INSPECTION TICKET PAGE 9
City of
College Station
INSPECTOR: BUILDING INSPECTOR DATE 7/14/08
------------------------------------------------------------------------------------------------
ADDRESS
. : 4136 MCFARLAND
DR
SUBDIV: SOUTHERN TRACE PH 2
CONTRACTOR STYLECRAFT
BUILDERS PHONE (979) 690-1222
OWNER
BCS DEVELOPMENT
CO
PHONE
PARCEL
579530-0209-0030
APPL NUMBER: 08-00000336
RESIDENTIAL, 1 UNIT DETACHED NEW
------------------------------------------------------------------------------------------------
PERMIT:
BLDG 00 BUILDING
PERMIT
REQUESTED
INSP
DESCRIPTION
TYP/SQ
COMPLETED
RESULT
RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
B100 01
3/17/08
BB
BLDG, FOUNDATION -SLAB TIME: 17:00
3/17/08
AP
March 17, 2008 11:08:24 AM glsouth.
03/17/2008 04:35 PM BB PDA
Strings up. Slab ground installed.
B120 01
4/01/08
OC
BLDG, FRAMING -PARTIAL TIME: 17:00
4/01/08
CA
March 31, 2008 2:30:25 PM acarter.
apa inspection
B145 01
4/01/08
OC
BLDG, EXT. SHEATHING FASTENER TIME: 17:00
4/01/08
AP
B115 01
4/21/08
OC
BLDG, FRAMING TIME: 17:00
4/21/08
AP
April 18, 2008 10:48:58 AM acarter.
B130 01
4/23/08
BB
BLDG, INSULATION TIME: 17:00
4/23/08
AP
April 22, 2008 3:11:05 PM glsouth.
B132'01
4/25/08
BB
BLDG, SHEETROCK FASTENER TIME: 17:00
4/25/08
DA
04/25/2008 03:20 PM BB PDA
Need correct fastening in multiple areas.
B132 02
4/28/08
BB
BLDG, SHEETROCK FASTENER TIME: 17:00
4/28/08
AP
April 25, 2008 3:11:11 PM npadilla.
B125 01
7/03/08
BB
BLDG, FINAL TIME: 17:00
7/03/08
DP
July 2, 2008 4:12:44 PM ccourt.
Need insulation certificate in attic. Need proper hand rail
height. Irrigation installed.
B125 02
7/14/08
BI
BLDG, FINAL TIME: 17:00
Im
AlLr July 14, 2008 9:18:52 AM acarter.
COMMENTS AND NOTES ---- --------------
O
Inspection Comments for Final! Date: 7/3/2008
Permit Year: 8 permit Number: 33E
Address: 4136 MCFARLAND DR
Insp.
Inspection Type Code
Description
status
Inspection Result Comments
B100
BLDG, FOUNDATION -SLAB
IC
03/17/2008 04:35 PM BB PDA
B100
BLDG, FOUNDATION -SLAB
IC
Strings up. Slab ground installed.
B132
BLDG, SHEETROCK FASTED
IC
04/25/2008 03:20 PM BB PDA
B132
BLDG, SHEETROCK FASTEl'
IC
Need correct fastening in multiple areas.
E110
ELEC, ROUGH IN
IC
04/17/2008 03:10 PM BB PDA
E110
ELEC, ROUGH IN
IC
Need to install elec. box for light over stairs and for
Ell
ELEC, ROUGH IN
IC
outlet in storage room, by framing.
E150
ELEC, FINAL
IC
04/23/2008 12:33 PM BB PDA
E150
ELEC, FINAL
IC
Wrong inspection. At insulation, not ready for finals.
E150
ELEC, FINAL
IC
Need proper groundrod clamp by building final. Need acorn
E150
ELEC, FINAL
IC
clamp that is brass or copper.
P100
PLBG, ROUGH IN
IC
February 28, 2008 1:55:22 PM kwolfe.
P100
PLBG, ROUGH IN
IC
Ben called to cancel
P100
PLBG, ROUGH IN
IC
February 29, 2008 12:03:57 PM kwolfe.
P105
PLBG, TOP OUT
IC
04/09/2008 10:41 AM RH PDA
P105
PLBG, TOP OUT
IC
Correct backfall on drain arm in upstairs front bath by
P105
PLBG, TOP OUT _
IC
framing.
P125
PLBG, FINAL
IC
All electric.
Page 1
-.; -Apr. 4. 2008•- 9:47AM S t Y I e c r a f t Builders,
"Shielding & Protecting
Moines Against Posts"
I n c. No. 8561 • P. 41
Renewable 5 Year
D9,33K
Subterranean
Termite Retreatment
Agreement
(Does got cover any other species of Termites)
This agreement provides for retreatment only of the infested areas covered under the original treatment areas (See Graph
Cus� t merhamc Date Billing Name if differem
/ /A C 41 Q:Q,�
Street Address of treated structure Billing Address if different
C, S 71 772
City State Zip Code City State Zip Code
ou
Initial Termite Cost $
Additional Renewals Paid
Other
Tax
Cash Check# Total S 7
Payment $
Balance $
Credit Card
Type Exp. Date Card Number
Year $ghigrra a Termite Retreatment S'spoonteet RP Lee Termite and Pcst Control will retreat the structure for Subterranean
Termites at no cost to the customer, if an infestation of Subterranean Termites is found, as long as the original treatment is paid in full
and the customer is current on their yearly renewals. This Agreement will expire in one (1) year unless the customer elects to pay
the yearly warranty fee. The guarantee can be renewed for up to five ($) years by paying the yearly warranty fee. RP Lee Termite
and Post Control may approve additional war=. ty years after the five (5) years with an additional increase in the yearly warranty fee.
The guarantee does not cover any damages to the structure or contents of the customer. The customer agrees to control all condusivc
conditions that may cause reinfestation. If the structure is modified, added on to, altered, or if the soil treatment around the structure
is removed the customer must contact RP Lee Termite and Pest Control andpay for additional treatment in order to keep the guarantee
in effect If the customer does not pay for additional treatment the retreatment guarantee can be cancelled. u�
Reeewal Fee: Customer may elect to renew the retreatment guarantee for additional years. The renewal fee is S• nlus tart.
The renewal fee is due on or before the annual anniversary date or paid $ -' plus tax every third (3) month with inspection,
jAalntaining the Guarantee: The customer agrees to correct all condusive conditions, at owner's expense, as they exist or as they
occur in the future in order for the guarantee not to be cancelled. Customer will make the structure available for inspections and
treatments as requested by .RP Lee Termite and Pest Control,
RelnspCdgm RP Lee Termite and Pest Control will reinspect the structure at customers request or any other times RP Lee Termite
and Pest Control deems necessary, .RP Lee Termite and Pest Control recommends that the customer call and setup an annual inspec-
tion at the time of customers yearly renewal.
lhpgx; This agreement may be transferred to a new owner with the paymcut of a transfer fee of S , copy of the Wood
Destroying Insect Report from the sell, and approval of RP Lee Termite and Pest Control.
This Subterranean T1grmjtA-Rfttu9ment Guarantee does not nrevent and is not i"tended to control other forms ot•Termites
fl2Mag - Formosan, etc.), Wood Boring Beetles. Carpenter Ants, Carpenter Bees. Wood Rot . EanQus. Dmy, or any_other
wood dent mine insects or organisms.
gam; In the event of any dispute arising out of this agreement or any other services performed or not performed the parties
above agree to participate in mediation through and in accordance with the commercial mediation rules of the American Arbitration
Association. The Arbitrator shall consider the legal defenses raised in the arbitration, and the decision of the arbitrator shall be final,
binding, non -appealable and may be entered and enforced in any court having jurisdiction in accordance with the Federal Arbitration
Act
Limitation of • Landscaping and grass next to the slab may be damaged during treatment, carpet may need to be pulled
up in certain areas around the home, drill holes may need to be made iu floor coverings such as file or linoleum or in cabinets next
to pipe areas, and holes may need to be cut in walls. Customer agrees not to hold RP Lee Termite and Pest Control liable for these
damages, or treatment techniques, or other damages that may occur during treatment.
AgMMe This Agreement shall be the entire agreement between customer and RP LeeTetmite and Pest Control. if any part of
this agreement is found to be invalid it shall not affect the validity of any other part of the Agreement
Home Phone
Work Phoue
Type of Treatment Partial Bait yPre-Treat
Treatment for: X Prevention Control of Subterranean
Termites
Notes:
We are licensed U the Structural Pest Control Board - 333-Guadalupe. Suite 1-510
Austin. TX 78701512 3.Q5:= r J
RP Lce Termite &�est Control Ccrt. Apl. C tomer gnature Date
r Apr. 4. 2008 9:47AM Stylecraft Builders, Inc, No.8561 P. 46
New Construction $ubtarranean Termite Ap`"° a P. IMIM
Spit Treatment Record
This tom fs ca lOtod >y tho I10011=1 POat Control t;otnpnn —
i'stotb n1{iornnp urdelt for ua coteetiret of �natkn 4 ostlmatod to aUo oG'o autos poi reitwnLo: ani�uding uw r cio fur ioo,vm�d �►ivucbc+s, $01V ris
oxhtlnp dele trvurses. Oadtertrto and molyd"a trio. data neudu4. and Ca' tpladrtq and raHoamw the aofecuon rA rntorrtsdtm nt= mrorn>.tmm b nwn0aton tu,d io
► 4 wed to d*M b000bre. HUD m6r not a&A fig odotmetlan. aad you tus not rogtrhad t# cc=mto atd tuna. wdom tt dimes a ewr"I Vold Cu& conoot
numbs.
s cion 24 CFR 200.92od(b)(0) re0MA $0 ft &keg for HUb Inyumd aruduroz; ntuat W froo vl Wrmitu huzards. TT3 Iniumeaon Wadon towbw the bustler to ,
terrify ant an aAl*aued hoot GadM eAmmw perlarned all tequkod 9estmml ke jwunw. and (het Oro btLWcr Vudrrintow fie Vowed ate BPIIA irttosraaan tpr
Otte year. DutUder�, Plat toatrol oorntu+iae, mort}jago tmdom, ternetuyors, end N4'G ss a reearJ of traatmont fcr apoatn: t,unton way uao 1!w odurma9un COtlLued.
Tho intorwt;an'a: nd �enrw+ad oa�'�d�dstL _ -- -
Tnts report isswunilwa tar tntormauomat purposes M 1he bulltler on prol)Md (now) conauuraion cosos wher. zoo trutmont for pravonuon a aubWmanaan
tormit& infoctation Ic cpec flad by tho &uffdo►, areldtool, or requtrht by tho NOW. architect, FKA, or VA
Ail tmntraM tot sorvieoa M Wtwoon Ito Post ConIF01 Operator and bulldor. unlot:s 91-0.tad o;hwwuo.
Epotton 1: Generd Informx1a„7(Tr6419 Otinptury IntOM6917)
Con�ny Noma _ S_ �itn� rx c i t s l emlll n f �,
cernpMY Addroae o o z3 t uy _. t4, �. -
ComPQftY 8uctnacs jrporma tfo- i9 CemyanY Fttarw Ntr. r.._
FFWYA Oaso'Kc. (U any)
Seottoll 21 BuW lffivm t)on
Company Namo
SaGtiOA f: Property lnfGrtnirtian
Loco6w of $tn akq (a) TtoulW (Shoot p4jtou or Legal Dascrlptlor., QiY, awb and 71p)
1}" of Contttudlion (Moro than o box UVY W oLtrof.o0) t.lJ :feb
orSaSema! Crarii i� OVor — -
ApprmdmWA Oap1h of Fooling; Ou'.alde ltwlda Typo of FRI
' $rcUon 4: Ytmafiront )nfonaattan
3•
Oato(e) of Tivatmartt(a) 14V
gwmd Nuns of Pr dLa(5) Liao
r1 t4 C 4 n6 ---
EPA Repfa don Na
fo
Approxlmato Final WX Solution % r
ApptoxUWata wlze of 7roamtontAroo; 5y ft Omar IL Linear fi. of Masonry Yoko �—
Aptuoxlmate Total a0ona d Sotutien Aj*1od �� 6r4
Was trgtlirr WA cawaad on uzlwurtr 21 Yes i; -tt No
SatvtcaAgzsantorttAvallrtdo4 Yes fo No
Nate: Some *We laws require aorvioo sgroemoms to Lo iaauol Thor form 0uar nut proarwl lwts law-
COrttrtten;a
Name ut Applkawr(s) �9VD
ed(tmrzow No. (If requirod by $tole taw) p7
Thu eppfcatot hu used a PrOdt d fn &WOrdun1;9 with Uts producl table and stato (equirewrtm. All troatrWM rnaturl�ls and nrotjjodb rood comply With
toato and WOW togulAtiorta.
Atrttw&.ed 0gnntwo -cam -- ovtu
twMin HM wit txaroatto tdho dlrna am rt7temeRr� Ccrrvirdsnn rnny n�sttrr 1n utrruunat tnhhv ri St »} ewhien _�G U.S.G. !rT?r t rin 10� 2: 11 U S.r:. X x i! t)?j M
Form NpC1rt)" may sU2 be ucod Rvin taD-rtKAI&a (04P.003)
Apr. 4. 2008 9:48AM •Stylecraft Builders, Inc.
No.8561 P. 48
SUBTERRANEAN TERMITE PRE -CONSTRUCTION TREATMENT DISCLOSURE FOR EACH ESTIMATE
Licensed and regulator under the Texas Structural Pest Control Act
RP LEE TERMITE & PEST CONTROL
PO Box 9423 • College Station, TX 77842 • (972) 690.8622 • TPCL #111486
-CUSTOMER INFOR WyTIrJ{J:
Name: fV / C fl4 A= 7" Phone 41: Phone #2:
Address; City: State: 9r zipCoda,. ,y S�5 77
Location to be Treated:
For all treatments there will be a diagram showing exactly what will be treated prior to the beginning of treatment Revlewthe pesticide label provided to you at this time for minimum treatment standards.
Remember that your architects or design engineers specifications must also be followed, unless they are in violation of the low. Review the consumer information shoot for further information. If you
have any questions, contact the nest eantrol camoamr or the Texas Structural Pest Control Board, P.O. Box 1927, Austin, TX 78767•1927. Telephone number (512) n8250.
Before conducting a termite preconsiructlon treatment, the company will present a completa diagram of the structure including construction details. When construction prevents performance of a full
treatment, in accordance with a bid for full treatment, any change to a partial treatment by the company providing the treatment will be permuted If the owner of the structure or the person in charge of
the construreon and the certified applicator for the past control company sign a statement attesting to the construction oordhions. The agreement must be attached to the contract with an amended
diagram showing the exact areas to be heated, Copies must be sent to the owner of the property within seven days of the application. /�
notes: &P e'q e4'4e
&1/!e ` � P47�Ajc'iv7
14r
ad
g ON o/V b
7 i¢l C4oye�
Type of treatment proposed: (check all that apply): 0 Full ' Partial �6 Wood 0 Batt ❑ Commercial ❑Ingle Family
Total square feet to be treated: % . Total linear feet to be treated: Z6 6 . Approximate measurements of structure(s) to be treated:
A label of U R j4C r4 A< termiticide(s) is attached. The percentage of the termulcide(s) to be applied at this location is
Estimated amount of termulcide to be applied: 13 gallon(s).
THE SUBTERRANEAN TERMITE PRECONSTRUCTION TREATMENT BUILDERS GUIDE ISATTACHED ON BACK (SPCBID-4). THE BOARD APPROVED SUBTERRANEAN TERMITE
PRECONSTRUCTION TREATMENT BUILDERS GUIDE MUST BE PROVIDED TO, AND SIGNED BYTHE CONTRACTOR OR PURCHASER OF THE PRECONSTRUCTION TREATMENT
SERVICE. Complete details of warranty (If any) including time period of warranty, renewal options and cost, and obligations of the contracting parties is attached. Ifthe wamrnty does not
include the entire structure treated, the areas Included in the warranty are (speetf# x
A consum informatiion sheet is also attached.
Signature o r Technician Printed Name Date Signature of Customer Verifying Recelpt of This Document Date
MA a STPA 3e2 • frAw 01OM7 Whb Capy • seNree ProWder ..Yellow Copy - Cummer ram Dmb and P6nro00y 8mNau" m mudmo m i-bw 2fig5 , oieRB.B. nt A=
service Treatment Invoice
outer Q% 1Nap Code:
tart Time: am/pm Finish Time amlpm
ype of Searvlce: �Itltlal Regular Follov► Up One Tbne Charity
��
-ervice Address
lame: , f-Ier,24$-•T
rddress: & Ale air av�i
TX 77;, V-5'
'hone:
Billing:
7 L
iUiT a ilk S- 10 '11,110-1
Date: 3'���� Appoint. Time: -1 amlpm
Frequency: M ISM Q S V
Struchav: 6pCrarvl P/B Combo
Pets: Dog(s) Cat(a) Bird(s) Fish
Cost of Service $ %�7•
Tax S '
Total Due S
Payment S
Balance $
TST PROBLEMS: DIRECl'IONS / INSTRUCTIONS:
EQUIP. METH. LOCATIONS) PRODUCT
WOOD DESTROYING >i�NsF�$
QTY
TARGET PEST(S)
Payment by:
Cash O
Check D #,
Credit Card Q
PAYMENT DUE
UPON RECEIPT
Ternddor W-Fiprorll ,"No Sublerranemr Tcrjnitcs, Anls Siseof Tank Posted
Termidor@4%V-F1prona A6% Subterranean Termites. Sine ol'1•ark Posted
Bore•earo-DisodiumOetaburnteTetrahydatc56•J. y SulbienvnearlFornwerlDrywrud'1'ernkee,Cnrpea[erAatn,Dectles, Posted r/
[wader RPH-Baygon 1%i
Demos ►VP-t.)mno-Pherosypheryl
Dimahycykyeloprepamearbanylarte 1%
Tempo 1J11raMVP-Cyliu1hvin.WSi6 (Rest)
(gem. srrlacespray, spot, mist, crack& crevice)
Talstor IEZ BDenihrin .21/6
N1axforce-Hydrant hylcn•1°i6-215or6
Cyl lck CS Cyilutbrin AS%.
Pkantom m/o
'lengard-Permethrin .5%
Srrpend SC-Dellaretrr9n4.75% (REST)
N?guard-Methyletroxy 18% (REST)
Excite R Pyrclhrin AS'/e
Fastrac-Brometbalin .01%
Bait Stadon.LargeiR nall Glne Boards
Pro-Conlrvl Ptu Pyrelhrins 50%.
Masterline Birenthrin .060A
Carpenler Ards, Spiders, Crickets, Millipedes, Beetles, Tenn ilea.
Codkroadres, Millipedes, Sowbugs, Flies, Ticks, Mosquitos, Pillbugs,
Silrerlisk Bee++, Avts, CarpenterAots, Scorpions, Spiders.
Arta (Eseept Pharaoh), Cockroadies, Crickets, Farwlgs, 611111pedes, Fllea, Fruit Flies, Deelles,
Pillbugs, S1lverlisk, Spklors, Guts, Hornets, Wasm Velio» fackem
Ants, Cerdpedes, Cockroaches, Clrlckeft, Grassaappern, Scorpions, 7lclL%Sllverlisk, SpkJt%m
Yharaoh Amh, Cri.iwts, CarpenterAnts, Lg. Roaches, Variety ofAmts.
Splders,Scotpion%Ants, Carpenter Ants. Carpenter Bces,Ronches, Crlekets, Silverrirh.
Pharob Ants, Varieq olAnts, Roaches.
Fleas,7lck%Auta, Centipedes, CarpeoterAats, Bees, Wusps,CarpeoterBees, Coekruaches,
Crickets, Flies, tam1V,bl1WpedM Mettles, Plllbugs.
Fleas, Bees, Reetlss, Roaches, Crickets, Lace, Flies, Seorplaam, Ticks, Wasps.
[GR-Growth Regulator -Fleas, Roaches, Crickets, Flylog Insects, Stared Product Pests.
1''1eu.
Mice, Rodents, Rots,
Mice, Rodeuh, Rals, Bug Nlonitors-
Housettes,1Ussguifw, Moltrs, Was, Wasps, llmrnels,'Ucks, Cockruaclic&
Spicims,Ants. Rowher, Silverisb, Farwir,% 9'Iear,Smrpioars
A -Compressed Sprayer P-Power Sprayer B-Bait Dispenser BS-Bait Station BT-DaitTrap D-Aerosol Can G-Glue Board H-Haud Duster S-Spreader W-Fogger Fhl-Faamcr AC-Actisol unit Other
Localiomg 1-Kitchen 2-Bath(s) 3-Bedrowns 4-DitingRoom S-Utility 6Storlgo 7-Coml000Areas &.Gangs 9-Perimeter of Structure WAtlic 11-Yard 12-UndcrHome 13-Weschouse 14-Office 15-Piposed WoW 2' up treat Slab Other
►fethod of lWatments: CC -Crack & Crevice SS.Sub-Slab Injection VT -Void Treatment BP -Bait Placeanent BS-Broadcast Spray PB-Periteter Barrier BV-Brick Venire WT-Wood'frralmett
PRECAUTIONS: Do not touch treated areas till dry. Do not tamper with bait stations. Ventilate rooms after treatment. Keep pets away until pesticides have dried.
Licenced by the Texas Department of Agriculture Structural Pest Control Service - P.O. Box 12847 • Austin; TX 78711 •512-30S-82S0
SERVICE TECHNICIAN: J f c CUSTOMER SIGNATURE: DATE:
-� lease review the Customer Information on the other side ofluvolm
P.O. Box 9423 • College Station, TX 77842 • (979) 690-8622 • Fax (979) 690-8840
WFl003035 / 001 City c;f-College Station
PAGE 1
REQ. DATE: 02/08/08 02/08/08 9:19:42
LOCATION: 4136 MCFARLAND DR LOC ID: 208524
REQUESTOR: STYLECRAFT BUILDERS ORIGIN: CUSTOMER -WALK IN
REQ USER: GLSOUTH AUTH USER:GLSOUTH WRK TYPE:
SWR 4" WTR 3/4"
TASK: SET UP NEW UTILITY ACCT SET READY
SCHED START: 02/08/08 SCHED COMPLETION: 02/08/08
********************************************************************************
JOB ORDER RESULT COMMENTS
. Y
(7/15/2008) Amber CarterRe Calling for C 0�@ 4136 Mcfarland Dr� Page
From: Terry Boriskie
To: Amber Carter; Benjamin McCarty; Chris Haver; Gina Southerland; Joe G...
Date: 7/14/2008 4:54 PM
Subject: Re: Calling for C.O. @ 4136 Mcfarland Dr
Contacted Stylecraft Via -email to notify of issues.
Terry Boriskie
City of College Station
Residential Plans Examiner
Ofc. 979-764-3744 Fax 979-764: 3496
>>> Paul Schoenfeld 7/14/2008 3:50 pm >>>
NO for CO.
Water needs to be raised to grade.
Paul
>>> Gina Southerland 7/14/2008 12:35 PM >>>
08-336
Gina Southerland
CSR - Planning & Development Services
City of College Station
979-764-3570
www.csbc.gov
JY111R 11
More Home, Less Money
SHEET INDEX
COVER SHEET
G-1
ENERAL NOTES
G-2
'ITE PLAN
C-1
FOUNDATION PLAN
S-1
DIMENSION PLAN
S-2
DETAILS
S-3
BRACING PLAN
S-4
FRAMING PLAN
S-5
ROOF FRAMING PLAN
S-6
DECKING LAYOUT
S-7
ELEVATIONS
S-8
FRAMING DETAILS
S-9
ELECTRICAL PLAN
E-1
FLOOR PLAN
A-1
FLOORING PLAN
A-2
CABINET LAYOUT
A-3
PLAN APPROVAL
APPROVED
INITIAL81
DATE
ADMINISTRATOR
/
SUPERINTENDENT
/
CUSTOMER
/
NOTICE
THIS SET OF DRAWINGS FOR A HOME IS THE
COPYRIGHTED PROPERTY OF STYLECRAFT
BUILDERS, INC. THIS SINGLE COPY IS LICENSED AND
NO RIGHT TO REPRODUCE, COPY OR DUPLICATE ALL
OR ANY PORTION OF THE LICENSED PLANS IS
GRANTED, EITHER EXPRESSLY OR IMPLIED.
ALL IDEAS, DESIGNS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THE DRAWING ARE
OWNED BY AND THE PROPERTY OF THE DESIGNERS
AND WERE CREATED, EVOLVED AND DEVELOPED
FOR USE ON AND IN CONNECTION WITH THE
SPECIFIED PROJECT. NONE OF SUCH IDEAS,
DESIGNS, ARRANGEMENTS OR PLANS SHALL BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR
CORPORATION FOR ANY PURPOSE WHATSOEVER
WITHOUT THE WRITTEN PERMISSION OF THE
DESIGNERS.
PORCH
9a•
STORAGE 14' x x 4'.1'
sa-
1ra' x T-r
LIVING
9a'
fd•a• x u•-0•
FOYER
9-0
,x 17-11'
DINING
9a•
x 8'a'
KITCHEN
F
ma' x f9a'
W�
BEDROOM 1
9a'
fre x IZV
PORCH
9a'
BUILDING FOOTPRINT
9a'
Y9a• % a4-fo•
1 ST PLAN PREVIEW
SCALE:3/32 =l'-O"
r-------------------------
I i
I I
I I
I
1 I
I
L------------J
2ND PLAN PREVIEW
SCALE:3/32"=1'-0"
FE*41SHING NOTES
1 1 Notes
COMMENTS
AREA
SUMMARY
ILOCATIONI
l ' N
b
o�
O n
a
U�
W 0 QQ
W
W
a
0
V
U°
E-F
rn
� a
d
w
SHEET:
G-1
COVER SHEET
e
c
CFRONT ELEVATION
SCALE:3/32'=l'-0'
BUILDING PFxRMIT :T
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Application Number . . . . . 08-00000336 Date 2/07/08
Application pin number . . . 968304
Property Address . . . . . . 4136 MCFARLAND DR
Property ID: 579530-0209-0030
R #: R305165
Application type description RESIDENTIAL, 1 UNIT DETACHED NEW
Subdivision Name . . . . . . SOUTHERN TRACE PH 2
Property Use . . . . . . . . RESIDENTIAL
Property Zoning . . . . . . . SINGLE FAMILY CLUSTER DEV
Application valuation . . . . 112926
Owner Contractor
------------------------ ------------------------
BCS DEVELOPMENT CO STYLECRAFT BUILDERS
4090 SH 6 S 4090 SH 6 S
COLLEGE STATION TX 77845 COLLEGE STATION TX 77845
(979) 690-1222
--- Structure Information 000 000 SINGLE FAMILY
Construction Type . . . . . COMBUSTIBLE (UNPROTECTED)
Occupancy Type . . . . . . RESIDENTIAL-SFR/DUPLEX
Other struct info . . . . . EXTERIOR WALL TYPE BRICK
IMPACT/PRORATA FEES PAID N/A
FOUNDATION TYPE SLAB
TYPE OF GARAGE (ATT/DET) NA
HEATED AREA 1710.00
INTERIOR WALL TYPE SHEETROCK
NUMBER OF BATHROOMS 4.00
NUMBER OF BEDROOMS 4.00
SEWER TYPE PUBLIC
TRAFFIC IMPACT ANAL (TAZ) 405.00
----------------------------------------------------------------------------
Permit . . . . . . BUILDING PERMIT
Additional desc . . GS
Permit pin number . 550400
Permit Fee . . . . 499.00 Plan Check Fee .00
Issue Date . . . . 2/07/08 Valuation . . . . 112926
Expiration Date . . 8/05/08
Qty Unit Charge Per Extension
BASE FEE 460.00
13.00 3.0000 THOU BLDG, VAL 100001-500000 39.00
----------------------------------------------------------------------------
Special Notes and Comments
-Left side 10' PRAE
-Make sure 2nd floor windows are 24" AFF Minimum
-Narrow Wall Bracing Engineered Method
--------------------------------------------- - - -�---------
BUILDING DEPT REPPASENTkTIVE:
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 2
Application Number . . . . . 08-00000336 Date 2/07/08
Application pin number . . . 968304
----------------------------------------------------------------------------
Special Notes and Comments
*ALL BRANCH CIRCUITS THAT SUPPLY OUTLETS IN DWELLING
UNIT BEDROOMS SHALL BE PROTECTED BY AN ARC -FAULT CIRCUIT
INTERRUPTERS)
*PROVIDE ATTIC ACCESS OPENING (MINIMUM ROUGH -FRAMED SIZE 22"
X 3011) WITHIN 20' OF THE MECHANICAL EQUIPMENT AND WALKWAY
*PROVIDE CHEMICAL TREATMENT OR PHYSICAL BARRIER (SUCH AS
METAL OR PLASTIC TERMITE SHIELDS) FOR PROTECTION
AGAINST TERMITES. IF CHEMICAL TREATMENT IS USED, THE
CONCENTRATION, RATE OF APPLICATION AND TREATMENT
METHOD SHALL BE CONSISTENT WITH THE TERMITICIDE LABEL.
BORACARE TREATMENT IS A SUITABLE SUBSTITUTE.
ALL METHODS MUST BE USED IN CONJUNCTION WITH TREATED
SILL PLATES. PROOF OF METHOD TO BE USED SHALL BE RECEIVED
IN OUR OFFICE BEFORE A CERTIFICATE OF OCCUPANCY WILL BE
ISSUED.
*PROVIDE COMBUSTION AIR FOR GAS FIRED APPLIANCES PER
CHAPTER 17, 2006 INTERNATIONAL RESIDENTIAL CODE
*Surface Drainage Shall Be Diverted to an Approved Point of
Collection. Lots Shall Have a Grade Fall Minimum of 6"
inches Within the First 10' feet Away From the Foundation
Walls.
*ELECTRICAL SHALL BE INSTALLED PER 2005 National Electrical
Code & LOCAL AMENDMENTS
*ELECTRIC STRIP HEATING NOT ALLOWED FOR RESIDENTIAL
PROPERTIES WITH FLOOR AREA GREATER THAN 500 Sq. FEET
*MINIMUM FOUNDATION STANDARD - ALL FOUNDATION SHALL COMPLY
WITH THE MINIMUM FOUNDATION STANDARD AS PER CITY'S
ORDINANCE (FOUNDATION DETAIL SHALL BE SHOWN ON PLANS)
MAKE SURE TO INCLUDE REBAR SLAB GROUND
*ALL FRAMING SHALL COMPLY WITH 2O06 INTERNATIONAL
RESIDENTIAL CODE
*Assure Proper GFI Locations, Including One Within 25' Of
Outside A/C Unit
*PLATFORM FOR MECHANICAL EQUIPMENT AND/OR ACCESS MAY HAVE TO
BE ELEVATED TO ALLOW FOR ATTIC INSULATION
*Wall and Ceiling Insulation are as follows respectively.
If Wall to Window Ratio is up to 15% the Values Shall be
R-13 and R-30, above 15% the Ceiling Insulation is Increased
to R-38.
*IF LAWN SPRINKLERS IS PROVIDED, PERMIT MUST BE ISSUED PRIOR
TO CERTIFICATE OF OCCUPANCY.
-
--------------- ----- ---------------- ----- -f�i•- -------------------
BUILDING DEPT REPRESENTATIVE:
A A?
APPLICANT:
BUILDING PERMIT,
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 3
Application Number . . . . . 08-00000336 Date 2/07/08
Application pin number . . . 968304
----------------------------------------------------------------------------
Special Notes and Comments
*REQUIRED EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE
WITHOUT THE USE OF A KEY,TOOL OR SPECIAL KNOWLEDGE/EFFORT
*A Minimum of No. 15 Asphalt Felt or Other Approved Water
Resisitive Barrier Shall be Placed Over All Exterior
Sheathing Per 2006 IRC Section R703.2
*If PEX water supply piping is sleeved below the slab, seal
annular space at ends with caulk, foam or other means.
Also assure proper protection of pipe to U.V. light.
*ANY CHANGES OR ALTERATIONS TO SUBMITTED PLANS MUST BE
RESUBMITTED AND APPROVED BEFORE WORK IS DONE IN ORDER TO
ASSURE CODE COMPLIANCE
*POST PERMIT CARD ON JOB SITE TO BE VISIBLE FROM ROAD
*WHEN WATER MAIN PRESSURE EXCEEDS 80' PSI, AN APPROVED
PRESSURE REDUCING VALVE SHALL BE PROVIDED THAT LIMITS THE
MAXIMUM STATIC WATER PRESSURE TO 80 PSI
*RECESSED LIGHTING INSTALLED IN THE BUILDING ENVELOPE SHALL
BE IC RATED AND SEALED TO PREVENT AIR LEAKAGE
*For residential applications with a glazing area that
exceeds 150 of the gross area of exterior walls, R-8 duct
insulation is required. As an alternative, R-6 duct
insulation can be used if the a/c system has a SEER rating
of 12 or more.
*PROVIDE SANITARY FACILITIES FOR WORKERS ON SITE LOCATED OFF
THE PUBLIC RIGHT-OF-WAY.
*SMOKE DETECTORS MUST HAVE 3' CLEARANCE FROM FORCED AIR
DUCTS, CEILING FANS AND RETURN AIR
*PROVIDE STRING LINES FOR ALL BUILDING SETBACKS AND
EASEMENTS ON FOUNDATION INSPECTION.
FORM SURVEY MAY BE SUBMITTED IN PLACE OF STRINGS.
*SHOWERS AND TUB/SHOWER COMBINATIONS SHALL BE EQUIPPED WITH
AN ANTI -SCALD VALVE THAT LIMITS WATER TEMPERATURE TO 120
DEGREES
*THE COMBINED SOLAR HEAT GAIN COEFFICIENT OF ALL GLAZED
FENESTRATION/WINDOW PRODUCTS DEPENDING ON PERCENTAGE OF WALL
TO GLAZING/WINDOW RATIO UP TO 20% A .40 OR LOWER FACTOR AND
ABOVE 20o TO 30o A .35 FACTOR OR LOWER SHALL BE MET.
*ALL SILLS AND BOTTOM PLATES IN CONTACT WITH CONRETE MUST BE
TREATED OR NATURALLY RESISTANT TO INSECTS AND DECAY
*SMOKE DETECTORS SHALL BE INTERCONNECTED, 120 VOLT W/BATTERY
BACKUP AND LOCATED IN EACH SLEEPING ROOM AND OUTSIDE EACH
SEPARATE SLEEPING AREA IN THE IMME ATE VI INITY OF THE
------------------------------------------ ---- - -�--------------
BUILDING DEPT REPRE�ENTAnIVE:
APPLICANT:
BUILDING PERMIT,
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page
4
Application'Number . . . . . 08-00000336 Date
2/07/08
Application pin number . . . 968304
----------------------------------------------------------------------------
Special Notes and Comments
BEDROOMS
*REMOVE ALL VEGETATION AND FOREIGN MATERIAL FROM SLAB AREA
PRIOR TO PLACING FILL. FILL SHALL BE FREE FROM
VEGETATION AND FOREIGN MATERIAL.
*STAIRS SHALL COMPLY WITH SECTION R-311 (2006 IRC) WITH A
CONTINUOUS HANDRAIL OR SECTION
1009 (2006 IBC) AS APPROPRIATE, CONTINUOUS HANDRAIL
NEEDED, ENDS SHALL BE RETURNED OR SHALL TERMINATE INTO A
NEWEL POST OR SAFETY TERMINAL ON COMMERCIAL JOBS.
*WINDOWS ADJACENT TO TUBS WITHIN 60" ABOVE DRAIN SHALL BE
TEMPERED GLASS
*TEMPERED GLASS REQUIRED IN WINDOWS WITHIN 24" OF DOORS IN
ADJACENT WALLS
*AN APPROVED DEVICE FOR THERMAL EXPANSION CONTROL SHALL BE
PROVIDED FOR BUILDINGS UTILIZING STORAGE WATER HEATING
EQUIPMENT AND A PRESSURE REDUCING VALVE
*PER R308.4 GLAZING ADJACENT TO STAIRWAYS WITHIN 36" AND
LESS THAN 60" ABOVE WALKING SURFACE MUST BE TEMPERED (2003
IRC)
*U-Factor Ratings for Window % up to 1501 is .65, from 15%
to
20% is .55, from 20% to 25% is .54 and above 25% is .46 or
lower.
*RANGE/DRYER DUCT MUST COMPLY WITH 2O06 IMC
*IF AN OPERABLE WINDOW IS MORE THAN 72" ABOVE EXTERIOR
FINISHED GRADE THEN THE LOWEST PART OF THE WINDOW OPENING
MUST BE AT LEAST 24" ABOVE THE FINSHED FLOOR FROM INSIDE THE
ROOM.
*ALL PLUMBING, ELECTRICAL, AND HVAC (mechanical) WORK MUST
BE PERFORMED BY LICENSED CONTRACTORS. CONTACT BUILDING
DEPARTMENT FOR INSPECTIONS PRIOR TO COVERING ANY WORK
----------------------------------------------------------------------------
Other Fees . . . . . . . . . SEWER TAP 4"
350.00
WATER TAP 3/4"
----------------------------------------------------------------------------
400.00
Fee summary Charged Paid Credited
-----------------
Due
----------------------------------------
Permit Fee Total 499.00 499.00 .00
.00
Plan Check Total .00 .00 .00
.00
Other Fee Total 750.00 750.00 .00
.00
Grand Total 1249.00 1 49.00 .00
.00
BUILDING DEPT REPRESENTATIVE:
APPLICANT:
BUILDING PERMIT ,
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Application Number . . . . . 08-00000336
Application pin number . . . 968304
Page 5
Date 2/07/08
--------------------------------------------- ----- ------------
BUILDING DEPT }REPRESENTATIVE:
APPLICANT:
TEMPORARY POLE PEP -MIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
----------------------------------------------------------------------------
Application Number . . . . .
Application pin number . . .
Property Address . . . . . .
Property ID:
R #.
Application type.description
Subdivision Name . . . .
Property Use . . . . . . . .
Property Zoning . . . . . . .
Application valuation . . . .
08-00000337 Date
051543
4136 MCFARLAND DR
579530-0209-0030
R305165
TEMP POLE
SOUTHERN TRACE PH 2
RESIDENTIAL
SINGLE FAMILY CLUSTER DEV
0
2/07/08
Owner
------------------------
Contractor
BCS DEVELOPMENT CO
------------------------
STYLECRAFT BUILDERS
4090 SH 6 S
4090 SH 6 S
COLLEGE STATION
TX 77845
COLLEGE STATION
TX 77845
(979) 690-1222
----------------------------------------------------------------------------
Permit . . . . . .
TEMP POLE
PERMIT
Additional desc . .
GS
Permit pin number .
550418
Permit Fee . . . .
20.00
Issue Date . . . .
----------------------------------------------------------------------------
2/07/08
Valuation . . . .
0
Other Fees . . . .
----------------------------------------------------------------------------
. . . . .
TEMP ELECT POLE CONNECT
45.00
Fee summary
Charged
Paid Credited
Due
-----------------
Permit Fee Total
----------
20.00
------------------------------
20.00 .00
.00
Other Fee Total
45.00
45.00 .00
.00
Grand Total
65.00
65.00 .00
.00
n
-------------------------------------- - - - - -- ----IL./•- - - - - - - - - - - -
BUILDING DEPT REPAESEN�ATIVE.
APPLICANT:
(*//q" APPLICATION FOR BUILDING PERMIT
1101 TEXAS AVENUE
COLLEGE STATION, TX 77840
Crnt OF COLLEGE STATION (979) 764-3570 (979) 764-3496 FAX
Pla nmg & Decdopmmr Sermw
WWW.CSTX.GOV
DATE:
APPLICATION 9 1/ a 00 W
TEMP POLE # 109! 07
ADDRESS/LOCATION:_ _ 4r% AtFAP--mr) (L
LOT 3 /BLOCK �� SUBDIVISION 50UT eT-M -TALE SEC/PH 2
BUSINESS/OWNER NAME: STYLECRAFT BUILDERS, INC. PHONE: 690-1222 ext. 120
CONTRACTOR/HOMEOWNER: STYLECRAFT BUILDERS, INC. PHONE: 690-1222 ext. 120
CONTACT PERSON FOR REVIEW COMMENTS: ERIC WIVAGG PHONE: 690-1222 ext. 120
FAX: 690-0348 EMAIL: ewivagg(�stylecraft-builders.com
ELECTRICIAN: Brazos Valley Electric PLUMBER: Bass Plumbinq .
HVAC: Control Tema GOOD CENTS (Residential only): No
ACCESSORY/STORAGE LOCATION RE -ROOF
ADDITION MOVING SHELL ONLY
DEMOLITION (Asbestos Survey) X NEW CONSTRUCTIONSLAB ONLY
DUPLEX (Landscape Plans) REMODEURENOVATION* SWIMMING POOL
TENT/CANOPY
DESCRIPTION OF WORK: Conventional Framing
PROPOSED USE: Single Family Residence
WALL BRACING METHOD: PRESCRIPTIVE ❑ APA PORTAL FRAME W/ CSPS ENGINEERED fn
HOMEOWNER ASSOCIATION/ARCHITECTUAL OR DESIGN REVIEW COMMITTEE APPROVAL:
TEXAS ACCESSIBILITY STANDARD PROJECT REGISTRATION# EABPRJ NIA
VALUATION: $ ng?,L �(TABTOTAL AREA: f 4 u9 HEATED'AREA: 1710
(Cost of Labor and Materials)
q
�X PUBLIC SEWER
NUMBER OF BEDROOMS:
qG
❑ SEPTIC/TREATMENT SYSTEM
NUMBER OF BATHROOMS:
'1
QX SEWER TAP:
4°
S2
INTERIOR WALL TYPE:
Sheet Rock
OX WATER TAP:
%"
SIZE
EXTERIOR WALL TYPE:
Siding and/or Masonry
10
OTHER TAP:
FOUNDATION TYPE:
Slab on Grade
SIZE
+4)`�
II
OX TEMP POLE
ROOF TYPE:
COmpOSItIOn
1
GARAGE TYPE:
SINGLE EJ�DETARPORT
TIPLE
ATTACHED
SIGNATURE OF APPLICANT:
*If proposed work involves new commercial cons tructi or f Ocade
commercial property, building elevations are required.
Official Use Only
Plans Examiner Zoning Official
S,dQ )1DI P R w Comments:
F lour. • W,1.,am wS LY A�F Maty. S r NO
im rovements/teftovations to an existing
Fire Marshall
Energy Code Compliance Information
Glazing of exterior walls
Insulation R value of exterior walls
Insulation R value of ceiling 1 (flat areas)
Insulation R value of ceiling 2 (vaulted areas/no attic)
Glazing SHGC (Solar Heat Gain Coefficient)
Glazing U-Factor
R value of ductwork
A/C SEER Rating
Protection Against Subterranean Termites
❑ Chemical Termiticide Treatment (Soil Treatment)
%
R13
R30
.35
.53
R6
13
Chemical Termiticide Treatment (Field Applied Wood Treatment)
❑ Physical Barriers
❑ Other
*Verification of Application shall be submitted', to' the City of College Station
Building Department prior to issuance of the Certificate of Occupancy.
y PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
(*flq"
CITY OF COLLEGE STATION
CITY OF COLLEGE STATION 1101 TEXAS AVENUE
Planning& DevelopmentSeruicei COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
PLAN REVIEW/PERMIT NUMBER# -3 36oDATE:
BUILDING ADDRESS: 36 Mc,
I. Foundation Requirements- MinimumMinimumlty
Foundation Standards
N
A.
Concrete minimum compression strength of 3000 PSI
B.
Minimum four 4 inch slab thickness
C.
Vapor barrier Emil. Poly min.
D.
Slab/beam or pier layout shown
1. Footings/beams are continuous over the length and width of foundation
2. Footings 30" exterior, 24" interior, unless over 60' long must be 30"
3. Spacing of beams does not exceed 15'
E.
Reinforcement details to meet minimum requirements
1. Slab reinforcement and Beam Reinforcement
F.
Protection Method used for Termites.
G.
Wood foundation details indicated
K
ll. Framing: Floor, Wall, Ceiling and Roof Requirements
NA/
A.
Girder or sill dimensions, grade & species
B.
Floor joist size, spacing, grade & direction of span indicted on plans
C.
Treated sill plate or bottom plate
D.
Tenant separation in duplex
OK
1. One -hour rated extendingN to roof deck
O
E.
Header sizes indicated on plans
N
F.
Emergency bedroom egress
1. Exit direct to outside
2. Operable window
a. Twenty 20 inch clear width by twenty-four 24 inch clear height
b. Maximum sill height of forty-four 44 inches above finished floor
G.
Operable bathroom window required when mechanical ventilation is not provided
H.
Stud grade andspacing
I.
Exterior wall details
1. Sheathing indicated on plans for Wall Bracing
2. Moisture barrier indicated on plans
3. Exterior Wall Covering
J.
Roof framing Ian or elevation shown
K.
Ceiling joist size, spacing, grade and direction of span indicated on plans
L.
Attic access location and size indicated on plans
M.
Span exceeding code tables must be engineered
N.
Rafter size, spacing, roof slope & purlin bracing if required to reduces an
O.
Roof covering
P.
All girders & beams for support of floors, walls, ceiling & roofs must have the size, grade &
location indicated on plans
Q. Tempered Glass required in all hazardous locations
R. 18" Overhangs allowed on zero lot line, non-combustible perforated soffit only
S. All walls within 3' of property line to have protected openings.
OK
K
PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
CITY OF COLLEGE STATION 1101 TEXAS AVENUE
Planning& Development Services COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
III. Stairway Requirements
A. Stairway Details
NAIbKT
1. Maximum riser height 7-3/4 inches
2. Minimum tread width 10 inches
3. Stairway risers are uniform 3/8" Max. difference
4. Stairway width not less than 36 inches
5. Stairway headroom not less that six ft. eight 6'-8"
B. Winder details
1. Treads a minimum of six 6 inches on narrow edge
2. Treads a minimum often (10) inches at a distance of twelve (12) inches from the
narrow edge
C. Spiral stairway details
1. Riser height less than nine and one-half 9-1/2 inches
2. Treads a minimum of seven and one-half (7-1/2) inches at a distance of twelve (12)
inches from the narrow edge
3. Stairway width not less than thirty-six inches
4. Headroom required not less than six ft six 6-6 inches
5. All treads must be identical
D. Guards/handrail details
1. Guards required when a porch, deck, balcony or landing is thirty (30) inches
above grade or finished floor
2. Handrails are required on stairways located two or more risers above floor/grade
3. Handrails must be thirty-four to thirty-eight (34-38) inches when measured from the
leading edge of the tread
4. Handrails must not project more than four & one-half (4-1/2) inches into width of a
stairway
5. Guards must be a minimum of thirty-six 36 inches above finished floor
6. Guards & handrails along open-side(s) of stairway must have intermediate
railing or uprights that prevent the passage of a four 4 inch sphere
IV. Fireplace Requirements
M K
A. Hearth extensions
1. Fireplace opening < 6 s , ft, extensions: 8" & 16" forward
2. Fireplace opening > 6 s . ft. extensions: 12" side & 20" forward
B. Masonry fireplace requires 2" clearance from all combustible materials
C. Chimneys must meet IRC Chapter 10 Requirements
V. Electrical Service Requirements
A. Electrical plan to include:
N
1. Electrical fixtures & switches indicated
2. Smoke detector locations indicated as required
3. GFI circuits indicated where required
4. Arc fault protection for bedroom circuits
5. Panel location
(*t/qq4,1
CITY OF COLLEGE STATION
Planning d Development Serviat
PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
VI. Plumbing Requirements
A. Pressure reducing valve required when water pressure exceeds 80 psi
N
B. Plumbing access to bathtubs
C. Means for thermal expansion provided when required
D. Water heaters elevated 18" when installed in the garage or room directly off garage
VII. Mechanical Requirements
N OK
A. All mechanical ventilation's in bathrooms & range hood ventilation must be ducted to
outside excludes ductless units
B. Attic installed H.V.A.C. requirements:
1. Twenty-four (24) inch wide unobstructed walkway from attic access to equipment
must be provided
2. Attic access located within 20 feet of equipment
C. Combustion air supplied for gas appliances when required)
VIII. Energy Requirements
N K
A. Compliance software worksheet MECcheck submitted, or
B. Energy data supplied Percent of glazing, insulation R-values, window U-values, etc.
Zoning Ordinance Requirements — Ordinance 850
N K
Permitted use for district
Density requirements
Minimum lot size
Setbacks
Easements
Required parking
Street Ordinance Requirements
FN
Maximum drive width for residence is 25' combined for circular and 12' minimum for single
Minimum 20 feet from driveway to side(intersecting) street property line sight triangle
Driveway access to lesser street for corner lots
Subdivision Regulations — Ordinance 690
NA4rOX
Approved subdivision
Plat filed
Flood lain Regulations — Ordinance 1301
K
Does not block an water course or divert an flow
JA
Elevation certificate needed
K
"APPROVED PLANS. PER IRC SECTION R106.3.1."
PLANS EXAMINER
02-S-C) 8
DATE
Permit #
Permit Date
REScheck Software Version 3.7.3
Compliance Certificate
80/1
Project Title: 1711
Report Date: 02/04/08
Data filename: S:IACADIRESCheck11711.00-Master.rck
Energy Code:
2003 IECC
Location:
College Station, Texas
Construction Type:
Single Family
Glazing Area Percentage:
11%
Heating Degree Days:
1788
Construction Site:
Owner/Agent:
Designer/Contractor:
College Station, TX 77845
Stylecraft Builders, Inc.
Stylecraft Builders, Inc.
4090 SH 6 South
4090 SH 6 South .
College Station, TX 77845
College Station, TX 77845
979-690-1222 x127
979-690-1222 x127
jsaucier@stylecraft-builders.com
jsaucier@stylecraft-builders.com
Maximum SHGC: 0.40 Your SHGC: 0.40
Wall 1: Wood Frame, 16" o.c.:
Window 1: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 2: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 3: Metal Frame: Double Pane with Low-E:
SHGC: 0.40
Window 4: Metal Frame: Double Pane with Low-E:
SHGC: 0.40
Window 5: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 6: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 7 Twin: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 7 Twin: Metal Frame: Double Pane with Low-E:
SHGC: 0.40
Window 8: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 9: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 10: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 11: Metal Frame: Double Pane with Low-E:
SHGC: 0.40
Window 12: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 13: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
Window 14: Metal Frame:Double Pane with Low-E:
SHGC: 0.40
1711
2254 13.0
0.0
163
16
0.670
11
16
0.670
11
16
0.670
11
16
0.670
11
4
0.670
3
4
0.670
3
16
0.670
11
16
0.670
11
4
0.670
3
16
0.670
11
16
0.670
11
4
0.670
3
13
0.670
9
3
0.670
2
4
0.670
3
Page 1 of 2
Window 15: Metal Frame:Double Pane with Low-E:
4
SHGC: 0.40
Window 16: Metal Frame:Double Pane with Low-E:
4
SHGC: 0.40
Window 17: Metal Frame:Double Pane with Low-E:
6
SHGC: 0.40
Window 18 Twin: Metal Frame:Double Pane with Low-E:
13
SHGC: 0.40
Window 18 Twin: Metal Frame:Double Pane with Low-E:
13
SHGC: 0.40
Window 19: Metal Frame:Double Pane with Low-E:
4
SHGC: 0.40
Window 20: Metal Frame:Double Pane with Low-E:
3
SHGC: 0.40
Window 21: Metal Frame:Double Pane with Low-E:
4
SHGC: 0.40
Window 22: Metal Frame:Double Pane with Low-E:
13
SHGC: 0.40
Window 23: Metal Frame:Double Pane with Low-E:
3
SHGC: 0.40
Door 1: Solid:
20
Door 2: Glass:
18
SHGC: 0.40
Ceiling 1: Flat Ceiling or Scissor Truss:
873
Floor 1: Slab-On-Grade:Unheated: , Insulation Depth: 0.0'
127
Floor 2: All -Wood Joist/Truss:Over Unconditioned Space:
24
Furnace 1: Forced Hot Air: 80 AFUE
Air Conditioner 1: Electric Central Air: 13 SEER
0.670
3
0.670
3
0.670
4
0.670
9
0.670
9
0.670
3
0.670
2
0.670
3
0.670
9
0.670
2
0.500
10
0.440
8
30.0 0.0
31
0.0
132
13.0 0.0
2
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2003 IECC requirements in
REScheck Version 3.7.3 and to comply with th anda ry re uirem ted in the REScheck Inspection Checklist.
`JhfLELQRfrI141b6
Builder/Designer Company Name Date
Project Notes:
All U-Factors and SHGC are at entered at higher than actual amounts.
Actual amounts are lower, but are entered higher to account for
differences in ratings per material.
1711
Page 2 of 2