Loading...
HomeMy WebLinkAboutFire Flow Test EXHIBIT B SCHULTZ ENGINEERING, LLC FIRM #12327 WATER SYSTEM FIRE HYDRANT FLOW TEST REPORT 11 -16 -2016 Date: Water System Owner: _Wellborn SUD Saddle Creek Subdivision Development Project: East of the intersection of Latigo Court and Stirrup Drive Flow Test Location: Nozzle size (in.): _2.5 Discharge Coeff: (c) = 0.90 62 z i/z Pitot Reading (psi): Flowrate Formula: Q= 29.84cd p 1320 c = discharge coeff. Flowrate (gpm): d = orifice size (in) P = pitot pressure (psi) South of the intersection of Saddle Creek Drive and Stirrup Drive Pressure Gauge Location: 90 Static Pressure (psi): 60 Residual Pressure (psi): 2085 Computed Discharge at 20 psi Residual Pressure: QR = 0 54 0.54 Discharge Formula: QR = QF X (h� ' /hf ) Note: The flow test and report were prepared in accordance with NFPA 291. Joe Schultz Report Prepared by: Ricky Flores oF r • Others Present: _ Clenden Adams — Wellborn SUD_ ti 1* JOSEPH P. SCHULTZ _ Britt Curless •'�,.....65889, , I -f F -12327 /2 SCHULTZ ENGINEERING. LLC.