drjve City: Colltqe Sla!lori •. County; ISRAZOS ZlP Code :.J..~_J4~Q.,__.....~
Location AcC4s3 OasCl'iption;J:f2!1.~ ComeJJJ!rlv• at BC!ntwo~ Drive -----·---·-----------
leob'ludo:~_!L •-~·•AR N Longlu.lQe;,.!.!. • ...1!..' ~I!." W Degrees(•), Mlll\ltes ('J. and Seconds(")
La.UllJde ; __ Longilud&; - _ DflClmal Form
standard lndu~!tial Clas.c;rncanon (SIC) code; ~-Also, describe Ille oonstruC1ion eclivlty el Iola ail$ (do flOt rew.11t1e SIC eode): ___ .._ ___ ... _____ ~-~-------··-·------------------~~-.._--...
Has a etorm water polu1ion i:irevan1ion ph"' b~ propar.ad u ~podliod in lho gcne1-.,I 1Jn11nl1 (TXft1~ooor1 l!JYes LJ No
Ealimaled area of land dlalurbed (lo ~e riea.ritst acre):_a.4 __ ls lfle project/ site local11d 1m lndl~ Country L11nds? CJ Yes II] No
Does lhl$ project/ elte dls~ge atorm water loto 8 munldpal s&pgrate alorm sewer aystern (M~)? llJY•i; tJ No
If yes, provide Iha nama of lhe MS4 operalor:J!1!_9i\V.2Uloll.!Sla Sia lion _________ ~----·-----~--·--
Provide the neme OI' segment number of the wa!QI' body that rec:eives slorm wat41rflom Ihle proJ11ct J alt&:j:a!!!rs Cr~
D. Contact -If lhe TCEQ needs addttion.i lnrormaliol'I regarding lllia applicalioo, who should be contacted?
Name: Dan Bensimon --·------Title: Owner Phone-,;;,;;; 1s1:aP_1~-1,22s ____ EJIJ.e."13100: _:--=...F";x ~;;;=_:-..:_ <s1ap~e4:i1-.=~~~
E-mall.Address:.dben&lmon@~.1.net -----~·----
E. Payment lnformaUon • Check f Money OrrlAr N1 1mb61':,__ N;l1t10 on Ch~k I Mone>-Ot~; ;;.:__..;....:,.;:.,........:..;.:;.,;;,,;;.~__::..:...;.;..__;,_;..:.;.;...;_.~,:_~~----"=:.:===~==-~-
F. Certification
I cenlfyund4r penally off aw thal :his dccumenl waa prepa:e<l tmder rnydltfctlon or cuparvl&lon 1n •ccor<lanee with a system designed 1o G$&11te tllil quali~ed
per.iOlll\.t propor1'J llalhttr .nd evaluate\M Information aUblhltted . Band on my illqutryof lhc: pe~Dtl « perwns who m.n11g11 tit• •Y11em, Dr l\oH pauorn1
Cltreclly r~pol\S:bl• for ga111e11n9 lheklromi•tlon. Iha inlorl!lllllon submltt11d is, to the beat of rnv kllewledge and beDef, 1r11•. •cc:urai., and complelll. I al'I
sware 1held 111"9 .-.11111cant P8"'-hles 9or 51,1b1111t\lni1 lat-.., hfor11111ion, lrie1Udlng the possibility of fin& and lmplfaonrnerrt b' knowine vlolatio~
Cons1r1.1etlon Sita Operator Representative:
Prefi>C Firs!:_~,--------· _Middle;_~-·--·--~---·---~ Last:___ _ __ Sulli:xi-----~ Tltte: __ . _______ __..,..._ ___ , ____ ,
Slonalure: ---,~7t::~9----yC--#----::;~------.:::::..-:::::----Date : 7 -Z ..J'. ~ CJ 3
Ir you have ciuos Ofl ~ow onl or about the eiormwa:er progr&rn, pltai• <10n1aol ua 11t (S12) 23~eri .
lndivt®abaraen:illad to requutand revlew11t111tpel"30011 lnrC>mlatlon ltlittttJe •oencvo:itheri o~ !IS farms . Thay may 11$011av11 :uiy eno1s In their lnl'orm3\lon
corrected . To 18View .ueti lnl'Drmetion, contact u1 e.1 (512) 239-3282.
TCeQ-20022 (02/03)
Tha i;omplels:t NOi must ba mailed to 11111 fo11ow1ng address . Usa lhe attached docun1ont lo submit !he $100
11pplkaUon fn. P!Qase nQ!e !hat the NO! and applice.tion fee ar11 l'Jbmltted ~para.lely to different addres541e .
Texas CoJTVnletlon of! EnvlronmtNtt•I Quality
Storm WalQf & General Permit& Team: MC -228
P.O. Bax 13087
Auclin, Texas '111711·3067
Carol Cotter
City of College Station
Planning & Development
PO Bo x 9960
College Station, TX 77840
MITCHELL
MM
MORGAN
RE: Fire Hydrant Test for Autumn Chase Subdivision
Dear Carol:
June 7, 2005
In December 2004 a hydrant test was run for the Autumn Chase Subdivision per your comments
on a November submittal. At that time we completed a MikeNET analysis to compare the City of
College Station water model to actual hydrant flow data . We believe that we relayed the results to
you verbally, but we do not have any written correspondence for this comment.
Please see the table below for a comparison between the results of the MikeNET analysis and the
hydrant flow data . For your convenience I have attached the flow test report to this letter.
Flow Test and MikeNET Comparison
Residual Demand Method
Flow Test
MikeNET
Static
99 .0 psi
100.1 psi
~~~~~-+--~~~~~~---<
96 .0 psi 1405 gpm
~~~~~-+--~----""----~~~----;
91.3 psi 1405 gpm
~~~~~~~----""----~~~~
Based on the above results, we believe that the MikeNET model is a good approxi mation for real
flow co n ditions . if yo u have any further comme nts or questions pleas e fee! free to con tact me.
Sin ~~
Rebecca A. Rigg s, EIT
Graduate Engineer
cc. file
Attachment: Hydrant Flow Test
S :\ProJ\04 58 -A utumn-C hase -Vil las -N EVv\docs\04 58-hydrant-te st-050607. doc
D~ .. \ct L\
511 UNIVERSITY DRI VE EAST, SUITE 204 • COLLEGE STAT ION, TX 77840 • T 979 .260.6963 • F 979 .260.3564 \.,~
lo · 'b -o'S
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan .com • www mitchellandmorgan .com
06/06 /2005 08 :50 FAX 979 764 3452 COLLEGE STATION PUB .UTL.
fl~{ College Station Utilities ~ Reliablf, Affo1·d11ble, Community Owned
1601 GRAHAM ROAD
COLLEGE STATION TEXAS 77845
Date:-23DECEMBER2004-{o ;;-t..1/UZ ~ ~
Number pages including cover sheet - 1
Fax to: 260-3564
Attention: REBECCA
Company: MITCHELL AND MORGAN
From: Butch Willis Water Wastewater Division
Phone: 979-764-3435 Fax: 979-764-3452
FLOW TEST REPORT
Nozzle size: 2.5 inch
Location: 2316 CORNELL
Flow hydrant number: E-142
Pitot reading: 70
(GPM): 1405
Static hydrant number: E-14
Static PSI: 99
Residual PSI: 96
~001
fo/7 j ()r-
Alan Gibbs , P.E.
Development Services
P.O. Box 9960
College Station, TX 7 7840
MITCHELL
MM
MORGAN
RE: Autumn Chase Subdivision-Fire Flow Analysis Addendum
Dear A lan:
May 16, 2005
Below is the water analysis for the A utumn Chase Subdi v ision . Domestic flows were
calculated using the Normal Flow method 2 as presented in the February 2004 B/CS
Unified Design Guide lines . The townhomes and duplexes consist of 56 total units,
requiring a peaked domestic flow of approximately 41 .5 gpm .
The largest possible townhome building is 5903 square feet, with firewalls
constructed per bu ilding code between units (a ll owing a reduction in square
footage to 1,500 square feet for the fire area) requiring a fireflow of 1500 gpm per
the 2000 International Fire Code. A building type of V-B is projected as our build ing
t ype. The fireflow required to ser ve this proj ect is sma ll enough that only one fire
hydrant is required . Please see attached excerpt from the 2000 International Fire
Code (Exhibit 1 ).
Using the updated College Station w ater system mode l in MIKE NET, a domestic
flow of 41.5 gpm, and a fire flow of 1500 gpm, flows and pressures in the lines
adjacent to the hydrants are as follows:
Item ID Demand Pressure Flow Veloci t
Junction 2087 1541.5 gpm 78.12 psi NI A N/A
(H d rant)
Pipe2461 (6") N/A N/A 864 .7 gpm 9 .8 fps
Pipe 2469 (6") N/A N/A -676 .8 pm -7 .7 f s
Please see the attached M IKE NET report for pipe and junction loca t ions as well as
additio na l resu lts (Exhib it 2).
511 UNIVERSITY DRIVE EAST, SUI TE 204 • COLLEGE STATION , TX 77840 • T 979.260.6963 • F 979.260.3564
CIVIL ENGINEERING • HYDRA ULI CS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan.com • www.m1tchellandmorgan.com
The hydrant and proposed lines are sufficient for the fire flow requirements for the
Autumn Chase Subdivision. In the analysis flows were kept below 12 fps and
pressure remained above 20 psi, as per the B/CS Unified Des ign Guidelines Manual.
If you have any further comments or questions please feel free to contact me.
cere1y, _ ...... ;'toF"~~'''• ~.(,..,,..,. .. *·"""·····:;+-""-.,, ; .. ..... ·· ... u-. ''· ~ * ... .... * ~ ~ 1"'eAONicA'j:e:·MORG.AN~
l~~········:,·168'9''''''''/fi!
V . M o ··.~ <)/!ii~ eronica . . g . ~ ... ~a1srE~~ ... · ~ -,, ''& ... .. ~ .:' Managing Partner ''\,s1c)'NAL·€.~--..:-
S(1lP f~?"''~
cc: file
Attachments
S:\Proj\0458-A utumn -Chase-Villas-NEW\docs\0 45 8 -fireflow-u pdate-050516 .doc
ARE-FLOW REQUIREMENTS FOR BUILDINGS
TABLE B105.1
MINIMUM REQUIRED FIRE FLOW AND FLOW DURATION FOR BUILDINGS
FIRE AREA ,_,.,.. teetl
Type IA Ind 1119 Type llA Md lllA" Type IV end V-A" Type UB and ma" 1'VDe v-B"
0-22,700 0-12,700 0-8,200 O-S,900 0-3,600
22.701 -30,200 12.701-17,000 8,201-10,900 S,901-7,900 3,601-4,800
30,201-38,700 17,001-21,800 10,901-12.900 7,901-9,800 4,801-6,200
38,701-48,300 21,801-24,200 12.901-17,400 9,801-12,600 6,201-7,700
48,301 -59,000 24,201-33,200 17,401-21,300 12.601-15,400 7,701-9,400
59,001-70,900 ,.--33;to f .:j9,70ct 21.301-25.SOO 15,401-18,400 9,401-11.300
70.901-83,700 39,701-47,100 25.SOl-30,100 18,401-21,Soo 11.301-13,400
83,701-97,700 47,101-54,900 c3o.ro1~5.iOQ 21,801-25,900 13,401-lS,600
97,701-112.700 54,901-63,400 35,201-40.600 25,901-29,300 15,601-18,000
112.701-128,700 63,401-72,400 40,601-46,400 29,301-33.SOO 18,001-20,600
128,701-145,900 72.401-82.100 46,401-52.500 . . 33,501-31,900 20,601-23.300
145,901-164,200 82.101-92,400 52.SOl-59,100 37,901-42.700 23.301-26.300
164.201-183,400 92,401-103,100 59,101-66,000 42.701-47,700 26,301-29.300
183,401-203,700 103,101-114,600 66,001-73.300 47,701-53,000 29.301-32.600
203,701-225,200 114,601-126,700 73.301-81,100 53,001-S8,600 32.601-36,000
225.201-247,700 126,701-139,400 81,101-89,200 58,601-65,400 36,001-39,600
247,701-271,200 139,401-1S2.600 89,201-97,700 65,401-70,600 39,601-43,400
271,201-295,900 152.601-166.SOO 97,701-106.SOO 70,601-77,000 43,401-47,400
295,901.r--·-166.SO I-Greater 106.SOl-1 lS,800 77,001-83,700 47,401-Sl.SOO
--115,801-125.SOO 83,701-90,600 51.SOl-SS,700
--12S.S01-13S.SOO 90,601-97,900 5S,701-60.200
--13S.S01-14S,800 97.901-106,800 60,201-64,800
--14S,801-1S6,700 106,801-113,200 64,801-69,600
--1S6.701-167,900 113,201-121.300 69,601-74,600
--167,901-179,400 121,301-129,600 74,601-79,800
--179,401-191,400 129,601-138.300 79,801-SS,100
--191,401-Grcater 138,301-Grcater 85, l 01-Grcater
For SI: I square foot -0 .0929 m2, I gallon per minutc • 3.78S Um, I pound per square inch., 6.89S kPa.
L Types of con..;truction arc based on the lnl~rnariONJI Building Cod~.
b. Measured at 20 psi .
ARE FLOW FLOW
taallona _,. """"'9)~ DURATION (hours)
l.SOO
l,7SO
2.000 2
2.2SO
2.500
2,7SO
3,000
3.2SO 3
3.SOO
3,7SO .
4,000
4,2SO
4.SOO
4,750
5,000
5,2SO
s.soo
S,1SO
6,000 4 n ;;.---, 6,2SO _
6 .soo
6,7SO
7,000
7,2SO
7-500
7,7SO
8,000
... --··--• --·--·· ·---# .. _,_ --....
(
-t
358 20001NTE EXHIBIT 1
fireflow-051605.GDB
Analysis Type: Steady State
Project Description: Autumn Chase Villas , fireflow of 1500 gpm
/
/
~ / > /
EXHIBIT 2
Results -Junctions
Number of Junctions: 13(Selection)
Junction ID Description Elevation Demand Grade Pressure
[ft] [gpm] [ft] [psi]
167 J-8580 298.000 0.000 506.467 90 .32 9
1173 29 7 .000 0.000 505.145 90.189
2074 294 .000 0.000 506.214 91.952
2075 297 .000 0.000 505 .079 90 .161
2076 300 .000 0.000 500 .862 87 .033
2081 301.500 0 .000 494 .503 83.628
2082 305 .650 0 .000 486.071 78.176
2083 303.600 0.000 491.925 81.601
2085 297.250 0.000 505.096 90 .060
2086 300.500 0.000 495.869 84.653
2087 h ydrant 303 .575 1541.500 483 .858 78.117
2088 301.800 0 .000 497.084 84.617
2089 298 .500 0.000 504.707 89.350
EXHIBIT 2
Results -Pipes
Number of Pipes: 13(Selection)
Pipe ID Node 1 Node2 Diameter Length Roughness Flow Velocity Head loss
[in] [ft] [millift] [gpm] [ft/s] [ft]
2204 167 2085 8.000 132.992 130.000 734.452 4 .688 1.372
2453 2074 2075 8.000 235.053 140.000 525.013 3.351 1.135
2454 2075 1173 8 .000 134 .998 140.000 -151.792 -0.969 0.065
2455 2075 2089 8 .000 48.195 140.000 676.805 4.320 0.372
2461 2081 2087 6.000 215.500 140.000 864 .695 9 .812 10 .645
2463 2082 2083 6.000 186.570 140.000 -676.805 -7.680 5.854
2465 2085 1173 8.000 117.494 130.000 -130.243 -0.831 0.049
2466 2086 2081 6.000 27 .651 140 .000 864.695 9.812 1.366
2467 2085 2086 6 .000 186 .803 140 .000 864.695 9.812 9.227
2468 2083 2088 6 .000 164.418 140.000 -676.805 -7.680 5.159
2469 2087 2082 6.000 70.511 140.000 -676.805 -7.680 2.213
2470 2088 2076 6.000 120.379 140.000 -676.805 -7 .680 3.777
2471 2089 2076 6.000 122.550 140.000 676.805 7 .680 3.845
EXHIBIT 2
0P ()5 --I q --5
5 -;w-ifJ
~'.:},D
Bridgette George
City of College Stat ion
Development Services
PO Box 9960
College Station, TX 77840
MITCHELL
M M
MORGAN
Re : Autumn Chase Subdivision Pr elim in ary and Fin al Plat s Submittal
Dear Bridgette,
Attached are the following items for t he Autumn C hase Subdivision Replat.
• One copy of the Fire Flow An alys is
• One copy of the Engineer 's Estim ate
• One copy of the Drainag e Re p o rt
e let us know if you have any qu es t ion s.
Si 1 erely, ;c.Jofy~ :ero~~~org~ 1, PE CFM
Managing Partner
Cc. File
Dan Bensimon
Attachments
s~
May 16, 2005
511 UNI VERSITY DRI VE EAST, SUITE 204 • COLLEGE STATION , TX 77840 • T 979 .260.6963 • F 979.260.3564
CIVIL ENG IN EERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@m1tchellandmorgan.com • www.m1tchellandmorgan.com
CrTY OF COLLEGE STATION
Planning & Development Services
FOR OF~SE,Q~
P&Z CASE NO .: 0-::::>
---DATE SUBMITTED: ~ -}{p-fX:::>
FINAL PLAT APPLICATION
(Check one) D Minor
($300 .00)
D Amending
($300 .00)
D Final
($400.00)
D Vacating
($400 .00)
~ Replat
($600.00)*
*Includes public hearing fee
The following items must be submitted by an established filing deadline date for P&Z Commission consideration.
MINIMUM SUBMITTAL REQUIREMENTS:
N/A Filing Fee (see above) NOTE: Multiple Sheets -$55 .00 per additional sheet
NIA Variance Request to Subdivision Regulations -$100 (if applicable)
t' L Development Permit Application Fee of $200 .00 (if applicable).
N/A Infrastructure Inspection Fee of $600.00 (applicable if any public infrastructure is being constructed)
L Application completed in full.
N/A Copy of original deed restrictions/covenants for replats (if applicable).
_..J_ Thirteen (13) folded copies of plat. (A signed mylar original must be submitted after staff review.)
N/A One (1) copy of the approved Preliminary Plat and/or one (1) Master Plan (if applicable).
L Paid tax certificates from City of College Station , Brazos County and College Station l.S .D .
..J A copy of the attached checklist with all items checked off or a brief explanation as to why they are not.
_..J_ Two (2) copies of public infrastructure plans associated with this plat (if applicable).
_..J_ Parkland Dedication requirement approved by the Parks & Recreation Board, please provide proof of
approval (if applicable).
Date of Preapplication Conference: _______________________ _
NAME OF SUBDIVISION Autumn Chase Subd ivision
SPECIFIED LOCATION OF PROPOSED SUBDIVISION (Lot & Block) Lots 1-13. Block 3 and Lots 1-6, Block 4
APPLICANT/PROJECT MANAGER'S INFORMATION (Primary Contact for the Project):
Name Veronica Morgan . PE
Street Address 511 Un iv ersity Drive East, Su ite 204
State TX Zip Code .:....77.:....:8"-'4=0 ___ _
Phone Number -'9"-'7--=9-=-2=6=0__,-6=9=6=-3 ______ _
PROPERTY OWNER'S INFORMATION :
Name Dan Bensimon
Street Address 5810 Tom Wooten Drive
State TX Zip Code -'--78::....:7-=3'-'-1 ___ _
Phone Number ~5~1~2~-3~3~8~-1~2~2~5 ______ _
ARCHITECT OR ENGINEER'S INFORMATION :
Name Veronica Morgan , PE
Street Address 511 University Drive East, Suite 204
State TX Zip Code .:....77.:....:8"-'4=0 ___ _
Phone Number ~9~7~9-=-2::..::6'"""'0__,-6~9=6=-3 ______ _
6/13/03
City College Station
E-Mail Address v@mitchellandmorgan .com
Fax Number 979-260-3564
City Austin
E-Mail Address dbensimon@swbell.net
Fax Number 512-795-8431
City College Station
E-Ma il Address v@mitchellandmorgan .com
Fax Number 979-260-3564
I of 5
Is there a temporary blanket easement on this property? If so , please provide the Volume N/A and Page# N/A
. J l1l .
Acreage -Total Property 5.64 ac Total# Of Lots 19 R-0-W Acreage. b Bf' Q,/;,..
Existing Use :V ~=a=ca=n=t __________ _ Proposed Use :Duplexes/Fourplexes ________ _
Number Of Lots By Zoning District ..:..;19,,____ I R-4
Average Acreage Of Each Residential Lot By Zoning District:
.21 I ~R_-4 ___ _
Floodplain Acreage Q
A statement addressing any differences between the Final Plat and approved Master Plan and/or Preliminary Plat (if
applicable):
N/A
Requested Variances To Subdivision Regulations & Reason For Same : N/A
Requested Oversize Participation : N/A
Total Linear Footage of
Proposed Public:
1182 Streets -
Parkland Dedication due prior to filing the Final Plat:
ACREAGE : NIA
913_ Sidewalks N/A
N/A
# of acres to be dedicated + $ ____ development fee
807 -Sanitary Sewer Lines # of acres in floodplain
885 Water Lines NIA #of acres in detention -
0 Channels N/A #of acres in greenways
337 Storm Sewers OR -
0 Bike Lanes I Paths FEE IN LIEU OF LAND:
N/A #of Single-Family Dwelling Units X $556 = $ ___ _
_______ (date) Approved by Parks & Recreation Board
NOTE: DIGITAL COPY OF PLAT MUST BE SUBMITTED PRIOR TO FILING.
The applicant has prepared this application and certifies that the facts stated herein and exhibits attached hereto are true,
correct, and complete. The undersigned hereby requests approval by the City of College Station of the above-identified
finf lat and attests that this request does not amend any covenants or restrictions associated with this plat
' .
Date
2 of5
6/13/03
SUPPLEMENTAL DEVELOPMENT PERMIT INFORMATION
Application is hereby made for the follow ing development spec ific site/waterway alterations:
None
ACKNOWLEDGMENTS:
I, Veronica Morgan , desig n engineer/owner, hereby acknowledge or affirm that:
The information and conclusions conta ined in the above plans and supporting documents comply with the current
r irements of the City of Col lege Stat ion , Texas City Code , Chapter 13 and its associated Drainage Policy and Design
Sa dards . As a condition of approval of this permit applicat ion , I agree to construct the improvements proposed in this
a I cation~cc ing t these documents and the re quirements of Chapter 13 of the College Station City Code .
~~~~~~~~~~~~~~~~~
Contractor
CERTIFICATIONS: (for proposed alterations within designated flood hazard areas .)
A.I, NIA certify that any nonresidential structure on or proposed to be on this site
as part of this application is designated to prev ent damage to the structure or its contents as a result of flooding from the
100 year storm .
Engineer Date
8 . I, N/A certi fy that the finished floor elevation of the lowest floor , including any
basement, of any residential structure , proposed as part of this application is at or above the base flood elevation
established in the latest Federal Insurance Ad m inistration Flood Hazard Study and maps , as amended .
Engineer Date
C. I, N/A , certify that the alterations or development covered by this permit shall
not diminish the flood-carrying capacity of the wate rway adjo ini ng or crossing this permitted site and that such alterations
or development are consistent with requirements of the City of College Station City Code, Chapter 13 concerning
encroachments of floodways and of floodway fr in ges .
Engineer Date
D. I, N/A , do certify that the proposed alterations do not raise the level of the 100
year flood above elevation established in the latest Federal Insurance Administration Flood Hazard Study .
Engineer Date
Conditions or comments as part of approval : !...:N~/A...!,_ ________________________ _
In accordance with Chapter 13 of the Code of O rd inances of the City of College Station , measures shall be taken to insure
that debris from construction , erosion , and sedimentation shall not be depos ited in city streets , or existing drainage
facilities . All development shall be in accordance with the plans and specifications submitted to and approved by the City
Engineer for the above named project. All of the applicable codes and ordinances of the City of College Station shall
app~. . -
6/13 /03
3 of 5
SUBMIT APPLICATION AND THIS
LIST CHECKED OFF W ITH 13
FOLDED COPIES OF PLAT FOR REVIEW
C ITY O F COLLEGE S TATION
Planning & D evel.opmmt Services
FINAL PLAT MINIMUM REQUIREMENTS
(ALL CITY ORDINANCES MUST BE MET)
INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
(Requirements based on field survey and marked by monuments and markers.)
1. Drawn on 24" x 36 " sheet to scale of 100 ' pe r inch or larger.
2 . Vicinity map which includes enough of surrounding area to show general location of subject
property in relat ionship to College Station and its City Limits . No scale required but include north
arrow.
~ 3 . Title Block with the follow ing informat ion :
G( Name and add ress of subdivider, recorded owner, planner, engineer and surveyor.
Gt' Proposed name of subdivision . (Subd ivision name & street names will be approved
through Brazos County 911 .) (Replats need to retain original subdivision name.)
Date of preparat ion .
Engineer's scale in feet.
Total area intended to be developed .
Gf 4. North Arrow.
0 5 .
fSll~ 6 .
Subdivision boundary i nd icated by heavy lines .
If more than 1 sheet , an inde x sheet showi ng entire subdivision at a scale of 500 feet per inch or
larger.
G(
6/13/03
7 .
8.
9 .
All applicable certifica ti ons based on the type of final plat. g Ownership and Dedi cation
~ Surveyor and/o r E ng ineer
CJ" City Engineer (a nd C ity Planne r , if a minor plat)
~
D
Plann ing and Zon ing Commission (delete if m inor plat)
Brazos County C lerk
Brazos County Co m miss ioners Cou rt Approval (ET J Plats only)
Paid tax certificates .
If submitting a replat w here there are existing improvements , submit a survey of the subject
property showing th e imp rovements to ensure that no encroachments will be created .
10 . If using private septi c sys tems , add a general note on the plat that no private sewage facility may
be installed on any lo t i n this subdiv is ion without the issuance of a license by the Brazos County
Health Unit under the p rov is ions of the pri vate faci lity regulations adopted by the Commissioner's
Court of Brazos Cou nty , pursuant to the provisions of Section 21 .004 of the Texas Water Code .
11 . Location of the 100 Y ear Floodpla in and floodway , if applicable , according to the most recent
available data .
12 . Lot corner markers a nd s u rvey monuments (by symbol) and clearly tied to basic survey data .
13. Matches the approv ed p re liminary pl at and/or master development plan .
4 ofS
14. The location and description with accurate dimensions, bearings or deflection angles and radii,
area, center angle , degree of curvature , tangent distance and length of all curves for all of the
following: (Show existing items that are intersecting or contiguous with the boundary of or forming
a boundary with the subdivision, as well as , those within the subdivision).
Existing Proposed
D ~ Streets . Continuous or end in a cul -de-sac, stubbed out streets must end into a temp
turn around unless they are shorter than 100 feet.
~
ri
i
0 rs1' Public and private R.O .W . locations and widths. (All existing and proposed R.0.W.'s
_/ sufficient to meet Thoroughfare Plan .)
D hl \bf Street offsets and/or intersection angles meet ordinance .
D O~\f' Alleys.
@ ~ Easements .
Q ~ A number or letter to identify each lot or site and each block . Q--Et~\t< Greenbelt area/park linkages/parkland dedication ( All proposed dedications must be
reviewed by the Parks and Recreation Board prior to P & Z Commission consideration.)
15. Construction documents for all public infrastructure drawn on 24" x 36" sheets and properly sealed
by a Licensed Texas Professional En gi neer that include the following:
16 .
17.
18.
0 Street, alley and sidewalk plans , profiles and sections. One sheet must show the overall
street, alley and/or sidewalk layout of the subdivision . (may be combined with other
utilities).
Sanitary sewer plan and profile show ing depth and grades . One sheet must show the
overall sewer layout of the subdivision . (Utilities of sufficient size/depth to meet the
utility master plan and any future growth areas .)
Water line plan showing fire hydrants , valves , etc. with plan and profile lines showing
depth and grades . One sheet must show the overall water layout of the subdivision .
(Utilities of sufficient size/depth to meet the utility master plan and any future growth
areas.)
Storm drainage system plan with contours , street profile, inlets, storm sewer and
drainage channels , with profiles and sections. Drainage and runoff areas, and runoff
based on 5 , 1 O, 25 , 50 and 100 year rain intensity. Detailed drainage structure design,
channel lining design & detention if used . One sheet must show the overall drainage
layout of the subdivision.
Detailed cost estimates for all public infrastructure listed above sealed by Texas P.E.
Drainage Report .
Erosion Control Plan (must be included in construction plans).
All off-site easements necessary for infrastructure construction must be shown on the final plat
with a volume and page listed to indicate where the separate instrument easements were filed .
Separate instrument easements must be filed prior or concurrently with Final Plat.
Are there impact fees associated with this development? 0 Yes D No
Impact fees for R-1 , R-2, & R-3 zoned final plats , must be paid prior to filing.
Will any construction occur in TexDOT rights-of-way? 0 Yes 0 No
If yes , TexDOT perm it must be submitted along with the construction documents.
NOTE: 1 . We will be requesting the corrected Final Plat to be submitted in digital form if available prior to
filing the plat at the Courthouse .
6/13/03
2. If the construction area is greater than 5 acres , EPA Notice of Intent (NOi) must be submitted
prior to issuance of a development permit.
5 of5
Alan Gibbs, P.E.
Assistant City Engineer for Development
Development Services
P.O . Box 9960
College Station, TX 77840
MITCHELL
MM
MORGAN
Re: Autumn Chase Villas Drainage Addendum
Dear Alan,
~o-r;-14 es&~-s
'5-;)J)-v :5"
J :;LO
~
May 16, 2005
The inte nt of this letter is to detail changes to the proposed drainage infrastructure
de scribed in the Autumn Chase Villas Drainage Analysis , submitted by Mitchell & Morgan,
LLP to the City of College Station in December 2004 . While none of the Cornell Street
infrastructure will be modified, the proposed layout for the Autumn Chase Villas ha s
changed since the last report was submitted, resulting in the need for updated drainage
design.
The new layout includes the subdividing of Lot 6, Block 2 into several smaller lots. This site
design also includes the construction of Autumn Chase Loop, which will serve as the access
route to all the lots in this portion of the Autumn Chase Subdivision . The new layout can
be seen in ExhibitC of the attached sheets . The proposed drainage system will continue to
discharge into the existing detention pond located at the east corner of the property,
adjacent to Cornell Street. The drainage design was analyzed in XP-S torm 9 .1 .4 just as the
December 2004 report was.
While the configuration of the Autumn Chase subdivision has changes, the relative amount
of impervious cover has not changed significantly. Only a slight variation exists in the
postdevelopment flow into the pond between the old and new design, leaving the
conditions in the pond and downstream of the Autumn Chase subdivision largely the same,
with a slight increase upward for the new layout. The new drainage infrastructure consists
of approximately 50 LF of 30" RCP and 308 LF of 18" RCP as detailed in Exhibit C of this
addendum. Modeling of the sys tem indicates that these pipes provide adequate
conveyance into the detention pond . In addition, the capacity of the proposed 4" rollover
curb was analyzed to determine street capacity. This was done using Manning's equation
as opposed to the gutter equations in the College Station Drainage Policy and Design
Standards (DPDS) because these equations are based on a 6" curb and Manning's was
more conservative . These calculations have been prov ided as Exhibit D.
The plan and profile sheet provided as Exhib it C indicates a small stub out located along on
of the interior property lines . This stub out will serve the future development of the
property by providing access to the drainage system. The property was analyzed at
estimated full development levels and as such, some drainage assumptions were made to
account for all of the flow into the detention pond . An updated drainage area map has
been provided as Exhibit B of the report. The current site configuration has only two inlets
on it; one 5 ' recessed inlet at the southwest corner of the property and on 1 O' recessed
511 UNIVERSITY DRIVE EAST, SUITE 204 • COLLEGE STATION, TX 77840 • T 979.260.6963 • F 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan .com • www.mitchellandmorgan.com
inlet at the southeast corner of the property, adjacent to the detention pond . Flow from
the north end of the property will be conveyed in the streets and within the Right-of-Way
for the 100-year event. The project will continue to meet the drainage object ives of the
College Station DPDS .
If you have any questions or comments, please feel free to contact either Veronica Morgan
or myself at 260-6963.
Sincere ly ,
~~
Terry M . Barr, E.l.T, C.F.M
Graduate Eng ineer
Cc: File
Dan Bensimon, Owner
-0
~
c
0
~ -=;
a.
E wo
T""" ()
,.... en co -..._
,..._ Q)
C') Q)
()) -~ . Cl
0 c zw
,q UTV~A/ CHP)~£
A-DD-EN CU
&~ U}PlfCIT'( CC-F-S_)
'2..z fel:CIF>Te.DC~ e>p CRC)S$ SU> '£.
,.., .. "'( ~>-/ ~ 1 >-l(7S R-o vt;,J.f NESS.
.S • LON' 1rll()l;./1¥,.. .SL..()P1'_;
0 =". IYC.PT'f ( FT)
l}s./J.l<; A ~£..PTJ-f OF fr::.()."'67SP( FOR. A to-Tit,A-~ t,;vEA{T A"/{J
.f D-UTJ/ -DI=-();:;... fJ.50 F-T FOle. A /DD-/E~'< El/EJ.IT A-VI:>
VA-R'(tr{f, ~,..,f;,ITll0l"4Prl-..SLOP€SA
{). ''I
(). ,,
fJ .C/t'
I. ?..8
()t!Pnf f)::;. IJ.375 l="T
(to-)'cA~)
c ("cps
~,04(
", S"g
7-lf '6
e.ss
/J-:::. D. ~75 ~r fj:. O . So !=T
f}.6"f
IJ. u,
o-t:JB
1. zi
A :: ~ • 11 .re1. F-T
1<.~ 9,1s7 FT
A .. .J. 93 SdJ.FT
R.= ().~78 ~T
~€.Pl>i D= 0. 375 FT
C ro-YUtR)
c Cc
'-/, I :J_
'i . "I 't
:s. 05
5. Cj'3
DEPnf t>:::. {) .. S-0 c
c {00 -)'"...:~)
PAC (~PS)
13. 03
I~. Z.O
lb. 12.
18. "'IS
~ c.-C4Plierry (CP.S)
f) ~ "1AliN1._J &.S ~V6J./N f;SS
A-~ ctz..AS.S-.secr;r>Nltt-A-fee.A G T-)
R.::;. ff/D~Ut-.fc, ~A-~'V-S c FT)
s = t-...ON~ITUt?'"'AL-.:st-orrv
/)!ZPTif /);; P.6 .D 0
([IJO-'(£.AR.)
If. 0~
F· og
13 • .S7
115 ~ "1
((~
t
Item
No. Quantity Units
1 1 LS
2 4 EA
3 1500 LF
4 4 EA
5 3000 CY
6 2293 LF
7 3033 SF
8 3033 SY
9 4040 SY
10 4875 SF
11 808 LF
12 4 EA
13 6 EA
14 3 EA
15 8 EA
16 2 EA
17 150 LF
18 1074 LF
19 372 LF
20 1 EA
21 2 EA
22 9 EA
23 7 EA
24 7 EA
25 2 EA
26 1 EA
27 3 EA
28 4 EA
29 3 EA
30 1 EA
31 3 EA
32 2 EA
33 6 EA
34 2 EA
35 50 LF
36 54 LF
37 1 EA
ENGINEERS ESTIMATE FOR
AUTUMN CHASE SUBDIVISION
Description & Unit Price in Words
GENERAUELECTRICAL ITEMS
Mobilization & Traffic Control
Street Liqhtinq
Electrical Conduit
Transformer Pads
ROADWAY ITEMS
Earthwork , Including Import and Export
Type Ill Curb
2" HMAC
6" Crushed Limestone Base
Lime Stabilized Subbase
Concrete Sidewalk & Ramps
SANITARY SEWER ITEMS
6" Sanitary Sewer
Sewer Manhole
6" Sanitary Sewer Service(< 25')
6" San itary Sewer Service (> 25')
4" Sanitary Sewer Service(< 25')
4" Sanitary Sewer Service (> 25')
Remove Ex . Sewer System
WATER LINE ITEMS
6" PVC Water Line with Structural backfill (AWWA C909)
3" PVC Water Line with structural backfill (AWWA 02241)
Fire Hydrant
Connect to Ex . 6" & 8" Water Line
6" M .J. Gate Valve & Box
3" M .J . Gate Valve & Box
6" x 3" M .J . Tee
6" x 1.5" M.J. Tee
6" x 90 M .J. Bend
6" x 45 M.J . Bend
6" x 22.5 M .J. Bend
6" x 11 .25 M .J. Bend
3" x 11.25 M .J. Bend
3" x 22.5 M .J . Bend
3" x 45 M .J . Bend
1 .5" Water Service (< 25')
1.5" Water Service (> 25')
6" PVC Casing (AWWA C905)
14" Steel Casing
2" Blow off Assembly
Unit Price Total Price
$10,000 .00 $10 ,000
$3,500.00 $14 ,000
$4.50 $6,750
$400 .00 $1 ,600
$8 .00 $24 ,000
$9.00 $20,637
$6 .00 $18,198
$10 .00 $30,330
$2 .00 $8,080
$3 .00 $14,625
$35 .00 $28 ,280
$2 ,300 .00 $9,200
$1 ,200 .00 $7,200
$1 ,800.00 $5,400
$900 .00 $7,200
$1,200 .00 $2,400
$5 .00 $750
$40 .00 $42,960
$35 .00 $13,020
$2 ,000.00 $2,000
$500 .00 $1 ,000
$500.00 $4 ,500
$400.00 $2 ,800
$200.00 $1,400
$200.00 $400
$200 .00 $200
$200.00 $600
$200.00 $800
$200.00 $600
$150.00 $150
$150.00 $450
$150 .00 $300
$800 .00 $4 ,800
$900.00 $1 ,800
$20 .00 $1,000
$40 .00 $2,160
$500 .00 $500
Page 1 of2
f
Item
No. Quantity Units
38 1 LF
39 1 LF
40 322 LF
41 28 LF
42 1 EA
43 1 LF
44 50 SF
45 2 EA
46 1 EA
47 1000 SY
48 10000 SY
49 1 LS
ENGINEERS ESTIMATE FOR
AUTUMN CHASE SUBDIVISION
Description & Unit Price in Words
STORM DRAIN ITEMS
5' Recessed Storm Drain Inlet
1 O' Recessed Storm Drain Inlet
18" Cl Ill RCP Storm Drain
30" Cl Ill RCP Storm Drain
30" x 30 Degree RCP Bend
30" Sloped Headwall
Remove Ex . Cone Flume
30" Junction Box
54" Special Junction Box
POLLUTION PREVENTION ITEMS
Sod in developed areas
Hydro Seeding in undeveloped areas
Storm Water Pollution Prevention Implementation
Base Bid Subtotals:
GENERAUELECTRICAL ITEMS
ROADWAY ITEMS
SANITARY SEWER ITEMS
WATER LINE ITEMS
STORM DRAIN ITEMS
POLLUTION PREVENTION ITEMS
Grand Total
Unit Price Total Price
$2 ,000 .00 $2 ,000
$2 ,500 .00 $2 ,500
$40 .00 $12 ,880
$70 .00 $1 ,960
$560.00 $560
$1,400 .00 $1,400
$4 .00 $200
$1 ,500 .00 $3 ,000
$3 ,000 .00 $3 ,000
$8 .00 $8 ,000
$2.00 $20,000
$4 ,000 .00 $4 ,000
$ 32 ,350 .00
$ 115,870 .00
$ 60,430 .00
$ 80 ,940 .00
$ 27 ,500 .00
$ 32 ,000.00
$ 349 ,090 .00
Page 2 of 2
Bridgette George
City of College Station
Planning & Development Services
P .O . Box 9960
College Station, TX 77842
MITCHELL
MM
MORGAN
Re: Autumn Chase (FP) Staff Review Comments
Dear Bridgette,
Please find attached with this letter two (2) sets of revised drawings, and the answers to
the Staff Review Comments .
Comment :
Answer :
Gate valves are required; one less than every leg of a tee connection .
Acknowledged , changes have been made on drawings .
If you have any questions or comments please feel free to contact us at 260-6963 . Thank