HomeMy WebLinkAboutRES2008-0158790 /687 1
WF1044997 / 001 City of College Station PAGE 1
REQ. DATE: 06/10/08 06/10/08 12:25:47
LOCATION: 929 DOVE LANDING AVE LOC ID: 209238
REQUESTOR: KM CUSTOM HOMES ORIGIN: CUSTOMER -WALK IN
REQ USER: CCOURT AUTH USER:CCOURT WRK TYPE:
WTR 3/4" SWR 4"
********************************************************************************
TASK: SET UP NEW UTILITY ACCT SET READY
SCHED START: 06/10/08 SCHED COMPLETION: 06/10/08
********************************************************************************
JOB ORDER RESULT COMMENTS
(9/10/2008 Beth Boerboom - Re Calling for CO for 929 Dove Landing Page 1
From: Paul Schoenfeld
To: Benjamin McCarty; Beth Boerboom; Chris Haver; Christina Court; Gina ...
Date: 9/10/2008 11:36 AM
Subject: Re: Calling for CO for 929 Dove Landing
NO for CO.
Sewer box needs to be raised.
Paul
>>> Christina Court 9/8/2008 12:51 PM >>>
any issues?
by#08-1587
Christina Court
CSR
Planning & Development
City Of College Station
979.764.3570
Sep 09 08 02:50p MACIAS
4A
Ace Pest Controt
PO Box 4474
Bryan TX 77805
Bill To
KM CUSTOM HOMES, INC.
12633 STATE HWY 30
COLLEGE STATION, TX. 77845
9797744736 p.2
Date: September 9, 2008
979-823-7777
TPCL 712OPT
Professions' Se-v:ces A' An A ord-a�Ie F1,:e
All bills DUE on or before the 10"h of the month
following date of service. Service Charge of
1 % %, per month (18% per year)
Added to Past Dues Accounts. THIS PORTION 1S
FOR YOUR RECORDS. YOUR CHECK IS YOUR
RECIEPT
Service
Type Of Service
Linear
Square ft
Check#
Amount
Date
ft
j 215 ME SLAB PRETREAT
225
1-
9354
8/15/08
7/18/2008
H:1974
_06 BIFENTHRIN SOLUTION 65 GALS
213 MEIR ✓ SLAB PRETREAT
225
9354
8/15108
7/16/2008
H:1974
_06 BIFENTHRIN SOLUTION 65 GALS
923 DOVE LANDING ✓ SLAB PRETREAT
212
9354
8/15X8
7115/2008
H:1625
06 BIFENTRIN SOLUTION 60 GALS
925 DOVE LANDING ✓ SLAB PRETREAT
216
9354
8/15108
7114/2008
H:1720
.06 BIFENTHRIN SOLUTION 60 GALS
947 DOVE LANDING ✓ SLAB PRETREAT
205
9409
8/27/08
6/24/2008
H:1856
.06 BIFENTHRIN SOLUTION 60 GALS
927 DOVE LANDING ✓ SLAB PRETREAT
201
9409
8/27108
6/23/2008
H:1720
.06 BIFENTHRIN SOLUTION 60 GALS
h�
929 DOVE LANDING ✓ SLAB PRETREAT
192
9409
8/27/013
6/16/2008
H:1720
.06 BIFENTRIN SOLUTION 60 GALS
5.15'
am ftmmm ftw� mws-�
c7c 7
...r� ....n.► 9 �
so �59 5
55.
15",
� I
DRIVE I
55.1
....EM =WAN
I
lk
93�q Do\f t La.d�n) Avc..
PREPARED 9/10/08, 7:53:12 INSPECTION TICKET PAGE 11
City of College Station INSPECTOR: BUILDING INSPECTOR DATE 9/09/08
------------------------------------------------------------------------------------------------
ADDRESS . : 929 DOVE LANDING AVE SUBDIV: DOVE CROSSING PH 3
CONTRACTOR K M CUSTOM HOMES PHONE (979) 589-3739
OWNER PHI -TON INVESTMENTS L.P. PHONE
PARCEL 230100-0309-0240
APPL NUMBER: 08-00001587 RESIDENTIAL, 1 UNIT DETACHED NEW
------------------------------------------------------------------------------------------------
PERMIT: BLDG 00 BUILDING PERMIT
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
B100 01 6/18/08 RH BLDG, FOUNDATION -SLAB TIME: 17:00
6/18/08 AP June 18, 2008 10:45:04 AM ccourt.
Strings up, slab ground installed.
B120 01 7/08/08 OC BLDG, FRAMING -PARTIAL TIME: 17:00
7/08/08 AP July 7, 2008 3:19:51 PM acarter.
apa inspection
sheetrock fireplace chase.
B115 01 7/24/08 TB BLDG, FRAMING TIME: 17:00
7/25/08 AP July 24, 2008 12:05:29 PM acarter.
VENT EXHAUST FANS BY INSULATION
B130 01 7/28/08 RH BLDG, INSULATION TIME: 17:00
7/28/08 AP July 25, 2008 3:40:26 PM glsouth.
B125 01 9/08/08 BB BLDG, FINAL TIME: 17:00
9/08/08 DA September 8, 2008 12:04:35 PM glsouth.
Need clamp on elec. whip. Need fixture or blank installed on
open box in attic, by furnace.
B125 02 9/09/08 BI BLDG, FINAL TIME: 17:00
�/� 0-00 -September 9, 2008 1:20:09 PM bboerboom.
-------------------------------------- COMMENTS AND NOTES -----------------------------------
7-/vim �l
Date: 9/10/2008
Inspection Comments for Final,
Permit Year: 8 'ermit Number: 1587
Address: 929 DOVE LANDING AVE
insp.
Type
Inspection Type Code
Description
Insp
status
Inspection Result Comments
B100
BLDG, FOUNDATION -SLR
IC
Strings up, slab ground installed.
6115
BLDG, FRAMING
IC
VENT EXHAUST FANS BY INSULATION
B120
BLDG, FRAMING-PARTIA
IC
sheetrock fireplace chase.
B125
BLDG, FINAL
IC
Need clamp on elec. whip. Need fixture or blank installed
B125
BLDG, FINAL
IC
open box in attic, by furnace.
E150
ELEC, FINAL
IC
need service at meter.
M100
MECH, ROUGH IN
IC
EXHAUST FANS NOT DUCTED OUT, DO BY
lKlCl n ATll'%Kl
M110
MECH, FINAL
IC
Need grille on A/C register in front bathroom. Need clamp
M110
MECH, FINAL
IC
electrical whip for condenser.
P100
PLBG, ROUGH IN
IC
June 13, 2008 8:53:26 AM ccourt.
Page 1
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3576 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Application Number . . . . . 08-00001587 Date 6/10/08
Application pin number . . . 726241
Property Address . . . . . . 929 DOVE LANDING AVE
Property ID: 230100-0309-0240
R #: R305811
Application type description RESIDENTIAL, 1 UNIT DETACHED NEW
Subdivision Name . . . . . . DOVE CROSSING PH 3
Property Use . . . . . . . . RESIDENTIAL
Property Zoning . . . . . . . SINGLE FAMILY RESIDENTIAL
Application valuation . . . . 113000
Owner Contractor
------------------------ ------------------------
PHI-TON INVESTMENTS L.P. K M CUSTOM HOMES
1401 SEBESTA RD 232 SOUTHWEST PKWY E
COLLEGE STATION TX 778455527 COLLEGE STATION TX 77840
(979) 589-3739
--- Structure Information 000 000 SINGLE FAMILY
Construction Type . . . . . COMBUSTIBLE (UNPROTECTED)
Occupancy Type . . . . . . RESIDENTIAL-SFR/DUPLEX
Other struct info . . . . . A/C SEER RATING 14.00
CEILING 1 R VAL. (FLAT) 30.00
CEILING 2 R VAL-NO ATTIC 19.00
DUCT R VALUE 6.00
EXTERIOR WALL TYPE BRICK
IMPACT/PRORATA FEES PAID N/A
FOUNDATION TYPE SLAB
NUMBER OF GARAGE BAYS 2.00
TYPE OF GARAGE (ATT/DET) ATT
% GLAZING 10.00
GLAZING U-FACTOR .65
HEATED AREA 1712.00
INTERIOR WALL TYPE SHEETROCK
NUMBER OF BATHROOMS 3.00
NUMBER OF BEDROOMS 4.00
EXTERIOR WALL INSUL R VAL 13.00
GLAZING SHGC .40
SEWER TYPE PUBLIC
TRAFFIC IMPACT ANAL (TAZ) 405.00
----------------------------------------------------------------------------
Permit . . . . . . BUILDING PERMIT
Additional desc . . CC
Permit pin number . 579623
Permit Fee . . . . 499.00 Plan Check Fee .00
Issue Date . . . . 6/10/08 Valuation . . . . 113000
Expiration Date 12/07/08
` - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ----------
BUILDING DEPT ;2;T IVE:
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
Application Number .
Application pin number
Qty Unit Charge Per
13.00 3.0000 THOU
08-00001587
726241
BASE FEE
BLDG, VAL 100001-500000
Page 2
Date 6/10/08
Special Notes and Comments
-Add smoke detectors inside and outside bedroom #4
-Narrow Wall Bracing Fully Sheathed with 16" Minimum APA
Garage Framing
*ALL BRANCH CIRCUITS THAT SUPPLY OUTLETS IN DWELLING
UNIT BEDROOMS SHALL BE PROTECTED BY AN ARC -FAULT CIRCUIT
INTERRUPTERS)
*PROVIDE CHEMICAL TREATMENT OR PHYSICAL BARRIER (SUCH AS
METAL OR PLASTIC TERMITE SHIELDS) FOR PROTECTION
AGAINST TERMITES. IF CHEMICAL TREATMENT IS USED, THE
CONCENTRATION, RATE OF APPLICATION AND TREATMENT
METHOD SHALL BE CONSISTENT WITH THE TERMITICIDE LABEL.
BORACARE TREATMENT IS A SUITABLE SUBSTITUTE.
ALL METHODS MUST BE USED IN CONJUNCTION WITH TREATED
SILL PLATES. PROOF OF METHOD TO BE USED SHALL BE RECEIVED
IN OUR OFFICE BEFORE A CERTIFICATE OF OCCUPANCY WILL BE
ISSUED.
*PROVIDE COMBUSTION AIR FOR GAS FIRED APPLIANCES PER
CHAPTER 17, 2006 INTERNATIONAL RESIDENTIAL CODE
*Surface Drainage Shall Be Diverted to an Approved Point of
Collection. Lots Shall Have a Grade Fall Minimum of 6"
inches Within the First 10' feet Away From the Foundation
Walls.
*ELECTRICAL SHALL BE INSTALLED PER 2005 National Electrical
Code & LOCAL AMENDMENTS
*ELECTRIC STRIP HEATING NOT ALLOWED FOR RESIDENTIAL
PROPERTIES WITH FLOOR AREA GREATER THAN 500 Sq. FEET
*MINIMUM FOUNDATION STANDARD - ALL FOUNDATION SHALL COMPLY
WITH THE MINIMUM FOUNDATION STANDARD AS PER CITY'S
ORDINANCE (FOUNDATION DETAIL SHALL BE SHOWN ON PLANS)
MAKE SURE TO INCLUDE REBAR SLAB GROUND
*ALL FRAMING SHALL COMPLY WITH 2O06 INTERNATIONAL
RESIDENTIAL CODE
*PROVIDE ENGINEERED BEAM FOR GARAGE DOOR HEADER
*ATTACHED GARAGES SHALL HAVE ALL TOP PLATE AND HEADER
PENETRATIONS SEALED
Extension
460.00
39.00
*Assure Proper GFI Locations, Includin One Within 25' Of
Outside A/C Unit .
---------------------------------------- - -- -�-----------
BUILDING DEPT Pj'fRIXSEjgT4VE :
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 3
Application Number . . . . . 08-00001587 Date 6/10/08
Application pin number . . . 726241
----------------------------------------------------------------------------
Special Notes and Comments
*PLATFORM FOR MECHANICAL EQUIPMENT AND/OR ACCESS MAY HAVE TO
BE ELEVATED TO ALLOW FOR ATTIC INSULATION
*Wall and Ceiling Insulation are as follows respectively.
If Wall to Window Ratio is up to 150-. the Values Shall be
R-13 and R-30, above 15% the Ceiling Insulation is Increased
to R-38.
*ACCESS TO JACUZZI TUB CIRCULATION PUMPS SHALL BE PROVIDED
IN ACCORDANCE WITH 421.5 OF THE 2006 INTERNATIONAL PLUMBING
CODE. IF NOT DETERMINED BY MANUFACTURER IT SHALL BE A
MINIMUM OF 12" X 12" AND IF PUMP IS GREATER THAN 2' FROM
ACCESS OPENING THEN IT MUST BE 18" X 18" OPENING
*IF LAWN SPRINKLERS IS PROVIDED, PERMIT MUST BE ISSUED PRIOR
TO CERTIFICATE OF OCCUPANCY.
*REQUIRED EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE
WITHOUT THE USE OF A KEY,TOOL OR SPECIAL KNOWLEDGE/EFFORT
*A Minimum of No. 15 Asphalt Felt or Other Approved Water
Resisitive Barrier Shall be Placed Over All Exterior
Sheathing Per 2006 IRC Section R703.2
* THE MAXIMUM ALLOWABLE RESIDENTIAL DRIVEWAY WIDTH MEASURED
AT THE PROPERTY LINE IS 25' AND MINIMUM WIDTH OF 12'
*DRIVEWAY DISTANCE FROM CORNER: "NO RESIDENTIAL DRIVEWAY
SHALL BE CONSTRUCTED WITHIN TWENTY FEET (201) OF THE
CORNER OF A STREET INTERSECTION. THIS MEASUREMENT
SHALL BE TAKEN FROM THE INTERSECTION OF PROPERTY LINES
AT THE CORNER." ALSO NOTHING SHALL BE CONSTRUCTED IN
THIS TRIANGLE TO IMPAIR VEHICLE DRIVERS VISION.
*MUST INDICATE METHODS ON FLOOR PLAN TO BE USED TO MEET
NARROW WALL BRACING REQUIREMENTS PER CODE SECTION R602.10 IN
2006 IRC
*ON NARROW WALL BRACING WHERE SPECIAL NAILING PATTERN OR
HOLD DOWNS ARE REQUIRED THESE ITEMS MUST REMAIN VISIBLE
UNTIL THE INSPECTION PROCESS HAS BEEN DONE TO ALLOW FOR
COVER-UP. A SPECIAL "APA" NAILING PATTERN INSPECTION SHALL
BE PERFORMED PRIOR TO FRAMING INSPECTION.
*If PEX water supply piping is sleeved below the slab, seal
annular space at ends with caulk, foam or other means.
Also assure proper protection of pipe to U.V. light.
*ANY CHANGES OR ALTERATIONS TO SUBMITTED PLANS MUST BE
RESUBMITTED AND APPROVED BEFORE WORK IS DONE IN ORDER TO
ASSURE CODE COMPLIANCE
*POST PERMIT CARD ON JOB SITE TO BE VIS BLE FROM ROAD
------------------------------------------------—'sst�----------
BUILDING DEPT R#RFgENTAAIVE :
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
Application Number . . . . . 08-00001587
Application pin number . . . 726241
Page 4
Date 6/10/08
Special Notes and Comments
*WHEN WATER MAIN PRESSURE EXCEEDS 80 PSI, AN APPROVED
PRESSURE REDUCING VALVE SHALL BE PROVIDED THAT LIMITS THE
MAXIMUM STATIC WATER PRESSURE TO 80 PSI
*RECESSED LIGHTING INSTALLED IN THE BUILDING ENVELOPE SHALL
BE IC RATED AND SEALED TO PREVENT AIR LEAKAGE
*For residential applications with a glazing area that
exceeds 15% of the gross area of exterior walls, R-8 duct
insulation is required. As an alternative, R-6 duct
insulation can be used if the a/c system has a SEER rating
of 12 or more.
*PROVIDE SANITARY FACILITIES/PORTA-CAN FOR WORKERS ON SITE
LOCATED OFF
THE PUBLIC RIGHT-OF-WAY.
*ADD SMOKE DETECTOR(S) PER NOTES ON PLANS
*SMOKE DETECTORS MUST HAVE 3' CLEARANCE FROM FORCED AIR
DUCTS, CEILING FANS AND RETURN AIR
*PROVIDE STRING LINES FOR ALL BUILDING SETBACKS AND
EASEMENTS ON FOUNDATION INSPECTION.
FORM SURVEY MAY BE SUBMITTED IN PLACE OF STRINGS.
*SHOWERS AND TUB/SHOWER COMBINATIONS SHALL BE EQUIPPED WITH
AN ANTI -SCALD VALVE THAT LIMITS WATER TEMPERATURE TO 120
DEGREES
*THE COMBINED SOLAR HEAT GAIN COEFFICIENT OF ALL GLAZED
FENESTRATION/WINDOW PRODUCTS DEPENDING ON PERCENTAGE OF WALL
TO GLAZING/WINDOW RATIO UP TO 20% A .40 OR LOWER FACTOR AND
ABOVE 20% TO 30% A .35 FACTOR OR LOWER SHALL BE MET.
*U-Factor Ratings for Window % up to 15% is .65, from 15% to
20% is .55, from 20% to 25% is .54 and above 25% is .46 or
lower.
*ALL SILLS AND BOTTOM PLATES IN CONTACT WITH CONRETE MUST BE
TREATED OR NATURALLY RESISTANT TO INSECTS AND DECAY
*SMOKE DETECTORS SHALL BE INTERCONNECTED, 120 VOLT W/BATTERY
BACKUP AND LOCATED IN EACH SLEEPING ROOM AND OUTSIDE EACH
SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
BEDROOMS
*REMOVE ALL VEGETATION AND FOREIGN MATERIAL FROM SLAB AREA
PRIOR TO PLACING FILL. FILL SHALL BE FREE FROM
VEGETATION AND FOREIGN MATERIAL.
*WINDOWS ADJACENT TO TUBS WITHIN 60" ABOVE DRAIN SHALL BE
TEMPERED GLASS
*TEMPERED GLASS REQUIRED IN WINDOWS WITH N 24" OF DOORS IN
--------------------------------------------- ------ --- '#-------------
BUILDING DEPT R E T E:
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page
5
Application Number . . . . . 08-00001587 Date
6/10/08
Application pin number . . . 726241
----------------------------------------------------------------------------
Special Notes and Comments
ADJACENT WALLS
*AN APPROVED DEVICE FOR THERMAL EXPANSION CONTROL SHALL BE
PROVIDED FOR BUILDINGS UTILIZING STORAGE WATER HEATING
EQUIPMENT AND A PRESSURE REDUCING VALVE
*RANGE/DRYER DUCT MUST COMPLY WITH 2O06 IMC
*ALL PLUMBING, ELECTRICAL, AND HVAC (mechanical) WORK MUST
BE PERFORMED BY LICENSED CONTRACTORS. CONTACT BUILDING
DEPARTMENT FOR INSPECTIONS PRIOR TO COVERING ANY WORK
*GAS APPLIANCES HAVING AN IGNITION SOURCE SHALL BE ELEVATED
SUCH THAT THE IGNITION SOURCE IS 18" ABOVE THE FLOOR IN
PRIVATE GARAGES. THIS INCLUDES BOTH WATER HEATERS AND
CLOTHES DRYERS.
*PROTECTION FROM IMPACT - APPLIANCES LOCATED IN A GARAGE OR
CARPORT SHALL BE PROTECTED FROM IMPACT BY AUTOMOBILES BY
BEING ELEVATED A MINIMUM OF 18" ABOVE FLOOR LEVEL.
----------------------------------------------------------------------------
Other Fees . . . . . . . . . SEWER TAP 4"
350.00
WATER TAP 3/4"
400.00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------------------------------
-----------------
Permit Fee Total 499.00 499.00 .00
.00
Plan Check Total .00 .00 .00
.00
Other Fee Total 750.00 750.00 .00
.00
Grand Total 1249.00 1249.00 .00
.00
-------------------------------------------------- -----------------------
BUILDING DEPT R /E��'ENTAT •
`"' - r
APPLICANT:
APPLICATION FOR BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
(W COLLEGE STATION, TX 77840
CITY OF COLLEGE STATION (979) 764-3570 (979) 764-3496 FAX
Planning 6r Drvdnpmrnt Srrvirrr
WWW.CSTX.GOV
ADDRESS/ OCATION:
LOT BLOCK
BUSINESS/OWNER NAME
CONTRACTOR/HOMEOWNER:
APPLICATION# �I55
TEMP POLE #
SUBDIVISION o v t C.'rO s `' "r SEC/PH_
�KA CkS-�ola* Wake,(- PHONE: 5$ 1_ Zz 7�
CONTACT PERSON FOR REVIEW COMMENTS:
FAX:
ELECTRICIAN: f'�A
HVAC: Ajo
PHONE:
PHONE:
EMAIL:
PLUMBER: V 9
GOOD CENTS (Residential only):
ACCESSORY/STORAGE MOVING RE -ROOF
ADDITION NEW CONSTRUCTION" SHELL ONLY
DEMOLITION (ASBESTOS SURVEY) PORTABLE STORAGE (RESIDENTIAL) SLAB ONLY
DUPLEX (LANDSCAPE PLANS REQUIRED) PORTABLE STORAGE (NON-RESIDENTIAL) SWIMMING POOL
LOCATION REMODEL/RENOVATION"
DESCRIPTION OF WORK:
PROPOSED USE:
STRUCTURE USE:
HOMEOWNER ASSOCIATION/ARCHITECTUAL OR DESIGN REVIEW COMMITTEE APPROVAL:
TEXAS ACCESSIBILITY STANDARD (TAS) PROJECT REGISTRATION# EABPRJ
VALUATION: $ 1131 O U O !// TOTAL AREA' a3 HEATED AREA: _7I Z
(Cost of Labor and Materials)
dPUBLIC SEWER NUMBER OF BEDROOMS:
SEPTIC/TREATMENT SYSTEM
EWER TAP:
WATER TAP:
OTHER TAP:
❑ TEMP POLE
GARAGE TYPE
4P
SIZE
3 y
SIZE
SIZE
SINGLE a
ATTACHED Fe
NUMBER OF BATHROOMS
INTERIOR WALL TYPE:
EXTERIOR WALL TYPE:
FOUNDATION TYPE:
ROOF TYPE:
DOUBLE
IU ACUED_.
TRIPLE
CARPORT
3
`g+" C)L
g gote"It
51�
SIGNATURE OF APPLICANT: v" / 1 ""
`If proposed work involves new commerciaf co struction oiyfacade improvements/renovations to an existing
commercial property, building elevations are required.
............................................................
Official Use Only
!o-a_oL
GAa^y Mu Plans Examiner Zoning Official
— Add 0 II AJ4 w+ 9 �
_. �J-Acwvt f4CCeii
—M1 eg4v" D 4- tA
— r41(III( nAjGj w/ 1 G
C ents:
Y or NO
Energy Code Compliance Information
% Glazing of exterior walls =` f 6 ? 0
Insulation R value of exterior walls ?J
Insulation R value of ceiling 1 (flat areas)
Insulation R value of ceiling 2 (vaulted areas/no attic)
Glazing SHGC (Solar Heat Gain Coefficient) ►
Glazing U-Factor } 6 S
R value of ductwork
A/C SEER Rating
Protection Against Subterranean Termites
Chemical Termiticide Treatment (Soil Treatment)
❑ Chemical Termiticide Treatment (Field Applied Wood Treatment)
❑ Physical Barriers
❑ Other
* 'Verification -of Application shall be submitted to the City of College Station
Building Division prior to issuance of the Certificate of Occupancy.
v
CITY OF COLLEGE STATION
Planning d Development Services
PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
PLAN REVIEW/PERMIT NUMBER#
w I
DATE: l^'
W � �✓ v
BUILDING ADDRESS:
°� flJe , &e
I. Foundation Requirements- Minimum City Foundation Standards
NA/ K
A.
Concrete minimum compression strength of 3000 PSI
B.
Minimum four 4 inch slab thickness
C.
Vapor barrier Emil. Poly min.
D.
Slab/beam or pier layout shown
1. Footings/beams are continuous over the length and width of foundation
2. Footings 30" exterior, 24" interior, unless over 60' long must be 30"
3. Spacing of beams does not exceed 15'
E.
Reinforcement details to meet minimum requirements
1. Slab reinforcement and Beam Reinforcement
F.
Protection Method used for Termites.
G.
Wood foundation details indicated
NAQJK
II. Framing:
Floor, Wall, Ceiling and Roof Requirements
N K
A.
Girder or sill dimensions, grade & species
B.
Floor joist size, spacing, grade & direction of span indicted on plans
C.
Treated sill plate or bottom plate
D.
Tenant separation in duplex
NMK
1. One -hour rated extending to roof deck
OK
E.
Header sizes indicated on plans
F.
Emergency bedroom egress
1. Exit direct to outside
2. Operable window
a. Twenty 20 inch clear width by twenty-four 24 inch clear height
b. Maximum sill height of forty-four 44 inches above finished floor
G.
Operable bathroom window required when mechanical ventilation is not provided
H.
Stud grade andspacing
I.
Exterior wall details
1. Sheathing indicated on plans for Wall Bracing
2. Moisture barrier indicated on plans
3. Exterior Wall Covering
J.
Roof framing plan or elevation shown
K.
Ceiling joist size, spacing, grade and direction of span indicated on plans
L.
Attic access location and size indicated on plans
M.
Span exceeding code tables must be engineered
N.
Rafter size, spacing, roof slope & purlin bracing if required to reduces an
O.
Roof covering
P.
All girders & beams for support of floors, walls, ceiling & roofs must have the size, grade &
location indicated on plans
Q.
Tempered Glass required in all hazardous locations
R.
S.
18" Overhangs allowed on zero lot line, non-combustible perforated soffit only
All walls within 3' of property line to have protected openings.
OK
N OK
PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
CITY OF COLLEGE STATION 1101 TEXAS AVENUE
Planning& DevelopmentSemice; COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
III. Stairway Requirements
A.
Stairway Details
K
1.
Maximum riser height 7-3/4 inches
2.
Minimum tread width 10 inches
3.
Stairway risers are uniform 3/8" Max. difference
4.
Stairway width not less than 36 inches
5.
Stairway headroom not less that six ft. eight 6'-8"
B.
Winder details
1.
Treads a minimum of six 6 inches on narrow edge
2.
Treads a minimum often (10) inches at a distance of twelve (12) inches from the
narrow edge
C.
Spiral stairway details
0
1.
Riser height less than nine and one-half 9-1/2 inches
2.
Treads a minimum of seven and one-half (7-1/2) inches at a distance of twelve (12)
inches from the narrow edge
3.
Stairway width not less than thirty-six inches
4.
Headroom required not less than six ft six 6-6 inches
5.
All treads must be identical
D.
Guards/handrail details
1.
Guards required when a porch, deck, balcony or landing is thirty (30) inches
above grade or finished floor
2.
Handrails are required on stairways located two or more risers above floor/grade
3.
Handrails must be thirty-four to thirty-eight (34-38) inches when measured from the
leading edge of the tread
4.
Handrails must not project more than four & one-half (4-1/2) inches into width of a
stairway
5.
Guards must be a minimum of thirty-six 36 inches above finished floor
6.
Guards & handrails along open-side(s) of stairway must have intermediate
railing or uprights that prevent the passage of a four 4 inch sphere
IV. Fireplace
Requirements
OK
A.
Hearth extensions
1.
Fireplace opening < 6 s , ft, extensions: 8" & 16" forward
2.
Fireplace opening > 6 s . ft. extensions: 12" side & 20" forward
B.
Masonry
fireplace requires 2" clearance from all combustible materials
C.
Chimneys must meet IRC Chapter 10 Requirements
V. Electrical Service Requirements
A. Electrical Ian to include:
N K
1.
Electrical fixtures & switches indicated
2.
Smoke detector locations indicated as required
3.
GFI circuits indicated where required
4.
Arc fault protection for bedroom circuits
5.
Panel location
CITY OF COLLEGE STATION
Planning d Development Services
PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
VI. Plumbing Requirements
A. Pressure reducing valve required when water pressure exceeds 80 psi
N K
B. Plumbing access to bathtubs
C. Means for thermal expansion provided when required
D. Water heaters elevated 18" when installed in the garage or room directly off garage
VII. Mechanical Requirements
N
A. All mechanical ventilation's in bathrooms & range hood ventilation must be ducted to
outside excludes ductless units)
T
B. Attic installed H.V.A.C. requirements:
1. Twenty-four (24) inch wide unobstructed walkway from attic access to equipment
must be provided
2. Attic access located within 20 feet of equipment
C. Combustion air supplied for gas appliances when required)
VIII. Energy Requirements
W06)
A. Compliance software worksheet MECcheck submitted, or
B. Energy data supplied Percent of glazing, insulation R-values, window U-values, etc.
Zoning Ordinance Requirements — Ordinance 850
N
Permitted use for district
Density requirements
Minimum lot size
Setbacks
Easements
Required parking
Street Ordinance Requirements
N K
Maximum drive width for residence is 25' combined for circular and 12' minimum for single
Minimum 20 feet from driveway to side(intersecting) street property line sight triangle
Driveway access to lesser street for corner lots
Subdivision Regulations — Ordinance 690
N K
Approved subdivision
Plat filed
Flood lain Regulations — Ordinance 1301
N K
Does not block any water course or divert any flow
Elevation certificate needed
K
"APPROVED PLANS PER IRC SECTION R106.3.1."
6-g-
DATE