July 26, 2006
Benjamin McCarty
City of College Station
Development Services
1101 Texas Avenue South
P.O. Box 9960
College Station, Texas 77842
RE: Adam Plaza
Application #05-3934
Dear Mr. McCarty,
This letter is in reference to the monumental stair from the 9`h to 10`h floors of Adam Plaza.
It is part of the project submitted in October 2005 under the 2000 IBC.
The referenced stair is an interconnecting stair that connects the 901 and 10`h floors. It is not a
required exit stair and the building is fully sprinkered.
Per our conversation earlier today and your previous conversation with the building official, it is
my understanding that since our building is fully sprinklered we are not required to provide a 1-
hour enclosure around our stair opening nor a draft curtain. (Per section 404.3.)
I look forward to your response and confirmation of these findings.
Sincerely,
Corey Credeur, AIA
Associate
Pennzoil Place
700 Milam Screec
Suite .{00
Houston Texas 77001
Tel: 713. 118. Soso
Fax: 713. 129. 9343
Archirecrure, Design & Planning Worldiuirle Gensler
January 12, 2006
Benjamin McCarty
City of College Station
Development Services
1101 Texas Avenue South
P.O. Box 9960
College Station, Texas 77842
RE: Adam Plaza
Dear Mr. McCarty,
We are in receipt of your letter dated December 20, 2005.
In response to your letters dated December 20, 2005 regarding 9th floor Core Lobbv Area
and loth floor Offices — First American Blvd:
Application #05-3934
/��f1. Need to submit information regarding the plan to block off finished areas from unfinished
TY�__ future tenant spaces, including elevator doors.
�Q `n" ��•� The unfinished future tenant spaces will be blocked off using partitions as .scheduled on
C the drawings. Doors with locks are provided into all unoccupied spaces with free egress
from those spaces.
Submit details on the fireplace in Mr. Adam's office.
Details have been added.
Refer to revised Sheets A11.59 and Al2.65
Pennzoil Place
-oo Nfilan: Street
Suite 400
Houston Texas 77002
-lel: 7/13. 225. 8050
Fax: 713. 229. 9343
Gensler
d3I--,' Verify the accessibility of the telephone room near the boardroom to comply with section
704 of the ICC/ANSI Al 17.1-1998, Accessible and Useable Buildings and Facilities.
Section 704.2.1—The clear floor area in the telephone room is 60 'X60"with an
additional 21 " of knee -room below the countertop.
Section 704.2.1.2 — The telephone will be a countertop phone and will be less than 20
inches away from the front edge of the counter.
Section 704.2.2 — Operable parts of the telephone will be within the reach ranges
specified in Section 308. The telephone will sit on a counter that is 30 1/2 "aff.
Section 704.2.3 — No telephone directories are provided.
Section 704.2.4 — The owner to ensure that the handset cord length will be 29 inches
minimum.
Section 704.2.5 — The owner to ensure that the telephone shall be hearing -aid
compatible.
Section 704.3 — The owner to ensure that if the telephone has volume control it will be
equipped with a receive volume control with a range that provides 12 dB of gain
minimum and 20dB of gain maximum. An automatic reset shall.be provided.
Section 704.4 and 704.5 —pay telephones are not used.
Section 704.5 - The clear knee -space below the counter is 27 Y2 "aff.
Submit verification of smokeproof enclosures for all stairways and their exit passageways
to comply with section 909.20 of the 2003 IBC.
Stairwells and exit corridors are part of the base building and not in this scope of work.
Refer to the base building permit for compliance.
NpTE S1 Need to verify and submit automatic fire alarm and emergency voice/alarm
communication system prior to installation to comply with section 907.2.12 of the 2003
International Building Code.
The automatic fire alarm and emergency voice/alarm communication system will be
submitted separately by the fire alarm sub -contractor.
No Need to submit fire sprinkler plans prior to installation.
See response above to item 2.
The fire sprinkler plans will be submitted separately by the fire sprinkler sub -contractor.
Pennzoil Place
,00 Nlilam Streec
Suife :goo
Houston Texas -7 , o o z
Tel: 77 i. 228. 8050
Fax: 713. 129. 9343.
Gensler
Need fire extinguisher size and location to comply with the City of College Station Fire
Marshall's Office.
Per the 2003 IBC, Section 906, Portable fire extinguishers shall be provided in
occupancies and location as required by the International Fire Code.
Per the 2003 International Fire Code, Section 906.1, Portable fire extinguishers shall be
installed in the following locations:
L In all Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies.
Exception: In all Group A, B and E occupancies equipped throughout with quick
response sprinklers, fire extinguishers shall be only in special -hazard areas.
Afire extinguisher has been provided in Catering 1051 per the IFC Section 906.1
(2) Within 30 feet of commercial cooking equipment.
Size is per Specification Section 10520, attached
No other fire extinguishers are required.
Need to submit complete lighting plan for permitted area, please include all emergency
lighting, required exit signs and exit stairway lighting to comply with section 1006 of the
2003 International Building Code.
Exit signs are provided on sheets E4.09 and E4.10.
Refer to Lighting drawings for emergency lighting and exit discharge emergency lighting
to be issued by the General Contractor.
Provide stairway floor number signs throughout both stairways to comply with all of
section 1019.1.7 of the 2003 IBC.
Stairways are part of the base building and not in this scope of work. Refer to the base
building permit for compliance.
Provide information on the door hardware, including any lock and latch devices, and
emergency exit panic hardware on all exterior [exit doors] to comply with sections
1008.1.8.1 and 1008.1.9 of the 2003 IBC.
The door hardware on all exit stairs is part of the base building. Refer to the base
building permit for compliance. We are changing out the lever on the corridor side to
match the rest of the hardware on the floor and are adding an electronic hinge as shown
in Specification Section 08711, which do not alter the compliance with the 2003 I4C nzoil Place
700 Milani Street
Suite 400
Houston Texas 7 7 0 0 ,
Tel: 713. 128. 8050
Fax: 7a i. z29. 9343
Benja:4°tin McCa - Re: Adam Plaza - Permitting _Pa:!ge 1
From: "Marq Synwolt" <msynwolt@madison-construction.com>
To: "Benjamin McCarty" <BMcCarty@cstx.gov>
Date: 1 /25/2006 12:59:38 PM
Subject: Re: Adam Plaza - Permitting
Ben,
In response to your letter to Gensler dated January 24, 2006 we have
confirmed the following with Bouyea and Associates / Lutron:
f-Ci ui' it C-8 all sconces in the Dining Room, sheet LC00-01 B) will be
added to emergency panel DP1-EM'to comply with section 1006.3 of the 2003
International Building`Code.
2. Circuit Referenced C-1 on emergency panel DP1-EM will actually be
Lesignated-as'a sparr_e.
3.jCircui� t CR1 tenth floor corridor 1000A, 1000B_and 1000C (sheet
LC00=10) ,will be added to the emergency panel DP10-EM ,j
We hope that this information sufficiently addresses items 1,2 and 3 of your
January 24, 2006 letter to Gensler.
We have yet to receive clarification of items 4, 5 and 6 (Application #
05-3935 Finish -out of office building garage) that you addressed on your
January 24, 2006 letter to Gensler.
Please let me know if you need further information or documentation.
Thank You,
Marq D. Synwolt
Application #05-3932 (1 st Floor Amenity Wing)
----- Original Message -----
From: "Benjamin McCarty" <BMcCarty@cstx.gov>
To: <msynwolt@madison-construction.com>
Sent: Tuesday, January 24, 2006 4:31 PM
Subject: Adam Plaza
>1 sent the attached letter to architect Bonny McLoud of Gensler
> Benjamin McCarty '00
> Commercial Plans Examiner
> City of College Station
> 1101 Texas Avenue
> College Station, TX 77842
> 979.764.3570
> College Station. Heart of the Research Valley.
Benjamin McCart - Re: Adam Plaza- Permitting Page 2
CC: "Matt Nash" <matt@madison-construction.com>
CITY OF COLLEGE STATION
Planning er Development Services
A -,en•' I/I g��b
V✓i.1� Ss+ I la.,
L' l rv»Y «- p o m.- s n r- -ow 4— be 41&e14 u' +o u 0 �P//o.. s & A—
�nVG �BO✓5 �0✓v9rraw�a�i rLe'7F D�eH l� H F+�r..SGv-0' 7 l GBrS.
�P3 .o
4:' do3.o2
N«'W4 1�o
r- e -C, '.�L- CP O -1 7-- / (f .
f34 N l� Are.— ^
NyT`f �NC �� �L.' f S ��5 ✓+ R IJ O H �IQ m" r S I ✓1 R r� I� firCa
PEQC'w vl/Iwli�✓Rwq f �TYD e .
n S%R • r �...�`.y �%m ey YI a &I" li t r f
ON
1
Y rPC.: C N:.*-5,e- � /° mw�,. �a.�:w•^e. _>
,hPoe Goy ✓es' 50► -fps, 't 4o.1F
�0►r� S�/n h,o
3 clp*q
P.O. BOX 9960 • 1101 TEXAS AVENUE
COLLEGE STATION • TEXAS • 77842
j 979.764.3570
WWW.CSU(.gOV
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
FACSIMILE COVER SHEET
Date: _ o / /zy f o & # of pages including cover: 3
If you did not receive a complete fax please call our office immediately for a new transmittal.
TO: 6011r2y Tea- M a z-ow/
COMPANY: Ue h s /e ,,-
RE: Aa(a H-, J01 R z, -
FAX: -7/3-zZ9-93�l3
COMPANY: City of College Station, Development Services
REMARKS: ❑ Urgent RTFor your review ❑ Replay ASAP FYI
�Lle �e %�Pv wr'�� H ctG�r.�✓e SS Sw,
re q yrrk�.
—rk7a n k
CITY OF COLLEGE STATION
Planning d- Development Services
January 24, 2006
Re: Adam Plaza- 2nd Submittal Plan Review for the listed Tenant Finish -out.
Dear, Bonny Jean McLoud
I have completed the plan review for the above referenced project and have the following
comments. The plan review is based on the 2003 International Codes, the 2002
National Electrical Code and our local amendments. Where appropriate, I have included
the applicable code sections.
Application #: 05-3932 (First Floor Amenity Wing)
1. Provide emergency lighting in Dining Room to comply with section 1006.3 of
the 2003 International Building Code.
2. Verify location of Circuit C1 on sheet LC00-01B for emergency power panel
DP 1-EM.
Application #: 05-3934 (Ninth Floor Core and Tenth Floor Offices)
3. From sheet LC00-10, Circuit CR1.2 of tenth floor corridor 1000A, 1000B,
and 1000C needs to be added to emergency power panel DP 10-EM.
Application #: 05-3935 (Finish -out of office building garage)
4. The plans show that computer and electrical equipment are intended to be
located within the UPS/IDF room, therefore details and size of equipment are
required to complete the plan review and approve for a building permit. If the
room is not for UPS or IDF equipment, then the equipment and UPS/IDF
room labels on the plans must be removed from all plan sheets, and relabeled
to your proposed use.
5. The door swing on the mechanical room needs to be change to swing toward
the direction of egress before a building permit will be issued. The
mechanical room is subject to new plan review and code compliance because
modifications or new equipment not part of the base building are introduced.
6. If the UPS room is to remain for that purpose, then its door(s) swing will also
need to be changed out towards egress. The UPS room may require a second
means of egress depending on the size of the equipment.
The review does not include any civil or zoning issues or NRA requirements of the
Unified Development Ordinance. Please respond to the plan review comments at your
P.O. BOX 9960. 1101 TEXAS AVENUE
COLLEGE STATION • TEXAS • 77842
979.764.3570
www.csb(.gov
convenience. Three sets of plans addressing these issues will be required. Should
you have any questions, contact me at 979-764-3570.
Thank You
Ben McCarty
Plans Examiner
TRANSMISSION VERIFICATION REPORT
DATE DIME
FAX NO./NAME
DURATION
PAGE(S)
RESULT
MODE
TIME
01/23/2006 23:03
NAME
COCS DEVELOPMENT SER
FAX
9797643496
TEL
9797643570
SER.#
BROE2J341073
01/23 23:02
917132299343--170
00: 00: 40
03
OK
STANDARD
ECM
CITY OF COLLEGE STA110N
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77,942
Phone 979.764.3570 / Fax 979.764.3496
FACSIMILE COVER SHEE r
Date: d / "Z� `/ /-- 6 _ #� of Pages uicludling cover; 3
If you did not re=' e a compote fox, please cell Our office tmmecliaf* for a new transmittal.
TO: 600r?y lea H Mc LooW FAX: -213 - .;>- 2-g f 9 3 y 3
COMPANY: &e Y2 s /e --
RE• A: -(a a"-, 1 a Z ^ --
%&ev, me, (f-,ct0-
PROVIDE SEPARATION OF UNFINISHED FLOORS FROM HAVING ACCESS BY
ELEVATOR DOORS, NEITHER BY PROGRAMMING ELEVATOR TO NOT STOP
AT UNFINISHED FLOORS OR PROVIDE PARTITION WALLS AT EACH
ELEVATOR DOOR TO PROHIBIT ACCESS AND EXITING ELEVATORS ONTO
UNFINISHED FLOORS ONLY.
ALL STAIRWAY FLOOR NUMBER SIGNS THROUGHOUT BOTH STAIRWAYS
MUST BE INSTALLED AND APPROVED PRIOR TO ANY TENANT SPACE CO.
1. 1. 0
MADISON
CONSTRUCTION, L.P.
40,
MEMORANDUM
DATE:
January 19, 2006
TO: City of College Station
Attn: Ben McCarty
TELE:
FAX:
979-764-3570
979-764-3496
FROM: Marq D. Synwolt
TELE:
FAX:
979-268-5520
979-268-6022
RE: Adam Plaza — Gensler Responses (Basement &
9th/10th floor)
Pages Sent Including
This Memo
00
MESSAGE:
Ben,
For your use and Information we are forwarding the following items from Gensler and Madison:
lea — letter dated January 12, 2006 from Gensler.
lea — Specification section 10520 — Fire Extingushers.
lea — Sheets A11.59, Al2.65, A02.0B and E5.01 dated.
lea - Dimmer Panel Schedules (BB&A / Lutron dated Jan. 17, 2006)
Please call me at 979-268-5520 or 979-412-1017 if I can be of assistance in any way.
Thank you,
IF THERE IS ANY PROBLEM WITH THIS TRANSMISSION PLEASE CONTACT 979-268-5520.
P. 0. BOX 3787 - BRYAN, TEXAS 77805-3787
T
MADISON
CONSTRUCTION, L.P.
LETTER OF TRANSMITTAL
TO:
City of College Station — Planning and Development Serv.
979-764-3570
979-764-3496 (f)
VIA:
DATE:
01/20/06
PROJECT:
Adam Plaza —
College Station, Texas
ATTN:
Ben McCarty
We Are Sending You
X ATTACHED UNDER SEPARATE COVER VIA
The following items:
I I Shop Drawings I I Specifications I X I Plans I I Product Data I
The following quantities and descriptions are included:
QTY
I DESCRIPTION OF ITEM
3 Copies
Lighting Drawings: L00-01A, L00-01B, L00-02, L00-09, L00-10, LC00-0IA, LC00-0113, LC00-02,
LC00-09 and LC00-10.
2 Copies
Gensler Drawings (Bulletin #3): Al 1-59, Al2-65, A02-OB and E5-01.
3 Copies
Gensler Drawings (Bulletin #2): A02-01A.
2 Sets
Lighting Dimmer Panel Schedules: (BB&A /Lutron dated Jan. 17, 2006)
These are Transmitted as Checked Below:
FTT As requested I I Approved as Submitted T7Resubmit X For your Use
REMARKS: please call me at 268-5520 or 412-1017 if you need an further information.
Thank You, f1l (-�, ,
Marq D. Synwolt"
Project Superintendent
P.O. BOX 3787 • BRYAN, TEXAS 77805-3787 9 TELE 979-268-5520 • FAX 979-268-6022
Gensler
02.3101.000
October 7, 2005
Issue for Permit, Pricing & Construction
SECTION 10520 —FIRE EXTINGUISHERS
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. Portable fire extinguishers.
2. Fire -protection cabinets.
3. Mounting brackets for fire extinguishers.
Adam Plaza
1.2 SUBMITTALS
A. Product Data: For each type of product indicated.
1. Fire Extinguishers: Include rating and classification.
2. Fire -Protection Cabinets: Include door hardware, cabinet type, trim style, panel style,
and details of installation.
B. Samples: For each exposed cabinet. finish.
C. Maintenance data.
1.3 QUALITY ASSURANCE
A. NFPA Compliance: Fabricate and label fire extinguishers to comply with NFPA 10, "Portable
Fire Extinguishers."
B. Fire Extinguishers: Listed and labeled. for type, rating, and classification by an independent
testing agency acceptable to authorities having jurisdiction.
C. Fire -Rated Fire -Protection Cabinets: Listed and labeled to comply with requirements of
ASTM E 814 for fire -resistance rating of walls where they are installed.
1.4 COORDINATION
A. Coordinate size of fire -protection cabinets to ensure that type and capacity of fire extinguishers
indicated are accommodated.
FIRE EXTINGUISHERS 10505 - l
Copyright 2004 Gensler
Q•
Gensler October 7, 2005 Adam Plaza
02.3101.000 Issue for Permit, Pricing & Construction
1.5 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or
replace components of portable fire extinguishers that fail in materials or workmanship within
specified warranty period.
Failures include, but are not limited to, the following:
a. Failure of hydrostatic test according to NFPA 10.
b. Faulty operation of valves or release levers.
2. Warranty Period: Six years from date of Substantial Completion.
PART 2-PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
manufacturers specified.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the
manufacturers specified.
3. Basis -of -Design Product: The design for each product is based on the product named.
Subject to compliance with requirements, provide either the named product or a
comparable product by one of the other manufacturers specified.
2.2 MATERIALS
A. Cold -Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B.
2.3 PORTABLE FIRE EXTINGUISHERS
A. Manufacturers:
1. Amerex Corporation.
2. Ansul Incorporated.
3. Badger Fire Protection.
4. Buckeye Fire Equipment Company.
5. Fire End & Croker Corporation.
6. General Fire Extinguisher Corporation.
7. JL Industries, Inc.
FIRE EXTINGUISHERS
Copyright 2004 Gensler
10505 - 2
0
Gensler October 7, 2005
02.3101.000 Issue for Permit, Pricing & Construction
8. Kidde Fymetics.
9. Larsen's Manufacturing Company.
10. Modern Metal Products; Div. of Technico.
11. Moon American.
12. Potter Roemer; Div. of Smith Industries, Inc.
13. Watrous; Div. of American Specialties, Inc.
Adam Plaza
B. General: Provide fire extinguishers of type, size, and capacity for each fire -protection cabinet
and mounting bracket indicated.
1. Instruction Labels: Include pictorial marking system complying with NFPA 10,
Appendix B.
C. Multipurpose Dry -Chemical Type in Steel Container: UL-rated 4-A:60-B:C, 10-lb (4.5-kg)
nominal capacity, with monoammonium phosphate -based dry chemical in enameled -steel
container.
2.4 FIRE -PROTECTION CABINET
A. Basis -of -Design Product: or a comparable product by one of the following:
B. Manufacturers:
1. Fire End & Croker Corporation.
2. General Accessory Mfg. Co.
3. JL Industries, Inc.
4. Kidde Fymetics.
5. Larsen's Manufacturing Company.
6. Modern Metal Products; Div. of Technico.
7. Moon American.
8. Potter Roemer; Div. of Smith Industries, Inc.
9. Watrous; Div. of American Specialties, Inc.
C. Cabinet Type: Suitable for fire extinguisher.
D. Recessed Cabinet: Cabinet box recessed in walls of sufficient depth to suit style of trim
indicated.
1. Trimless with Plaster Stop: Surface of surrounding wall finishes flush with exterior
finished surface of cabinet frame and door, without overlapping trim attached to cabinet.
Provide recessed flange, of same material as box, attached to box to act as plaster stop.
E. Door Material: Steel sheet.
F. Door Style: Flush opaque panel, frameless, with no exposed hinges.
FIRE EXTINGUISHERS
Copyright 2004 Gensler
10505 - 3
Gensler October 7, 2005
02.310L000 Issue for Permit, Pricing & Construction
Adam Plaza
G. Door Hardware: Manufacturer's standard door -operating hardware of proper type for cabinet
type, trim style, and door material and style indicated.
1. Provide projecting door pull and friction latch.
2. Provide concealed hinge permitting door to open 180 degrees.
H. Accessories:
1. Mounting Bracket: Manufacturer's standard steel, designed to secure fire extinguisher to
fire -protection cabinet, with plated or baked -enamel finish.
2. Door Lock: Cam lock that allows door to be opened during emergency by pulling
sharply on door handle.
3. Identification: Lettering complying with authorities having jurisdiction for letter style,
size, spacing, and location. Locate as indicated by Architect.
a. Identify fire extinguisher in fire -protection cabinet with the words "FIRE
EXTINGUISHER."
1) Location: Applied to cabinet door.
2) Application Process: Silk-screened.
3) Lettering Color: Black.
4) Orientation: Horizontal.
I. Finishes:
1. Manufacturer's standard baked -enamel paint for the following:
a. Exterior of cabinet door, except for those surfaces indicated to receive another
finish. Color to match adjacent portion.
b. Interior of cabinet and door.
2. Steel: Factory primed with manufacturer's standard, lead- and chromate -free, universal
primer, for field painting.
2.5 MOUNTING BRACKETS
Delete this Article if mounting brackets separate from fire -protection cabinets are not required.
A. Manufacturers:
1. Amerex Corporation.
2. Ansul Incorporated.
3. Badger Fire Protection.
4. Buckeye Fire Equipment Company.
5. Fire End & Croker Corporation.
6. General Fire Extinguisher Corporation.
7. JL Industries, Inc.
FIRE EXTINGUISHERS 10505 -4
Copyright 2004 Gensler
Gensler October 7, 2005
02.3101.000 Issue for Permit, Pricing & Construction
8. Larsen's Manufacturing Company.
9. Potter Roemer; Div. of Smith Industries, Inc.
Adam Plaza
B. Mounting Brackets: Manufacturer's standard galvanized steel, designed to secure fire
extinguisher to wall or structure, of sizes required for types and capacities of fire extinguishers
indicated, with plated or baked -enamel finish.
1. Color: Black.
C. Identification: Lettering complying with authorities having jurisdiction for letter style, size,
spacing, and location. Locate as indicated by Architect.
1. Identify bracket -mounted fire extinguishers with the words "FIRE EXTINGUISHER" in
red letter decals applied to mounting surface.
a. Orientation: Horizontal
2.6 FABRICATION
A. Fire -Protection Cabinets: Provide manufacturer's standard box (tub), with trim, frame, door,
and hardware to suit cabinet type, trim style, and door style indicated. Weld joints and grind
smooth.
1. Construct fire -rated cabinets with double walls fabricated from 0.0428411ch- (1.1-mrn-)
thick, cold -rolled steel sheet lined with minimum 5/8-inch- (16-nrm-) thick, fire -barrier
material. Provide factory -drilled mounting holes.
B. Cabinet Doors: Fabricate doors according to manufacturer's standards, from materials indicated
and coordinated with cabinet types and trim styles selected.
1. Fabricate door frames with tubular stiles and rails and hollow -metal design, minimum
1 /2 inch (1 3 mm) thick.
2. Miter and weld perimeter door frames.
C. Cabinet Trim: Fabricate cabinet trim in one piece with corners mitered, welded, and ground
smooth.
PART 3 - EXECUTION
3:1 INSTALLATION
A. Examine walls and partitions for suitable framing depth and blocking where recessed cabinets
will be installed.
FIRE EXTINGUISHERS 10505 - 5
Copyright 2004 Gensler
Gensler October 7, 2005 Adam Plaza
02.3101.000 Issue for Permit, Pricing & Construction
B. Examine fire extinguishers for proper charging and tagging. Remove and replace damaged,
defective, or undercharged units.
C. Prepare recesses for recessed fire -protection cabinets as required by type and size of cabinet and
trim style.
D. Install fire -protection specialties in locations and at mounting heights indicated or, if not
indicated, at heights acceptable to authorities having jurisdiction.
E. Fire -Protection Cabinets: Fasten fire -protection cabinets to structure, square and plumb.
1. Unless otherwise indicated, provide recessed fire -protection cabinets. If wall thickness is
not adequate for recessed cabinets, notify architect.
2. Provide inside latch and lock for break -glass panels.
3. Fasten mounting brackets to inside surface of fire -protection cabinets, square and plumb.
F. Mounting Brackets: Fasten mounting brackets to surfaces, square and plumb, at locations
indicated.
G. Identification: Apply decals at locations indicated.
H. Adjust fire -protection cabinet doors to operate easily without binding. Verify that integral
locking devices operate properly.
I. Replace fire -protection cabinets that have been damaged or have deteriorated beyond successful
repair.
END OF SECTION 10520
FIRE EXTINGUISHERS
Copyright 2004 Gensler
10505 - 6
01/24/2006 12:46 FAX 9792686022
■
�■
I"
M"IsON
CONSTRUCTION, L.P.
MADISON CONSTRUCTION
1@ 0 0 1 / 0 0 2
MEMORANDUM
DATE:
January 24, 2006
TO: City of College Station
Attn: Ben McCarty
TELE:
FAX:
979-764-3570
979-764-3496
FROM: Marq D. Synwolt
TELE:
FAX:
979-268-5520
979-268-6022
RE: Adam Plaza — Elevator "Lockout" for Unoccupied
Floors.
Pages Sent Including
This Memo
02
MESSAGE:
Ben,
As we discussed, the elevators can be programmed so they will not open to an unoccupied floor
(re: attached transmittal sheet from Schindler Elevator Corporation dated 1/23/06). We will
coordinate with Lyda Swinerton Builders and Schindler Elevator Corporation to insure the
appropriate programming takes place.
Please call me at 979-268-5520 or 979-412-1017 if you need further information.
Thank you,
CC. Jody Quimby — AC
Mike Jones — MC
Corby Rodgers — MC
IF THERE IS ANY PROBLEM WITH THIS TRANSMISSION PLEASE CONTACT 979-268-6520.
P. 0. BOX 3787 - BRYAN, TEXAS 77805-3787
O1/24/2006 12:46 FAX 9792686022 MADISON CONSTRUCTION fM 002/002
SCHINDLER ELEVATOR CORPORATION
FACSIMILE TRANSMITTAL SHRRT
t'O: k�ROM:
Matk Jew Burke
COMPANY: DAM O
Madison Canstxwadon 1/23/2006
PAX NUhQHP, TOTAL NO. OF PA rUS INGLUI)LNG COVPR!
979-269-6022
P140NU NIJNMHR; SANDER'S REFRFt iNCU NUMBER:
979-26&SMO
RIP., PROJECP:
Adam Plaza
0 URGENT R REVIEW C3 PLkSASE COJKMXNT 0 PLEASE REPLY 0 PLEASE PRCYCLU
NGTWCOMMANTB,
Kuk-
Per gut dlscusdon, the elevator at Adorn Plus can be prog mmmed to lock out un
oocapled &mm a4 diftcteeL
If you brave any gtteWene please feel free to contact me.
Thank You- Have a Nice Days
t201 WRST LOOP NORTH, SUITIS 190
HOUSTON, TX 77055
jEtiAN-RURKi;@U8,8C14INDLI:R.COM
71g-670.2307-DIRECT LINE
71 s-dD2,007s-PAX
Igo
C�®i1p�0
965Z 'ON Wd :E 90OZ 'E 'uEr
ion :
1st Floor Electrical Room
Customer Panel : i
DPI-EM /
1
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(WNA)
Max Load
(WNA)
BRKR Size"
Phase
Eight Poles
Incandescent
1920
1920
20A-1P
A
Fluor. Downlights
Fluor. Non -Dim
900
1920
20A-1 P
B
Downlights 2nd Floor
Incandescent
9001
1920
20A-1P
C
Wallwashers
Incandescent
1400
1920
20A-1 P
A
Downlights
10A CHOKE
Incandescent
500
960
10A-1P
B
Entry Downlights
Incandescent
300
1920
20A-1P
C
Sconces
Incandescent
1600
1920
20A-1P
A
Sconces
Incandescent
1600
192020A-1P
B
2nd Floor Downlights
Switched
600
1920
20A-1P
C
Cove
Fluor. 3Wire
1200
1920
20A-1P
A
Incandescent
0
1920
20A-1P
B
Incandescent
0
1920
20A-1 P
C
10920
(7,
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
1Pole branch breaker rated at 10,000AIC for each of the 12 dimming circuits.
Max Input feed = 80A CGP199 Panel contains 10A chokes
Phase A
6120.00
Project Name
First American Plaza
Phase B
3000.00
Page Number
1 L4
Phase C
1800.00
Project Location
Bryan, TX
,,+, ����0�®
GP Panel Load Schedule
Job Number
88347
Designed By
TBW
Date IJanuary
17, 2006
CGP24-1204ML-10120-CGP199 N/E
Panel Add:
Location :
10th Floor Electrical Room
Customer Panel :
DP10=EM l
rea/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(WNA)
Max Load
(WNA)
BRKR Size
Phase
Mr. Adam' Office 1072 —�
Al
1
1
Desk Accent
Incandescent
375
1920
2OA-1P
A
Mr. Adam' Office 1072 ti�
A6
6
2
Sconces
Incandescent
400
1920
20A-1 P
B
Mr. Atkinson's Office 1060
AA-1
1
3
Desk Accent
Incandescent
750
1920
20A-1 P
C
Executive Waiting 1067 .�!
EXW3
3
4
Downlights
10A-CHOKE
Incandescent
300
960
10A-1P
A
Executive Conference 1064 -�
EXC6
6
5
Sconces
Incandescent
400
1920
20A-1P
B
Dining 1054
D2
2
6
Sconces
Incandescent
600
1920
20A-1P
C
Spare
BB1
7
Spare
Incandescent
0
192020A-1P
A
Spare
BA1
8
Spare
Incandescent
0
1920
20A-1P
B
Vkinson Bathrm 1063 ,�•
AABR2
2
9
Sconces
Incandescent
400
1920
20A-1 P
C
Cinema Room 1079 -1%
Cf1
1
10
Art Accents
Incandescent
1700
1920
20A-1P
A
Cinema Room 1079 -:�Ib
Cl2.3
2
11
Cove
10A-CHOKE
Incandescent
800
960
10A-1P
B
Boardroom 1042
BR3
3
12
Sconces
Incandescent
1200
1920
20A-1P
C
Prefunction 1043 /!
PF1
1
13
Sconces
Incandescent
800
1920
20A-1 P
A
Coffee Bar 1007
COF1
1
14
Coffee Pendant
Incandescent
200
1920
20A-1P
B
Corridor 10007 c / j
.
CR1.1
1
15
Art Accents
Incandescent
1200
1920
20A-1 P
C
Corridor 1000 ��
CR3
3
16
Downlights
Incandescent
200
1920
20A-1P
A
Reception 10th Floor
R3
3
17
Lamps @ Reception
Incandescent
200
1920
20A-1P
B
Reception 10th Floor -j
R5
5
18
Walfwashers
Incandescent
1080
192020A-1P
C
Reception 9th Floor ---3,
R10
10
19
Sconces 9th floor
Incandescent
1600
1920
20A-1P
A
aiting Room 10th Floor --vw
WR3.1
3
20
Downlights
10A-CHOKE
Incandescent
600
960
10A-1P
B
aiting Room 10th Floor y
WR3.2
3
21
Downlights
10A-CHOKE
Incandescent
600
960
10A-1P
C
Mr. Adam' Bathrm 1066,68-69 JV
ABR1
1
22
Downlights
Incandescent
100
1920
20A-1P
A
Shared Conference 1024 —V
SC4
4
23
Waffwashers
Incandescent
1400
1920
20A-1P
B
SPARE
24
Incandescent
0
1920
20A-1P
C
14905
'Suggested N/E circuits, ' , e
subject to change. 4�1 M4►
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
1Pole branch breaker rated at 10,000AIC for each of the 24 dimming circuits.
Max input feed = 175A CGP199 Panel contains 10A chokes
Phase A
5075.00
Project Name
First American Plaza
Phase B
4000.00
Page Number
101
Phase C
5830.00
Project Location
Bryan, TX
III
IIf LTTRON®
GP Panel Load Schedule
Job Number
88347
Designed By
Tsw
Date JJanuary
17, 2006
CGP20-1204ML-10/20-CGP199
Panel Add:
Location :
1st Floor Electrical Room
Customer Panel :
DP1-1
rea/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(WNA)
Max Load
(WNA)
BRKR Size
Phase
Cafeteria 1st Floor
C2.1
2
1
Center Cove
Fluor. 3Wire
1200
1920
20A-1P
A
Cafeteria 1st Floor
C2.2
2
2
Center Cove
Fluor. 3Wire
1200
1920
20A-1P
B
Cafeteria 1st Floor
C3
3
3
New Center Cove
Neon/Cold Cathode
5001
1920
20A-1 P
C
Cafeteria 1st Floor
C4.1
4
4
Sconces
Incandescent
1200
1920
20A-1P
A
Cafeteria 1st Floor
C4.2
4
5
Sconces
Incandescent
1200
1920
20A-1P
B
Cafeteria 1st Floor
C5
5
6
FL Cove @ Beverage Cntr
Fluor. Non -Dim
250
1920
20A-1P
C
Spare
C5.2
7
Incandescent
0
1920
20A-1 P
A
Spare
C6
8
Incandescent
0
1920
20A-1P
B
e
C6.2
9
Incandescent
0
1920
20A-1P
C
Cafeteria 1st Floor
C7.1
7
10
Pendants Table
Incandescent
1200
1920
20A-1P
A
Cafeteria 1st Floor
C7.2
7
11
Pendants Table
Incandescent
.1200
1920
20A-1P
B
Cafeteria 1st Floor
C8
8
12
Large Sconces
Incandescent
1800
1920
20A-1P
C
Cafeteria 1st Floor
C9.1
9
13
General Downlights
10A-CHOKE
Incandescent
600
960
10A-1P
A
Cafeteria 1st Floor
C9.2
9
14
General Downlights
10A-CHOKE
Incandescent
800
960
10A-1P
B
Cafeteria 1st Floor
C9.3
9
15
General Downlights
10A-CHOKE
Incandescent
600
960
10A-1P
C
Cafeteria 1st Floor
C9.4
9
16
General Downlights
10A-CHOKE
Incandescent
500
960
10A-1P
A
Cafeteria 1st Floor
C11
11
17
FL 1x4 Serving
Switched
500
1920
20A-1P
B
Expandable
18
Incandescent
0
1920
20A-1P
C
Expandable
19
Incandescent
0
1920
20A-1 P
A
Expandable
20
Incandescent
0
1920
20A-1P
B
12750
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
1Pole branch breaker rated at 10,000AIC for each of the 20 dimming circuits.
Max input feed = 150A. CGP199 Panel contains 10A chokes.
Phase A
4700.00
Project Name
First American Plaza
Phase B
4900.00
Page Number
1 L1
Phase C
3150.00
Project Location
Bryan, TX
�j�P LUTI�ON®8347
GP Panel Load Schedule
Job Number
Designed By
TBW
Date
IJanuary 17, 2006
CGP24-1204ML-10/20-CGP199
Panel Add:
Location :
1st Floor Electrical Room
Customer Panel :
:DPi-2
rea/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(WNA)
Max Load
(W/VA)
BRKR Size
Phase
Bank Lobby 1st Floor
B4.1
4
1
Sconces
Incandescent
1500
1920
20A-1P
A
Bank Lobby 1st Floor
B4.2
4
2
Sconces
Incandescent
600
1920
20A-1P
B
Bank Lobby 1st Floor
B5
5
3
Counter
Incandescent
7501
1920
20A-1P
C
Bank Lobby 1st Floor
B6
6
4
Counter under cabinet
10A-CHOKE
Incandescent
9001
960
10A-1P
A
Bank Lobby 1st Floor
B7
7
5
Floor Plugs
Incandescent
800
1920
20A-1P
B
Spare
B8
6
Incandescent
0
1920
20A-1P
C
Bank Lobby 1st Floor
B10
10
7
Signage Wallwashers
Incandescent
500
1920
20A-1P
A
Bank Lobby 1st Floor
B11
11
8
Pendant
Incandescent
600
1920
20A-1P
B
Lobby 1st Floor
B12
12
9
Pendant
Incandescent
400
1920
20A-1P
C
Bank Lobby 1st Floor
B13
13
10
Waiting Wallwashers
Incandescent
540
1920
20A-1P
A
Bank Lobby 1st Floor
B15
15
11
Accents
Incandescent
375
1920
20A-1P
B
Bank Lobby 1st Floor
B16
16
12
Downlights
10A-CHOKE
Incandescent
600
960
10A-1P
C
Entry/Lobby 1st Floor
E1
1
13
Entry Wallwash
Incandescent
400
1920
20A-1P
A
Entry/Lobby 1st Floor
E3
3
14
Chandelier
Incandescent
1200
1920
20A-1P
B
Entry/Lobby 1st Floor
E4
4
15
Neon Cove
Neon/Cold Cathode
800
1920
20A-1P
C
Entry/Lobby 1st Floor
E6
6
16
Small Cove
Neon/Cold Cathode
1000
1920
20A-1P
A
Entry/Lobby 1st Floor
E7
7
17
Downlights
Incandescent
300
1920
20A-1P
B
Entry/Lobby 1st Floor
E13.1
13
18
Sconces
Incandescent
1400
1920
20A-1P
C
Entry/Lobby 1st Floor
E13.2
13
19
Sconces
Incandescent
1400
1920
20A-1P
A
Entry/Lobby 1st Floor
E13.3
13
20
Sconces
Incandescent
1400
1920
20A-1P
B
Entry/Lobby 1st Floor
E15
15
21
Mezzanine Cove
Neon/Cold Cathode
800
1920
20A-1P
C
Expandable
22
Incandescent
0
192020A-1P
A
Expandable
23
Incandescent
0
1920
20A-1 P
B
24
Incandescent
0
192020A-1P
C
VExandable
16265
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
1Pole branch breaker rated at 10,000AIC for each of the 24 dimming circuits.
Max input feed = 175A. CGP199 Panel contains 10A chokes
Phase A
6240.00
Project Name
First American Plaza
Phase B
5275.00
Page Number
1 L2
Phase C
4750.00
Project Location
Bryan, TX
LUTRON®
GP Panel Load Schedule
Job Number
88347
Designed By
TBW
Date JJanuary
17, 2006
GP16-1204ML-20
Panel add:
Location :
2nd Floor Electrical Room
Customer Panel :
DP2-1
rea/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(WNA)
Max Load
(WNA)
BRKR Size
Phase
Bank Lobby 2nd Floor
81.1
1
1
Cove 2nd Floor
Neon/Cold Cathode
400
1920
20A-1 P
A
Bank Lobby 2nd Floor
B1.2
1
2
Cove 2nd Floor
Neon/Cold Cathode
400
1920
20A-lP
B
Bank Lobby 2nd Floor
61.3
1
3
Cove 2nd Floor
Neon/Cold Cathode
400
1920
20A-1 P
C
Bank Lobby 2nd Floor
131.4
1
4
Cove 2nd Floor
Neon/Cold Cathode
400
1920
20A-lP
A
Bank Lobby 2nd Floor
B1.5
1
5
Cove 2nd Floor
Neon/Cold Cathode
400
1920
20A-1P
B
Bank Lobby 2nd Floor
B1.6
1
6
Cove 2nd Floor
Neon/Cold Cathode
400
1920
20A-1 P
C
Bank Lobby 2nd Floor
B2.2
2
7
Downlights 2nd Floor
Switched
900
1920
20A-lP
A
Bank Lobby 2nd Floor
B3.1
3
8
Chandelier Large
Incandescent
1920
1920
20A-1P
B
Lobby 2nd Floor
B3.2
3
9
Chandelier Small
Incandescent
1200
1920
20A-1 P
C
ntry Lobby 2nd Floor
E8
8
10
2nd Floor Cove Large
Neon/Cold Cathode
1000
1920
20A-1 P
A
Entry Lobby 2nd Floor
E9
9
11
2nd Floor Cove Small
Neon/Cold Cathode
600
1920
20A-1 P
B
Entry Lobby 2nd Floor
E11
11
12
Chandelier Large
Incandescent
1200
1920
20A-1 P
C
Entry Lobby 2nd Floor
E12
12
13
Chandelier Small
Incandescent
800
1920
20A-1P
A
Entry Lobby 2nd Floor
E14
14
14
Downlights 2nd Floor
Switched
300
1920
20A-1 P
B
SPARE
15
Incandescent
0
1920
20A-1P
C
SPARE
16
Incandescent
0
1920
20A-1 P
A
0
0
0
0
10320
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
Vole branch breaker rated at 10,000AIC for each of the 16 dimming circuits.
Max input feed = 125A
Phase A
3500.00
Project Name
First American Plaza
phase B
3620.00
Page Number
1 L3
Phase C
3200.00
Project Location
Bryan, TX
-,,,,� LUTF�aN®
GP Panel Load Schedule
Job Number
88347
Designed By
TBW
Date
1January 17, 2006
CGP24-1204ML-10/20-CGP199
Panel Add:
Location :
10th Floor Electrical Room
Customer Panel :
DP10-1
rea/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(WNA)
Max Load
(WNA)
BRKR Size
Phase
Mr. Adam' Office 1072
A2
2
1
Table Accent
Incandescent
375
1920
20A-1 P
A
Mr. Adam' Office 1072
A3
3
2
Art Accent
Incandescent
750
1920
20A-1 P
B
Mr. Adam' Office 1072
A4
4
3
Art Accent
Incandescent
11501
1920
20A-1 P
C
Mr. Adam' Office 1072
A5.1
5
4
Bookcase
10A CHOKE
Incandescent
600
960
10A-1 P
A
Mr. Adam' Office 1072
A5.2
5
5
Bookcase
10A CHOKE
Incandescent
600
960
10A-1 P
B
Mr. Adam' Office 1072
A5.3
5
6
Bookcase
10A CHOKE
Incandescent
800
960
10A-1P
C
Spare
A5.4
7
10ACHOKE
Incandescent
0
96010A-1P
A
Mr. Adam' Office 1072
A5.5
5
8
Bookcase
10A CHOKE
Incandescent
800
960
10A-1 P
B
I' ,dam' Office 1072
A5.6
5
9
Bookcase
10A CHOKE
Incandescent
600
960
10A-1 P
C
Mr. Adam' Office 1072
A5.7
5
10
Bookcase
10A CHOKE
Incandescent
600
960
10A-1 P
A
Mr. Adam' Office 1072
A7
7
11
Receptacle
Incandescent
200
1920
20A-1P
B
Mr. Adam' Office 1072
A8
8
12
Receptacle
Incandescent
200
1920
20A-lP
C
Mr. Adam' Office 1072
A9
9
13
Cove
10A CHOKE
Neon/Cold Cathode
600
960
10A-1P
A
Mr. Adam' Office 1072
A10
10
14
Cove
10A CHOKE
Neon/Cold Cathode
600
960
10A-1 P
B
Mr. Adam' Office 1072
A11
11
15
Picture Light
Incandescent
300
1920
20A-1P
C
Mr. Atkinson's Office 1060
AA2
2
16
Table Accent
Incandescent
300
1920
20A-1P
A
Mr. Atkinson's Office 1060
AA3
3
17
Downlight
10A CHOKE
Incandescent
150
960
10A-1 P
B
Mr. Atkinson's Office 1060
AA4
4
18
Par Cove
Incandescent
300
1920
20A-1 P
C
Mr. Atkinson's Office 1060
AA5.1
5
19
Under Cabinet
10A CHOKE
Incandescent
800
960
10A-1P
A
Mr. Atkinson's Office 1060
AA6
6
20
Pendant
Incandescent
300
1920
20A-1 P
B
Mr. Atkinson's Office 1060
AA5.2
5
21
Under Cabinet
10A CHOKE
Incandescent
800
960
10A-1 P
C
Mr. Atkinson's Office 1060
AA7
7
22
Art Accent
Incandescent
375
1920
20A-1 P
A
Mr. Atkinson's Office 1061
AA8
8
23
Picture Light
Incandescent
600
1920
20A-lP
B
SPARE
24
Incandescent i01
1920
20A-1P
C
11800
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
1Pole branch breaker rated at 10,000AIC for each of the 24 dimming circuits.
Max input feed = 175A. CGP199 Panel contains 10A chokes.
Phase A
3650.00
Project Name
First American Plaza
Phase B
4000.00
Page Number
1 L5
Phase C
4150.00
Project Location
Bryan, TX
t1�� LVT -- ON®
GP Panel Load Schedule
Job Number
88347
gned By
Designed
T BW
BW
Date
January 17, 2006
CGP24-1204ML-10/20-CGP199
Panel Add:
Location :
10th Floor Electrical Room
Customer Panel :
DP10-2
rea/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(WNA)
Max Load
(WNA)
BRKR Size
Phase
Executive Waiting 1067
EXW1
1
1
Accent
Incandescent
600
1920
20A-1P
A
Executive Waiting 1067
EXW2
2
2
Art
Incandescent
600
1920
20A-1P
B
Executive Waiting 1067
EXW4
4
3
Reception
Incandescent
2001
1920
20A-1P
C
Executive Conference 1064
EXC1
1
4
Wallwash
Incandescent
500
1920
20A-1P
A
Executive Conference 1064
EXC2
2
5
Wallwash
Incandescent
500
1920
20A-1P
B
Executive Conference 1064
EXC3
3
6
Table Accent
Incandescent
800
1920
20A-1P
C
Executive Conference 1064
EXC4
4
7
Pendant
Incandescent
300
1920
20A-1P
A
Executive Conference 1064
EXC5
5
8
Art
Incandescent
300
1920
20A-1 P
B
;utive Conference 1064
EXC7
7
9
Cove
Neon/Cold Cathode
500j
1920
20A-1P
C
Dining 1054
D1
1
10
Pendant
Incandescent
1920
1920
20A-1P
A
SPARE
D2em
2
11
Incandescent
0
1920
20A-1P
B
Dining 1054
D3.1
3
12
Wallwash
Incandescent
1200
1920
20A-1P
C
Dining 1054
D3.2
3
13
Wallwash
Incandescent
900
1920
20A-1P
A
Dining 1054
D4
4
14
Table Accent
Incandescent
600
1920
20A-1 P
B
Dining 1054
D5
5
15
Receptacles
Incandescent
800
1920
20A-1P
C
Dining 1054
D6.1
6
16
General Downlights
10A CHOKE
Incandescent
600
960
10A-1P
A
Dining 1054
D6.2
7
17
General Downlights
10A CHOKE
Incandescent
450
960
10A-1P
B
Bar 1065
BB2
2
18
Lower Cabinet
10A CHOKE
Incandescent
480
960
10A-1 P
C
Bar 1045
BA2
2
19
Lower Cabinet
10A CHOKE
Incandescent
750
960
10A-1P
A
Mr. Atkinson's Bthrm 1063
AABR1
1
20
Downlight
Incandescent
100
1920
20A-1P
B
Bar 1065
B61
21
Upper Cabinet
10A CHOKE
Incandescent
560
960
10A-1 P
C
Bar 1045
BA1
22
Upper Cabinet
10A CHOKE
Incandescent
350
960
10A-1P
A
Mr. Atkinson's Bthrm 1063
AABR3
23
Pendant
Incandescent
300
1920
20A-1P
B
SPARE
24
Incandescent
0
1920
20A-1 P
C
13310
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
1Pole branch breaker rated at 10,000AIC for each of the 24 dimming circuits.
Max input feed = 175A CGP199 Panel contains 10A filter chokes
Phase A
5920.00
Project Name
First American Plaza
Phase B
2850.00
Page Number
1 L6
Phase C
4540.00
Project Location
Bryan, TX
:V.0 L"TRON.
GP Panel Load Schedule
Job Number
88347
Designed By
TBW TBW
Date
IJanuary 17, 2006
CGP20-1204ML-10/20-CGP199
Panel Add:
Location :
10th Floor Electrical Room
Customer Panel :
DP10-3
Area/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(WNA)
Max Load
(WNA)
BRKR Size
Phase
Cinema Room 1079 10th FL
Cl2.1
2
1
Cove
10A CHOKE
Incandescent
800
960
10A-1P
A
Cinema Room 1079 10th FL
Cl2.2
2
2
Cove
10A CHOKE
Incandescent
800
960
10A-1P
B
Cinema Room 1079 10th FL
Cl2.4
2
3
Cove
10A CHOKE
Incandescent
8001
960
10A-1 P
C
Cinema Room 1079 10th FL
Cl2.5
2
4
Cove
10A CHOKE
Incandescent
800
960
10A-1P
A
Cinema Room 1079 10th FL
Cl2.6
2
5
Cove
10A CHOKE
Incandescent
800
960
10A-1P
B
Cinema Room 1079 10th FL
Cl2.7
2
6
Cove
10A CHOKE
Incandescent
800
960
10A-1P
C
Cinema Room 1079 10th FL
Cl2.8
2
7
Cove
10A CHOKE
Incandescent
800
960
10A-1P
A
Cinema Room 1079 10th FL
C12.9
2
8
Cove
10ACHOKE
Incandescent
800
960
10A-1P
B
i' na Room 1079 10th FL
C12.10
2
9
Cove
10A CHOKE
Incandescent
800
960
10A-1 P
C
Cinema Room 1079 10th FL
Cl2.11
2
10
Cove
10A CHOKE
Incandescent
800
960
10A-1P
A
Cinema Room 1079 10th FL
Cl2.12
2
11
Cove
10A CHOKE
Incandescent
800
960
10A-1P
B
Cinema Room 1079 10th FL
Cl2.13
2
12
Cove
10A CHOKE
Incandescent
800
960
10A-1P
C
Cinema Room 1079 10th FL
C12.14
2
13
Cove
10A CHOKE
Neon/Cold Cathode
800
960
10A-1 P
A
Cinema Room 1079 10th FL
Cl2.15
2
14
Cove
10A CHOKE
Neon/Cold Cathode
800
960
10A-1 P
B
Cinema Room 1079 10th FL
Cl2.16
2
15
Cove
10A CHOKE
Incandescent
800
960
10A-1P
C
Cinema Room 1079 10th FL
Cl2.17
2
16
Cove
10A CHOKE
Incandescent
800
960
10A-1P
A
Cinema Room 1079 10th FL
Cl2.18
2
17
Cove
10A CHOKE
Incandescent
800
960
10A-1P
B
Cinema Room 1079 10th FL
CI13
3
18
Par Cove
Incandescent
900
1920
20A-1 P
C
SPARE
19
Incandescent
0
1920
20A-1P
A
SPARE
20
Incandescent
0
1920
20A-1P
B
1
14500
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
1Pole branch breaker rated at 10,000AIC for each of the 20 dimming circuits.
Max input feed = 150A CGP199 Panel contains 10A chokes
Phase A
0
Project Name
First American Plaza
Phase B
0
Page Number
1 L7
Phase C
0
Project Location
Bryan, TX
50
��+�� LVTRQN®
GP Panel Load Schedule
Job
88347
Designed By
Designed By
TBW
TBW
Date
January 17, 2006
GP24-1204ML-20
Panel Add:
Location :
10th Floor Electrical Room
Customer Panel :
DP10-4
rea/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(WNA)
Max Load
(WNA)
BRKR Size
Phase
Boardroom 1042
BR1
1
1
Pendant
Incandescent
1920
1920
20A-1P
A
Boardroom 1042
BR2
2
2
Table Accent
Incandescent
1920
1920
20A-1 P
B
Boardroom 1042
BR4
4
3
Art Accents
Incandescent
300
192020A-1P
C
Boardroom 1042
BR5
5
4
Cove
Neon/Cold Cathode
575
1920
20A-1 P
A
Prefunction 1043
PF2
2
5
Door Downs
Incandescent
600
1920
20A-1P
B
Prefunction 1043
PF3
3
6
Accent
Incandescent
475
1920
20A-1P
C
Prefunction 1043
PF4
4
7
Table
Incandescent
780
1920
20A-1P
A
Prefunction 1043
PF5
5
8
Art Accents
Incandescent
960
1920
20A-1 P
B
dor 1000 10th FL
CR1.2
1
9
Art Accents
Incandescent
1800
1920
20A-1 P
C
Corridor 1000 10th FL
CR2.1
2
10
Cove
Neon/Cold Cathode
800
1920
20A-1 P
A
Corridor 1000 10th FL
CR2.2
2
11
Cove
Neon/Cold Cathode
800
1920
20A-1 P
B
Corridor 1000 10th FL
CR2.3
2
12
Cove
Neon/Cold Cathode
800
1920
20A-1 P
C
Corridor 1000 10th FL
CR2.4
2
13
Cove
Neon/Cold Cathode
800
1920
20A-1 P
A
Corridor 1000 10th FL
CR2.5
2
14
Cove
Neon/Cold Cathode
800
1920
20A-1 P
B
Corridor 1000 10th FL
CR2.6
2
15
Cove
Neon/Cold Cathode
800
1920
20A-1 P
C
Corridor 1000 10th FL
CR4
4
16
Down Vestibule
Incandescent
100
1920
20A-1P
A
Corridor 1000 10th FL
CR5
5
17
Wallwashers
Incandescent
800
1920
20A-1P
B
Corridor 1000 10th FL
CR6
6
18
Art Accents
Incandescent
400
1920
20A-1 P
C
Corridor 1000 10th FL
CR7
7
19
Sconces
Incandescent
800
1920
20A-1P
A
Corridor 1000 10th FL
CR8
8
20
Art Accents
Incandescent
375
1920
20A-1 P
B
Corridor 1000 10th FL
CR9
8
21
Cove
Neon/Cold Cathode
300
1920
20A-1 P
C
Corridor 1000 10th FL
CR10
2
22
Vestibule Downlights
Fluor. 3Wire
128
1920
20A-1 P
A
Corridor 1000 10th FL
CR11
3
23
Pendant
Incandescent
200
1920
20A-1P
B
SPARE
24
Incandescent
0
1920
20A-1P
C
17233
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
1Pole branch breaker rated at 10,000AIC for each of the 24 dimming circuits.
Max input feed = 175A
Phase A
5903.00
Project Name
First American Plaza
phase B
6455.00
Page Number
1 L8
Phase C
4875.00
Project Location
Bryan, TX
����= LVTRQN®
GP Panel Load Schedule
Job Number
88347
Designed By
TBW
BW
Date
JJanuary 17, 2006
CGP24-1204ML-10/20-CGP199
Panel Add:
Location :
10th Floor Electrical Room
Customer Panel :
DP10-5
Area/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(W/VA)
Max Load
(W/VA)
BRKR Size
Phase
Reception 10th
R1.1
1
1
Large Pendant Over Stairs
Incandescent
1920
1920
20A-1 P
A
Reception 10th
R1.2
1
2
Large Pendant Over Stairs
Incandescent
1920
1920
20A-1P
B
Reception 10th
R1.3
1
3
Large Pendant Over Stairs
Incandescent
19201
1920
20A-1 P
C
Reception 10th
R1.4
1
4
Large Pendant Over Stairs
Incandescent
1920
1920
20A-1P
A
Reception 10th
R2
2
5
Under Counter @ Recptn
Incandescent
600
1920
20A-1 P
B
Reception 10th
R4.1
4
6
Vaulted Ceiling Cove
Fluor. 3Wire
1080
1920
20A-1P
C
Reception 10th
R4.2
4
7
Vaulted Ceiling Cove
Fluor. 3Wire
1080
1920
20A-1P
A
Reception 10th
R6
6
8
Outlets
Incandescent
800
1920
20A-1P
B
ption 9th
R7.1
7
9
Type J Vestibule 10th
10A Choke
Incandescent
9601
960
10A-1P
C
Spare
R7.2
10
Incandescent
0
1920
20A-1P
A
Reception 9th
R8
8
11
Adjustables @ Elevators
Incandescent
300
1920
20A-1P
B
Reception 9th
R9
9
12
Art Accents 9th
Incandescent
1920
1920
20A-1 P
C
Reception 9th
R11
11
13
Elevator Cove 9th 10th
Neon/Cold Cathode
500
1920
20A-1 P
A
Reception 9th
R12.1
12
14
Downlights 9th Floor
10A Choke
Incandescent
750
960
10A-1P
B
Reception 9th
R12.2
12
15
Downlights 9th Floor
10A Choke
Incandescent
750
960
10A-1P
C
Reception 9th
R13
13
16
Sconces 9th Floor
Incandescent
800
1920
20A-1P
A
Reception 9th
R14
14
17
Desk Accents 9th Floor
Incandescent
850
1920
20A-1P
B
Reception 9th
R15
15
18
Cove 9th Floor
10A Choke
Incandescent
400
960
10A-1P
C
Coffee Bar 1007
COF2
2
19
Under/Above Cabinet
Switched
300
1920
20A-1P
A
Coffee Bar 1007
COF3
3
20
Downlights/Wallwash
10A Choke
Incandescent
650j
1920
20A-1P
B
SPARE
21
Incandescent
0
1920
20A-1P
C
SPARE
22
Incandescent
0
1920
20A-1P
A
SPARE
23
Incandescent
0
1920
20A-1P
B
SPARE
24
Incandescent
0
1920
2OA-1P
C
19420
V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
ranch breaker rated at 10,000AIC for each ofthe 24 dimming circuits.
ut feed = 175A CGP199 panel contains 10A filter chokes
Phase A
0
Project Name
First American Plaza
Phase B
0
Page Number
1L9
Phase C
0
Project Location
Bryan, TX
,AI% LUTRON.
�,,,`
II
GP Panel Load Schedule
Job Number
88347
Designed By
TBW
TBW
Date
January 17, 2006
CGP20-1204ML-10/20-CGP199
Panel Add:
Location :
10th Floor Electrical Room
Customer Panel :
DP10-6
rea/Room
Customer
Circuit
Customer
Zone
Lutron
Circuit
Lutron
Zone
Zone/Circuit Description
Interfaces
Load Type
Actual
Load
(W/VA)
Max Load
(WNA)
BRKR Size
Phase
Waiting Room 10th Floor
WR1
1
1
Wallwashers
Incandescent
800
1920
20A-1P
A
Waiting Room 10th Floor
WR2
2
2
Art Accents
Incandescent
600
1920
20A-1 P
B
Waiting Room 10th Floor
WR4.1
4
3
Under Cabinet
10A choke
Incandescent
640
960
10A-1 P
C
Waiting Room 10th Floor
WR5
5
4
Receptacles
Incandescent
800
1920
20A-1P
A
Waiting Room 10th Floor
WR6
6
5
Art Accents
Incandescent
300
1920
20A-1 P
B
Waiting Room 10th Floor
WR4.2
4
6
Under Cabinet
10A choke
Incandescent
640
960
10A-1P
C
Waiting Room 10th Floor
WR4.3
4
7
Under Cabinet
10A choke
Incandescent
640
960
10A-1 P
A
Waiting Room 10th Floor
WR4.4
4
8
Under Cabinet
10A choke
Incandescent
640
960
10A-1 P
B
'iE
5
9
Incandescent
0
1920
20A-1P
C
SPARE
6
10
Incandescent
0
1920
20A-1P
A
Mr. Adam' Bathrm 1066,68-69
ABR2
2
11
Cove
Neon/Cold Cathode
150
1920
20A-1P
B
Mr. Adam' Bathrm 1066,68-69
ABR3
3
12
Art Accents
Incandescent
150
1920
20A-1 P
C
Mr. Adam' Bathrm 1066,68-69
ABR4
4
13
Sconces
Incandescent
800
1920
20A-1P
A
Mr. Adam' Bathrm 1066,68-69
ABR5
5
14
Pendant
Incandescent
300
1920
20A-1P
B
Mr. Adam' Bathrm 1066,68-69
ABR6
6
15
Par Cove
Incandescent
1000
1920
20A-1 P
C
Shared Conference 1024
SC1
16
Incandescent
300
1920
20A-1P
A
Shared Conference 1025
SC2
17
Incandescent
225
1920
20A-1P
B
Shared Conference 1026
SC3
18
Incandescent
200
1920
20A-1P
C
SPARE
19
Incandescent
0
1920
20A-1 P
A
SPARE
20
Incandescent
0
1920
20A-1P
B
8185
120/208V, 3 Phase, 4 Wire Main Lugs Only Dimming Panel containing 1 20A-
1Pole branch breaker rated at 10,000AIC for each of the 20 dimming circuits.
Max input feed = 150A CGP199=Panel contains 10A chokes
Phase A
3340.00
Project Name
First American Plaza
Phase B
2215.00
Page Number
1 L10
Phase C
2630.00
Project Location
Bryan, TX
Vhr' LVTRaN®88347
GP Panel Load Schedule
Job Number
Designed By
ew
TBW
Date
January 17, 2006
Transmittal Gensler
to Attention
City of College Station - Planning & Deve.
Chris Haver 979.764.6254
Address
1101 Texas Avenue South
City
State
zip
College Station
Texas
77840
Protect
Project Number
Flie
Adam Plaza - Application #05-3934
02.3101.000
3c
Subject
Level 10 drinking fountains and door hardware
Prepared by
This Is page
Date
Corey Credeur 713.356.1390
1 of 1
03.13.07
For Your
❑ Approval and selection
® use
®
Record
❑ Review / Comment
❑ Distribution
❑
Information
Action Required ❑ Indicated on Item transmitted
❑ Comment and return to Hensler
®
No action required
❑ Sign and return to this office
❑ See remarks below
❑
Other
Delivered Via
❑ Messenger
❑ Two-0ay Express
❑
Pick-up
❑ Same Day Express
® Mail
®
other. Email
❑ Next Day Express
❑ Hand carried
Remarks
The attached letters are record of our conversation earlier today.
Quantity Description Dated
Letter regarding door hardware 03.13.07
Letter regarding drinking fountains 03.13.07
Transmittal Copies To Enclosures: Delivered Via
If enclosures are not as described,
please advise Gensler immediately.
Jody Quimby / The Adam Corporation Same Email
Mike Jones / Madison Construction Same Email
Pennzoil Place
I:\02.3101.000\documentation\3_regulatory\3c\tt070313_ch.doc 700 Milam Street, Suite 400
Houston Texas 77002
Tel: 713.228.8050
TR_080705 Fax: 713.229.9343
Architecture, Design & Planning Worldwide Gensler
March 13, 2007
Chris Haver
City of College Station
Development Services
1101 Texas Avenue South
P.O. Box 9960
College Station, Texas 77842
RE: Adam Plaza
.Application #05-3934
Dear Mr. Haver,
This letter is to document some changes to the door hardware on the 10`h floor of Adam Plaza
that were verbally approved in February 2007.
The owner would like to put card readers on the three sets of double doors indicated on the
attached drawing. One leaf will be active and have an electric hinge. The other leaf will be
inactive with top and bottom flush bolts to hold the door in a fixed position so the active leaf can
latch into it. To avoid confusion over which door was active or inactive, we agreed that the
inactive leaf would not have a lever.
Sincerely,
Corey Credeur, AIA
Associate
Attachments: Sketch No. 1 — Level 10 Partial Plan
cc: Jody Quimby/The Adam Corporation
Mike Jones/Madison Construction Pennzoil Place
700 Milam Street
Suite 400
Houston Texas 77002
Tel: 7t3. 2 28. 8050
Fax: 713. 229. 9343
�' Ilr�lll lI
�;. ►: : III
`i3
� IIII � , I � � �� �-. ` �C•7� .
-�-, M
>,
/ -
---
911
m
- .,�:�: III
■LE
MR. ADAM
1072
■'II
Architecture, Design 6- Planning Worldwide Gensler
March 13, 2007
Chris Haver
City of College Station
Development Services
1101 Texas Avenue South
P.O. Box 9960
College Station, Texas 77842
RE: Adam Plaza
Application #05-3934
Dear Mr. Haver,
This letter is to document our conversation earlier today regarding drinking fountains on the 10`h
floor of Adam Plaza.
The City of College Station will allow the removal of the public drinking fountains if a water
dispenser is located in the coffee bar for the tenants of this floor.
Sincerely,
Corey Credeur, AIA
Associate
cc: Jody Quimby/The Adam Corporation
Mike Jones/Madison Construction
Pennzoil Place
700 Milam Street
Suite 400
Houston Texas 77002
Tel: 713. 228. 8050
Fax: 713. 229. 9343
BU LDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE:
----------------------------------------------------------------------------
(979)764-3570 FAX: (979)764-3496
Application Number
. . . . . 05-00003934 Date 1/27/06
Property Address
. . . . . . 1 FIRST AMERICAN BLVD
Property ID . . .
. . . . . . 212200-0001-0010
R# . . . . . . .
. . . . . .
Tenant nbr, name
. . . . . . LOBBY & OFFICES
Application type description COMMERCIAL, OFFICES/BANKS/PROFESSION
Subdivision Name
. . . . . .
Property Use . .
. . . . . .
Property Zoning .
. . . . . . GENERAL COMMERCIAL
Application valuation
. . . . 2556694
Owner
Contractor
------------------------
------------------------
MADISON CONSTRUCTION CORP
MICHAEL R JONES
1640 BRIARCREST
BRYAN TX 77802
(979) 268-5520
--- Structure Information
000 000 TENANT FINISHOUT AT ADAM PLAZA
Construction Type
. . . . . FIRE RESISTANT
Occupancy Type .
. . . . . BUSINESS
Other struct info
. . . . . EXTERIOR WALL TYPE BRICK
IMPACT/PRORATA FEES PAID NA
FOUNDATION TYPE SLAB
HEATED AREA 26486.00
INTERIOR WALL TYPE SHEETROCK
SEWER TYPE PUBLIC
TAZ 164.00
----------------------------------------------------------------------------
Permit . . . . .
. BUILDING PERMIT
Additional desc .
. GS
Permit Fee . . .
. 5774.00 Plan Check Fee .00
Issue Date . . .
. 1/27/06 Valuation . . . . 2556694
Expiration Date .
. 7/26/06
Qty Unit Charge Per Extension
BASE FEE 1660.00
2057.00 2.0000 THOU BLDG, VAL 500001 & UP 4114.00
----------------------------------------------------------------------------
Special Notes and Comments
NOTE FROM WATER DEPT--REDUCED PRESSURE ASSEMBLY REQUIRED FOR
CAR WASH, POSTMIX CARBONATER, AND HEATING/AC WITH DIRECT
CONNECTION TO WATER SUPPLY AND LAWN IRRIGATION SYSTEMS.
ALL DEVICES MUST BE TESTED UPON INSTALLATION BY CERTIFIED
TESTER REGISTERED WITH THE CITY OF COLLEGE STATION PUBLIC
UTILITIES DEPT. LAWN IRRIGATION MAY USE A PRESSURE VACCUM
------------------ ----- ---------------------------- ---------------
BUILDING DEPT RE ESENTATIVE: i�---
APPLICANT: / �a
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
Page 2
Application Number . . . . . 05-00003934 Date 1/27/06
----------------------------------------------------------------------------
Special Notes and Comments
BREAKER INSTALLED PER AWWA STANDARDS AND CITY'S ORD #2394.
ALL DEVICES MUST BE INSTALLED PER AWWA AND CITY'S ORD#2394
PROVIDE COMBUSTION AIR FOR GAS FIRED APPLIANCES PER
CHAPTER 17, 2003 INTERNATIONAL RESIDENTIAL CODE
Electrical conduit installation shall be installed per
city specs and is the responsibility of the owner and/or
contractor. Contact the electrical division at (979) 764-
6314 for more information.
ELECTRICAL SHALL BE INSTALLED PER 2002 National Electrical
Code & LOCAL AMENDMENTS
SUBMIT FIRE ALARM PLANS WITH PRODUCT DATA SHEETS - DESIGN
AND INSTALL AS PER NFPA 72
NO WORK SHALL START UNTIL PLANS HAVE BEEN REVIEWED AND
RETURNED
PROVIDE FIRE EXTINGUISHERS) - VERIFY LOCATION AND PLACEMENT
WITH THE FIRE MARSHALL'S OFFICE (MIN. 2A10BC)
SUBMIT FIRE SPRINKLER PLANS AND CALCULATIONS FOR REVIEW
NO WORK ON SPRINKLER SYSTEM SHALL
BEGIN UNTIL PLANS HAVE BEEN REVIEW AND RETURNED.
SPRINKLER SYSTEM CONTROLS AND WATER FLOW SWITCHES ARE
REQUIRED TO BE MONITORED BY AN APPROVED MONITORING
COMPANY. A COPY OF THE MONITORING CONTRACT SHALL BE
SENT TO THE COLLEGE STATION FIRE DEPARTMENT, FIRE
PREVENTION DIVISION.
INTERIOR FINISH MATERIAL SHALL HAVE A CLASS A RATING
REQUIRED EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE
WITHOUT THE USE OF A KEY,TOOL OR SPECIAL KNOWLEDGE/EFFORT
All outdoor lighting must be in compliance with Section
7.10, Outdoor lighting Standards of the City's Unified
Development Ordinance
THERE SHALL BE NO COMBUSTIBLE OR FLAMMABLE MATERIALS
PLACED ON SITE, LOT OR SUBDIVISION WHERE WATERLINES AND
FIRE HYDRANTS AS REQUIRED BY THE APPLICABLE SUBDIVISON
REGULATIONS ARE NOT COMPLETED AND IN SERVICE AND WHERE
ALL-WEATHER ACCESS FOR EMERGENCY VEHICLES DOES NOT EXIST
TO WITHIN ONE HUNDRED FIFTY FEET (1501) OF THE MOST
REMOTE PART OF THE STRUCTURE. (IFC section 501.4)
ANY CHANGES OR ALTERATIONS TO SUBMITTED PLANS MUST BE
RESUBMITTED AND APPROVED BEFORE WORK IS DONE IN ORDER TO
ASSURE CODE COMPLIANCE
POST PERMIT CARD ON JOB SITE
ALL PLUMBING, ELECTRICAL, AND HVAC (mechanical) WORK MUST
BUILDING DEPT R R ENTAT
APPLICANT: /
BUILDING PERMIT
CITY OF COLLEGE STATION ,
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496'
Page 3
Application Number . . . . . 05-00003934 Date 1/27/06
----------------------------------------------------------------------------
Special Notes and Comments
BE PERFORMED BY LICENSED CONTRACTORS. CONTACT BUILDING
DEPARTMENT FOR INSPECTIONS PRIOR TO COVERING ANY WORK
CIRCUIT CR1.2 IN CORRIDOR 1000A, 1000B, AND 1000C OF THE
TENTH FLOOR WILL BE ADDED TO THE EMERGENCY POWER PANEL
DP10-EM.
COMMERCIAL KITCHEN HOOD ON TENTH FLOOR REQUIRES THE
INSTALLATION OF NONCOMBUSTIBLE MATERIALS FOR WALLS AND
FINISHES WITHIN 18" OF HOOD AND COOKING AREA.
Fee summary Charged
----------------- ----------
Permit Fee Total 5774.00
Plan Check Total .00
Grand Total 5774.00
Paid Credited Due
5774.00 .00 .00
.00 .00 .00
5774.00 .00 .00
-----------------
-------------------------------- -----------------
BUILDING DEPT P SENTATIV :/
APPLICANT:
V1*4
CrIy oP CO=0S S A,n0N
Pkttn,,*r 41.bJvtlofMMl StNiI[r
ADDRESS/LOCATION:
APPLICATION POR, SUILDINC KNIT
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
OOLLEGE STATION, TX 77840
(�Jti.fT.V010)��T04.3670 (970) 784.3498 FAX
��SM40V f1
r9 f_ Aryxf•v j earl &,Vck '
CEVAsi
LOT. —I BLOCK1 SUgpIVISION Crescent Pointe 7�
SECIPH
1USINES(OWNERNAMI Adam Development Properties,pH: 776-1111
CONTRACrOR/HOMEOWNCR:Xadi Sip_ Construction L P-PHokE: 268-5520
CONTRACTOR ADDRESS: 1640 ' Briarcrest) A Suite 125 Bryan, TX 77802
SLECTA10AN: ggBe Determined PLUMOER: To Be Determined
IfVAv: TQ. BQ.. D�.tee mMj ed GOOD CENTS tResldentlai o I--.--��—.
CLASS OIL WORK h
ACCESS RYISTORAGE LOCATION R�-Roori
MCsVIN.G SMELL ONLY
DEMOLITION (Asbestos Survey) NEW CONSTRUCTION ° S�AB ONLY
DUPLEX (Landscape Puns REMODELJRENOVATION"
Required) SWIMMING POOLi
QESCRIPTION OF WORK: �; aa
.�ilQ._ 1 iish of Office Bui;lUincy� Y
!ore area.and Tebh Floor Office
STRUCTURE USE: ^Lobby. and Offices
HOMEOWNER ASSMIATInN/AIRCHITEQTUAL OR DESIGN REVIEW 00MMITTC'E Al
'TF-XAS ACCE351811.I7Y STANDARD (TAB) PROJECT REGISTRATION# EASPRJ A6
VALUATION: $ TOTAL ARW 6 4 8 6 S F HEA
• l�%oe of Labor and Meter a s
PV13LICSEWER In Base Building
U SEPTIMREATMENT SYSTEM
[I SEWERTAP:In Base Building
�3 WATERTWIn BAse Building
size
OTHERTAP:In ,B.azg Building
Size
TEUP PoL.E
GARAOF. TYPE:
In Base.
Building
SINGLE ED
ATTACHED M
4 8 4
ARFH. 26486SF
NUMBER OF BEDROOMS: �pL
NUM8EROF BATHROOMS: ale m2 female publicy- 2
INMRIOR WALL. TYPE; In Gypsum Wall Assembly -private
ExTERiOR WALL TYPE: I n ' l d i- _
FOUNDATION TYPE: In Bash Building
ROOF TYPF_r
DOUBLE TRIPLE;
4 ACH>wD CARPORT
SIGNATURE OF APPLICANT:
"If proposed work involves new coA�erc6i1a;R(c'14;)7n9-qt;rtinn nr f€aaads improvernenti
oornmerdat property, building elevations are req�l read,
aa�irag•epaeoaaraaa�aoa*r�aaaaeaaaaaosa4•aa♦ara+♦
Ofllulrs/V ev Only
Flans Exainlner zon,Ing O'flloial
OYtitlur�� t Gan. eximinq
>a�aar�eeta.a4•
Brits:,
Ir8 Or NO
From: "Marq Synwolt" <msynwolt@madison-construction.com>
To: "Benjamin McCarty" <BMcCarty@cstx.gov>
Date: 1/25/2006 12:59:38 PM
Subject: Re: Adam Plaza - Permitting
Ben,
In response to your letter to Gensler dated January 24, 2006 we have
confirmed the following with Bouyea and Associates / Lutron:
1!Circuit C-8�(wall sconces in the�D Wing Room, sheet LC00-01 B) will be
added toiemergency panel DP1-EM7to`comply with section 1006.3 of the 2003
International'Building'Code;-=
2!Circuit Referenced C=1 on emergency panel DP1-EM will actually be
designated as a spare;
3. Circuit'CR172 of=the�tenth floor corridor 1000A71000E and -1000C,(sheet
LC00=10) will be added to the emergency panel DP10-EM/. ---------
We hope that this information sufficiently addresses items 1,2 and 3 of your
January 24, 2006 letter to Gensler.
We have yet to receive clarification of items 4, 5 and 6 (Application #
05-3935 - Finish -out of office building garage) that you addressed on your
January 24, 2006 letter to Gensler.
Please let me know if you need further information or documentation.
Thank You,
Marq D. Synwolt
Application #05-3932 (1st Floor Amenity Wing)
----- Original Message -----
From: "Benjamin McCarty" <BMcCarty@cstx.gov>
To: <msynwolt@madison-construction.com>
Sent: Tuesday, January 24, 2006 4:31 PM
Subject: Adam Plaza
>1 sent the attached letter to architect Bonny McLoud of Gensler.
> Benjamin McCarty'00
> Commercial Plans Examiner
> City of College Station
> 1101 Texas Avenue
> College Station, TX 77842
> 979.764.3570
> College Station. Heart of the Research Valley.
0
PROJECT f�dcv`^ 01 L" PLAN REVIEW NO O S- 31 3 Y
rP
Corn 4,•'e*- BUSINESS OCCUPANCY REQUIREMENTS
"(7. 2000 International Building Code
CODE
SECTION
ITEM
O.K.,
COMMENT
OR N/A
Table 503
Building Height and Area
O IC
504
Height Modifications
N/A
505
Mezzanines
508.4
Special Unlimited Height
506
Area Modifications
302.3
Mixed Occupancy Separation
302.2
Accessory Use Areas
pig
302.1.1
Incidental Use Areas
p (�
411.3
Special Amusement Buildings -
Automatic Fire Detection
N/�
412.1
Air Traffic Control Towers
903
SPRINKLERS WHERE
REQUIRED
N/A
OK
903.2.12.1
Basements > 1500 sq ft
AIIA
903.2.12.3
Buildings Over 55 Feet in Height
01<
507.2, 507.3
Unlimited Area
WIA
Table 601
Note d
Reduction of Hourly Ratings
with Sprinklers
O lc.
603.1(8)
Partition Material Exception for
Type I and Type II Construction
D
Table
1004.3.2.1
Exit Access Corridor Rating
OK
Table 803.4
Interior Finish Classification
J@Mok<
907.2.2
Fire Alarms With Occupant
Load of 500 or more
N 0Tr- E
1004.2.4
Exit Access Travel Distance
0 1(1
903.3.1
Sprinkler Standard NFPA 13
IJflf €
905
STANDPIPES WHERE
REQUIRED
N/A
0
905.2
Standpipe Standard NFPA 14
905.3.1
Building With Floors 30 ft above
Fire Department Vehicle Access
2000 Plan Review Forms
CODE
ITEM
O.K.,
SECTION
COMMENT
OR N/A
905.3.2
Building With Story > 10,000 sq
ft and > 200 ft travel to Fire
0 �.
Department Vehicle Access
905.4 - 905.6
Hose Connection Location
O /C
905.9
Valves Controlling Water Supply
6 [C
1001
EGRESS GENERAL
1003.2.3
Exit Capacity • Occupant
O (4
Content
1003.2.2.7
Converging Exits
OK
1004
Travel Distance & Arrangement
of Exits
Table 1004.2.1
Two Exits (Room or Tenant
Space > 50 Occupants or travel
> than 1004.2.5)
1004.2.5
Common Path of Travel
1004.2.2.1
Exit Separation (''/s Diagonal
Dimension of Building)
1004.3.2.2
Minimum Width of Access
Corridor
1003.3.3.1
Minimum Stair Width
1003.3.1.1
Minimum Exit Door Width
Table 1005.2.2
Single Exit (One Story, 50
Occupants, and 75 ft Travel
NIA
Distance)
Table 1005.2.2
Single Exit (Two Stories, 30
Occupants, and 75 ft Travel
N/A
Distance)
1007.1
Boiler, Incinerator or Furnace
VIA
1007.2
Refrigeration Machinery
N/�
Rooms
1004.3.1.1
Aisle Width in Public Areas
1004.3.2.3
Dead End Corridor • 20 ft
1004.3.2
Exit Access Corridors
O ��
1004.3.2.1
Corridor Rating
Page 28 of 60
7
W
c
N
z
m
Cn
PROJECT PLAN REVIEW NO
BUSINESS OCCUPANCY REQUIREMENTS
2000 International Building Code
CODE
SECTION
ITEM
C
gNIA
1004.3.2.5
Exit Access Corridor Continuity
1004.2.3.1
Multiple Tenants
A
W/14
1005.3.2.5
Smokeproof Enclosures
NO is
1003.2.2.8
Mezzanines
A11A
1005.3.2
Enclosed Stairs
OK
707.2(7)
Floor Opening Permitted
nic
1005.3.6
EXTERIOR EXITWAY STAIRS
1005.3.6.1
Height • 6 Stories • 75 ft
1004.2.4.2
Balcony Travel Distance
Increase
1005.3.6.5
Fire Resistive Separation
1006.2.2
Adjacent Lot Lines
1003.3.3.5
STAIRWAY
CONSTRUCTION
N/A
0 ��
1003.3.3.5
Stairway Construction
1003.3.3.3.2
Closed/Open Risers
1005.3.2.2
Separation of Closets Below
Stairways
1005.3.2.3
Stairway Identification for Stairs
That Continue Below the Level of
Discharge
1003.3.3.3
Stair Treads and Risers
1003.3.3.3.1
Uniform Treads and Risers
1003.3.3.7
Circular Stairs
1003.3.3.4
Landings
1003.3.3.11
Handrails
1003.3.3.2
Headroom
1003.3.3.12
Access to Roof
1005.3.5
Horizontal Exits
1006
Exit Discharge
1003.3.1.3.4
Access -Controlled Egress
Doors
N/a,
CODE
SECTION
ITEM
O.K.,
COMMENT
OR N/A
1003.3.1.3.5
Security Grilles
MIA
1003.3.1.8
Latching and Locking Hardware
AK
1003.3.4
Ramps
Jvl,4
1004.3.3
Balconies
P//+
1003.2.12
Guards
u/A
1003.2.10
Exit Illumination and Signs
OK
1005.3.2.4
Stairway Floor Number Signs
OK
2000 Plan Review Forms Page 29 of 60
PROJECT PLAN REVIEW NO
BUSINESS OCCUPANCY REQUIREMENTS
2000 International Building Code
INTERIOR FINISH
INTERIOR FINISH
SECTION 803.4
UNSPRINKLERED°
SPRINKLERED°
REQUIRED
ACTUAL
O.K.,
REQUIRED
ACTUAL
O.K.,
COMMENT
COMMENT
OR NIA
OR NIA
Vertical Exits and Exit
A
B
Passageways 8,b
Exit Access Corridors
B
C
and Other Exitways
oK
Rooms and Enclosed
C
C
Spaces
Floor Covering
0.22 watt/
0.22 watt/
Corridors & Exits
sq cm.
sq cm.
a. Class C interior finish materials shall be permitted for wainscotting or paneling of not more than 1,000 square feet of applied surface area in the
grade lobby where applied directly to a noncombustible base or over furring strips applied to a noncombustible base and fireblocked as required by
Section 803.3.1.
b. In vertical exits of buildings less than three stories in height of other than Group 1-3, Class B interior finish for unsprinklered buildings and Class C
interior finish for sprinklered buildings shall be permitted.
C. Requirements for rooms and enclosed spaces shall be based upon spaces enclosed by partitions. Where a fire -resistance rating is required for
structural elements, the enclosing partitions shall extend from the floor to the ceiling. Partitions that do not comply with this shall be considered
enclosing spaces and the rooms or spaces on both sides shall be considered one. In determining the applicable requirements for rooms and
enclosed spaces, the specific occupancy thereof shall be the governing factor regardless of the group classification of the building or structure.
d. Applies when the vertical exits, exit passageways, exit access corridors or exitways, or rooms and spaces are protected by a sprinkler system
installed in accordance with Section 903.3.1.1 or Section 903.3.1.2.
2000 Plan Review Forms Page 30 Of 60
040dr,
City of College Station ' Page of
Building Inspection Department
PLANS EXAMINATION REPORT
Address: First Date: I.. Jic/oS—
fL./a f�/Asp
Project Name: W hlt,
--�
Lore 14ru+J
✓S O/ K'c e. 'M +G✓,'or r,'n;5 `I v I4f-
Drawing
Number
Code
Ref.
Number
Questions or Comments
7 Fl�va�rS -'o uv► �%N�sG+Y� f oor5
/SLoc14 all 010«5f +o KPi+,'p/s614W areas -Frio&,•-I
1064 EX; f s4-a; r r ,
Prn✓ide -it OL1a.-r,-. /ar►s /.'vr
�n i rC /Q C e ► H o,--, r S O `7"nPy ce
a O ��
`C de. =vL e_ ro a
OF Al o IL
T
l of 2 0
V"e►, ; -F I ►1 D
1:13 C-
100(,. 3
F1.1 G.^ Cvic G,` Li�;n •v ; �1n .`v, t7�r���,,�a ?
Received by: Date:
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
FACSIMILE COVER SHEET
Date: 1 Zj 2 0/0 # of pages including cover: Y
Ifyou did not receive a complete fax, please call our office immediately for anew transmittal.
TO: /3 or,r y a -ea h w1 Z-0",/
COMPANY: (--,-e H 5 le r
RE: Ada r,, PlR z�
FROM: 13eH %y%C-
FAX: 7/3 - L z- 9- 9 3 y 3
COMPANY: City of College Station, Development Services
REMARKS: ❑ Urgent ® For your review ❑ Replay ASAP ❑ FYI
fier a 4 r e- /C Her 5 tb7 CowrP"eHfs
IF
-ror 3 sc,pat.-u � e lv 1De r w� : �cc/ GZ req s c '�
A -erg ea c A le'OC i-
i%A7�t�CQ'he.
T-h 4 r
h 1c �D !�
TRANSMISSION VERIFICATION REPORT
DATE DIME
FAX NO./NAME
DURATION
PAGE(S)
RESULT
MODE
TIME 12/20/2005 00:02
NAME COCS DEVELOPMENT SER
FAX 9797643496
TEL 9797643570
SER.# BROE2J341073
12/20 00:01
917132299343--170
00: 01: 08
04
OK
STANDARD
ECM
CITY OF COURGE STATION
DEVELOPMENT SERVICES
110.1 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / fax 979.764.3496
FACSIMILE. COVER SHEET
Date: I z I.-e- O 0 5- # of pages including cover:
If you did not receive a complete fax, plegm call our Office immedialciy for anew ftNnsm,,&1
TO: 4oL,.w FAX 7 13 — .z cj - 9 3 Y .?
COMPANY: &eh 5 % i,
RE: Ad'a " r f a 2 e-,-
FROM: l!)ev, MG Ga fl �f
CITY OF COLLEGE STATION
Planning d Development Services
December 20;
Re: Adam Plaza- 91h Floor Core Lobby Area and 10`h Floor Offices- First American Blvd.
Application # 05-3934
Dear, Bonny Jean McLoud
I have completed the plan review for the above referenced project and have the following
comments. The plan review is based on the 2003 International Codes, the 2002 National
Electrical Code and our local amendments. Where appropriate, I have included the
applicable code sections.
1. Need to submit information regarding the plan to block off finished areas from
unfinished future tenant spaces, including elevator doors.
2. Submit details on the fireplace in Mr. Adam's Office.
3. Verify the accessibility of the telephone room near the board room to comply
with section 704 of the ICC/ ANSI Al 17.1- 1998, Accessible and Useable
Buildings and Facilities.
4. Submit verification of smokeproof enclosures for all stairways and their exit
passageways to comply with section 909.20 of the 2003 IBC.
5. Need to verify and submit automatic fire alarm and emergency voice/ alarm
communication system prior to installation to comply with section 907.2.12 of
the 2003 International Building Code.
6. Need to submit fire sprinkler plans prior to installation.
7. Need fire extinguisher size and locations to comply with the City of College
Station Fire Marshall's Office.
8. Need to submit complete lighting plan for permitted area, please include all
emergency lighting, required exit signs, and exit stairway lighting to comply
with section 1006 of the 2003 International Building Code.
9. Provide stairway floor number signs throughout both stairways to comply
with all of section 1019.1.7 of the 2003 IBC.
10. Provide information on the door hardware, including any lock and latch
devices, and emergency exit panic hardware on all exterior to comply with
sections 1008.1.8.1, 1008.1.8.3, and 1008.1.9 of the 2003 IBC.
The review does not include any civil or zoning issues or NRA requirements of the
Unified Development Ordinance. Please respond to the plan review comments at your
convenience. Three sets of plans addressing these issues will be required. Should you
have any questions, contact me at 979-764-3570.
Thank You
Ben McCarty