HomeMy WebLinkAboutRES2008-00328, 08-329PREPARED 7/24/08, 12:01:43 INSPECTION TICKET PAGE 4
City of College Station INSPECTOR: BUILDING INSPECTOR DATE 7/24/08
------------------------------------------------------------------------------------------------
ADDRESS . : 2927 MCLAREN DR SUBDIV: SOUTHERN TRACE PH 2
CONTRACTOR STYLECRAFT BUILDERS PHONE (979) 690-1222
OWNER- BCS DEVELOPMENT CO PHONE
PARCEL 579530-0207-0180
APPL NUMBER: 08-00000328 RESIDENTIAL, 1 UNIT DETACHED NEW
------------------------------------------------------------------------------------------------
PERMIT: BLDG 00 BUILDING PERMIT
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
B100 01 3/14/08 BB BLDG, FOUNDATION -SLAB TIME: 17:00
3/14/08 CA March 14, 2008 9:40:25 AM glsouth.
03/14/2008 04:29 PM BB PDA
Not ready
B100 02 3/24/08 BB BLDG, FOUNDATION -SLAB TIME: 17:00
3/24/08 AP March 20, 2008 1:53:40 PM acarter.
03/24/2008 10:07 AM BB PDA
Strings up. Slab ground installed.
B145 01 4/03/08 RH BLDG, EXT. SHEATHING FASTENER TIME: 17:00
4/03/08 AP April 3, 2008 11:59:56 AM glsouth.
April 3, 2008 4:26:17 PM kwolfe.
B115 01 4/29/08 BB BLDG, FRAMING TIME: 17:00
4/29/08 DP April 25, 2008 11:21:58 AM glsouth.
04/29/2008 11:53 AM BB PDA
Need bracing at bottom of stairs and in ext. wall in
bathroom, to right at top of stairs. Stair Winder is less
than 6" at narrowest point, need to repair.
B115 02 5/01/08 OC BLDG, FRAMING TIME: 17:00
5/01/08 AP May 1, 2008 9:00:22 AM glsouth.
Stairs will either be repaired or a column will be added to
disallow for anyone to step in area that is less than 6"
This was discussed with super intendant Eddie Green and he
said he will do one of the above options.
B130 01 5/01/08 OC BLDG, INSULATION TIME: 17:00
5/01/08 AP May 1, 2008 9:00:47 AM glsouth.
B125 01 7/2 /08 BLDG, FINAL TIME: 17:00
July 24, 2008 10:16:09 AM acarter.
-------------------------------------- COMMENTS NOTES ------- -- -------------------------
Rpr.29. 2008,� 3:53P9:-*,-Stylecraft Builders, Inc,
"Shielding & Protecting
Homes Against Pests"
No. 9823 ,.. P. 11
Renewable 5 Year ag r
3B
Subterranean
Termite Retreatment
Agreement
moss not cover any other species of Termites)
This agreement provides for retieatment only of the Infested areas covered under the original treatment areas (See Grapb}
Customef Name Date Billing Name if different
&0 I'-1 ez,4,%ej
Street Address of treated structure
1',-10 r)( 71-09
City State Zip Code
Home Phonc Work Phone
Type of Treatment Partial Bait Pre -Treat
Treatment for: Prevention Control of Subterranean
Termites
Notes:
Billing Address if different
City State Zip Code
7nttlal Termite Cost $ /3
D�
Additional Renewals Paid
Other
Tga �'k
Cash Cheep# Totx31
Payment $
Balance $
Credit Card:
Type Exp. Date Card Number
iUku-SOMMUM Termite t Gu RP Lee Termite and Pest Control will retreat the structure for Subtetraoean
Termites at no cost to the customer, if an infestation of Subterranean Termites is found, as long as the original treatment is paid in full
and the ooswmer is eurreat on their yearly renewals. This Agreement will expire in one (1) year takes the customer elects to pay
the yearly warranty foc. The guarantee can be renewed for up to fivo (5) years by paying the yearly warranty fee. RP Lee Termite
and Pest Control may approve additional warranty years after the five (5) years with an additional increase in the yearly warranty fee.
The guarantee does not cover any damages to the structure or contents of the customer. The customer agrees to control all oondusive
conditions that may cause rekfestation. If the structure is modified, added on to, altered, or if the soil treatment around the structure
is removed the customer must contact RP Lee Termite and Pest Control and pay for additional treatment in order to keep the guatautcc
in effect. If the customer does not pay for additional treatment the retreatment guarantee can be canccllcd. AC
Renewal Fee: Customer may elect to renew the retreatment guarantee for additional years. The renewal fee is S 0• —plus tax.
The renewal fee is due on or bcfoic the annual anniversary date or paid $_el"' plus tax every third (3) month with inspection.
M— g the Guarantee: The mmtomcr agrees to correct all conclusive conditions, at owner's expense, as they exist or as they
odour in the Arnrre in order for the guarantee not to be cancelled- Customer will make the structure available for inspections and
ireatmu nts as requested by RP Lee Termite and Pest Control.
Reinspeetion: RP Lee Termite and Pest Control will reinspect the structure at customers request or any other times RP Lee Termite
and pest Control deems necessary. U Lee Termite and Pest Control recommends that the customer call and setup an annual inspec-
tion at the time of customers yearly renewal.
f ; This agreement may be transferred to a new owner with the payment of a transfer fee of $ / , copy of the Wood
Destroying Insect Report from the sell, and approval of RP Lee Termite and Pest Control.
This Subterranean Termtee Retreatmept Guarantee does not proven and is not intended to Lgyt rol other forms of Termites
m-yw^^a gMosau, etc. Carpenter AOL Carpeniter Em, Wood Rot, Fungus, De or an: er
Mod &&ffidal, ansRM Or ms.
BSa In the event of any dispute arising out of this agreement or any other services performed or not performed the parties
above agree to participate in mediation through and in accordance with the commercial mediation rules of the American Arbitration
Association, The Arbitrator shall consider the legal defenses raised in the arbitration, and tho decision of the arbitrator shall bo final,
binding, non -appealable and may be entered and enforced in any court having jurisdiction in accordance with the Federal Arbitration
Act
Ltmitadan of Liabilitv: Landscaping ad grass next to the slab may be damaged during treatment, carpet may need to be pulled
up in certain areas around the home, drill holes may need to be made in floor coverings sucb as the or linoleum or in cabinets next
to pipe areas, and holes may need to be cat in walls. Customer agrees not to hold RP Lee Termite and Pest Control Gable for these
damages, or tratment techniques, or other damages that may occur during treatment
AffreeMISl This Agreement Shall be the entire agreement between aastomer and RP LeeTermite and Pest Control. If any part of
this agreement is found to be invalid it shall not affect the validity of any other part of the Agreement
We are licensed by the Stru etp ads p
Austin. TX 78701.512-30&9250
Z
ed
e-s If y-?A
RP Lee Termite&Pest Control
Ceti Apl.#
Custdmcr Sign
uze Date
Rpr.29, 2008 3:53PM Stylecraft Builders, Inc.
No.9823 P. 10
z
New Construction Subterranean Termite
Soil Treatment Record
oslsdaD data aaxoac, 0eMV0 and mei! '&a 'no data nertdtid. and onrtpl,
fWMAf9 I to abutat barOltte' HUE) MY not;vbg it>i9 edant> m arm you Am
nwntw.
CIAO Approval Nc. 2.=W-052S
(s)<N.1ar31/2C35)
tb D�DUIW p+r r►spOn1A, UWudMu 11jc�i90 (iW *'W 0MWJ o►ynieQuts, ivarCraj —
MvbOd to Corplo M ItAM,, Uri= tPr tlW- a aWnntt/r.'dd CMD h00 is
r
So:%A 2+ CFR ,^00.1130d(b)(3) rates that ibo ales far KID kuAM "%haw anus( Lv ttvo nt E mow hh2j&, 1T$3 int =tm edD;d n ioa,&m Ina Duldtl lU
&aL* oral an ard&ori:pd Pmi CUMW CCrrrytPy pert alod ell jequfrod 1jO&Wtant kr temdW. mid umt Uro UUWCr Vwrarnttaa dts UDWOd arena AWfW Uaoswrior, kv
aio yew, Qulldaro, potd wnwf oompurlDu m0r�a8o landara, homatarym; and HUG as a ra pid of uoa1 n0t1 ks ai5otrfio l,unwn rriG u® a�, adurartJun eolrctea
trrD fnfotm W b rrd cupztrtnrad avfdarrtinL _
Thts sport Is r4iaU&W for Intormatl 91 pumutis to the twl)dur On prop0e0a (now) r onnuvoup Carus Nh*r, soo trawmant Worpeant,on of aubtorr, n
iWMR& infootat'i n is cpaciaad by tho bundor, oroLlloot, or roquhud ay ttro lOrrdpr, urehitact, FNA. or VA.
A3 rsmud413 iat boMOS am bottwon thO F'091 CanUor Operator and bulldar. Unlosa stated othan+dao,
60cagn 1: Gonarol Infatmptton (Traii*q CCOPAny Itdorma'.ion) A
Gaopmy
CompanyAddrm - 2`
Caffoany @usfAs" I -Mn 12 NO.
e U`j/ZC V A17?
r--
_
FKA/VA Casa Nc (U any) �^--
Soc!!on 23 f3uttdmr InixMdon
Compitny Namo - -- - --. phorvt No,
$acdaa 3: Propotty !olormauon
LotaLlon of Suvctaxo (a) Ttouloti (3lrool A0063 *f L09W Deaerip>fon, CiW, OU') Una ZIP)
Typo a! GaAG1iu0llan {facra uran urro btuc rrwy bo ohool,aa) 09 sob f)asamont Crawl E. Omer
Appro>dmato oaplh a Pooling: Ou:eidB Inslde Typo 4f ni —
3cctlan a: 7reatrrmnt lototraaffon /� {!
pslo(e) of 7rrralotwnt{vj "l }�'�" -
Stand MAIM of PtOWr-f(c) Uaod
EPA SojifiOralon No. e O 6 %
App OMmato Pawl W Soiulhui'6 � lr.-
✓� Ungar P,, of MaWill VO b
Approxirt>ato:in of TroatMentArOW S4.1 _`�,, ;� Uncork ---��- - '--
Approximate Tole! (;<pfian9 0! Stlutlon AFDlled _l�rr'� ,
V�ds lrOaG(W(rI aam{dOiad un uzwnuR Yes No
Ser WAgroartmt.Air"Ablo7 � Yes t�Ct
Now Soma &do Iowa roquku aorbloe egraemanta to bo lamrol 'rhlu (arm woo nut yrbompt AID law-
AWtGtvAvnls 00 "-"
COrotttertta � +—�T
Nerne of AppilGaWr(s) `-"
CeWifAretlal N0. (II ragd!(Od by 5tatd law) JC I
Tho appikAtar has used a product In 4canla W wCh tho produoi 13bo1 and slato requ)rornants A2 trO+,177 rwrp rnaldrlv;r and motho<fD usod t otnply wNh
=u And foderM requIsWona. 17
AMU=Uad E)lgnaturu
Folm NFCA 9" may vlf be ucad
('wvm :5rMb
MM
pu[n 7 �1�4
11.IS. C. MIin
uvna ISUD-H; CA-OWG (04r.003i
Apr.29. 2008 3:54PM S t y I e c r a f t Builders, Inc. No.9823 P. 12
SUBTERRANEAN TERMITE PRE -CONSTRUCTION TREATMENT DISCLOSURE FOR EACH ESTIMATE
Licensed and regulated under the Texas Structural Pest Control Act
RP LEE TERMITE & PEST CONTROL
PO Box 9423 • College Station, TX 77842 • (972) 690-8622 • TPCL #11486
—CUSTOMER 1NFORMATI
Name: _ k_4t a F� Phone art: Phone #2:
Address: ����% �G���� City (� 15 State: 7— Zip Code:
Locatlon to be Treated:
tor am«eaurienismore vneoeaoiagremsnowing exaarywnatM11DetreataapnXtotyrebeginningoftreatment Review thepeeticidelabelprovidedtoyouatthtstimeforminimumtreatmentstandards.
Remember that your ardiilects ordesign engineers specifications must also be Wowed, unless they are in violation of the law. Review the consumer information sheet for further information. If you
have any questions, contact the nest control company or the Texas Structural Pest Control Board, P0. Box 1927, Austin, TX 78787-1927. Telephone number (512) 305-8250.
Before conducting a termite preconslruction treatment, the company will present a complete diagram of the structure including oonshuction details, When construction prevents pedomiance of a full
treatrnent in acciirdwa with a bld for Nil treatmermt, any change to a partial treatment by the company providing the treatment will be permitted H the owner of the shuoture or the person In charge of
the construction and the certified applicator for the pest control company sign a statement attesting to the construction conditions. The agreement must be attached to the contract with an amended
diagram showing the exact areas to be treated. Copies must be cent to the owner of the pmperiy wfthin seven days of the application.
notes: /i�jp�¢Ci¢ ve
�cs-T.yrvzf
lao
Type of treatment proposed: (check all that apply): 0 Full is Partial LYWood ❑ Bak 0 Commercial U'(ngle Family
Total square feet to be Total linear feet to be treated: �2 Approximate measurements of structure(s) to be treated: �'
A label of _ �� termHlclde(s) fs atteched. The percentage of the termlticfde(s) to be applied at this location is�o/,,
Estimated amount of temriticide to be
THE SUBTERRANEAN TERMITE PRECON$TRUCTION TREATMENT BUILDERS GUIDE 18 ATTACHED ON BACK (SPCBlD.4j THE BOARD APPROVED SUBTERRANEAN TERMITE
PRECONSTRUC71ON TREATMENT BUILDERS GUIDE MUST BE PROVIDED TO, AND SIGNED BY THE CONTRACTOR OR PURCHASER OF THE PRECONSTRUCTION TREATMENT
SERVICE. Complete detailsofwarranty (dany) including tlme period of warranty, renewal options and cast, and obllgatlons of the contracting parties is attached. If the warraidy does not
include the entire structure treated, the areas Included In the warranty are (spedty): �(
` A consum ormalon sheetialso attached,
Signature of CA fednician Printed Name Date signature of Customier VerHying Receipt of Ths Document Date
REM 0 Swrw 01mm7 white Copy • Service ProWdor Yonow Dopy • Customor r*m DnWW eM NM t7W*eAWk CgmnX m 10&7*4M.0" T%A 20
Service Treatment Invoice
101 tq: d Z l4lap Code:
ifUrt�lime m FirllshTime• amlpm
lope of Sesvlce: � tial war Follow Up One Time Charity
5ervice AdtirIs
same- eC�2,�F�
Address- rI A1 eIgge- J
City: (' , s TX
Date: T Z�^ � AppolnL •lime• 47 slnlpm
Frequency. NI_ Q S 'Y
Stroctwv: Crawl! P/B
Pets: Dogba) Cat(s) Bird(s)
Combo
Fish '441 vc
rx-
Cost ot'Service S
Tax. 5
Total Due,:S
Payment S
Phone; Gr
Balance. S 7317,
PEST PROBLEMS: /Ill. c -- ici4 Tel DIRECTIONS I INSTRUCTIONS:
Billing:
P EE
"rShWdWnq & ProteotiAq
Homes Against Posts'
TPCL #1I486
..EQUIP. METH. LOCATION(S) PRODUCT QTY TARGET PEST(S)
WOOD DESTROY7N Ii�FS r"1 c
83 97
Payment by:
Cash ❑
Check ❑ #_
Credit Card ❑
-PAYMENT DUE
UPON RECEIPT
TernAdarSC-ftrvnH.06%
StitVtMaseanTt:rmlte%AMc Sizeof%mak Posted
1`armJdor8GW-F4ramUA6%
Somerraaeaulbrmtte& SEW ofTamk Pealed
Bua-cuoWoodlruOetabanLewrat dsl¢50% -��Srbterra"WdFormasenl
`GENE>_RAL•
xywmWTermitee,Cal perterAmtr, Bee4hes, Foetal G
P NTfi
lavad"KFH-Brygon 1%
CarpeateirAnts, Spldaas6Crlckeli6NMUpedcs,Beede%'Urn tm
Vernon WP-Cyaao-Pbenoxypbegyt
Cockroaches, 11114ndes, Sawbugs, Flies, lkb, Alasquites, Pifibag9,
Dimethyeyleydapropameearbwylate 1%
S91%wflsb, Bees, Ant4, Carpea6erAat% Scarptama, S131dert
Tempo Mrs. WY-CyOuthula.M%(Rest)
Arcs (E:ceptPLaraoh), Caekrnacbc0,Crlckel8,FAr%%1V, rellllipede% Flica,Fiuit Vl&r,Hralke,
(gas. arrlace spays spot, naUt, crack & crevice)
Pilbege. Silrerf ds6 Spiders, Gaals, Hornets, Wasps, YcUovr Jackets.
Talttar EZBllenthria .2%
Ants, CeMlpedes, Coclanaebes, Crldttt% Granboppeas, Scorplunq Incks, Silrerftdy SpUlem
MmdoaceaHydramedlayloo 146-2AS%
PLarash Ants,Crkkds, Qw1rcaterAata,1C, RearLes, Variety] ofAnts.
Cyhkk CS Cylluthrin AS%
Spiders, Sompians,Anls,Ca aterAn rpe ts,CArpenterQece,l2aaches.Grkkete,311rert'sL.
Phantom SYo
.ItLEAS -
Pkamh Acts, Variety o1A3ab, Raachea.
T> mgard-PcrmefLrin .S�i
€leas, Ticks, Ante, Centipcdea, CarpeaterArt% Beea, Wasp, Carpenter Bees, Cuckroaebee,
Cdcheta,Flka,Earrl6s,MNipedes,Ueedes,PlJbui p.
Srsperd SC.Deltenelmda 4.75% (REST)
Fleas, Becs, BecHes, Roaches, Crickets, Lice, Mks, SnarplDas, Tkka, Waap&
Nyguard-Metbyletaoxy 10% (BXST)
IGli GroMb Regulator -Fleas, Reacbes. Crkkels, Plying Insects, Stored Product Pests.
Excite R.Pyrethrbi .(15%
INITM )RODENTS, RMS- MONITORc
Flea&
Fortrao-Brmmethalln .91%
Alice, Radmtk Eats
oTx�R Batt Stadon-I.ArgrlSmaR Ghte.Boords
dLee. Rodents, Eats, Bag Monitors.
Pr*,Conlr l Play Pyrethrhna .51M
Harsetlley Mosgaltms. Mulhs, Fleas, Wasps, Herneb,'lldta, Cockroadies.
Mavterlir¢ Bi&aBula ,d6%
Spiders, An Is. Roaches, S1lverlleb, Larwhgs, €less, Soorplwe
aioment: A -Compressed Sprayer P-Power Sprayer B-Bai[Dispenser B&Bait Station BT-Bait Trap D-Aerosol Can G-Gluc Board H-Hand Duster S-Spaeader F-Pogger FM-Foarner AC-AcAsDl unit Other
aHane:l-I itchea 7,fWh(a) 3-Bedrooms a-DimngRoom S-ULdity 6-Sto¢ap 7-ColmnonAtras BGaiage 941erimeterofSmmture 10-Attic 11-Yard 12-UaderHow 13-Watchmsel"fficelS-FxposedWaod2'upfmmSsab Other
meHtodefTmatments: CC-Clack&Ctevke S3-SubSlabInjection VT-Void7hatmeld BP-BaitPlaooment BS-BroadcastSpmy PB-Perimeterllurier BV-Brick Venire WT-WoodTreattnent
:. PRECAUTIONS: Do not touch treated areas till dry. Do not tamper with bait stations. Ventilate rooms after treatment. Keep pets away until pesticides have dried.
Licensed by the Texas Department of'Agricultllr+e Structural Pest Control Service - P.O. Box 12847 • Austin, TX 78711 -- 512-305-,8250 /�
SERVICE TECHNICIAN: CUSTOMER SIGNATURE: ��� `j/JG e 5 � �!` DATEa! -e/ GE
Please review the Customerlulormalion on the other side of Invoice
P.O. ox 9423 • College Station, TX 77842 - (979) 690-8622 • Fax (979) 690-8840
0
0
w
WFl003024 / 001 City of__C llege Station PAGE 1
r`
REQ. DATE: 02/08/08 02/08/08 9:09:00
LOCATION: 2927 MCLAREN DR LOC ID: 208590
REQUESTOR: STYLECRAFT BUILDERS ORIGIN: CUSTOMER -WALK IN
REQ USER: GLSOUTH AUTH USER:GLSOUTH WRK TYPE:
SWR 4" WTR 3/411
********************************************************************************
TASK: SET UP NEW UTILITY ACCT SET READY
SCHED START: 02/08/08 SCHED COMPLETION: 02/08/08
********************************************************************************
JOB ORDER RESULT COMIENTS
. . SHEET INDEX
COVER SHEET
G-1
GENERAL NOTES
G-2
SITE PLAN
C-1
FOUNDATION PLAN
S-1
DIMENSION PLAN
S-2
DETAILS
S-3
BRACING PLAN
S -4
FRAMING PLAN
S-5
ROOF FRAMING PLAN
S-6
DECKING LAYOUT-
S-7
ELEVATIONS
S-8
FRAMING DETAILS
S-9
ELECTRICAL PLAN
E-1
FLOOR PLAN
A-1
FLOORING PLAN
A-2
CABINET LAYOUT
A-3
PLAN APPROVAL
APPROVED
INITIALS
I DATE
ADMINISTRATOR
/
SUPERINTENDENT
/
CUSTOMER
/
NOTICE
THIS SET OF DRAWINGS FOR A HOME IS THE
COPYRIGHTED PROPERTY OF STYLECRAFT
BUILDERS, INC. THIS SINGLE COPY IS LICENSED AND
NO RIGHT TO REPRODUCE, COPY OR DUPLICATE ALL
OR ANY PORTION OF THE LICENSED PLANS IS
GRANTED, EITHER EXPRESSLY OR IMPLIED.
ALL IDEAS, DESIGNS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THE DRAWING ARE
OWNED BY AND THE PROPERTY OF THE DESIGNERS
AND WERE CREATED, EVOLVED AND DEVELOPED
FOR USE ON AND IN CONNECTION WITH THE
SPECIFIED PROJECT. NONE OF SUCH IDEAS,
DESIGNS, ARRANGEMENTS OR PLANS SHALL BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR
CORPORATION FOR ANY PURPOSE WHATSOEVER
WITHOUT THE WRITTEN PERMISSION OF THE
DESIGNERS.
BUILDING ENVELOPE
8'0
27'-2' : sa'a•
1 ST PLAN PREVIEW
SCALE:3/32"=1'-0"
2ND PLAN PREVIEW
SCALE:3/32"=1'-0"
FMSHING NOTES
1 lNotes
COMMENTS
AREA
SUMMAR
U�
V)
vn I-
I/W�1 O
a F
�D
W
= a
O
V
�o
U14
�cl
�0
SHEET:
G-1
COVER SHEET
AFRONT ELEVATION
SCALE:3/32"=1'-O"
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Application Number .
. . . . 08-00000328 Date 2/07/08
Application pin number
. . . 716544
Property Address . .
. . . . 292.7 MCLAREN DR
Property ID:
579530-0207-0180
R #:
R305144
Application type description
RESIDENTIAL, 1 UNIT DETACHED NEW
Subdivision Name . .
. . . . SOUTHERN TRACE PH 2
Property Use . . . .
. . . . RESIDENTIAL
Property Zoning . . .
. . . . SINGLE FAMILY CLUSTER DEV
Application valuation
. . . . 106326
Owner
------------------------
Contractor
BCS DEVELOPMENT CO
------------------------
STYLECRAFT BUILDERS
4090 SH 6 S
4090 SH 6 S
COLLEGE STATION
TX 77845 COLLEGE STATION TX 77845
(979) 690-1222
--- Structure Information
000 000 SINGLE FAMILY
Construction Type . .
. . . COMBUSTIBLE (UNPROTECTED)
Occupancy Type . . .
. . . RESIDENTIAL-SFR/DUPLEX
Other struct info . .
. . . EXTERIOR WALL TYPE BRICK
IMPACT/PRORATA-FEES PAID N/A
FOUNDATION TYPE SLAB
TYPE OF GARAGE (ATT/DET) NA
HEATED AREA 1610.00
INTERIOR WALL TYPE SHEETROCK
NUMBER OF BATHROOMS 4.00
NUMBER OF BEDROOMS 4.00
SEWER TYPE PUBLIC
----------------------------------------------------------------------------
TRAFFIC IMPACT ANAL (TAZ) 405.00
Permit . . . . . .
BUILDING PERMIT
Additional desc . .
GS
Permit pin number .
550293 -
Permit Fee . . . .
481.00 Plan Check Fee .00
Issue Date . . . .
2/07/08 Valuation . . . . 106326
Expiration Date
8/05/08
Qty Unit Charge
Per Extension
BASE FEE 460.00
7.00 3.0000
THOU BLDG, VAL 100001-500000 21.00
----------------------------------------------------------------------------
Special Notes and Comments
-Make sure 2nd Floor
Windows are 24" AFF Minimum
-Narrow Wall Bracing
to be Prescriptive Methods
*ALL BRANCH CIRCUITS
THAT SUPPLY OUISIN DWELLING
------------------------------------------40
BUILDING DEPT REPR SENTATIVE: IV -- --- -----------
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 2
Application Number . . . . . 08-00000328 Date 2/07/08
Application pin number . . . 716544
----------------------------------------------------------------------------
Special Notes and Comments
UNIT BEDROOMS SHALL BE PROTECTED BY AN ARC -FAULT CIRCUIT
INTERRUPTER(S)
*PROVIDE ATTIC ACCESS OPENING (MINIMUM ROUGH -FRAMED SIZE 22"
X 3011) WITHIN 20' OF THE MECHANICAL EQUIPMENT AND WALKWAY
*PROVIDE CHEMICAL TREATMENT OR PHYSICAL BARRIER (SUCH AS
METAL OR PLASTIC TERMITE SHIELDS) FOR PROTECTION
AGAINST TERMITES. IF CHEMICAL TREATMENT IS USED, THE
CONCENTRATION, RATE OF APPLICATION AND TREATMENT
METHOD SHALL BE CONSISTENT WITH THE TERMITICIDE LABEL.
BORACARE TREATMENT IS A SUITABLE SUBSTITUTE.
ALL METHODS MUST BE USED IN CONJUNCTION WITH TREATED
SILL PLATES. PROOF OF METHOD TO BE USED SHALL BE RECEIVED
IN OUR OFFICE BEFORE A CERTIFICATE OF OCCUPANCY WILL BE
ISSUED.
*PROVIDE COMBUSTION AIR FOR GAS FIRED APPLIANCES PER
CHAPTER 17, 2006 INTERNATIONAL RESIDENTIAL CODE
*Surface Drainage Shall Be Diverted to an Approved Point of
Collection. Lots Shall Have a Grade Fall Minimum of 6"
inches Within the First 10' feet Away From the Foundation
Walls.
*ELECTRICAL SHALL BE INSTALLED PER 2005 National Electrical
Code & LOCAL AMENDMENTS
*ELECTRIC STRIP HEATING NOT ALLOWED FOR RESIDENTIAL
PROPERTIES WITH FLOOR AREA GREATER THAN 500 Sq. FEET
*MINIMUM FOUNDATION STANDARD - ALL FOUNDATION SHALL COMPLY
WITH THE MINIMUM FOUNDATION STANDARD AS PER CITY'S
ORDINANCE (FOUNDATION DETAIL SHALL BE SHOWN ON PLANS)
MAKE SURE TO INCLUDE REBAR SLAB GROUND
*ALL FRAMING SHALL COMPLY WITH 2O06 INTERNATIONAL
RESIDENTIAL CODE
*Assure Proper GFI Locations, Including One Within 25, Of
Outside A/C Unit
*PLATFORM FOR MECHANICAL EQUIPMENT AND/OR ACCESS MAY HAVE TO
BE ELEVATED TO ALLOW FOR ATTIC INSULATION
*Wall and Ceiling Insulation are as follows respectively.
If Wall to Window Ratio is up to 1501 the Values Shall be
R-13 and R-30, above 15% the Ceiling Insulation is Increased
to R-38.
*IF LAWN SPRINKLERS IS PROVIDED, PERMIT MUST BE ISSUED PRIOR
TO CERTIFICATE OF OCCUPANCY.
*REQUIRED EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE
-------------------------------------------- ------ - ----------
BUILDING DEPT REPRESENTATIVE:
APPLICANT: &, & J�, A
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 3
Application Number . . . . . 08-00000328 Date 2/07/08
Application pin number . . . 716544
----------------------------------------------------------------------------
Special Notes and Comments
WITHOUT THE USE OF A KEY,TOOL OR SPECIAL KNOWLEDGE/EFFORT
*A Minimum of No. 15 Asphalt Felt or Other Approved Water
Resisitive Barrier Shall be Placed Over All Exterior
Sheathing Per 2006 IRC Section R703.2
*ON NARROW WALL BRACING WHERE SPECIAL NAILING PATTERN,
STRAPPING BETWEEN STORIES, OR HOLD DOWNS ARE REQUIRED THESE
ITEMS MUST REMAIN VISIBLE UNTIL THE INSPECTION PROCESS HAS
BEEN DONE TO ALLOW FOR COVER-UP
*MUST INDICATE METHODS ON FLOOR PLAN TO BE USED TO MEET
NARROW WALL BRACING REQUIREMENTS PER IRC CODE SECTION
R602.10 IN 2006 IRC
*If PEX water supply piping is sleeved below the slab, seal
annular space at ends with caulk, foam or other means.
Also assure proper protection of pipe to U.V. light.
*ANY CHANGES OR ALTERATIONS TO SUBMITTED PLANS MUST BE
RESUBMITTED AND APPROVED BEFORE WORK IS DONE IN ORDER TO
ASSURE CODE COMPLIANCE
*POST PERMIT CARD ON JOB SITE TO BE VISIBLE FROM ROAD
*WHEN WATER MAIN PRESSURE EXCEEDS 80 PSI,AN APPROVED
PRESSURE REDUCING VALVE SHALL BE PROVIDED THAT LIMITS THE
MAXIMUM STATIC WATER PRESSURE TO 80 PSI
*RECESSED LIGHTING INSTALLED IN THE BUILDING ENVELOPE SHALL
BE IC RATED AND SEALED TO PREVENT AIR LEAKAGE
*For residential applications with a glazing area that
exceeds 150 of the gross area of exterior walls, R-8 duct
insulation is required. As an alternative, R-6 duct
insulation can be used if the a/c system has a SEER rating
of 12 or more.
*PROVIDE SANITARY FACILITIES FOR WORKERS ON SITE LOCATED OFF
THE PUBLIC RIGHT-OF-WAY.
*SMOKE DETECTORS MUST HAVE 3' CLEARANCE FROM FORCED AIR
DUCTS, CEILING FANS AND RETURN AIR
*PROVIDE STRING LINES FOR ALL BUILDING SETBACKS AND
EASEMENTS ON FOUNDATION INSPECTION.
FORM SURVEY MAY BE SUBMITTED IN PLACE OF STRINGS.
*SHOWERS AND TUB/SHOWER COMBINATIONS SHALL BE EQUIPPED WITH
AN ANTI -SCALD VALVE THAT LIMITS WATER TEMPERATURE TO 120
DEGREES
*THE COMBINED SOLAR HEAT GAIN COEFFICIENT OF ALL GLAZED
FENESTRATION/WINDOW PRODUCTS DEPENDING ON PERCENTAGE OF WALL
TO GLAZING/WINDOW RATIO UP TO 20o A .40 OR LOWER FACTOR AND
BUILDING DEPT REPRES`�NTA IVEE:
APPLICANT: / _ /ic-
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Page 4
Application Number . . . . . 08-00000328 Date 2/07/08
Application pin number . . . 716544
----------------------------------------------------------------------------
Special Notes and Comments
ABOVE 20% TO 30% A .35 FACTOR OR LOWER SHALL BE MET.
*ALL SILLS AND BOTTOM PLATES IN CONTACT WITH CONRETE MUST BE
TREATED OR NATURALLY RESISTANT TO INSECTS AND DECAY
*SMOKE DETECTORS SHALL BE INTERCONNECTED, 120 VOLT W/BATTERY
BACKUP AND LOCATED IN EACH SLEEPING ROOM AND OUTSIDE EACH
SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
BEDROOMS
*REMOVE ALL VEGETATION AND FOREIGN MATERIAL FROM SLAB AREA
PRIOR TO PLACING FILL. FILL SHALL BE FREE FROM
VEGETATION AND FOREIGN MATERIAL.
*STAIRS SHALL COMPLY WITH SECTION R-311 (2006 IRC) WITH A
CONTINUOUS HANDRAIL OR SECTION
1009 (2006 IBC) AS APPROPRIATE, CONTINUOUS HANDRAIL
NEEDED, ENDS SHALL BE RETURNED OR SHALL TERMINATE INTO A
NEWEL POST OR SAFETY TERMINAL ON COMMERCIAL JOBS.
*WINDOWS ADJACENT TO TUBS WITHIN 60" ABOVE DRAIN SHALL BE
TEMPERED GLASS
*TEMPERED GLASS REQUIRED IN WINDOWS WITHIN 24" OF DOORS IN
ADJACENT WALLS
*AN APPROVED DEVICE FOR THERMAL EXPANSION CONTROL SHALL BE
PROVIDED FOR BUILDINGS UTILIZING STORAGE WATER HEATING
EQUIPMENT AND A PRESSURE REDUCING VALVE
*PER R308.4 GLAZING ADJACENT TO STAIRWAYS WITHIN 36" AND
LESS THAN 60" ABOVE WALKING SURFACE MUST BE TEMPERED (2003
IRC )
*U-Factor Ratings for Window % up to 150-a is .65, from 15% to
20% is .55, from 20% to 25% is .54 and above 25% is .46 or
lower.
*RANGE/DRYER DUCT MUST COMPLY WITH 2O06 IMC
*IF AN OPERABLE WINDOW IS MORE THAN 72" ABOVE EXTERIOR
FINISHED GRADE THEN THE LOWEST PART OF THE WINDOW OPENING
MUST BE AT LEAST 24" ABOVE THE FINSHED FLOOR FROM INSIDE THE
ROOM.
*ALL PLUMBING, ELECTRICAL, AND HVAC (mechanical) WORK MUST
BE PERFORMED BY LICENSED CONTRACTORS. CONTACT BUILDING
DEPARTMENT FOR INSPECTIONS PRIOR TO COVERING ANY WORK
----------------------------------------------------------------------------
Other Fees . . . . . . . . . SEWER TAP 4" 350.00
WATER TAP 3/4" 400.00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
-
--------------- ----- ---------------------- ------ ---- - -- --------------
BUILDING DEPT REPR SENT IVE�:
APPLICANT: ®�� /i.
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE, COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
http://bpinspect.cstx.gov
----------------------------------------------------------------------------
Application Number . . . . .
Application pin number . . .
----------------- ----------
Permit Fee Total 481.00
Plan Check Total .00
Other Fee Total 750.00
Grand Total 1231.00
Page
5
08-00000328
Date
2/07/08
716544
--------------------
481.00
----------
.00
.00
.00
.00
.00
750.00
.00
.00
1231.00
.00
.00
05 '
----------------------------------------- '------------
BUILDING DEPT REPRESENTATIVE: -01 /. Oita -
APPLICANT:
TEMPORARY POLE PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
----------------------------------------------------------------------------
Application Number . . . . .
08-00000329 Date
2/07/08
Application pin number . . .
810192
Property Address . . . . . .
2927 MCLAREN DR
Property ID:
579530-0207-0180
R #:
R305144
Application type description
TEMP POLE
Subdivision Name . . . . . .
SOUTHERN TRACE PH 2
Property Use . . . . . . . .
RESIDENTIAL
Property Zoning . . . . . . .
SINGLE FAMILY CLUSTER DEV
Application valuation . . . .
0
Owner
Contractor
------------------------
BCS DEVELOPMENT CO
------------------------
STYLECRAFT BUILDERS
4090 SH 6 S
4090 SH 6 S
COLLEGE STATION TX 77845
COLLEGE STATION
TX 77845
(979) 690-1222
----------------------------------------------------------------------------
Permit . . . . . . TEMP POLE
PERMIT
Additional desc . . GS
Permit pin number . 550301
Permit Fee . . . . 20.00
Issue Date . . . . 2/07/08
----------------------------------------------------------------------------
Valuation . . . .
0
Other Fees . . . . . . . . .
----------------------------------------------------------------------------
TEMP ELECT POLE CONNECT
45.00
Fee summary Charged
-----------------
Paid Credited
Due
----------
Permit Fee Total 20.00
------------------------------
20.00 .00
.00
Other Fee Total 45.00
45.00 .00
.00
Grand Total 65.00
65.00 .00
.00
-------------------------------------------
BUILDING DEPT REPR ENTA VE:: C
APPLICANT: / —
- 4. --------------
�b(
1�0
(*//4"
CITY OF COLLEGE STATION
P&=mg d- Dexlopmmr &=wa
APPLICATION FOR BUILDING PERMIT
1101 TEXAS AVENUE
COLLEGE STATION, TX 77840
(979) 764-3570 (979) 764-3496 FAX
WWW.CSTX.GOV
D � uxj
DATE TRCC
APPLICATION
TEMP POLE #
ADDRESS/LOCATION: 2c121 Mc.,_4dzen) V/ ,UiL
LOTBLOCK -% /SUBDIVISION SOVTItOV TizotO / SEC/PH�_�
BUSINESS/OWNER NAME: STYLECRAFT BUILDERS, INC. PHONE: 690-1222 ext.120
CONTRACTOR/HOMEOWNER: STYLECRAFT BUILDERS, INC. PHONE: 690-1222 ext. 120
CONTACT PERSON FOR REVIEW COMMENTS: ERIC WIVAGG PHONE: 690-1222 ext.120
FAX: 690-0348 EMAIL: ewivagg(oD-stylecraft-builders.com
ELECTRICIAN: Brazos Valley Electric PLUMBER: Bass Plumbing
HVAC: Control Temp GOOD CENTS (Residential only): No
ACCESSORY/STORAGE LOCATION RE -ROOF
ADDITION MOVING SHELL ONLY
DEMOLITION (Asbestos Survey) X NEW CONSTRUCTION ' SLAB ONLY
DUPLEX (Landscape Plans) REMODEURENOVATION* SWIMMING POOL
TENT/CANOPY
DESCRIPTION OF WORK: Conventional Framing
PROPOSED USE: Single Family Residence
WALL BRACING METHOD: PRESCRIPTIVE APA PORTAL FRAME W/ CSPS ENGINEERED
HOMEOWNER ASSOCIATION/ARCHITECTUAL OR DESIGN REVIEW COMMITTEE APPROVAL:
TEXAS ACCESSIBILITY STANDARD (TAS) PROJECT REGISTRATION# EABPRJ NIA
VALUATION: $ 106 ,126 ;"' TOTAL AREA: no HEATED AREA: IVC)
(Cost of Labor and Materials)
DX PUBLIC SEWER
❑ SEPTIC/TREATMENT SYSTEM
OX SEWER TAP:
QX WATER TAP:
OTHER TAP:
❑X TEMP POLE
GARAGE TYPE:
4"
SIZE
y/n
SIZE
JIZE
NUMBER OF BEDROOMS:
NUMBER OF BATHROOMS:
INTERIOR WALL TYPE: Sheet Rock
EXTERIOR WALL TYPE: Siding and/Or Masonry
FOUNDATION TYPE: Slab On Grade
ROOF TYPE: Composition
SINGLE DOUBLE a TRIPLE a
ATTACHED E C A� � CARPORT D
SIGNATURE OF APPLICANT: \ R, ! I /—
*If proposed work involves new commercial construction-6r f cad,
commercial property, building elevations are required.
Official Use Only
Sim�SPlans Examiner
Zoning Official
to an existing
Fire Marshall
P"SCA,;Pf(ve 3"C'("`5
�C nents:
Cl(.S,br NO
Eizergy Code Compliance Information
% Glazing of exterior walls
Insulation R value of exterior walls
Insulation R value of ceiling 1 (flat -areas)
Insulation R value of ceiling 2 (vaulted areas/no attic)
Glazing SHGC (Solar Heat Gain Coefficient)
Glazing U-Factor
R value of ductwork
A/C SEER Rating
Protection Against Subterranean Termites
❑ Chemical Termiticide Treatment (Soil Treatment)
ID %
R13
R30
R19
.35
.53
Chemical Termiticide Treatment (Field Applied Wood Treatment)
❑ Physical Barriers
❑ Other
*Verification of Application shall be submitted to the City of College Station
Building Department prior to issuance of the Certificate of Occupancy.
crl
f PLAN REVIEW
(*//q" ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
CITY OF COLLEGE STATION 1101 TEXAS AVENUE
Planning& Development Services COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
PLAN REVIEW/PERMIT NUMBER# O Q _ —T
DATE:
BUILDING ADDRESS: 1`1
I. Foundation Requirements- Minimum i Foundation Standards
NA/
A.
Concrete minimum compression strength of 3000 PSI
B.
Minimum four 4 inch slab thickness
C.
Vapor barrier Emil. Poly min.
D.
Slab/beam or pier layout shown
1. Footings/beams are continuous over the length and width of foundation
2. Footings 30" exterior, 24" interior, unless over 60' long must be 30"
3. Spacing of beams does not exceed 15'
E.
Reinforcement details to meet minimum requirements
1. Slab reinforcement and Beam Reinforcement
F.
Protection Method used for Termites.
G.
Wood foundation details indicated
OK
II. Framing:
Floor, Wall, Ceiling and Roof Requirements
NA/
A.
Girder or sill dimensions, grade & species
B.
Floor joist size, spacing, grade & direction of span indicted on plans
C.
Treated sill plate or bottom plate
D.
Tenant separation in duplex
K
1. One -hour rated extendin to roof deck
CRAJOK
E.
Header sizes indicated on plans
NAOM
F.
Emergency bedroom egress
1. Exit direct to outside
2. Operable window
a. Twenty 20 inch clear width by twenty-four 24 inch clear height
b. Maximum sill height of forty-four 44 inches above finished floor
G.
Operable bathroom window required when mechanical ventilation is not provided
H.
Stud grade andspacing
I.
Exterior wall details
1. Sheathing indicated on plans for Wall Bracing
2. Moisture barrier indicated on plans
3. Exterior Wall Covering
J.
Roof framing Ian or elevation shown
K.
Ceiling joist size, spacing, grade and direction of span indicated on plans
L.
Attic access location and size indicated on plans
M.
Span exceeding code tables must be engineered
N.
Rafter size, spacing, roof slope & purlin bracing if required to reduces an
O.
Roof covering
P.
All girders & beams for support of floors, walls, ceiling & roofs must have the size, grade &
location indicated on plans
Q. Tempered Glass required in all hazardous locations
R. 18" Overhangs allowed on zero lot line, non-combustible perforated soffit only
S. All walls within 3' of property line to have protected openings.
MOK
K
• ! PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
CITY OF COLLEGE STATION 1101 TEXAS AVENUE
Planning 6Development Servien COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
III. Stairway Requirements
A. Stairway Details
N
1. Maximum riser height 7-3/4 inches
2. Minimum tread width 10 inches
3. Stairway risers are uniform 3/8" Max. difference
4. Stairway width not less than 36 inches
5. Stairway headroom not less that six ft. eight 6'-8"
B. Winder details
1. Treads a minimum of six 6 inches on narrow edge
2. Treads a minimum often (10) inches at a distance of twelve (12) inches from the
narrow edge
C. Spiral stairway details
1. Riser height less than nine and one-half 9-1/2 inches
2. Treads a minimum of seven and one-half (7-1/2) inches at a distance of twelve (12)
inches from the narrow edge
3. Stairway width not less than thirty-six inches
4. Headroom required not less than six ft six 6-6 inches
5. All treads must be identical
D. Guards/handrail details
1. Guards required when a porch, deck, balcony or landing is thirty (30) inches
above grade or finished floor
2. Handrails are required on stairways located two or more risers above floor/grade
3. Handrails must be thirty-four to thirty-eight (34-38) inches when measured from the
leading edge of the tread
4. Handrails must not project more than four & one-half (4-1/2) inches into width of a
stairway
5. Guards must be a minimum of thirty-six 36 inches above finished floor
6. Guards & handrails along open-side(s) of stairway must have intermediate
railing or uprights that prevent the passage of a four 4 inch sphere
IV. Fireplace Requirements
OK
A. Hearth extensions
1. Fireplace opening < 6 s , ft, extensions: 8" & 16" forward
2. Fireplace opening ? 6 s . ft. extensions: 12" side & 20" forward
B. Masonry fireplace requires 2" clearance from all combustible materials
C. Chimneys must meet IRC Chapter 10 Requirements
V. Electrical Service Requirements
A. Electrical plan to include:
N O
1. Electrical fixtures & switches indicated
2. Smoke detector locations indicated as required
3. GFI circuits indicated where required
4. Arc fault protection for bedroom circuits
5. Panel location
• 1 (*�
CITY OF COLLEGE STATION
Planning d Dmdopmrnt Sttviat
PLAN REVIEW
ONE and TWO FAMILY OCCUPANCY REQUIREMENTS
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
COLLEGE STATION, TEXAS 77840
(979) 764-3570; (979) 764-3496 FAX
VI. Plumbing Requirements
A. Pressure reducing valve required when water pressure exceeds 80 psi
N
B. Plumbing access to bathtubs
C. Means for thermal expansion provided when required
D. Water heaters elevated 18" when installed in the garage or room directly off garage
VII. Mechanical Requirements
N ME
A. All mechanical ventilation's in bathrooms & range hood ventilation must be ducted to
outside excludes ductless units)
T
B. Attic installed H.V.A.C. requirements:
1. Twenty-four (24) inch wide unobstructed walkway from attic access to equipment
must be provided
2. Attic access located within 20 feet of equipment
C. Combustion air supplied for gas appliances when required)
VIII. Energy Requirements
NA/
A. Compliance software worksheet MECcheck submitted, or
B. Energy data supplied Percent of glazing, insulation R-values, window U-values, etc.
Zoning Ordinance Requirements — Ordinance 850
NAI
Permitted use for district
Density requirements
Minimum lot size
Setbacks
Easements
Required parking
Street Ordinance Requirements
N
Maximum drive width for residence is 25' combined for circular and 12' minimum for single
Minimum 20 feet from drivewayto side (intersecting)street property line sight triangle
Driveway access to lesser street for corner lots
Subdivision Regulations — Ordinance 690
N
Approved subdivision
Plat filed
Flood lain Regulations — Ordinance 1301
N
Does not block an water course or divert an flow
Elevation certificate needed
OK
"APPROVED PLANS PER IRC SECTION R106.3.1."
PLANS EXAMINER
J,,.�%D0
DATE
k
i
0 REScheck Software Version 3.7.3
8/" Compliance Certificate
Project Title: 1611 Plan
Report Date: 02/04/08
Data filename: S:\ACAD\RESCheck\1611.00-Master.rck
Energy Code:
2003 IECC
Location:
College Station, Texas
Construction Type:
Single Family
Glazing Area Percentage:
10%
Heating Degree Days:
1788
Construction Site:
Owner/Agent:
College Station, TX 77845
Stylecraft Builders, Inc.
4090 SH 6 South
College Station, TX 77845
979-690-1222 x127
jsaucier@stylecraft-builders.com
Maximum SHGC: 0.40 Your SHGC: 0.40
Permit #
Permit Date
Designer/Contractor:
Stylecraft Builders, Inc.
4090 SH 6 South
College Station, TX 77845
979-690-1222 x127
jsaucier@stylecraft-builders.com
Wall 1: Wood Frame, 16" o.c.:
1096 13.0
0.0
76
Window 1: Metal Frame:Double Pane with Low-E:
4
0.670
3
SHGC: 0.40
Window 2: Metal Frame:Double Pane with Low-E:
4
0.670
3
SHGC: 0.40
Window 3: Metal Frame:Double Pane with Low-E:
13
0.670
9
SHGC: 0.40
Window 4: Metal Frame:Double Pane with Low-E:
21
0.670
14
SHGC: 0.40
Window 5: Metal Frame:Double Pane with Low-E:
21
0.670
14
SHGC: 0.40
Window 6: Metal Frame:Double Pane with Low-E:
21
0.670
14
SHGC: 0.40
Window 7: Metal Frame:Double Pane with Low-E:
16
0.670
11
SHGC: 0.40
Window 8 Twin: Metal Frame:Double Pane with Low-E:
16
0.670
11
SHGC: 0.40
Window 8 Twin: Metal Frame:Double Pane with Low-E:
16
0.670
11
SHGC: 0.40
Door 1: Solid:
18
0.500
9
Door 2: Glass:
20
0.440
9
SHGC: 0.40
Wall 2: Wood Frame, 16" o.c.:
974 13.0
0.0
75
Window 9: Metal Frame:Double Pane with Low-E:
6
0.670
4
SHGC: 0.40
Window 10: Metal Frame:Double Pane with Low-E:
13
0.670
9
SHGC: 0.40
Window 11: Metal Frame:Double Pane with Low-E:
13
0.670
9
SHGC: 0.40
Window 12: Metal Frame:Double Pane with Low-E:
3
0.670
2
1611 Plan
Page 1 of 2
SHGC: 0.40
Window 13 Twin: Metal Frame:Double Pane with Low-E: 13 0.670 9
SHGC: 0.40
Window 13 Twin: Metal Frame:Double Pane with Low-E: 13 0.670 9
SHGC: 0.40
Ceiling 1: Flat Ceiling or Scissor Truss: 818 30.0 0.0 29
Floor 1: Slab -On -Grade: Unheated: , Insulation Depth: 0.0' 122 0.0 127
Furnace 1: Forced Hot Air: 80 AFUE
Air Conditioner 1: Electric Central Air: 13 SEER
Compliance Statement. The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. Th op ed building has been designed to meet the 2003 IECC requirements in
REScheck Version 3.7.3 and to comply with the ndatory r ments ' t in the REScheck Inspection Checklist.
Builder/Designer Company Namb i Date
Project Notes:
All U-Factors and SHGC are at entered at higher than actual amounts.
Actual amounts are lower, but are entered higher to account for
differences in ratings per material.
1611 Plan
Page 2 of 2