HomeMy WebLinkAboutStaff Comments(*//q" CITY OF COLLEGE STATION Planning &Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM November 1, 2004 TO: Robert L. Payne, Jr., Via fax 696.8114 FROM: Bridgette George, Assistant Development Manager SUBJECT: BRAZOS VALLEY BANK BUILDING SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review and approval of the plans: Six (6) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (please submit additional copies to be stamped for your records). Two (2) revised site plans; and One (1) landscaping plan. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call Jennifer Reeves at 764.3570. Attachments: Staff review comments cc: Brazos Valley Bank Building Group, Ltd., via fax 979.690.2268 Joe Schultz, P.E., Texcon, Via fax 979.764.7759 Case file #04-00500233 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 2 Project: BRAZOS VALLEY BANK BUILDING SP) - 04-00500233 PLANNING 1. (Section 7.5.C.Landscape Requirements 4.) States: Every project must expend a minimum of 50% of its point total on canopy trees. It appears that 4,180 points are accrued by non-canopy trees and shrubs, and 3,340 are being accrued by Canopy trees. The total point requirement is 7,513. 50% of the total point requirement is 3,756.5. Please make landscape adjustments to meet the ordinance. Reviewed by: Jennifer Reeves Date: 10-20-04 ENGINEERING 1. The International Fire Code (Appendix B and C) must be used to determine the required fire flow for the bank building. The required fire flow is based on size of the building and construction type. The number of fire hydrants is then determined from the flow requirement. Reviewed by: Carol Cotter Date: November 1, 2004 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 3 ~i CITY OF COLLEGE STA11ON DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM October 8, 2004 TO: Robert L. Payne, AIA Via fax (979) 696-8114 FROM: Jennifer Reeves, Project Manager SUBJECT: BRAZOS VALLEY BANK BUILDING SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached Please note that the Easement Dedication Sheet and the necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Brazos Valley Bank Building Group, Ltd. Via fax (979) 690-2268 Texcon - Joe Schultz, P.E. Via fax (979) 764-7759 Case file #04-00500233 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: BRAZOS VALLEY BANK BUILDING SP) - 04-00500233 PLANNING 1. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right- of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. 2. Please be aware that signs are permitted separately. 3. The existing dumpster will need gates to screen it from the right-of-way. 4. Per the Fire Marshall's office (Steve Smith) the proposed fire hydrant located in the interior island adjacent to Graham Road will need to be relocated to the corner of Graham and the private drive. This will allow the FDC to be relocated on the west end island, of the first set of five parking spaces. The FDC is required to be located next to a fire lane. 5. Site specific note #5 needs to be changed to tmichalsky@cstx.gov 6. General not #13 needs to be changed to (UDO) Unified Development Ordinance. Ordinance #1638 is no longer applicable. 7. Please be aware that there will only be enough parking for the bank until the old bank building is removed and the rest of the parking is constructed. The proposed retail (4500 square feet) will not be issued a Certificate of Occupancy until all of the parking is complete. 8. Please be aware of Section 7.9 and Non-Residential Architectural Standards (A), (B), (C) Prohibited Materials, and (D) Building Mass and Design. LANDSCAPING/STREETSCAPING/BUFFER 9. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. 10. The end of parking rows adjacent to and visible from rights-of-ways will also need to be screened. Please provide additional shrubs. 11. Please be aware that all screening shrubs are required to be 3-feet in height at planting stage. 12. The additional 300 point streetscape calculation is also required along Graham road and the corner of the property. This will be an additional 338 linear feet divided by 50 x 300 = 2,028. Reviewed by: Jennifer Reeves Date: 10-07-04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 2 of 3 ENGINEERING 1. Provide water design report for fire protection. 2. The entire public fire line to the building requires a PUE unless it is made private by back flow prevention. 3. The notes on Sheet C5 refer to water line details sheet. Please add details or add a note that water and sewer construction to be in accordance with BCS Unified Design Guidelines and Standard Specifications and Details. Reviewed by: Carol Cotter Date: 10-07-04 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of rigid conduit for riser poles. Developer installs first 10'. City installs remainder. 4. Developer pours transformer pad(s) per city specs and design. 5. Developer installs pull boxes as per city specs and design.(pull boxes 6. provided by the city). 7. Developer provides digital AutoCAD 2000 version of plat and/or site plan. 8. email to tmichalsA_cstx.gov 9. Developer provides load data for project. 10. Developer provides temporary blanket easement for construction purposes. 11. Developer provides easements for electric infrastructure as installed for electric lines. 12. Once we receive site plan we will do an electric design for the installation of conduit. (Transformer location, you may want to locate closer to building. Metering will be on transformer. Cost of service from transformer to building responsibility of customer.) Also conduit must be installed from transformer location, through lot to provide electric service to lot 4 & 6, conduit crossing were installed across existing driveway. 13. To discuss any of the above electrical comments, please contact Tony Michalsky at 979.764.3438. Reviewed by: Tony Michalsky Date: 10-7-04 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 3 of 3 CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM October 8, 2004 TO: Brazos Valley Bank Building Group, Ltd. Via fax (979) 690-2268 FROM: Jennifer Reeves, Project Manager SUBJECT: BRAZOS VALLEY BANK BUILDING SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached Please note that the Easement Dedication Sheet and the necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Texcon - Joe Schultz, P.E. Via fax (979) 764-7759 Robert L. Payne, AIA Via fax (979) 696-8114 Case file #04-00500233 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: BRAZOS VALLEY BANK BUILDING SP) - 04-00500233 PLANNING 1. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right- of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. 2. Please be aware that signs are permitted separately. 3. The existing dumpster will need gates to screen it from the right-of-way. 4. Per the Fire Marshall's office (Steve Smith) the proposed fire hydrant located in the interior island adjacent to Graham Road will need to be relocated to the corner of Graham and the private drive. This will allow the FDC to be relocated on the west end island, of the first set of five parking spaces. The FDC is required to be located next to a fire lane. 5. Site specific note #5 needs to be changed to tmichalsky@cstx.gov 6. General not #13 needs to be changed to (UDO) Unified Development Ordinance. Ordinance #1638 is no longer applicable. 7. Please be aware that there will only be enough parking for the bank until the old bank building is removed and the rest of the parking is constructed. The proposed retail (4500 square feet) will not be issued a Certificate of Occupancy until all of the parking is complete. 8. Please be aware of Section 7.9 and Non-Residential Architectural Standards (A), (B), (C) Prohibited Materials, and (D) Building Mass and Design. LANDSCAPING/STREETSCAPING/BUFFER 9. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. 10. The end of parking rows adjacent to and visible from rights-of-ways will also need to be screened. Please provide additional shrubs. 11. Please be aware that all screening shrubs are required to be 3-feet in height at planting stage. 12. The additional 300 point streetscape calculation is also required along Graham road and the corner of the property. This will be an additional 338 linear feet divided by 50 x 300 = 2,028. Reviewed by: Jennifer Reeves Date: 10-07-04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 2 of 3 ENGINEERING 1. Provide water design report for fire protection. 2. The entire public fire line to the building requires a PUE unless it is made private by back flow prevention. 3. The notes on Sheet C5 refer to water line details sheet. Please add details or add a note that water and sewer construction to be in accordance with BCS Unified Design Guidelines and Standard Specifications and Details. Reviewed by: Carol Cotter Date: 10-07-04 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of rigid conduit for riser poles. Developer installs first 10'. City installs remainder. 4. Developer pours transformer pad(s) per city specs and design. 5. Developer installs pull boxes as per city specs and design.(pull boxes 6. provided by the city). 7. Developer provides digital AutoCAD 2000 version of plat and/or site plan. 8. email to tmichals .cstx.gov 9. Developer provides load data for project. 10. Developer provides temporary blanket easement for construction purposes. 11. Developer provides easements for electric infrastructure as installed for electric lines. 12. Once we receive site plan we will do an electric design for the installation of conduit. (Transformer location, you may want to locate closer to building. Metering will be on transformer. Cost of service from transformer to building responsibility of customer.) Also conduit must be installed from transformer location, through lot to provide electric service to lot 4 & 6, conduit crossing were installed across existing driveway. 13. To discuss any of the above electrical comments, please contact Tony Michalsky at 979.764.3438. Reviewed by Tony Michalsky Date: 10-7-04 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 3 of 3 CITY OF COLLEGE S'IAI"ION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764-3570 / Fax (979) 764-3496 MEMORANDUM October 8, 2004 TO: Texcon - Joe Schultz, P.E. Via fax (979) 764-7759 FROM: Jennifer Reeves, Project Manager SUBJECT: BRAZOS VALLEY BANK BUILDING SP) - Site Plan Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached Please note that the Easement Dedication Sheet and the necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Robert L. Payne, AIA Via fax (979) 696-8114 Brazos Valley Bank Building Group, Ltd. Via fax (979) 690-2268 Case file #04-00500233 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 1 Project: BRAZOS VALLEY BANK BUILDING SP) - 04-00500233 PLANNING f 1. Provide a general note that all roof and ground-mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right- of-way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. f 2. Please be aware that signs are permitted separately. Y The existing dumpster will need gates to screen it from the right-of-way. . Per the Fire Marshall's office (Steve Smith) the proposed fire hydrant located in the interior island adjacent to Graham Road will need to be relocated to the corner of Graham and the private drive. This will allow the FDC to be relocated on the west end island, of the first set of five parking spaces. The FDC is required to be located next to a fire lane. ✓5. Site specific note #5 needs to be changed to tmichalsky@cstx.gov ✓6. General not #13 needs to be changed to (UDO) Unified Development Ordinance. Ordinance #1638 is no longer applicable. J7. Please be aware that there will only be enough parking for the bank until the old bank building is removed and the rest of the parking is constructed. The proposed retail (4500 square feet) will not be issued a Certificate of Occupancy until all of the parking is complete. J8. Please be aware of Section 7.9 and Non-Residential Architectural Standards (A), (B), (C) Prohibited Materials, and (D) Building Mass and Design. J ANDSCAPING/STREETSCAPING/BUFFER b 9. Provide a general note that 100% coverage of roundcover, decorative 9 ~ paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights-of-way, and adjacent property disturbed during construction. .10. The end of parking rows adjacent to and visible from rights-of-ways will also need to be screened. Please provide additional shrubs. J11. Please be aware that all screening shrubs are required to be 3-feet in height at planting stage. J2. The additional 300 point streetscape calculation is also required along Graham road and the corner of the property. This will be an additional 338 linear feet divided by 50 x 300 = 2,028. Reviewed by: Jennifer Reeves Date: 10-07-04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 2 of 3 ENGINEERING 1. Provide water design report for fire protection. 2. The entire public fire line to the building requires a PUE unless it is made private by back flow prevention. 3. The notes on Sheet C5 refer to water line details sheet. Please add details or add a note that water and sewer construction to be in accordance with BCS Unified Design Guidelines and Standard Specifications and Details. Reviewed by: Carol Cotter Date: 10-07-04 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of rigid conduit for riser poles. Developer installs first 10'. City installs remainder. 4. Developer pours transformer pad(s) per city specs and design. 5. Developer installs pull boxes as per city specs and design.(pull boxes 6. provided by the city). 7. Developer provides digital AutoCAD 2000 version of plat and/or site plan. 8. email to tmichalsC)_cstx.gov 9. Developer provides load data for project. 10. Developer provides temporary blanket easement for construction purposes. 11. Developer provides easements for electric infrastructure as installed for electric lines. 12. Once we receive site plan we will do an electric design for the installation of conduit. (Transformer location, you may want to locate closer to building. Metering will be on transformer. Cost of service from transformer to building responsibility of customer.) Also conduit must be installed from transformer location, through lot to provide electric service to lot 4 & 6, conduit crossing were installed across existing driveway. 13. To discuss any of the above electrical comments, please contact Tony Michalsky at 979.764.3438. Reviewed by: Tony Michalsky Date: 10-7-04 MISCELLANEOUS Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 3 of 3 Response to Staff Review Comments No. 1 Brazos Valley Bank Building SP) - 04-00500233 Planning fl. See General Note #16. ,'2. Noted. .j3. Gates added to Site Plan. ,/4. The fire hydrant and FDC has been relocated as suggested. [Please note that the relocation of the fire hydrant increases the Vehicular Lay of Hose (VLH) to 372', which exceeds the 300' minimum required by the Unified Design Guidelines.] There is an existing fire hydrant on Graham Road at the North corner of the project that could be used, however it is not adjacent to the fire lane. Note changed. ✓6. Note changed. x/. See Site Specific Note #8. A. Noted. Landscaping / Streetscaping / buffer `I 9 - 12. Refer to Revised Landscape Plan. Engineering_ 1. Fire flow analysis and water design report provided. 2. Proposed PUE revised to extend to building. 3. Waterline detail sheet included with plan.