HomeMy WebLinkAboutSP2025-000013 Fire Flow Analysis Fire Flow Analysis Report for Brazos Valley Endodontic Associates College Station, Texas March 2025 Developer/Owner: Eilers Holdings, LLC 2901 E 29th Street Suite 117 College Station, Texas Prepared By: Schultz Engineering, LLC TBPE Firm #12327 911 Southwest Parkway East College Station, Texas 77840 979.764.3900 SE Job No. 24-188 D03/04/2024 Contents 1 General Information……………………………………………………………………………………1 1.1 Location……….…………………………..……………………………………….………………1 1.2 Primary Water Supply...………………..……………………………………….……………….1 2 Design Criteria…………………………………………………………………………….……………1 2.1 Pipe Selection……………………………...………………..…………………….……………….1 2.2 Existing System Pressure Tests……………..………………………………………..……………1 2.3 Demand – Domestic Use...………………………………………………...………………………2 2.4 Maximum Lengths for Water Mains………………………………………..……………………..1 3 Design………………………………………………..…………………………………………………2 3.1 Fire Flows…………………………………………………………...........……………….……….2 3.2 Domestic Design……..…………………………………………………………………………….2 3.3 Water System Summary.……………... …………………………………………………………..2 3.4 Design Results……………...………………………………………………………...……………2 4 Conclusion……………………………………………………………………………….……………..3 Exhibits A Vicinity Map B Water System Overall Layout C Flow Test Report D Pipe & Junction Analysis Summary – Domestic flow E Pipe & Junction Analysis Summary – Fire Flow Brazos Valley Endodontic Associates March 2025 1 1 General Information 1.1 Location The Brazos Valley Endodontic Associates is a 2.017 acre commercial development located in College Station. This project will be designed to meet the requirements of City of College Station. For location of the project site, refer to Exhibit A – Vicinity Map. 1.2 Primary Water Supply Brazos Valley Endodontic Associates water service is provided by an existing 6” line Corsair Drive. 2 Design Criteria 2.1 Pipe Selection 2.1.1 Pipe Materials Design Constraints: • Polyvinyl chloride pipe (PVC) shall be DR14 (meeting current AWWA C-900 standards) for sizes 4 through 12 inches; and DR 14 (meeting current AWWA C-905 standards) for sizes greater than 12 inches. • Type ‘K’ soft copper tubing shall be used for all service lines 2 inches and smaller. 2.1.2 Pipe Size Design Constraints: • The standard pipe sizes for water distribution mains are 4, 6, 8, 12, 16, and 18 inches in diameter. • Standard service lines within the right of way shall be 1, 1.5, or 2 inch. 2.2 Existing System Pressure Tests Flow Hydrant - See Exhibit C Flowrate: 1250 gpm Static Pressure: 80 psi Residual Pressure: 60 psi 2.3 Demand - Domestic Use Commercial Avg. Flow (Fixture Units): 6 gpm Peaking Factor: 4 Peak Flow: 24 gpm Brazos Valley Endodontic Associates March 2025 2 2.4 Maximum Lengths for Water Mains A 4-inch line may be allowed for permanent dead-end mains not exceeding 500 feet. A 6-inch main may be allowed up to a maximum of 1500 feet in length and must connect at each end to an 8 inch or larger main and shall have no more than 2 fire hydrants or flushing points. 3 Design 3.1 Fire Flows The minimum required fire flow for a Commercial Building IBC Type V-B of 3,620 sf is 1750 gallons per minute 3.2 Domestic Design Total Domestic Demand = 24 gpm The proposed 8” waterlines are in accordance with the Bryan/College Station Unified Design Guidelines – Domestic Water. This report provides the results of the water system analysis under the fire flow and domestic demand requirements, (1774 gpm) which produced the lowest pressure in the system. 3.3 Water System Summary As shown above the system exceeds the minimum required pressures of 35 psi for domestic flow and 20 psi for fire flow in both analyses. The maximum velocity of 11.76 fps is less than the required maximum of 12 fps. 3.4 Design Results Full design results shown in the following exhibits: Exhibit A – Vicinity Map Exhibit B – Water System Overall Layout Exhibit C – Flow Test Report Exhibit D – Pipe & Junction Analysis Summary – Domestic Flow Exhibit E – Pipe & Junction Analysis Summary – Fire Flow Summary of Calculations with Minimum Required Line Sizes Domestic Demand Pressure Min. 77.9 psi Velocity Max. 0.16 fps Fire Flow Demand FH Pressure Min. 29.4 psi Velocity Max. 11.76 fps Brazos Valley Endodontic Associates March 2025 3 4 Conclusion The proposed water lines and fire hydrants provide the required fire flow. The proposed 8” waterlines meet or exceed all of the design criteria for the Bryan/College Station Unified Design Guidelines – Domestic Water. They will provide adequate water pressure, flowrate and velocity for domestic demands and fire flow. EXHIBIT A VICINITY MAP VICINITY MAP NOT TO SCALECORSAIR DRIVESEBESTA ROADEMERALD PARKWA Y F O X F I R E D R I V E EXHIBIT A EXHIBIT B WATER SYSTEM OVERALL LAYOUT CORSAIR DR IVE LOT 11R 2.017 AC. S C A L E PL O TTIN G S C ALE : 1"=150' V E RTI C AL H O RIZ O N TAL FILE NA M E: SURV E YE D R C F D E SIG N ED R C F DRAW N APPR O V E D J P S J O B N O .D ATE 1:1 24-23624-236 J A N U A RY 2025 BWATER SYSTEM OVERALL LAYOUT E X H I B IT CAMWEST CROSSING II COLLEGE STATION, TX K E RR 911 Southwest Pkwy E. College Station, TX 77840 979.764.3900 TBPE NO. 12327 N/A EXHIBIT C FLOW TEST REPORT Date test completed Time completed Test completed by Witness FLOW HYDRANT Location Nozzle size Hydrant number Pitot reading in PSI Flow in G.P.M. STATIC HYDRANT Location Hydrant number Static PSI Residual PSI Requested By: Comments 1-23-25 Eric Macias Paul S 3109 CORSAIR DR 2.5 I-076 55 1250 1601 Harvey RD I-077 80 60 EXHIBIT D PIPE & JUNCTION ANALYSIS SUMMARY DOMESTIC FLOW Pipe Number Length (ft) Size (in) Material Hazen- Williams C Flow (gpm) Velocity (ft/s) P-1 173 6 PVC 110 14 0.16 P-2 90 8 PVC 110 24 0.15 P-RES1 32 6 PVC 110 14 0.16 P-3 9 8 PVC 110 0 0 P-4 356 6 PVC 110 -10 0.11 P-RES2 29 6 PVC 110 10 0.11 Junction Elevation Junction Demand (gpm) Pressure (psi) J-1 282.53 0 79.8 J-2 281.84 0 80.1 J-3 281.6 24 80.2 FH-1 281.58 0 80.2 J-4 287 0 77.9 Exhibit D WaterCAD Analysis Summary Pipe Analysis - Domestic Demand WaterCAD Analysis Summary Junction Analysis - Domestic Demand EXHIBIT E PIPE AND JUNCTION ANALYSIS SUMMARY FIRE FLOW Pipe Number Length (ft) Size (in) Material Hazen- Williams C Flow (gpm) Velocity (ft/s) P-1 173 6 PVC 110 1,037 11.76 P-2 90 8 PVC 110 1,774 11.32 P-RES1 32 6 PVC 110 1,037 11.76 P-3 9 8 PVC 110 -1,750 11.17 P-4 356 6 PVC 110 -737 8.37 P-RES2 29 6 PVC 110 737 8.37 Junction Elevation Junction Demand (gpm) Pressure (psi) J-1 282.53 0 40.2 J-2 281.84 0 32.4 J-3 281.6 24 29.7 FH-1 281.58 1,750 29.4 J-6 287 0 39 Junction Analysis - Fire Flow Demand (FH-1) Exhibit E WaterCAD Analysis Summary Pipe Analysis - Fire Flow Demand (FH-1) WaterCAD Analysis Summary