HomeMy WebLinkAboutRES2006-00865, 06-866WF0757370 / 001 City of College Station
PAGE 1
REQ. DATE:
04/03/06 • '
04/03/06
16:06:13
LOCATION:
1703 PARK PLACE
LOC ID:
204318
REQUESTOR:
J L M CONSTRUCTION ORIGIN:
CUSTOMER -WALK IN
REQ. USER:
GLSOUTH AUTH. USER: GLSOUTH
WORK TYPE:
ROUT
SWR 4"
WTR 3/41'
********************************************************************************
TASK:
SET UP NEW UTILITY ACCT SET
READY
SCHED START:
04/03/06 SCHED COMPLETION:
04/03/06
********************************************************************************
JOB ORDER RESULT COMMENTS
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, WX 77840
PHONE: (979)764-3570'l FAX: (979)764-3496
----------------------------------------------------------------------------
Application Number .
. . . . 06-00000865 Date 4/03/06
Property Address . .
. . . . 1703 PARK PLACE
Property ID:
367000-0002-0110
R #:
R30417
Application type description RESIDENTIAL, 1 UNIT DETACHED NEW
Subdivision Name . .
. . . . KAPCHINSKI
Property Use . . . .
. . . . RESIDENTIAL
Property Zoning . . .
. . . . SINGLE FAMILY RESIDENTIAL
Application valuation
. . . . 105600
Owner
Contractor
------------------------
ABRAHAM, ELLIS J
------------------------
J L M CONSTRUCTION
2609 SANDELWOOD
DARREL MUNSEY
COLLEGE STATION TX 77845 PO BOX 277
NORMANGEE TX 77871
(936) 396-5500
--- Structure Information
000 000 SINGLE FAMILY
Construction Type . .
. . . COMBUSTIBLE (UNPROTECTED)
Occupancy Type . . .
. . . RESIDENTIAL-SFR/DUPLEX
Other struct info . .
. . . EXTERIOR WALL TYPE SIDING
IMPACT/PRORATA FEES PAID NA
FOUNDATION TYPE SLAB
TYPE OF GARAGE (ATT/DET) NA
HEATED AREA 1600.00
INTERIOR WALL TYPE DRYWALL
NUMBER OF BATHROOMS 4.00
NUMBER OF BEDROOMS 4.00
SEWER TYPE PUBLIC
TAZ 288.00
----------------------------------------------------------------------------
Permit . . . . . .
BUILDING PERMIT
Additional desc
GS
Permit Fee
478.00 Plan Check Fee .00
Issue Date
4/03/06 Valuation . . . . 105600
Expiration Date
9/30/06
Qty Unit Charge
Per Extension
BASE FEE 460.00
6.00 3.0000
THOU BLDG, VAL 100001-500000 18.00
----------------------------------------------------------------------------
Special Notes and Comments
ALL BRANCH CIRCUITS
THAT SUPPLY OUTLETS IN DWELLING
UNIT BEDROOMS SHALL
BE PROTECTED BY AN ARC -FAULT CIRCUIT
INTERRUPTER(S)
PROVIDE ATTIC ACCESS
OPENING (MINIMUM ROU H-FRAMED SIZE 22"
----------------------------------------------
BUILDING DEPT RE k
------ --- --'- ----------
Er,S1ENTqlvE
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570° FAX: (979)764-3496
Application Number . . . . . 06-00000865
Page 2
Date 4/03/06
Special Notes and Comments
X 3011) WITHIN 20' OF THE MECHANICAL EQUIPMENT AND WALKWAY
PROVIDE CHEMICAL TREATMENT OR PHYSICAL BARRIER (SUCH AS
METAL OR PLASTIC TERMITE SHIELDS) FOR PROTECTION
AGAINST TERMITES. IF CHEMICAL TREATMENT IS USED, THE
CONCENTRATION, RATE OF APPLICATION AND TREATMENT
METHOD SHALL BE CONSISTENT WITH THE TERMITICIDE LABEL.
ALL METHODS MUST BE USED IN CONJUNCTION WITH TREATED
SILL PLATES
PROVIDE COMBUSTION AIR FOR GAS FIRED APPLIANCES PER
CHAPTER 17, 2003 INTERNATIONAL RESIDENTIAL CODE
ELECTRICAL SHALL BE INSTALLED PER 2002 National Electrical
Code & LOCAL AMENDMENTS
ELECTRIC STRIP HEATING NOT ALLOWED FOR RESIDENTIAL
PROPERTIES WITH FLOOR AREA GREATER THAN 500 Sq. FEET
MINIMUM FOUNDATION STANDARD - ALL FOUNDATION SHALL COMPLY
WITH THE MINIMUM FOUNDATION STANDARD AS PER CITY'S
ORDINANCE (FOUNDATION DETAIL SHALL BE SHOWN ON PLANS)
MAKE SURE TO INCLUDE REBAR SLAB GROUND
ALL FRAMING SHALL COMPLY WITH 2O03 INTERNATIONAL
RESIDENTIAL CODE
PLATFORM FOR MECHANICAL EQUIPMENT AND/OR ACCESS MAY HAVE TO
BE ELEVATED TO ALLOW FOR ATTIC INSULATION
IF LAWN SPRINKLER IS PROVIDED, PERMIT MUST BE ISSUED PRIOR
TO CERTIFICATE OF OCCUPANCY.
REQUIRED EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE
WITHOUT THE USE OF A KEY,TOOL OR SPECIAL KNOWLEDGE/EFFORT
ON NARROW WALL BRACING WHERE SPECIAL NAILING PATTERN,
STRAPPING BETWEEN STORIES, OR HOLD DOWNS ARE REQUIRED THESE
ITEMS MUST REMAIN VISIBLE UNTIL THE INSPECTION PROCESS HAS
BEEN DONE TO ALLOW FOR COVER-UP
MUST INDICATE METHODS ON FLOOR PLAN TO BE USED TO MEET
NARROW WALL BRACING REQUIREMENTS PER IRC CODE SECTION
R602.10 IN 2003 IRC
If PEX water supply piping is sleeved below the slab, seal
annular space at ends with caulk, foam or other means.
ANY CHANGES OR ALTERATIONS TO SUBMITTED PLANS MUST BE
RESUBMITTED AND APPROVED BEFORE WORK IS DONE IN ORDER TO
ASSURE CODE COMPLIANCE
POST PERMIT CARD ON JOB SITE
WHEN WATER MAIN PRESSURE EXCEEDS 80 PSI, AN APPROVED
PRESSURE REDUCING VALVE SHALL BE PROVIDED THAT LIMITS THE
MAXIMUM STATIC WATER PRESSURE TO 80 PSI
BUILDING DE
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570' FAX: (979)764-3496
----------------------------------------------------------------------------
Page 3
Application Number . . . . . 06-00000865 Date 4/03/06
----------------------------------------------------------------------------
Special Notes and Comments
RECESSED LIGHTING INSTALLED IN THE BUILDING ENVELOPE SHALL
BE IC RATED AND SEALED TO PREVENT AIR LEAKAGE
Refer To This Permit For Details For This Plan
PROVIDE SANITARY FACILITIES FOR WORKERS ON SITE LOCATED OFF
THE PUBLIC RIGHT-OF-WAY.
ADD SMOKE DETECTOR(S) PER NOTES ON PLANS
SMOKE DETECTORS MUST HAVE 3' CLEARANCE FROM FORCED AIR
DUCTS, CEILING FANS AND RETURN AIR
PROVIDE STRING LINES FOR ALL BUILDING SETBACKS AND
EASEMENTS ON FOUNDATION INSPECTION.
SHOWERS AND TUB/SHOWER COMBINATIONS SHALL BE EQUIPPED WITH
AN ANTI -SCALD VALVE THAT LIMITS WATER TEMPERATURE TO 120
DEGREES
THE COMBINED SOLAR HEAT GAIN COEFFICIENT OF ALL GLAZED
FENESTRATION PRODUCTS SHALL NOT EXCEED .4
ALL SILLS AND BOTTOM PLATES IN CONTACT WITH CONRETE MUST BE
TREATED OR NATURALLY RESISTANT TO INSECTS AND DECAY
SMOKE DETECTORS SHALL BE INTERCONNECTED, 120 VOLT W/BATTERY
BACKUP AND LOCATED IN EACH SLEEPING ROOM AND OUTSIDE EACH
SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
BEDROOMS
REMOVE ALL VEGETATION AND FOREIGN MATERIAL FROM SLAB AREA
PRIOR TO PLACING FILL. FILL SHALL BE FREE FROM
VEGETATION AND FOREIGN MATERIAL.
STAIRS SHALL COMPLY WITH SECTION R-311 (2003 IRC) WITH A
CONTINUOUS HANDRAIL OR SECTION
1009 (2003 IBC) AS APPROPRIATE, CONTINUOUS HANDRAIL
NEEDED, ENDS SHALL BE RETURNED OR SHALL TERMINATE INTO A
NEWEL POST OR SAFETY TERMINAL ON COMMERCIAL JOBS.
WINDOWS ADJACENT TO TUBS WITHIN 60" ABOVE DRAIN SHALL BE
TEMPERED GLASS
TEMPERED GLASS REQUIRED IN WINDOWS WITHIN 24" OF DOORS IN
ADJACENT WALLS
AN APPROVED DEVICE FOR THERMAL EXPANSION CONTROL SHALL BE
PROVIDED FOR BUILDINGS UTILIZING STORAGE WATER HEATING
EQUIPMENT AND A PRESSURE REDUCING VALVE
PER R308.4 GLAZING ADJACENT TO STAIRWAYS WITHIN 36" AND
LESS THAN 60" ABOVE WALKING SURFACE MUST BE TEMPERED (2003
IRC)
RANGE/DRYER DUCT MUST COMPLY WITH 2O03 IMC
ALL PLUMBING, ELECTRICAL, AND HVAC (mechanical) WORK MUST
BE PERFORMED BY LICENSED CONTRACTORS. CONTACT BUILDING
-------------------------------------------------------- - ----------
BUILDING DEPT REP�E,S�\NTATT- -^
1 1
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
----------------------------------------------------------------------------
Page
4
Application Number
. . . . .
06-00000865
Date
4/03/06
----------------------------------------------------------------------------
Special Notes and
Comments
DEPARTMENT FOR
INSPECTIONS
PRIOR TO COVERING
ANY WORK
Narrow wall Bracing Fully Sheathed
----------------------------------------------------------------------------
Other Fees . . .
. . . . . .
SEWER TAP 4"
350.00
WATER TAP 3/4"
400.00
----------------------------------------------------------------------------
Fee summary
Charged
----------
Paid Credited
------------------------------
Due
-----------------
Permit Fee Total
478.00
478.00
.00
.00
Plan Check Total
.00
.00
.00
.00
Other Fee Total
750.00
750.00
.00
.00
Grand Total
1228.00
1228.00
.00
.00
-------------------
BUILDING DE
APPLICANT:
use
(*. t/7 ..
CITY OF COLLEGE STATION
planningd'DewlvpmegiS vices
APPLICATION FOR BUILDING PERMIT
1101 TEXAS AVENUE
COLLEGE STATION, TX 77840
(979) 764-3570 (979) 764-3496 FAX
WWW.CSTX.GOV
ADDRESS/LOCATION: I I Ui _�_ 1; A\c
d.
LOT; BLOCK ` SUBDIVISIONr
BUSINESS/OWNER NAME:
CONTRACTOR/HOMEOWNERx,-TL. K in I L d-t
CONTRACTOR ADDRESS:
DATE3'A3 • ��+(T*C RREGG ell]
APPLICATION # v�/+�'
TEMP POLE # v`- Roo
SEC/PH
PHONE: �] - D'\ q `1-
PHONE: Salo - I q is
ELECTRICIAN: ��V�'� PLUMBER: v r`q-
HVAC: GOOD CENTS (Residential only):
CLASS OF WORK
ACCESSORY/STORAGE LOCATION
ADDITION MOVING
DEMOLITION (Asbestos Survey) NEW CONSTRUCTION
DUPLEX (Landscape Plans) REMODEL/RENOVATION"
DESCRIPTION OF WORK:
PROPOSED USE:
RE -ROOF
SHELL ONLY
SLAB ONLY
SWIMMING POOL
TENT/CANOPY
HOMEOWNER ASSOCIATION/ARCHITECTUAL OR DESIGN REVIEW COMMITTEE APPROVAL:
TEXAS ACCESSIBILITY STAN TA�ROJECT REGISTRATION# EABPRJ
VALUATION: $ IJJ TOTAL AREA: q HEATED AREA:
(Cost of Lab and Materials)
9LIPU61LIC SEWER
❑ SEPTICITREATMENT SYSTEM
SEWER TAP: L
2 JIZE
KJ-WATER TAP: 3
SIZE
❑ OTHER TAP:
NUMBER OF BEDROOMS
NUMBER OF BATHROOMS
INTERIOR WALL TYPE
EXTERIOR WALL TYPE
FOUNDATION TYPE
SIZE
U111TEMP POLE ROOF TYPE:
GARAGE TYPE: SINGLE F-1 DOUBLE TRIPLE
ATTACHED Fj DETACHED a CARPORT
SIGNATURE OF APPLICANT:
"If proposed work involves new commerc' ion. o c e improvements/renovations to an existing
commercial property, building elevations a\m. r quired.
Official Use Only
Plans Examiner
Z_ilu
Zoning Official
Comm
ES r NO
Fire Marshall
Energy Code Compliance Information
% Glazing of exterior walls
Insulation R value of exterior walls
13
Insulation R value of ceiling 1 (flat areas)
30
Insulation R value of ceiling 2 (vaulted areas/no attic)
Glazing SHGC
• qD
Glazing U-Factor
61
R value of ductwork
A/C SEER Rating
CITY OF COLLEGE STATION
Planning d Development Services
PLAN 'REVIEW
ONE and TWO FAMILY
OCCUPANCY REQUIREMENTS
PLAN REVIEW/PERMIT NUMBER# Q _ 8 s DATE: 3 h I a�
BUILDING ADDRESS:
I. Foundation Requirements
N
A. Concrete minimum f'c of 3000 PSI
B. Minimum four 4 inch slab thickness
C. Vapor barrier
1. 6 mil poly
D. Slab/beam or pier layout shown
1. Footings/beams are continuous over the length and width of foundation
2. Dimensions
3. Footings 30" exterior, 24" interior unless over 60' long then 30"
4. S acing of beams does not exceed 15'
E. Reinforcement details to meet minimum requirements
1. Slab reinforcement
2. Exterior beam reinforcement
3. Interior beam reinforcement
4. Masonry fireplace foundation reinforcement
F. Wood foundation details indicated
II. Framing: Floor, Wall, Ceiling and Roof Requirements
NA/
A. Girder or sill dimensions, grade & species
B. Floor joist size, spacing, grade & direction of span indicted on plans
C. Treated sill plate or bottom plate
D. Narrow Wall Bracing Methods indicated on plans
E. Header sizes indicated on plans
F. Emergency bedroom egress
1. Exit direct to outside
2. Operable window
a. Twenty 20 inch clear width by twenty-four 24 inch clear height
b. Maximum sill height of forty-four 44 inches above finished floor
G. Operable bathroom window required when mechanical ventilation is not provided
H. Stud grade andspacing
I. Exterior wall details
1. Exterior wall covering indicated on plans
2. Sheathing indicated on plans
3. Moisture barrier indicated on plans
J. Roof framing Ian or elevation shown
K. Ceiling joist size, spacing, grade and direction of span indicated on plans
L. Attic access location and size indicated on plans
1. If located in garage it is not to exceed 30" x 54"
M. Span exceeding code tables must be engineered
N. Rafters sizes, spacing, grade, slope and purlins if required.
PLAN' REVIEW
ONE and TWO FAMILY
CITY OF COLLEGE STATION OCCUPANCY REQUIREMENTS
Planning 6 Development Services
11. Framing: Floor, Wall, Ceiling and Roof Requirements (continued)
O. Roof Covering
1. Roof Decking indicated on plans.
N'T
2. Moisture barrier indicated on plans
P. All girders & beams for support of floors, walls, ceiling & roofs must have the size, grade &
location indicated on plans
Q. Tempered Glass required in all hazardous locations
R. Overhangs allowed on zero lot line construction up to 18"
jVA
S. Protected openings on walls < three feet from property line
T. One hour tenant separation to roof deck between duplexes
w,
/v
III. Stairway Requirements
N
A. Stairway Details
1. Maximum riser height 7-3/4 inches
2. Minimum tread width 10 inches
3. Stairway risers are uniform 3/8" Max. difference
4. Stairway width not less than 36 inches
5. Stairway headroom not less that six ft. eight 6'-8"
B. Winder details
1. Treads a minimum of six 6 inches on narrow edge
2. Treads a minimum often (10) inches at a distance of twelve (12) inches from the
narrow edge
C. Spiral stairway details
1. Riser height less than nine and one-half 9-1 /2 inches
2. Treads a minimum of seven and one-half (7-1/2) inches at a distance of twelve (12)
inches from the narrow edge
3. Stairway width not less than twenty-six inches
4. Headroom required not less than six ft six 6-6" inches
5. All treads must be identical
D. Guards/handrail details
1. Guards required when a porch, deck, balcony or landing is thirty (30") inches
above grade or finished floor
2. Handrails are required on stairways located four or more risers above floor/grade
3. Handrails must be thirty-four to thirty-eight (34-38) inches when measured from the
leading edge of the tread
4. Handrails must not project more than four & one-half (4-1/2") inches into width of a
stairway
5. Guards must be a minimum of thirty-six 36 inches above finished floor
6. Guards & handrails along open-side(s) of stairway must have intermediate
railing or uprights that prevent the passage of a four 4 inch sphere
IV. Fireplace Requirements to be indicated onplans)
OK
A. Hearth extensions
1. Fireplace opening < 6 s , ft, extensions: 8" & 16" forward
2. Fireplace opening > 6 s . ft. extensions: 12" side & 20" forward
B. Masonry fireplace requires 2" clearance from all combustible materials
C. Chimneys must extend at least three (3) feet higher than the highest point of roof & at
least two 2 feet higher than any portion of the building within ten 10 feet horizontal
PLAN REVIEW
(*hrq" ONE and TWO FAMILY
CITY OF COLLEGE STATION
OCCUPANCY REQUIREMENTS
Planning d Development Services
V. Electrical Service Requirements
N
A. Electrical plan to include:
1. Electrical fixtures & switches indicated
2. Smoke detector locations indicated as required
3. GFI circuits indicated where required
4. Arc fault protection for bedroom circuits
5. Panel and Meter location
VI. Plumbing Requirements
NAfOfO
A. Pressure reducing valve required when water pressure exceeds 80 psi
B. Access to Bathtubs
C. Means for thermal expansion provided.
D. Water heaters elevated 18" when installed in the garage or room directly off garage
VI1. Mechanical Requirements
N
A. All mechanical ventilation's in bathrooms & range hood ventilation must be ducted to
outside excludes ductless units
B. Attic installed H.V.A.C. requirements:
1. Twenty-four (24) inch wide unobstructed walkway from attic access to equipment
must be provided
2. Attic access located within 20 feet of equipment or 50' with 6' clearance
C. Combustion air supplied for gas appliances (when required)
Vill. Energy Requirements
NAJORI
A. Compliance software worksheet REScheck submitted, or
a. Energy data supplied (Percent of glazing, insulation R-values, window U-values,
etc.)
Zoning Ordinance Requirements — Ordinance 850
NAM
Permitted use for district
Density requirements
Minimum lot size
Setbacks
Easements
Required parking
On zero lot side 18" max. overhang allowed
Street Ordinance Requirements
NAM
Maximum drive width for residence is 28' combined for circular
Minimum 20 feet from driveway to side(intersecting) street
Subdivision Regulations — Ordinance 690
N
Approved subdivision
Plat filed
IVA
Flood lain Regulations — Ordinance 1301
OK
Does not block any water course or divert any flow
Elevation certificate if required
CITY OF COLLEGE STATION
Planning cr Devtlopment Services
Comments:
gz Joe ory
LANS EXAMINER
PLAN'REVIEW
ONE and TWO FAMILY
OCCUPANCY REQUIREMENTS
_2-7
DATE