HomeMy WebLinkAboutCNEW2008-01814PREPARED 7/21/08, 12:04:10 INSPECTION TICKET PAGE 35
City of College Station INSPECTOR: BUILDING INSPECTOR DATE 7/21/08
------------------------------------------------------------------------------------------------
ADDRESS . : 12815 FM 2154 160 SUBDIV: EDELWEISS BUSINESS CENTER
TENANT, NBR: GAME WARDEN OFFICE
CONTRACTOR J H W CONTRACTORS PHONE (979) 693-1617
OWNER SOUTHWOOD WEST PHONE
PARCEL 244010-0002-0050
APPL NUMBER: 08-00001814 COMMERCIAL, OFFICES/BANKS/PROFESSION
------------------------------------------------------------------------------------------------
PERMIT: BLDG 00 BUILDING PERMIT
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
B115 01 7/01/08 BB BLDG, FRAMING TIME: 17:00
7/01/08 DP July 1, 2008 10:35:50 AM acarter.
Hold for elec rough in.
_ Seal penetrations through firewall. Need rated doors and
jambs, where specified. Post permit.
B115 02 7/03/08 DS BLDG, FRAMING TIME: 17:00
7/03/08 AE July 2, 2008 2:29:41 PM ccourt.
needs to fire caulk penatration in 1 hr wall
B125 01 7/17/08 BB BLDG, FINAL TIME: 17:00
7/17/08 DA July 17, 2008 11:20:08 AM ccourt.
Move return airs out of the bathroom.
B125 02 7/21/08 BI BLDG, FINAL TIME: 17:00
e July 21, 2008 11:18:51 AM ccourt.
-------------------------------------- COMMENTS AND NOTES--------------------------------------
(7/23/2008) Amber'Carter - Re: Calling for CO for!2815 FM' 2154 Ste 160 page 1
From: Donnie Willis
To: Carter, Amber
Date: 7/23/2008 8:29 AM
Subject: Re: Calling for CO for 12815 FM 2154 Ste 160
OK with Drainage.
Donnie Willis, CFM
Environmental Engineering Technician
Certified Floodplain Manager
Public Works Department
979-764-6375 office
979-229-7632 cell
dwillis@cstx.gov
>>> On 7/23/2008 at 8:29 am, in message<4886EBCE.1265.003D.0@cstx.gov>, Amber Carter wrote:
Game Warden Office
by 08-1814
Owner Southwood West
Any issues, please contact JHW @ 693-1617.
[(7/30/2008) Gina Southerlarid - Re: Calllrig for CO for 12815 FM 2154 Ste 160 Page 1
From:
Pete Garcia
To:
COS
Date:
7/23/2008 3:48 PM
Subject:
Re: Calling for CO for 12815 FM 2154 Ste 160
Attachments:
Pete Garcia.vcf
They are OK.
'Do not ask the Lord to Guide your Footsteps if you are not willing to move your Feet'
This e-mail and/or attachment is for the sole use of the intended recipient(s) and may contain confidential and /or legally privileged
information. Any unauthorized review, use, disclosure or distribution is prohibited. If you are not the intended recipient, please
contact the sender by reply e-mail and destroy all electronic and paper copies of the original message and any attachments. Thank
You.
>>> On 7/23/2008 at 8:45 AM, in message<4886EF93.1265.003D.O(�cstx.aov>, Amber Carter wrote:
Game Warden Office - Interior work only
by 08-1814
Owner Southwood West
Any issues, please contact JHW @ 693-1617.
Thanks!
(7/30/2008) Gma Southerland yRe': Calling for CO for 12815tl FM 2154 Ste 160 M11111-1� Page 1
From: Eric Dotson
To: Alan Gibbs; Amber Carter; Benjamin McCarty; Brenda Godfrey; Bridgett...
Date: 7/24/2008 11:03 AM
Subject: Re: Calling for CO for 12815 FM 2154 Ste 160
No for CO no fire extinguisher
Eric Dotson '06
Deputy Fire Marshal
College Station Fire Department
edotson@cstx.gov
(979)764-3709
(979)764-3705
Fax(979)764-3403
>>> Amber Carter 7/23/2008 8:45 AM >>>
Game Warden Office - Interior work only
by 08-1814
Owner Southwood West
Any issues, please contact JHW @ 693-1617.
Thanks!
(7/30/2008) Gina Southerland Re-Callingfor CO for 12811-5 FM 2154 Ste 160 Page 1
From: Mitchell Carson
To: Alan Gibbs; Amber Carter; Benjamin McCarty; Brenda Godfrey; Bridgett...
Date: 7/24/2008 10:53 AM
Subject: Re: Calling for CO for 12815 FM 2154 Ste 160
This one is ok..... Mitch
>>> Amber Carter 07/23/08 8:45 AM >>>
Game Warden Office - Interior work only
by 08-1814
Owner Southwood West
Any issues, please contact JHW @ 693-1617.
Thanks!
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Application Number . . . . . 08-00001814 Date 6/18/08
Application pin number . . . 916006
Property Address . . . . . . 12815 FM 2154 160
Property ID: 244010-0002-0050
R #: R113840
Tenant nbr, name . . . . . . TENANT FINISHOUT
Application type description COMMERCIAL, OFFICES/BANKS/PROFESSION
Subdivision Name . . . . . . EDELWEISS BUSINESS CENTER
Property Use . . . . . . . .
Property Zoning . . . . . . . GENERAL COMMERCIAL
Application valuation . . . . 18000
Owner
Contractor
------------------------
SOUTHWOOD WEST
------------------------
J H W CONTRACTORS
4101 S TEXAS AVE
# B PO BOX 10220
BRYAN
TX 778024024 COLLEGE STATION TX 77842
(979) 693-1617
--- Structure Information
000 000 NEW GAME WARDEN OFFICE REMODEL
Construction Type
. . . . . COMBUSTIBLE (UNPROTECTED)
Occupancy Type .
. . . . . BUSINESS
Other struct info
. . . . . EXTERIOR WALL TYPE BRICK
IMPACT/PR�RATA FEES PAID N/A
FOUNDATION TYPE SLAB
HEATED AREA 2107.00
INTERIOR WALL TYPE SHEETROCK
SEWER TYPE PUBLIC
TRAFFIC IMPACT ANAL (TAZ) .10
----------------------------------------------------------------------------
Permit . . . . .
. BUILDING PERMIT
Additional desc .
. AC
Permit pin number
. 581926
Permit Fee . . .
. 100.00 Plan Check Fee .00
Issue Date . . .
. 6/18/08 Valuation . . . . 18000
Expiration Date .
. 12/15/08
Qty Unit Charge
Per Extension
BASE FEE 15.00
17.00 5.0000
THOU BLDG, VAL 1001-50000 85.00
----------------------------------------------------------------------------
Special Notes and
Comments
PROVIDE ADDRESS
ON COMMERCIAL BUILDINGS -FRONT: 5" ADDRESS
NUMBERS, AND ON
REAR DOOR(S): 2" HIGH ADDRESS NUMBERS AND
NAME OF BUSINESS.
FOR MULTI -FAMILY RESIDENTIAL PROVIDE UNIT
NUMBER ON FRONT
DOOR AND IDENTIFY EACH UNIT FROM A REAR FIRE
LANE. IDENTIFY
MULTI -FAMILY BUILDINGS WITH 12" BUILDING
-
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 2
Application Number . . . . . 08-00001814 Date 6/18/08
Application pin number . . . 916006
----------------------------------------------------------------------------
Special Notes and Comments
NUMBERS, VISIBLE FROM ALL ADJACENT/NEARBY FIRE LANES. ALL
NUMBERS AND LETTERS SHALL HAVE CONTRASTING BACKGROUNDS.
THE TEXAS DEPARTMENT OF HEALTH REQUIRES AN ASBESTOS SURVEY
IN CERTAIN CIRCUMSTANCES - CALL TDH Q (254) 778-6744 FOR
MORE INFORMATION
Shall advertise only the name of, uses of, or goods or
services available within the building, or tenant lease
space, to which the banner is attached.
Shall be mounted parallel to the face of the building.
Shall not be cantilevered away from the structure.
Shall not extend more than one foot from any exterior
building face, mansard, awning, or canopy.
Shall not obstruct any window, door, stairway, or other
opening intended for ingress or for needed ventilation or
light.
Shall not be attached to any tree, fence, or public utility
pole.
NOTE FROM WATER DEPT--REDUCED PRESSURE ASSEMBLY REQUIRED FOR
CAR WASH, POSTMIX CARBONATER, AND HEATING/AC WITH DIRECT
CONNECTION TO WATER SUPPLY, WATER SUPPLY LINES SERVING THE
THIRD FLOOR OR HIGHER, AND LAWN IRRIGATION SYSTEMS.
ALL DEVICES MUST BE TESTED UPON INSTALLATION BY CERTIFIED
TESTER REGISTERED WITH THE CITY OF COLLEGE STATION PUBLIC
UTILITIES DEPT. LAWN IRRIGATION MAY USE A PRESSURE VACCUM
BREAKER INSTALLED PER AWWA STANDARDS AND CITY'S ORD #2394.
ALL DEVICES MUST BE INSTALLED PER AWWA AND CITY'S ORD#2394
PROVIDE COMBUSTION AIR: FOR GAS -FIRED APPLIANCES PER SECTION
304 OF THE 2006 INTERNATIONAL FUEL GAS CODE; FOR OTHER FUELS
TO COMPLY WITH CHAPTER 7 OF THE 2006 IMC.
*ELECTRICAL SHALL BE INSTALLED PER 2005 National Electrical
Code & LOCAL AMENDMENTS
PROVIDE EXTERIOR LANDING LEVEL WITH THE INTERIOR FLOOR FOR
REQUIRED EXIT DOOR(S)
PROVIDE FIRE EXTINGUISHER(S) - VERIFY LOCATION AND PLACEMENT
WITH THE FIRE MARSHALL'S OFFICE (MIN. 2A10BC)
*Assure Proper GFI Locations, Including One Within 25' Of
Outside A/C Unit
PROVIDE MINIMUM 42" CLEARANCE FROM CENTER LINE OF WATER
CLOSET TO EDGE OF LAVATORY OR WALL TO COMPLY WITH ANSI 2003,
ACCESSIBLE STANDARDS.
PROVIDE A KNOX BOX FOR FIRE DEPARTMENT ACCESS. A KEY FOR
----------------------------- ___---------------
BUILDING DEPT REPRESENTATIVE:
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
Application Number . . . . . 08-00001814
Application pin number . . . 916006
Page 3
Date 6/18/08
Special Notes and Comments
EACH SHELL BUILDING AND/ OR TENANT DOOR IS REQUIRED.
REQUIRED EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE
WITHOUT THE USE OF A KEY,TOOL OR SPECIAL KNOWLEDGE/EFFORT
INTERIOR LIGHTING SHALL MEET THE CONTROLS AND WATTAGE
REQUIREMENTS OF SECTION 505 OF THE 2006 INTERNATIONAL ENERGY
CONSERVATION CODE.
All roof and ground -mounted mechanical equipment shall be
sreened from view or isolated so as not to be visible from
any public right-of-way or residential district within 150
feet of the subject lot, measured from a point five feet
above grade. Such screening shall be coordinated with the
building architecture and scale to maintain a unified
appearance. Acceptable methods of screening rooftop
equipment may include, but are not limited to encasement,
parapet walls, or partition screens.
CONSTRUCTION ACTIVITY BETWEEN THE HOURS OF 10:00 PM AND
7:00 AM MUST COMPLY WITH THE NOISE ORDINANCE (MAX. 55 DBA)
*If PEX water supply piping is sleeved below the slab, seal
annular space at ends with caulk, foam or other means.
Also assure proper protection of pipe to U.V. light.
*ANY CHANGES OR ALTERATIONS TO SUBMITTED PLANS MUST BE
RESUBMITTED AND APPROVED BEFORE WORK IS DONE IN ORDER TO
ASSURE CODE COMPLIANCE
*POST PERMIT CARD ON JOB SITE TO BE VISIBLE FROM ROAD
AS PER THE ZONING ORDINANCE SECTION 12.3.L; ATTACHED
SIGNS SHALL NOT EXTEND MORE THAN ONE FOOT AWAY
FROM EXTERIOR BUILDING FACE
*TEMPERED GLASS REQUIRED IN WINDOWS WITHIN 24" OF DOORS IN
ADJACENT WALLS
*ALL PLUMBING, ELECTRICAL, AND HVAC (mechanical) WORK MUST
BE PERFORMED BY LICENSED CONTRACTORS. CONTACT BUILDING
DEPARTMENT FOR INSPECTIONS PRIOR TO COVERING ANY WORK
Fee summary Charged Paid Credited Due
---------------------------------------------------------
Permit Fee Total 100.00 100.00 .00 .00
Plan Check Total .00 .00 .00 .00
Grand Total 100.00 100.00 .00 .00
----------------------------------- - - --------------
BUILDING DEPT REPRESENTATIVE: •
APPLICANT:
6
APPLICATION FOR BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
COLLEGE STATION, TX 77840
CITY OF COLLEGE STATION (979) 764-3570 (979) 764-3496 FAX
Planning L+ Development Services WWW CSTX.GOV
APPLICATION #
TEMP POLE #
ADDRESS/LOCATION: ZS L5 nt -:215-4 54 1160
LOT �S�I b BLOCK SUBDIVISION _GGI f b SEC/PH
BUSINESS/OWNER NAME: SOuAm ootl, Wet' PHONE: (093-I (p 1-1
CONTRACTOR/HOMEOWNER: JRW --qj G , PHONE: (011-1141-1
CONTACT PERSON FOR REVIEW COMMENTS: -SiXt Waco 5 PHONE: 1-7-7-6 9(o7
FAX: �79-t4b-913'S
ELECTRICIAN: Qk IL ?1 G r,
HVAC:
EMAIL: �k.w4c m Syddtnlinkmail .Cosk
PLUMBER: !iJA
GOOD CENTS (Residential only):
ACCESSORY/STORAGE MOVING RE -ROOF
ADDITION 10 NEW CONSTRUCTION" SHELL ONLY
DEMOLITION (ASBESTOS SURVEY) PORTABLE STORAGE (RESIDENTIAL) SLAB ONLY
DUPLEX (LANDSCAPE PLANS REQUIRED) PORTABLE STORAGE (NON-RESIDENTIAL) SWIMMING POOL
LOCATION EMODEURENOVATION' TENTS
DESCRIPTION OF WORK: :CkTj2Z_(L-Q 1 0e&-n MIq — Eltdrfn'ai -jSoilA WA115
PROPOSED USE: _ 0Vf=C`c.8
STRUCTURE USE: -em0 oYpt�
HOMEOWNER ASSOCIATION/ARCHITECTUAL OR DESIGN REVIEW COMMITTEE APPROVAL: NIA
O� TEXAS ACCESSIBILITY STANDARD (TAS) PROJECT REGISTRATION# EABPRJ µV
VALUATION: $ / e O OD , TOTAL AREA: a 1 O -j HEATED AREA: J 1 o-I
(Cost of Labor and Materials)
❑ PUBLIC SEWER
SEPTIC/TREATMENT SYSTEM
❑ SEWER TAP:
WATER TAP:
OTHER TAP:
0 TEMP POLE
GARAGE TYPE
SIZE
SIZE
SIZE
SINGLE
ATTACHED
NUMBER OF BEDROOMS:
NUMBER OF BATHROOMS:
INTERIOR WALL TYPE:
EXTERIOR WALL TYPE:
FOUNDATION TYPE:
ROOF TYPE:
DOUBLE [:] TRIPLE
DETACHED F—] CARPORT
—1
SIGNATURE OF APPLICANT: t�Wrk" 1t�(_
*If proposed work involves new commercial c nstruction or facade improvements/renovations to an existing
commercial property, building elevations are required.
............................................................
Official Use Only
Comments:
�rNO
Plans Examiner Zoning Official
Energy Code Compliance Information
% Glazing of exterior walls
Insulation R value of exterior walls
Insulation R value of ceiling 1 (flat areas)
Insulation R value of ceiling 2 (vaulted areas/no attic)
Glazing SHGC (Solar Heat Gain Coefficient)
Glazing U-Factor
R value of ductwork
A/C SEER Rating
Protection Against Subterranean Termites
❑ Chemical Termiticide Treatment (Soil Treatment)
❑ Chemical Termiticide Treatment (Field Applied Wood Treatment)
❑ Physical Barriers
❑ Other
* Verification of Application shall be submitted to the City of College Station
Building Division prior to issuance of the Certificate of Occupancy.
3
JHW, INC.
P.O. Box 10220
COLLEGE STATION, TX 77842
(979) 693-1617
FAX: (979) 846-9133
jhwgc@sudden1inkmai1;com
TO
_ WE ARE SENDING YOU ❑ Attached ❑ Under separate cover via.
❑ Shop drawings ❑ Prints ❑ Plans
❑ Copy of letter ❑ Change order ❑
LETTER OF TRANSMITTAL
DATE
2
ATTENTION
RE
! 2 $ al 64 Sk-]too
the following items:
❑ Samples ❑ Specifications
COPIES DATE NO. DESCRIPTION
antw
THESE ARE TRANSMITTED as checked below:
Wfor approval ❑ Approved as submitted
❑ For your use ❑ Approved as noted
❑ As requested ❑ Returned for corrections
❑ For review and comment ❑
❑ FOR BIDS DUE
REMARKS
❑ Resubmit copies for approval
❑ Submit copies for distribution
❑ Return corrected prints
❑ PRINTS RETURNED AFTER LOAN TO US
COPY TO
SIGNED:
It enclosured are not as noted, kindly notify us at once.