HomeMy WebLinkAboutRES2008-00429, 08-430r
PREPARED
6/27/08, 8:04:40
INSPECTION TICKET
PAGE 8
City of
College Station
INSPECTOR: BUILDING INSPECTOR
DATE 6/26/08
------------------------------------------------------------------------------------------------
ADDRESS
. : 918 EAGLE AVE
SUBDIV:
CONTRACTOR STYLECRAFT BUILDERS PHONE (979) 690-1222
OWNER
BCS DEVELOPMENT CO
PHONE
PARCEL
650730-0408-0400
APPL NUMBER: 08-00000429 RESIDENTIAL, 1 UNIT DETACHED NEW
------------------------------------------------------------------------------------------------
REQUESTED INSP
DESCRIPTION
TYP/SQ
COMPLETED RESULT
RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
B125 02
6/26/08 BI
BLDG, FINAL TIME: 17:00
AP
June 26, 2008 4:45:32 PM acarter.
^
--------------------------------------
COMMENTS AND NOTES --------------------------------------
Fd
PR PARE
6/25/08,
12:03:15
INSPECTION TICKET
PAGE 9
City of
College Station
INSPECTOR: BUILDING INSPECTOR
DATE 6/25/08
------------------------------------------------------------------------------------------------
ADDRESS
. : 918 EAGLE AVE
SUBDIV:
CONTRACTOR STYLECRAFT
BUILDERS PHONE (979) 690-1222
OWNER
BCS DEVELOPMENT
CO
PHONE
PARCEL
650730-0408-0400
APPL NUMBER: 08-00000429
RESIDENTIAL, 1 UNIT DETACHED NEW
------------------------------------------------------------------------------------------------
PERMIT:
BLDG 00 BUILDING
PERMIT
-
REQUESTED
INSP
DESCRIPTION
TYP/SQ
COMPLETED
RESULT
RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
B100 01
3/06/08
RH
BLDG, FOUNDATION -SLAB TIME: 17:00
3/07/08
DP
March 6, 2008 8:36:08 AM acarter.
March 7, 2008 8:43:54 AM kwolfe.
nned to wrap plumbing pipes
need strings on setbacks
B100 02
3/10/08
RH
BLDG, FOUNDATION -SLAB TIME: 17:00
3/10/08
CA
March 7, 2008 10:02:22 AM acarter.
Monday morning
B100 03
3/11/08
BB
BLDG, FOUNDATION -SLAB TIME: 17:00
3/11/08
DP
March 11, 2008 10:02:23 AM acarter.
-
03/11/2008 04:23 PM BB PDA
Remove water in rear beams. Need 3 inches clearance in
bottom of beams.
B100 04
3/12/08
BB
BLDG, FOUNDATION -SLAB TIME: 17:00
3/12/08
AP
March 12, 2008 10:16:17 AM kwolfe.
03/12/2008 03:11 PM BB PDA
Strings were up. Slab ground installed,
right side.
B120 01
3/28/08
BB
BLDG, FRAMING -PARTIAL TIME: 17:00
3/28/08
AP
March 28, 2008 9:51:44 AM kwolfe.
apa framing
B115 01
4/28/08
BB
BLDG, FRAMING TIME: 17:00
4/28/08
DP
April 25, 2008 4:58:29 PM npadilla.
04/28/2008 11:49 AM BB PDA
Need bracing and anchor bolts, in wall
between garage and
house. Need joist hangers in same area.
Need to double
joist on right side of attic entrance .
Note: All second
floor operable windows to be 24in AFF.
B115 02
4/29/08
RH
BLDG, FRAMING TIME: 17:00
4/29/08
AP
April 29, 2008 11:42:06 AM bcaldwell.
B130 01
5/02/08
RH
BLDG, INSULATION TIME: 17:00
5/02/08
DP
May 2, 2008 11:52:32 AM malford.
05/02/2008 03:21 PM RH PDA
Insulate outer rim joist between floor
areas. Did not
insulate wall tees. Do not stuff.
13130 02
5/06/08
BB
BLDG, INSULATION TIME: 17:00
nVI
5/06/08 DP May 5, 2008 4:47:59 PM acarter.
05/06/2008 12:26 PM BB PDA
Did not correct notes on previous inspection.
B130 03 5/07/08 BB BLDG, INSULATION TIME: 17:00
5/07/08 AP May 6, 2008 4:53:48 PM bcaldwell.
B125 01 6/25/08 BI BLDG, FINAL TIME: 17:00
June 25, 2008 11:00:50 AM acarter.
-------------------------------------- COMMENTS AND NOTES --------------------------------------
1-� ►al.l �'2�Z1 S Ai G 0 "To 'Q E A—% P,c e C. fL ABC, 4+T 3�j 'To
�2o�!'"j 6�C�� �G S'r�p � -ro —r.�� a►= �Lc� , ;.1eG� c�vG � P�,a�-r�s c�1
A�LL-
SuJ�/fCi rcS Omot'rlsc 71L_2'r-rn lT-tom! Zi.!�'trLl E.C. .
(6/30/2008) Amber CarterRe Calling for CO for 918 Eagle Ave w Page 1
From: Mitchell Carson
To: Amber Carter; Benjamin McCarty; Chris Haver; Gina Southerland; Joe G...
Date: 6/30/2008 7:41 AM
Subject: Re: Calling for CO for 918 Eagle Ave
This one is ok..... Mitch
>>> Amber Carter 06/27/08 8:32 AM >>>
by 08-429
Any issues?
WFl004710 / 001 City of College Station
PAGE 1
REQ. DATE: 02/14/08 02/14/08 15:19:33
LOCATION: 918 EAGLE AVE LOC ID: 203762
REQUESTOR: STYLECRAFT BUILDERS ORIGIN: CUSTOMER -WALK IN
REQ USER: GLSOUTH AUTH USER:GLSOUTH WRK TYPE:
SWR 4" WTR 3/41'
********************************************************************************
TASK: SET UP NEW UTILITY ACCT SET READY
SCHED START: 02/14/08 SCHED COMPLETION: 02/14/08
********************************************************************************
JOB ORDER RESULT CONP=S
COVER
THIS SET OF DRAWINGS FOR A HOME IS THE COPYRIGHTED PROPERTY OF STYLECRAFT BUILDERS,
INC. THIS SINGLE COPY IS LICENSED AND NO RIGHT TO REPRODUCE, COPY OR DUPLICATE ALL
OR ANY PORTION OF THE LICENSED PLANS IS GRANTED, EITHER EXPRESSLY OR IMPLIED.
-ALL IDEAS, DESIGNS, ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY THE DRAWING
ARE OWNED BY AND THE PROPERTY OF THE DESIGNERS AND WERE CREATED, EVOLVED AND
DEVELOPED FOR USE ON AND IN CONNECTION WITH THE SPECIFIED PROJECT. NONE OF SUCH
IDEAS, DESIGNS, ARRANGEMENTS OR PLANS SHALL BE USED BY OR DISCLOSED TO ANY PERSON,
FIRM OR CORPORATION FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION
OF THE DESIGNERS.
PLAN TYPES
S = SELECT SERIES
W = WAINSCOT WITH SIDING
F = MASONRY ON FRONT
3 = MASONRY ON THREE SIDES
4 = MASONRY ON FOUR SIDES
G = GOLF CART GARAGE
E = ELITE COLLECTION
C = COLLEGE HOUSING
A = ATTACHED.TOWNHOME
D = DETACHED TOWNHOME
X = DEVELOPMENT
Z = CUSTOM HOME
FRONT ELEVATION
FLOOR PLAN
SHEET INDEX
G-1
ICOVER SHEET
C-1
SITE
S-1
FOUNDATION
S-2
WALL FRAMING
S-3
FLOOR PLAN
S-4
DETAILS
S-5
JOIST FRAMING
S-6
ROOF FRAMING
S-7
ROOF
S-8
ELEVATIONS
E-1
ELECTRICAL
A-1
TRIM/CABINET
A-2
FLOORING
COMMENTS
FRAMED AREA
LIVING 1ST
954 SF
LIVING 2ND
610 SF
LIVING TOTAL
1564 SF
GARAGE
225 SF
PORCH
70 SF
FRAMED TOTAL
1859 SF
JOB#Q: 0V0:0�7]
w
z
Lu
Q Q
w w
z
w
� Q
Q w
00
o�1
PERMIT
CREATED:MH
2/11
PRE -CON: 1 /25
REVISED: 02/08
ISSUED:
PRINTED:
2/1 1
Q
10
Lu 1-O
O
U '-O
C)
SCALE: 1 /8'
11.17
G-1
1/2- DIA. SMOOTH DOWEL 2'-0'
LONG W/ PVC CAP - PLACE IN
SLAB OR DRILL 9'-INTO EXISTING
GRADE BEAM. TAPE CAP TO LEAVE
TOOL EDGE E.J.T. 1® END OF ROD
4' THICN PAVING 3000 PSI
REINF. W/ /3's ® 78' O.C.E.W.
MID DEPTH USE CHAIR SUPPORTS
DISCONTINUE REINF. ® E.J.
iX REDWOOD DIVIDER
D SECTION "D"
N.TS.
CONTINUE REINFORCEMENT
THROUGH KEYWAY
ONE CHAIR PER d- THICK PAVING 30DO P51
4 SO. FT. MIN. REINF. W/ #Y3 ® 18' O.C.E.W.
MID DEPTH USE CHAIR SUPPORTS
C SECTION "C"
N.TS
3/8' A. DOWEL W/ SLEEVE.
DRILL INTO EXISTING SIDEWALK
' 1X REDWOOD DIVIDER
B SECTION "B"
N.TS.
"" DIA. DOWEL W/ SLEEVE.
DRILL INTO EXISTING CURB
8' X 8' BEAM
W/ 4 R5 RE6AR
A SECTION "A"
N.TS
INSTALL EXPANSION JOINT
® MID -DRIVE IF OVER 45'
BUILDING L
d
d.
d
a d
C
c
0
I
d
PROPERTY LINE d
4" THICK 3000 P I CONC.
REINFORCE W/ 3 BARS
® 18" O.C.E.W.
VERIFY SIDEWDALK� CITY SIDE WALK
IN FIELD
d
0-- t
B C
MAIL BOX
d 4 /
d 'd
LAYDOWN CURB DETAILS
CONTRACTION JOINT WHEN
DRIVE < 16' WIDE
4" THICK 300Q PSI CONC.
REINFORCE W/ #3 BARS
18' O.C.E.
CONTRACTION JOINT
INSTALL METAL KEYWAY
EXP. JOINT W/ 3/§' DIA.
SLICK OWLS. ® 18 O.C.
W/ SLEEVES ONE SIDE
0
N
TO BE SET UP IN
TO AVOID LOW
IN CITY SIDE
DOUBLE SEWER ENTRANCE
918 EAGLE AVENUE
WESTFIELD VILLAGE
PHASE-4 : B LOCK-8: LOT-40
b�`� �08007
Lk S&A 0
�k 1 e
S,d O
CLEAR LEVEL
AND READY
FOR FORMS
NO PUMP TRUCK
18 EAGLE AVENUE
IESTFIELD VILLAGE
)T - 40
.00K - 8
SASE - 4
Lu
Lu
Q Q
Lu Lu
Z ,nI
LLJ V
0':� Q
Q Lu
00
PERMIT
CREATED:MH
2/11
PRE -CON: 1 /25
REVISED: 02/08
ISSUED:
PRINTED:
2/1 1
Q
�O
U -i
V
�O
Lo
SCALE:
1'--
201
C-�
: Apr.29. 2008-- 3:53PM-•".'Sty]ecraft Builders, Inc. .. .. - No.9823' :*P. T
Renewable 5 Year
Subterranean
Termite Retlreatment
Agreement
(Does not cover any other species of Termites)
Shielding A Protecting
Homes Against Pests"
og-10-7
This agreement provides for retreatmect only of the Infested areas covered under the odginal treatment area (See Graph).
Custorair Name Date
Billing Name if different
2/a 2e /e
Street Address of treated structure Billing Address if different
C. y 7F
-/-7
City State
Zip Code
City
State
Zip Code
Initial Termite Cost
S %id'
Home Phone work Phone
Additional Renewals Paid
Other
Type of Treatment Partial
Bait Y Pre -Treat
Tax
e
Treatment for: Prevention
Control of Subterranean
Cash_Check#
Total
$
Termites
Payment
$ "'
Notes, ,
13aiauce
$__
Credit Card:
Type Exp. Date Card Number
5 Year Subterranean Termite Retrgatment Guarantee: RP Lee Termite and Pest Control will retreat the structure for Subterranean
Termites at no cost to the customer, if an infestation of Subterranean Termites is found, as long as the original treatment is paid in full
and the customer is current on their yearly renewals. This Agreetnent will expire in one (1) year unless the customer elects to pay
the yearly warranty fee. The guarantee can be renewed for up to five (5) years by paying the yearly warranty fee_ RP Lee Termite
and Pest Control may approve additional warranty years after the five (5) years with an additional increase in the yearly warranty fee.
The guarantee does not cover any damages to the structure or contents of the customer. The customer agrees to control all eondosive
conditions that may cause reinfestation. If the structure is modified, added on to, altered, or if the soil treatment around the sttuettue
is removed the customer must contact RP Lee Termite and Pest Control and pay for additional treatment it order to keep the guarantee
in effect. If the customer does not pay for additional treatment the rctreatment guarantee can be cancelled CA
$fit Customer may elect to renew the rematment guarantee for additional years. The renewal fee is $ -O° plus tax.
The renewal fee is due on or before the annual anniversary date or paid $ plus tax every third (3) month with inspection.
Maintalnlnp the Guarantee: The customer agrees to correct all condusive conditions, at owner's expense, as they exist or as they
oa= in the firture in order for the guarantee not to be cancelled Customer will make the structure available for inspections sad
treatments as requested by RP Lee Termite and Pest Control.
ReinsRodlon, RP Lee Termite and pest Control will reinspect the structure at customers request or any other times RP Lee Termite
and Pcst Control deems neeessa y. RP Lee Termite and Pest Control rccommeads that the customer call and set up an annual inspec-
tion. at the time of customers yearly renewal.
3kggg� This agreement may be transfc�d to a new owner with the payment of a transfer fee of $ , copy of the Wood
Destroying Insect Report from the sell, and approval of RP Lee Termite and Pest Control.
This Subtterran ermlte Retreatment Guarantee dogynot greve and is not intended to control otbor forms of Termites
(j)yffu�6 Formosan. ate.). WoOLRoring Beetles. Carpenter Ants. Catpen er Bees. Wood Rot. foams, !)§= or any other
wood destroying inserts ptr•ormisms.
Ali In the event of any dispute arising out of this agreement or any other scryices performed or not performed the parties
above agree to participate in mediation through and in accordance with the commercial mediation rules of the American Arbitration
Association. The Arbitrator shall consider the legal defenses raised in the arbitration, and the decision of the arbitrator shall be final.
binding, coot -appealable and may be entered and enforced in any court having jurisdiction in accordance with the Federal Arbitration
Act.
Limitation of Liability: Landscaping and grass text to the slab maybe damaged during treatment, carpet may need to be pulled
up in certain areas around the home, drill holes may need to be made in floor coverings such as the or linoleum or in cabinets next
to pipe areas, and holes may need to be cut in walls. Customer agrees not to hold RP Leo Termite and Pest Control liable for these
damages, or treatment techniques, or other damages that may occur during treatment
Agfggmenr This Agreement shall be the entire agreement between customer and RP LeeTermite and Pest Coo rol. If any part of
this agreement is found to be invalid it shall tot affect the validity of any other part of the Agreement.
ng tit&s
RP Lee Termi Pcst Control Curt Apl.# Ccr stomcr Signaature Date
Apr, 29, 2008 3:52PM Stylecraft Builders, Inc. . No. 9823 P. 6
New Construction Subterranean Termite area App,ova t Z31 U200o5z
{axp. 1Qf3 )
5)
Soil Treatment Record
TNs torn is ompWWd by tho taco 80 halt Control Corn
ttH+` OTiurdnll mr Ittu rptas¢n of iremrmrdrn Is oomnalad tr,avaaG t minulol Ror r.spanro, dwudiergl?a'be+o ici ii�nvx,rc� a►)iniWc+,s. suuoA�++p .^
r WWlft nr aestee>i�. MI MO riot v�� tie o t(um�lara and m ae eairoqusr "MIDI > � 1- Wm t up s a c+, wl �rald CND mnoThis mIDMIAWn PP, n=dIllon o is
nmtbor.
5v ivn 94 CFR 2o0Md(b)(3) regArve Inc( the ekes for HUD 4u.urod strudrlrov moat W Uva ul km, Ita hwrd t h'S tr(ltmtaifan coRox'wl roauiroo ma Colder to
witay trot"Mallaaod fxRmul canpary porbsmed as IOOubad wealrwg IQ temriloo. and UZ Oro brihfcr Lwranteas sit 1400d ama a(wml Intmattar, Ru
a19 yw. DUN=, Pit contrd C,rrrpnniao hurvvO (arxim, Iromnbryer% and h1710s o recoil of tr6ZWW- W r.OariR -1-ni a vdV um thv biturmabn cdcrAad.
TN inwmirr m •s not evreidnled o�r�d'ardibL
This r Wort is sltn4VAJ for Intormra(Wna( purPOM ID the bulldor on proppcad (now) BOnalraction co501. Wher.:oa irv4tmont for pr:vonbon of vWbtvrrsn6an
(orrrule Hbctalgn Is tpeaiAod by rho baildor, atctdt0at, m raquirvj by the lendur.:vchllev. FKA. or VA
All ooltrtacts for sorviC08 tiro bohmarr Ure Post Control Operator and balder. unloss gtntad atharwiaa.
SeaWn 1: mans ml k orrrraxim (hea t+9 Cert)pW hilorolo'i9p)
campmy Names • W6, , ke .�irc 4 4 A.',',A1 — .
Compaq After
&473oar z City C'. s�(a _. ref . Zp �.
I.oingl4y BuWnera L)aanae Flo.
Company Fhorw No.
FKAIVA Caro No. (it vny)
FAu{Ton 2: Bugdar In trlttgticti
Company Nan U Mona No.
Sacdoa �: Prapartn fvtsYrmativn 7 ! � �G°
Location of OvuchAo (a) Ttoatod (Stroot Aaidrvm or Lope) DaWIP110n C4, Smfa end 7jp)
Typa of Grucgon (more Ulan one box Troy be vhwhao) �41ab L —] Sua(rmu! � Crawf � 00�ar
onst
Apprpldmato t)opth of F041b19 p(dstda , Irlclde — Typo 6r P111
SvWga 4: Tmafamtt )afonlea fan
PAID(s) of Tteatatartt(e)
ZV'V
Wam [dams or P& x7(r) (lead fDC1,0j?PG1WrL1
EPA Raftlanfon No. fev
AFFroxtlnaly Fired MU Solution 1A
ApproxititatoSize of Tract=%Area: sq. R, � Unaarrt co
Apwpx m W Testa( C><r arm at $oltdlorl Apd)Od
Was tMcj=rd rrort> smd on axt0rlor? Yes No
r
unaur t•' 01 dtoawty Vo°dv
9enr0aAgroormMAvA"o? 99 Yes LM NU
Not. Sumo 6W9 Iowa foqulrc voNido agraalaertts to be i6&61 Thio form dues mA preempt :iota law-
AttWrne�
Nerna WApP1I;=d6)
CeWcstloa No. of roqukad by State low) _ * ;W
Tiro appffcator has used a product )n A=rdw9v will Ulu Fraducr lobe) ana slato regCfralru nrs. M treatnxn% maUvL;r s and ntottlod8 usod comply wkh
crab And fadvtat regulatimu.
ArdtoAW Sfgnatwv
W"1Z we ph>•iaunv lobo '"". Cenv + n+e m7nR h ulrrunel n+NN +��r 1 r 8 U.S.C. 10ml 1010 1g12; .^i1 I M?)
Folm NPCA-6" may 6119 W ucad (orra lit.1"PCA-09-8 (04:0035
APr.29. 2008 3:53PM , S t y I e c r a f t Builders, Inc. . No.9823 P. 8
SUBTERRANEAN TERMITE PRE -CONSTRUCTION TREATMENT DISCLOSURE FOR EACH ESTIMATE
Licensed and regulated under the Taxes Struclurel Pest Control Act
-CUSTOMER
Name:
Address:
Location to be Treated:
RP LEE TERMITE & PEST CONTROL
PO Box 9423 • College Station, TX 77842 a (972) 690-8622 a TPCL #11486
y
city.
Phone ft.
4,5
Phone #2;
State; -V 1' 4 Code:
For all treatments there will be a diagram showing exactly what will be heated prior to the beginning of treatment. Review the pesticide label provided to you at this time for minimum treatment standards.
Remember that your architects or design engheere speefttions must also be followed, unless they are In violation of the law. Review the consumer information sheet for further information. If you
have any questions, Contact the pest cordremeenv or the Texas Structural Pest Control Board, P.O. Box 1927, Austin, TX 78167-1927. Telephone number (512) 305M.
Before conducting a termite preconstruotfon hatment, the company will present a complete diagram of the structure including construction details. When construction prevents performance of a full
treatment, In accordance with a bid for full treatment, any change to a partial treatment by the Company providing the treatment will be permitted If the owner of the structure or the person In charge of
the construction and the certified a0lcator for the pest control company sign a statement attesting to the construction conditions. The agreement must be attached to the contract with an amended
diagram showing the exactareas to ba treated. Copies must be sent to the owner of the property within seven days of the application. //��
Diagram of StruCWre(s) and Proposed Areas) To Be Treated notes: Age'164/de
■ ■Yi1i■YYiY■1WHAWS
��
■
uY■Y■Y■■■■■■■■tn■■IttttY■■Y■■i
t
YY■■Ya■r�■YY■a■la■i
tits'
■■�■■��n%,�i�t:..
� �
■A■■�Y.�■;.■■Yo■t:i■■.Y�Y■■t�YY■■■Y■
MIME`
■■vI�Y�■��■OHO
IYYI•Q1G'1F7®Y
rr■Yo■Y�Ytil1■■�m■
NREPJPV"li
Y�imrrYYl
Y■!■�Y■
utaYYYnn�YYntttiYrritttttttlttttnY
1■Y■Y�■■■■i�■ii■■t■YYWiYY��
YYo
Y■Y
I1■■■■Y■■
Yte�■YY
■A.
_I1■■YY■■■Y■�n■■�
IYY■!t■■■
Y■tiJ��YpY
�■�
��I
■Y■t■Il�
���Y��■Y�Y�
�■�YO�
��■p�t�
�■Y■Y
Y■■�Ya•■■Y■�■■�■■■AY/Y■YYY
0
t■�m®Y��IB
■�
CONSTRUCTION DETAILS:
��14e - Z",it ew rlsfew
wtV b
"q
JZS
•�•�ME
Type of treatment proposed: (check all that apply): 0 Full XPartial KWood 0 Balt 0 Commerelal 'Ingle Family
Total square feet to be treated: •��. Total linear feet to be treated: Approximate measurements of structure(s) to be treated: �' G'�
A �bal of, 1499I lf4G¢19C termiiticide(s) is attached. The percentage of the tormmltldde(s) to be applied at this location is ?� %.
Estimated amount of tenmltlolde to be applied: l gallon(s),
THE SUBTERRANEAN TERMITE PRECONSTRUC710N TREATMENT BUILDERS GUIDE IS ATTACHED ON BACK (SPCBID-4 THE BOARD APPROVED SUBTERRANEAN TERMITE
PRECONSTRUC77ON TREATMENT BUILDERS GUIDE MUST BE PROVIDED TO, AND SIGNED BY THE CONTRACTOR OR PURCHASER OF THE PRECONSTRUCTION TREATMENT
SERVICE. Complete details of warranty ('d any) including time periad of werranty, renewal options and cost, and obligations of the contracting parties is attached, if the warardy does not
Include the entire structure treated, the areas included in the warranty are (specify);
J A consu formation sheet iiso attached.
gel ail, /r y2
Signature of e ninon Printed Name Date Signature Customer oWng Receipt of This Document Date
pras
rtaaoz .10 IAZm WhlteCopy- aenkeProvldvr Yellow Copy •CuFlomor Fam 99KW W4 RWWby 5W&2M GW=z=M 1-N&7MZM, M2247XC 2W
Service Tl iatment Invoice
Route: Map Code: E ap E Fnene . DJ,�8 M
Start Time: pm Finis1119me: amlPaa i Structure:
Y htb raw
Appoint. Time: 41 asnlpun
Q S Y
l PB Combo
lype Servicef loitia4 Regular Follow Up Oue'nme Cbari€y Pets: Dog(s) Cat(s) Bird(s) Fish
i-411weramg At. ProkwUng
er ' e Ad Harms Agv hme Poestsls • Cast of Service
Name: leCr4 X7/j�/QJ��iU r U Billing: 7�C� ��t4B8
v ��(� g• T
ax
Address: �_ c Total Due
City: TX 'I��5� Payment
Phone: Balance
PEST PROBLENL5: 4 &'C _ Z&`i*> rz7 Y<A? DIRECTIONS ! INSTRUCTIONS:
EQUIP. NIETH. LOCATION(S)
. Y�S�D DEST_ROTIDIC INSECT`S
i
GENERAL PESTS'
PRODUCT
Dom!!!
TARGET PEST(S)
8398
Payment by:
Cash ❑
Check ❑
Credit Card O
PAYMENT DUE
UPON RECEIPT
'ftrmidorSC-F1Kou0.t16% SubtmrseenaTermites,Aab SlzeefTank Posted
'ArmidorOM-Fiptnua.36% subtercauezTermites. San ofrank Posted
BoracaroDkcdwnOciaborateTdrahydate50%. ` i SuLterraneaM"mLosaelDrymcdTeymlte%CuVerdcrAnle,Beelles, Posted
luvader HPH-Baygon l%
Deena WP.Cyan0-Pien03ypl=yl
Dhcelbycyleyclopr opanecorboaylate 1%.
lenpo Ultra WP-Cyluuthrin A25% ('acgo .
(gen. surface spray, spat, rain, crack & crevim)
Thlster NZ Wfeathrin.2%.
51asforce-Hydramett�ylsx M-2.15%
Cyldck CS Cylludrrta .OS%
Phautem.5%
Teagard-Permethrbr 5%
Suspend S64ildl ndtarla 4.75% (REST)
Nygaard-llletlyletnony 10•Yc (HEST)
Excite R PyrWirin.115%
Fn s tr ac4bone I hall n .p 1 %
Bait Slatk►a-Lavgd8nuO Glue Boards
Pm-Centrol Ms Pyrethrins.50%
Masterline HKent$rio .06%.
Carpenter Ante, Spiders, Crickets, N11111pedes6 Beetles, Termites.
Ooehroarihes, M011pedes, Sowbags, Flies, lldc% Mwgaitw. PBlbugs,
Sllve llskBees Ants, Carpenter Ants,Seorplams,Spiders,
Aata(FxocptPharaoh),Cockroacles,Ckleket%Eorwlgs,M ilpedes,Flles,Fruit Flies. Beetlm
Pilllbugs, Silverfish, Sgdders, Gnats, Burnell, Wasps, Yellow Jackets
Ants, Centipedes, Codtrowhes, Cirklima, Grasshoppers, Se orpkrus, Ticks, Sliverfisb, Spiders.
Pharaoh Ants, Crldieft, CarpenterAuts, Lg. Koachev, Variety ofAshls.
Spklera,Smrpi ms,Ants,CarpenlerArils,CarpenterBeal,Roaches,Crick^Silverfish.
Phawh Ants, variety oma* Roaches.
Finis, Tldws Acts, Centipedes, Carpenter Aots,Bees, Wasps, Carpenter flees, CoLkroachek
Ctkkels, F1M Earwtyp, Millpedes, Beetles, Pillbugs.
Fleas, Bees, Beetles, Reaehes,Crldwts,Ilee,Flies, Searplans,llelrs, Weeps.
IGR�Growtb Regulator-Flems,Roacbes, Crickets, €IyIng Insects, Stored Product Peals.
Fleas.
Now, Rodents, Hates
Mice, Rodents, Rals, Bug Monitors
Hersetilee, Meaqultos, Ma ft Flan, Wasps, Hornets, Ticks, Cockroackm
Splilms, Aide, Hoochea, SilverBsb, Ear"IM Fleas, Seospioas
Eguipmcnt: A -Compressed Sprayer P-Power Sprayea B-Bait Dispenser BS-Bait Slalion BT-Bait Trap WAerosol Can G-Glua Board H[-Hand Duster S-Spreader F-Fogger EM-Foamer AC-Actisol unit Other
Laggins: 1-Kitohm 2-B&Ns) 3-Bedcoons 4-Dining Room SUl ity 6-Storage 7-Common Arras 11-43yanege 4-Petimoter of Structure 10-Alk It -Yard MUnderHome 13-Warehowc 144fice lSExposedWood 2' up froan Slab Other
Method of Trcatmentse CC -Crack & Crevice S3-Sub-Slab Injection VT-Vbid Treatment BP -Bait Placement ES -Broadcast Spray PB-Perimeter Barrier BV-Brick Venire WT-WoodTreatmmt
PRECAUTIONS: Do not touch treated areas till dry. Do not tamper with bait Stations. Ventilate rooms after treatment. Keep pets away until pesticides have dried.
Licensed by the Texas Department ofAgriculture Structural Pest Control Service -P.O. Box 12847 • Austin, TX 7871.1 a 512-305-8250 SERVICE TECHNICIAN: �� CUSTOMER SIGNATURE: Gov f % �f DDATE:! y 9'
Please review the Customer Information on the other side of Invoice
P.O. Box 9423 • College Station, TX 77842 • (979) 690-8622 • Fax (979) 690-8840
BUILDING PERMIT
CITY OF COLLEGE S;.TATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Application Number . . . . 08-00000429 Date 2/14/08
Application pin number . . . 210599
Property Address . . . . . . 918 EAGLE AVE
Property ID: 650730-0408-0400
R #: R303422
Application type description RESIDENTIAL, 1 UNIT DETACHED NEW
Subdivision Name . . . . . .
Property Use . . . . . . . . RESIDENTIAL
Property Zoning . . . . . . . PLANNED DEVL DISTRICT
Application valuation . . . . 103224
Owner
------------------------
Contractor
BCS DEVELOPMENT CO
------------------------
STYLECRAFT BUILDERS
4090 SH 6 S
4090 SH 6 S
COLLEGE STATION
TX 77845 COLLEGE STATION
TX 77845
(979) 690-1222
--- Structure Information
000 000 SINGLE FAMILY
Construction Type . .
. ... COMBUSTIBLE (UNPROTECTED)
Occupancy Type . . .
. . . RESIDENTIAL-SFR/DUPLEX
Other struct info . .
. . . EXTERIOR WALL TYPE
MASONRY
IMPACT/PRORATA FEES PAID
NA
FOUNDATION TYPE
SLAB
NUMBER OF GARAGE BAYS
1.00
TYPE OF GARAGE (ATT/DET)
ATT
HEATED AREA
1564.00
INTERIOR WALL TYPE
SHEETROCK
NUMBER OF BATHROOMS
4.00
NUMBER OF BEDROOMS
4.00
SEWER TYPE
PUBLIC
TRAFFIC IMPACT ANAL (TAZ)
405.00
----------------------------------------------------------------------------
Permit . . . . . .
BUILDING PERMIT
Additional desc . .
GS
Permit pin number .
552299
Permit Fee . . . .
472.00 Plan Check Fee
.00
Issue Date . . . .
2/14/08 Valuation . .
. . 103224
Expiration Date . .
8/12/08
Qty Unit Charge
Per
Extension
BASE FEE
460.00
4.00 3.0000
THOU BLDG, VAL 100001-500000
12.00
----------------------------------------------------------------------------
Special Notes and Comments
-Make sure 2nd floor
operable windows are 24" AFF
-Narrow Wall Bracing
Fully Sheathed with 16" Minimum
APA
-------------------------------------------
BUILDING DEPT REPRESEN/!'ATIVE:
------ -- --�-
-:.------------
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 2
Application Number . . . . . 08-00000429 Date 2/14/08
Application pin number . . . 210599
----------------------------------------------------------------------------
Special Notes and Comments
Garage Framing and Interior Anchors and Bracing at Back Door
Area and Front Door Area Windows to get 32" OSB per Plans.
*ALL BRANCH CIRCUITS THAT SUPPLY OUTLETS IN DWELLING
UNIT BEDROOMS SHALL BE PROTECTED BY AN ARC -FAULT CIRCUIT
INTERRUPTER(S)
*PROVIDE ATTIC ACCESS OPENING (MINIMUM ROUGH -FRAMED SIZE 22"
X 30") WITHIN 20' OF THE MECHANICAL EQUIPMENT AND WALKWAY
*PROVIDE CHEMICAL TREATMENT OR PHYSICAL BARRIER (SUCH AS
METAL OR PLASTIC TERMITE SHIELDS) FOR PROTECTION
AGAINST TERMITES. IF CHEMICAL TREATMENT IS USED, THE
CONCENTRATION, RATE OF APPLICATION AND TREATMENT
METHOD SHALL BE CONSISTENT WITH THE TERMITICIDE LABEL.
BORACARE TREATMENT IS A SUITABLE SUBSTITUTE.
ALL METHODS MUST BE USED IN CONJUNCTION WITH TREATED
SILL PLATES.- PROOF OF METHOD TO BE USED SHALL BE RECEIVED
IN OUR OFFICE BEFORE A CERTIFICATE OF OCCUPANCY WILL BE
ISSUED.
*PROVIDE COMBUSTION AIR FOR GAS FIRED APPLIANCES PER
CHAPTER 17, 2006 INTERNATIONAL RESIDENTIAL CODE
*Surface Drainage Shall Be Diverted to an Approved Point of
Collection. Lots Shall Have a Grade Fall Minimum of 6"
inches Within the First 10' feet Away From the Foundation
Walls.
*ELECTRICAL SHALL BE INSTALLED PER 2005 National Electrical
Code & LOCAL AMENDMENTS
*ELECTRIC STRIP HEATING NOT ALLOWED FOR RESIDENTIAL
PROPERTIES WITH FLOOR AREA GREATER THAN 500 Sq. FEET
*MINIMUM FOUNDATION STANDARD - ALL FOUNDATION SHALL COMPLY
WITH THE MINIMUM FOUNDATION STANDARD AS PER CITY'S
ORDINANCE (FOUNDATION DETAIL SHALL BE SHOWN ON PLANS)
MAKE SURE TO INCLUDE REBAR SLAB GROUND
*ALL FRAMING SHALL COMPLY WITH 2O06 INTERNATIONAL
RESIDENTIAL CODE
*PROVIDE ENGINEERED BEAM FOR GARAGE DOOR HEADER
*ATTACHED GARAGES SHALL HAVE ALL TOP PLATE AND HEADER
PENETRATIONS SEALED
*Assure Proper GFI Locations, Including One Within 25' Of
Outside A/C Unit
*PROTECTION FROM IMPACT - APPLIANCES LOCATED IN A GARAGE
OR CARPORT SHALL BE PROTECTED FROM IMPACT BY AUTOMOBILES
*PLATFORM FOR MECHANICAL EQUIPMENT AND OR ACCESS MAY HAVE TO
------------------------- ------ - ------------
BUILDING DEPT RE,FVS TATIAE :
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE S'pT'ATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 3
Application Number . . . . . 08-00000429 Date 2/14/08
Application pin number . . . 210599
----------------------------------------------------------------------------
Special Notes and Comments
BE ELEVATED TO ALLOW FOR ATTIC INSULATION
*Wall and Ceiling Insulation are as follows respectively.
If Wall to Window Ratio is up to 15% the Values Shall be
R-13 and R-30, above 15% the Ceiling Insulation is Increased
to R-38.
*ACCESS TO JACUZZI TUB CIRCULATION PUMPS SHALL BE PROVIDED
IN ACCORDANCE WITH 421.5 OF THE 2006 INTERNATIONAL PLUMBING
CODE. IF NOT DETERMINED BY MANUFACTURER IT SHALL BE A
MINIMUM OF 12" X 12" AND IF PUMP IS GREATER THAN 2' FROM
ACCESS OPENING THEN IT MUST BE 18" X 18" OPENING
*IF LAWN SPRINKLERS IS PROVIDED, PERMIT MUST BE ISSUED PRIOR
TO CERTIFICATE OF OCCUPANCY.
*REQUIRED EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE
WITHOUT THE USE OF A KEY,TOOL OR SPECIAL KNOWLEDGE/EFFORT
*A Minimum of No. 15 Asphalt Felt or OtherApproved Water
Resisitive Barrier Shall be Placed Over All Exterior
Sheathing Per 2006 IRC Section R703.2
*THE MAXIMUM ALLOWABLE DRIVEWAY WIDTH MEASURED AT THE
PROPERTY LINE IS 25' AND MINIMUM WIDTH OF 12'
*ON NARROW WALL BRACING WHERE SPECIAL NAILING PATTERN,
STRAPPING BETWEEN STORIES, OR HOLD DOWNS ARE REQUIRED THESE.
ITEMS MUST REMAIN VISIBLE UNTIL THE INSPECTION PROCESS HAS
BEEN DONE TO ALLOW FOR COVER-UP
*MUST INDICATE METHODS ON FLOOR PLAN TO BE USED TO MEET
NARROW WALL BRACING REQUIREMENTS PER IRC CODE SECTION
R602.10 IN 2006 IRC
*If PEX water supply piping is sleeved below the slab, seal
annular space at ends with caulk, foam or other means.
Also assure proper protection of pipe to U.V. light.
*ANY CHANGES OR ALTERATIONS TO SUBMITTED PLANS MUST BE
RESUBMITTED AND APPROVED BEFORE WORK IS DONE IN ORDER TO
ASSURE CODE COMPLIANCE
*POST PERMIT CARD ON JOB SITE TO BE VISIBLE FROM ROAD
*WHEN WATER MAIN PRESSURE EXCEEDS 80 PSI, AN APPROVED
PRESSURE REDUCING VALVE SHALL BE PROVIDED THAT LIMITS THE
MAXIMUM STATIC WATER PRESSURE TO 80 PSI
*RECESSED LIGHTING INSTALLED IN THE BUILDING ENVELOPE SHALL
BE IC RATED AND SEALED TO PREVENT AIR LEAKAGE
*For residential applications with a glazing area that
exceeds 150 of the gross area of exterior walls, R-8 duct
insulation is required. As an alternative, R-6 duct
-------------------------------_�---------- ------ ----0 --.-,/ '------------
BUILDING DEPT REPAF,SENTAT
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 4
Application Number . . . . . 08-00000429 Date 2/14/08
Application pin number . . . 210599
----------------------------------------------------------------------------
Special Notes and Comments
insulation can be used if the a/c system has a SEER rating
of 12 or more.
*PROVIDE SANITARY FACILITIES FOR WORKERS ON SITE LOCATED OFF
THE PUBLIC RIGHT-OF-WAY.
*SMOKE DETECTORS MUST HAVE 3' CLEARANCE FROM FORCED AIR
DUCTS, CEILING FANS AND RETURN AIR
*PROVIDE STRING LINES FOR ALL BUILDING SETBACKS AND
EASEMENTS ON FOUNDATION INSPECTION.
FORM SURVEY MAY BE SUBMITTED IN PLACE OF STRINGS.
*SHOWERS AND TUB/SHOWER COMBINATIONS SHALL BE EQUIPPED WITH
AN ANTI -SCALD VALVE THAT LIMITS WATER TEMPERATURE TO 120
DEGREES
*THE COMBINED SOLAR HEAT GAIN COEFFICIENT OF ALL GLAZED
FENESTRATION/WINDOW PRODUCTS DEPENDING ON PERCENTAGE OF WALL
TO GLAZING/WINDOW RATIO UP TO 2001 A .40 OR LOWER FACTOR AND
ABOVE 20% TO 30% A .35 FACTOR OR LOWER SHALL BE MET.
*ALL SILLS AND BOTTOM PLATES IN CONTACT WITH CONRETE MUST BE
TREATED OR NATURALLY RESISTANT TO INSECTS AND DECAY
*SMOKE DETECTORS SHALL BE INTERCONNECTED, 120 VOLT W/BATTERY
BACKUP AND LOCATED IN EACH SLEEPING ROOM AND OUTSIDE EACH
SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
BEDROOMS
*REMOVE ALL VEGETATION AND FOREIGN MATERIAL FROM SLAB AREA
PRIOR TO PLACING FILL. FILL SHALL BE FREE FROM
VEGETATION AND FOREIGN MATERIAL.
*STAIRS SHALL COMPLY WITH SECTION R-311 (2006 IRC) WITH A
CONTINUOUS HANDRAIL OR SECTION
1009 (2006 IBC) AS APPROPRIATE, CONTINUOUS HANDRAIL
NEEDED, ENDS SHALL BE RETURNED OR SHALL TERMINATE INTO A
NEWEL POST OR SAFETY TERMINAL ON COMMERCIAL JOBS.
*WINDOWS ADJACENT TO TUBS WITHIN 60" ABOVE DRAIN SHALL BE
TEMPERED GLASS
*TEMPERED GLASS REQUIRED IN WINDOWS WITHIN 24" OF DOORS IN
ADJACENT WALLS
*AN APPROVED DEVICE FOR THERMAL EXPANSION CONTROL SHALL BE
PROVIDED FOR BUILDINGS UTILIZING STORAGE WATER HEATING
EQUIPMENT AND A PRESSURE REDUCING VALVE
*PER R308.4 GLAZING ADJACENT TO STAIRWAYS WITHIN 36" AND
LESS THAN 60" ABOVE WALKING SURFACE MUST BE TEMPERED (2003
IRC)
*U-Factor Ratings for Window % up to 15% is .65, from 15% to
-------------------------------- ----- --/-� --'--�----------
BUILDING DEPT RF/PRES14
TATIVEY
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
'
Page
5
Application Number . . . . .
08-00000429 Date
2/14/08
Application pin number . . .
----------------------------------------------------------------------------
210599
Special Notes and Comments
20% is .55, from 20% to 25% is
.54 and above 25% is .46 or
lower.
*RANGE/DRYER DUCT MUST COMPLY
WITH 2O06 IMC
*IF AN OPERABLE WINDOW IS MORE
THAN 72" ABOVE EXTERIOR
FINISHED GRADE THEN THE LOWEST
PART OF THE WINDOW OPENING
MUST BE AT LEAST 24" ABOVE THE
FINSHED FLOOR FROM INSIDE THE
ROOM.
*ALL PLUMBING, ELECTRICAL, AND
HVAC (mechanical) WORK MUST
BE PERFORMED BY LICENSED CONTRACTORS. CONTACT BUILDING
DEPARTMENT FOR INSPECTIONS
PRIOR TO COVERING ANY WORK
*GAS APPLIANCES HAVING AN IGNITION
SOURCE SHALL BE ELEVATED
SUCH THAT THE IGNITION SOURCE
IS 18" ABOVE THE FLOOR IN
PRIVATE GARAGES. THIS INCLUDES
BOTH WATER HEATERS AND
CLOTHES DRYERS.
----------------------------------------------------------------------------
Other Fees . . . . . . . . .
SEWER TAP 4" 350.00
----------------------------------------------------------------------------
WATER TAP 3/4" 400.00
Fee summary Charged
-----------------
Paid Credited Due
----------
Permit Fee Total 472.00
------------------------------
472.00 .00
.00
Plan Check Total .00
.00 .00
.00
Other Fee Total 750.00
750.00 .00
.00
Grand Total 1222.00
1222.00 .00
.00
BUILDING DE
APPLICANT:
TEMPORARY POLE PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
----------------------------------------------------------------------------
Application Number . . . . .
08-00000430 Date
2/14/08
Application pin number . . .
304330
Property Address . . . . . .
918 EAGLE AVE
Property ID:
650730-0408-0400
R #:
R303422
Application type description
TEMP POLE
Subdivision Name . . . . . .
Property Use . . . . . . . .
RESIDENTIAL
Property Zoning . . . . . . .
PLANNED DEVL DISTRICT
Application valuation . . . .
0
Owner
------------------------
Contractor
BCS DEVELOPMENT CO
------------------------
STYLECRAFT BUILDERS
4090 SH 6 S
4090 SH 6 S
COLLEGE STATION TX 77845
COLLEGE STATION
TX 77845
----------------------------------------------------------------------------
(979) 690-1222
Permit . . . . TEMP POLE
PERMIT
Additional desc . . GS
Permit pin number . 552307
Permit Fee . . . . 20.00
Issue Date . . . . 2/14/08
----------------------------------------------------------------------------
Valuation . . . .
0
Other Fees . . . . . . . . .
----------------------------------------------------------------------------
TEMP ELECT POLE CONNECT
45.00
Fee summary Charged
-----------------
Paid Credited
Due
----------
Permit Fee Total 20.00
------------------------------
20.00 .00
.00
Other Fee Total 45.00
45.00 .00
.00
Grand Total 65.00
65.00 .00
.00
-------------------------------------------- ----- z- I
-/&09406� -----------
BUILDING DEPT REBRESENTATIVE: A 4M;401�t
APPLICANT: /;).
Use Only
(*// APPLICATION FOR BUILDING PERMIT
1101 TEXAS AVENUE
COLLEGE STATION, TX 77840
CITY OF COLLEGE STATION (979) 764-3570 (979) 764-3496 FAX
Planning d- Development Snvitei
WWW.CSTX.GOV
DATE:
APPLICATION # 0 Wo '
TEMP POLE # -lq5 o
ADDRESS/LOCATION:_ q18 FA!4� � /
LOT AID -/BLOCK_eL—VSUBDIVISION 41E3FIGL0 SEC/PH_ 4
BUSINESS/OWNER NAME: STYLECRAFT BUILDERS, INC. PHONE: 690-1222 ext. 120
CONTRACTOR/HOMEOWNER: STYLECRAFT BUILDERS, INC. PHONE: 690-1222 ext. 120
CONTACT PERSON FOR REVIEW COMMENTS: ERIC WIVAGG PHONE: 690-1222 ext. 120
FAX: 690-0348 EMAIL: ewivagg(aD-stylecraft-builders.com
ELECTRICIAN: Brazos Valley Electric PLUMBER: Bass Plumbing
HVAC: Control Temp GOOD CENTS (Residential only): No
ACCESSORY/STORAGE LOCATION RE -ROOF
ADDITION MOVING SHELL ONLY
DEMOLITION (Asbestos Survey) X NEW CONSTRUCTION * SLAB ONLY
DUPLEX (Landscape Plans) REMODEURENOVATION* SWIMMING POOL
TENT/CANOPY
DESCRIPTION OF WORK: Conventional Framing
PROPOSED USE: Single Familv Residence
WALL BRACING METHOD: PRESCRIPTIVE ❑ APA PORTAL FRAME W/ CSPS V ENGINEERED
I"OMEOWNER ASSOC IATION/ARCHITECTUAL OR DESIGN REVIEW COMMITTEE APPROVAL:
TEXAS ACCESSIBILITY STANDARD (TAS) PROJECT REGISTRATION# EABPRJ N/A
VALUATION: $ 103'A4 -' TOTALAREA: /8541 HEATED AREA: /564
(Cost of Labor and Materials)
/�v XX PUBLIC SEWER
A
L� SEPTIC/TREATMENT SYSTEM
❑X SEWER TAP:
�X WATER TAP:
OTHER TAP:
V
�X TEMP POLE
GARAGE TYPE
4"
SIZE
% n
SIZE
NUMBER OF BEDROOMS:
NUMBER OF BATHROOMS: 1{
INTERIOR WALL TYPE
EXTERIOR WALL TYPE:
FOUNDATION TYPE:
JIZE
ROOF TYPE:
SINGLE b�j DOUBLE E]
ATTACHED a DETA,P14N
Sheet Rock
Siding and/or Masonry
Slab on Grade
ComDOsitlon
TRIPLE
,5RRgRT F
SIGNATURE OF APPLICANT: l /1 '1 1
*If proposed work involves new commercial construction -or fudde
commercial property, building elevations are required.
Official Use Only
lx d-/Z- Vg
5 e,4. ,s Plans Examiner
Z
ents/rIe-bovations to an existing
Zoning Official Fire Marshall
C ents — It/�I'rdvrt¢ �A+'iP.r'wt
coi..
Po 14 S"LQ'ft-40r / W / l to N A04 ES r NO ,
Energy Code Compliance Information
% Glazing of exterior walls
Insulation R value of exterior walls
Insulation R value of ceiling 1 (flat areas)
Insulation R value of ceiling 2 (vaulted areas/no attic)
Glazing SHGC (Solar Heat Gain Coefficient)
Glazing U-Factor
R value of ductwork
A/C SEER Rating
Protection Against Subterranean Termites
l0 %
/
R13
R30
R19
.35
.53
R6
.�
13
❑ Chemical Termiticide Treatment (Soil Treatment)
Chemical Termiticide Treatment (Field Applied Wood Treatment)
❑ Physical Barriers
❑ Other
*Verification of Application shall be submitted to the City of College Station
Building Department prior to issuance of the Certificate of Occupancy.
M
CITY OF COLLEGE STATION
Planning d Development Service;
PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
PLAN REVIEW/PERMIT NUMBER# O
DATE:
BUILDING ADDRESS: q Is t5" 1.,e- AV e
I. Foundation Requirements- Minimum City oundation Standards
N
A.
Concrete minimum compression strength of 3000 PSI
B.
Minimum four 4 inch slab thickness
C.
Vapor barrier Emil. Poly min.
D.
Slab/beam or pier layout shown
1. Footings/beams are continuous over the length and width of foundation
2. Footings 30" exterior, 24" interior, unless over 60' long must be 30"
3. Spacing of beams does not exceed 15'
E.
Reinforcement details to meet minimum requirements
1. Slab reinforcement and Beam Reinforcement
F.
Protection Method used for Termites.
ON
G.
Wood foundation details indicated
OK
II. Framing: Floor, Wall, Ceiling and Roof Requirements
A.
Girder or sill dimensions, grade & species
B.
Floor joist size, spacing, grade & direction of span indicted on plans
C.
Treated sill plate or bottom plate
D.
Tenant separation in duplex
K
1. One -hour rated extending to roof deck
O
E.
Header sizes indicated on plans
F.
Emergency bedroom egress
1. Exit direct to outside
2. Operable window
a. Twenty 20 inch clear width by twenty-four 24 inch clear height
b. Maximum sill height of forty-four 44 inches above finished floor
G.
Operable bathroom window required when mechanical ventilation is not provided
H.
Stud grade andspacing
I.
Exterior wall details
1. Sheathing indicated on plans for Wall Bracing
2. Moisture barrier indicated on plans
3. Exterior Wall Covering
J.
Roof framing Ian or elevation shown
K.
Ceiling joist size, spacing, grade and direction of span indicated on plans
L.
Attic access location and size indicated on plans
M.
Span exceeding code tables must be engineered
N.
Rafter size, spacing, roof slope & purlin bracing if required to reduces an
O.
Roof covering
P.
All girders & beams for support of floors, walls, ceiling & roofs must have the size, grade &
location indicated on plans
Q.
Tempered Glass required in all hazardous locations
R. 18" Overhangs allowed on zero lot line, non-combustible perforated soffit only
S. All walls within 3' of property line to have protected openings.
/ K
/OK
M
r,
CITY OF COLLEGE STATION
Planning &Development Service;
PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
III. Stairway Requirements
A. Stairway Details
N O
1. Maximum riser height 7-3/4 inches
2. Minimum tread width 10 inches
3. Stairway risers are uniform 3/8" Max. difference
4. Stairway width not less than 36 inches
5. Stairway headroom not less that six ft. eight 6'-8"
B. Winder details
1. Treads a minimum of six 6 inches on narrow edge
2. Treads a minimum often (10) inches at a distance of twelve (12) inches from the
narrow edge
C. Spiral stairway details
1. Riser height less than nine and one-half 9-1/2 inches
2. Treads a minimum of seven and one-half (7-1/2) inches at a distance of twelve (12)
inches from the narrow edge
3. Stairway width not less than thirty-six inches
4. Headroom required not less than six ft six 6-6 inches
5. All treads must be identical
D. Guards/handrail details
1. Guards required when a porch, deck, balcony or landing is thirty (30) inches
above grade or finished floor
2. Handrails are required on stairways located two or more risers above floor/grade
3. Handrails must be thirty-four to thirty-eight (34-38) inches when measured from the
leading edge of the tread
4. Handrails must not project more than four & one-half (4-1/2) inches into width of a
stairway
5. Guards must be a minimum of thirty-six 36 inches above finished floor
6. Guards & handrails along open-side(s) of stairway must have intermediate
railing or uprights that prevent the passage of a four 4 inch sphere
IV. Fireplace Requirements
OK
A. Hearth extensions
1. Fireplace opening < 6 s , ft, extensions: 8" & 16" forward
2. Fireplace opening > 6 s . ft. extensions: 12" side & 20" forward
B. Masonry fireplace requires 2" clearance from all combustible materials
C. Chimneys must meet IRC Chapter 10 Requirements
V. Electrical Service Requirements
A. Electrical plan to include:
NAT,
1. Electrical fixtures & switches indicated
2. Smoke detector locations indicated as required
3. GFI circuits indicated where required
4. Arc fault protection for bedroom circuits
5. Panel location
CITY OF COLLEGE STATION
Planning d Development Services
PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
COLLEGE STATION; TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
VI. Plumbing Requirements
A. Pressure reducing valve required when water pressure exceeds 80 psi
N
B. Plumbing access to bathtubs
C. Means for thermal expansion provided when required
D. Water heaters elevated 18" when installed in the garage or room directly off garage
VII. Mechanical Requirements
N K
A. All mechanical ventilation's in bathrooms & range hood ventilation must be ducted to
outside excludes ductless units)
T
B. Attic installed H.V.A.C. requirements:
1. Twenty-four (24) inch wide unobstructed walkway from attic access to equipment
must be provided
2. Attic access located within 20 feet of equipment
C. Combustion air supplied for gas appliances when required)
VIII. Energy Requirements
N
A. Compliance software worksheet MECcheck submitted, or
B. Energy data supplied Percent of glazing, insulation R-values, window U-values, etc.
Zoning Ordinance Requirements — Ordinance 850
N K
Permitted use for district
Density requirements
Minimum lot size
Setbacks
Easements
Required parking
Street Ordinance Requirements
N
Maximum drive width for residence is 25' combined for circular and 12' minimum for sin le
Minimum 20 feet from driveway to side(intersecting) street property line sight triangle
Driveway access to lesser street for corner lots
Subdivision Regulations — Ordinance 690
NA/OV
Approved subdivision
Plat filed
Flood lain Regulations — Ordinance 1301
N
Does not block any water course or divert any flow
—
Elevation certificate needed
W10K
h
"APPROVED PLANS PER IRC SECTION R106.3.1."
PLANS EXAMINER
2 - 13_62�
DATE
•
Permit #
Permit Date
REScheck Software Version 3.7.3
Compliance Certificate
Report Date: 02/11/08
Data filename: S:\ACAD\Archived\Old REScheck\1564_918 Eagle.rck
Energy Code:
2003 IECC
Location:
College Station, Texas
Construction Type:.
Single Family
Glazing Area Percentage:
10%
Heating Degree Days:
1788
Construction Site:
Owner/Agent:
Designer/Contractor:
918 Eagle
Stylecraft Builders, Inc.
Stylecraft Builders, Inc.
College Station, TX 77845
4090 SH 6 South
4090 SH 6 South
College Station, TX 77845
College Station, TX 77845
979-690-1222 x127
979-690-1222 x127
jsaucier@stylecraft-builders.com
jsaucier@stylecraft-builders.com
Maximum SHGC: 0.40 Your SHGC: 0.40
Wall 1: Wood Frame, 16" o.c.:
Window 1: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 2: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 3: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 4: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 5: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 6: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 7: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 8: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 9: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 10: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 11: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 12: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 13: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 14: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 15: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 16: Metal Frame:Double Pane with Low-E:
2134
8
8
24
25
25
3
4
4
4
13
13
13
12
11
13
13
13.0 0.0
154
0.670 5
0.670 5
0.670 16
0.670 17
0.670 17
0.670 2
0.670 3
0.670 3
0.670 3
0.670 9
0.670 9
0.670 9
0.670 8
0.670 7
0.670 9
0.670 9
Page 1 of 2
4
� 0
I *
SHGC: 0.40
Window 17: Metal Frame:Double Pane with Low-E:
6
0.670 4
SHGC: 0.40
Door 1: Solid:
38
0.500 19
Door 2: Glass:
18
0.440 8
SHGC: 0.40
Ceiling 1: Flat Ceiling or Scissor Truss:
763 30.0
0.0 27
Ceiling 2: Cathedral Ceiling (no attic):
67 19.0
0.0 3
Floor 1: Slab -On -Grade: Unheated: , Insulation Depth: 0.0'
119
0.0 124
Furnace 1: Forced Hot Air: 80 AFUE
Air Conditioner 1: Electric Central Air: 13 SEER
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The o osed building has bev -en designed to meet the 2003 IECC requirements in
REScheck Version 3.7.3 and to comply with the ndato re nts ' in the REScheck Inspection Checklisklvo
Builder/Designer Company Name Date
Project Notes:
All U-Factors and SHGC are at entered at higher than actual amounts.
Actual amounts are lower, but are entered higher to account for
differences in ratings per material.
Page 2 of 2