HomeMy WebLinkAboutWater System Analysis I thyme. aid M MEMORANDUM TO: Dale Schepers, P.E., City of College Station Ed Savage, City of College Station Trey Fletcher, City of College Station FROM: Thomas Haster, P.E., Freese and Nichols, Inc. Jessica L. Brown, P.E., Freese and Nichols, Inc. SUBJECT: Draft Water System Analysis Report of Animate Habitat, Ltd. and Pebble Creek Developments DATE: August 11, 2004 This memorandum report presents the results of a study of water distribution system improvements needed for the existing Pebble Creek development and the proposed Animate Habitat, Ltd. development. Pebble Creek is approximately 1300 acres, and Animate Habitat, Ltd. is approximately 1100 acres. Pebble Creek is expected to build out within seven years, and Animate Habitat, Ltd. is expected to buildout within fifteen to eighteen years. Freese and Nichols, Inc. (FNI) projected populations and water demands for the buildout of both developments with input from the City and used the City's InfoWater model to determine improvements needed to meet the buildout water demands. 1. EXISTING WATER SYSTEM This area is currently supplied from the southwest by a 24 "/18" line from the Greens Prairie Tank Elevated Tank. System improvements currently under design which were considered completed for this study were the 18" Barron Road water line, a portion of the 24" line along FM 2154, and the 18" water line along Rock Prairie Road. The 24" line in FM 2154 will be extended in the future along the future State Highway 40. The Rock Prairie water line will provide an 18" loop and improve supply to the area from the northwest once it is completed. These ongoing system improvements are shown as red dashed lines on Figure 1. 2. POPULATIONS & WATER DEMANDS The City provided FNI with the proposed land use plans for both developments, existing platted lots for the Pebble Creek development, proposed plats for the Pebble Creek development, proposed land use densities, phasing plans of both developments, and development standards from the B /CS Unified Design Guidelines Manual. The proposed land uses are shown on Figure 1; however, recent and proposed revisions in isolated areas are not reflected on the map. Freese and Nichols, Inc. • Engineers • Environmental Scientists • Architects 4055 International Plaza • Suite 200 • Fort Worth, Texas 76109 -4895 (817) 735 -7300 • Metro (817) 429 -1900 • Fax (817) 735 -7491 Draft Water System Analysis Report of Animate Habitat, Ltd. and Pebble Creek Developments August 11, 2004 Page 2 of 8 FNI developed populations and water demand projections for the following four demand conditions: • Average Day Demands, • Maximum Day Demands, • Peak Hour Demands and • Maximum Day Demands under Fire Flow Conditions. The assumptions used for developing the projected populations and water demands are summarized in Table 1. For the Pebble Creek development, the proposed number of units for a majority of the development has previously been determined; therefore, the actual number of units was used for projecting population. In areas where the number of units was unknown, the number of units was calculated based on the proposed land use densities. Table 1 Land Use & Demand Assumptions for Proposed Pebble Creek and Animate Habitat, Ltd. Developments Low Density Residential 2 units /acre Medium Density Residential 4.5 units /acre High Density Residential 9 units /acre Residential Attached 15 units /acre Residential People per Unit 2.67 Commercial People per Acre 30 Industrial People per Acre 15 Average Day to Peak Hour Peaking Factor 4 Average Day to Maximum Day Peaking Factor 2.25 Residential Average Day Demand 165 gpcd Commercial (Retail) Average Day Demand 30 gpcd Commercial (Office) Average Day Demand 60 gpcd Industrial Average Day Demand 60 gpcd Residential Fire Flow 1000 gpm Commercial & Industrial Fire Flow 2500 gpm The projected average day per capita demands shown in Table 1 for residential, commercial and industrial land uses were developed using historical water use records from the 2003 Southside Water Study performed by FNI. A higher per capita water use was used than the Development Guidelines because historical water usage for existing residences in Pebble Creek showed to be higher than 100 gpcd. Peaking factors and people per acre were obtained from the Development Guidelines. Freese and Nichols, Inc. • Engineers • Environmental Scientists • Architects 4055 International Plaza • Suite 200 • Fort Worth, Texas 76109 -4895 (817) 735 -7300 • Metro (817) 429 -1900 • Fax (817) 735 -7491 Draft Water System Analysis Report of Animate Habitat, Ltd. and Pebble Creek Developments August 11, 2004 Page 3 of 8 2.1 Existing Population & Water Demands The existing estimated residential population for Pebble Creek is 2,814 and is shown in Table 2. Approximately 13.76 commercial acres are developed, and approximately 51.9 industrial acres are developed. The population was estimated based on the total number of existing residential lots that were developed as of July 2004. Animate Habitat, Ltd. is expected to begin development in late 2004 or early 2005. The resulting average day demand is 0.53 MGD. The maximum day demand is 1.19 MGD, and the peak hour demand is 2.12 MGD. 2.2 Projected 2011 (Interim) Population & Water Demands The interim phase analyzed was for the buildout of the Pebble Creek development and partial development of the Animate Habitat, Ltd. development. The Animate Habitat, Ltd. development is expected to develop from west to east. The projected 2011 populations and water demands are shown in Table 3. The residential population for Pebble Creek was developed from a blend of land use by acreage and the number of units currently built. The projected residential populations for Animate Habitat, Ltd. are a product of the number of acres, the units /per acre and residential people per unit for each land use category. The buildout residential population for Pebble Creek is 5,541, and the projected 2011 residential population for Animate Habitat, Ltd. is 5,351. The total residential population for both developments is 10,892. The resulting average day demand is 2.27 MGD. The maximum day demand is 6.11 MGD, and the peak hour demand is 9.08 MGD. 2.3 Projected Buildout Population & Water Demands The second phase analyzed was for the buildout of both developments. The projected buildout populations and water demands are shown in Table 4. The buildout residential population for Animate Habitat, Ltd. is 14,126. The total buildout residential population for both developments is 19,667. The resulting average day demand is 3.73 MGD. The maximum day demand is 8.40 MGD, and the peak hour demand is 14.92 MGD. 3. WATER SYSTEM ANALYSIS The water distribution system was analyzed for the two phases: interim and buildout. The proposed development average day, maximum day and peak hour demands were added to the current water system model for each phase. The recently constructed improvements and near term improvements were also added to the model. Because of the lower elevations in the developments, pressures were not a controlling factor in determining future improvements. Additional transmission capacity will be needed to supply both interim and buildout water demands and projected fire flows. The model results are summarized in Tables 5, 6 and 7 for existing, 2011 and buildout demand conditions. The proposed system improvements are shown on Figure 2 by phase. Freese and Nichols, Inc. • Engineers • Environmental Scientists • Architects 4055 International Plaza • Suite 200 • Fort Worth, Texas 76109 -4895 (817) 735 -7300 • Metro (817) 429 -1900 • Fax (817) 735 -7491 Draft Water System Analysis Report of Animate Habitat, Ltd. and Pebble Creek Developments August 11, 2004 Page 4 of 8 3.1 Interim (2011) Improvements The improvements needed to support interim development, or the buildout of Pebble Creek and seven year development of Animate Habitat, are all on -site water system improvements. These improvements are shown as red dashed lines on Figure 2. The following improvements are recommended to serve 2011 demands: • A 12" line along Hwy. 6 from Greens Prairie Road to the existing 12" line to support future retail development in Pebble Creek. • A 16" water line loop along Rock Prairie Road from Greens Prairie Road and along the south property line of Pebble Creek to an extension of the existing 12" line in Pebble Creek Parkway. It is anticipated that this line will be extended further east on Rock Prairie Road for future development outside the scope of this study. • A 12" water line extension along a future road in the far east portion of Pebble Creek. • An extension of the 12" line along Pebble Creek Parkway as a 12" water line to the south property line of Pebble Creek and as a 16" to the future major thoroughfare in Animate Habitat, Ltd. • A proposed 16" line south along Pebble Creek Parkway and west along a future thoroughfare to the 18" line in the Animate Habitat, Ltd. development. • An extension of the existing 18" water line in Lakeway Drive to the proposed 16" line in Animate Habitat, Ltd. • A 12" line connecting the existing 8" line along Hwy. 6 and the proposed 16" loop in the Animate Habitat, Ltd. development. 3.2 Buildout Improvements The improvements to support buildout water demands in both developments include both on -site and off -site system improvements. These improvements are shown as dashed green lines on Figure 2. Additional off -site improvements will also be needed to improve the operation of the Greens Prairie Tank. The improvements needed for buildout demands include: • A 12" loop along future major thoroughfares in the Animate Habitat, Ltd. development that will supply the eastern portion of the development. (on -site) • A 24" line along FM 2154 from the existing 30" at Rock Prairie Road to the existing 12" in Graham Road and along future SH 40 from FM 2154 to the existing 24" line. (off-site) Freese and Nichols, Inc. • Engineers • Environmental Scientists • Architects 4055 International Plaza • Suite 200 • Fort Worth, Texas 76109 -4895 (817) 735 -7300 • Metro (817) 429 -1900 • Fax (817) 735 -7491 Draft Water System Analysis Report of Animate Habitat, Ltd. and Pebble Creek Developments August 11, 2004 Page 5 of 8 4. RECOMMENDATIONS The proposed phasing and sizing of water system improvements are shown on Figure 2. The proposed 18" line along Lakeway Drive and the proposed 16" line along Rock Prairie Road were also sized to allow for future water system expansion to the south and east. At least one off -site system improvement, the 24" line in FM 2154 and future SH 40, will be needed to serve buildout demands. Additional off -site system improvements will be needed to improve the operation of the Greens Prairie Elevated Tank and provide additional transmission capacity to this area. It is recommended that additional off -site improvements be evaluated as a part of the Water Master Plan to ensure that the improvements will be adequately sized for future development in the existing City limits and future service area in the ETJ. Freese and Nichols, Inc. • Engineers • Environmental Scientists • Architects 4055 International Plaza • Suite 200 • Fort Worth, Texas 76109 -4895 (817) 735 -7300 • Metro (817) 429 -1900 • Fax (817) 735 -7491 .. 0 0 0 0 0 0 0 0 0 0 r. 0 0 0 0 0 0 0 0 O 0 0 0 Lo 3 o o to n to , k, 'n ,_'„ ° c, 0 , '--� ,� .--� N N N . ti; v � n v O ,, r-' .--, ^■ N N N Cl O O O O O O O O 0 0,E ..•-• N %o O 0 "I' ":1- o o N N ° O a c A o A 4 t A O O 4 a O O 0 0.x E1: I o. : 2 L }$ . 0 o o o o O c o o ezi. kn in kn et o 'n ,n v) in r, O r N 8 O N N O N 1 . ; : as 0 6 es u 'a E u O O O 0 0 a ct f 4' °. ot 00000,00a= { ' m N 0 O . .- N N cs. r..i 0 j 0 d' 0 el• 0 0 0 0 0 a' r" p pp = • o O A o 0 0 • o O • O o �, -- U w ea C7 g V' 1� o d d U ' "crs M oo e}• 0 M O t� 01 O\ au O ++ £ .r ° N d k--. 00 N o0 7 N t. - O 75 0 c E. C64 N N 1 k C) N e 1 wi m oo et Q rt . n d• 0 en , - I d x c ° N 'l oo " `a a N > it Vj (L) y k.D 00 O �a U N 0 A ., N n In ti rn o 4t 0 et au p, p V o 000000 0 0 0 . ti a 0 00 oM� ch r ai f PI 14 .a C4 v a •CA a a :. °" r . Il M 1:3 r ,.r W p 0 0 0000 0 0 0 b 000 0 _ 0 d r.00000 a d 01 r 000.00��ri r+ L 4t s sq L $., a-1 ..n Z al a d ' ad a c s S,I o o Q O O co . o rs. Fv Q ` o ev rA as y . Oq R —_, . : °r d p a) 0 6 •••• j ✓l ,� id % C n O • ' A C % id v� o O yg i a Q° 4 . a > ; i c a C 0 " e• a c -" W b 44 aG a: a c 0 0 ..- W c . ; 0 '� ¢ �.. a) 7; W it • • - • . L- y t� W ' N a> 0 0 ax . "v -� w U 0 0 A aG ' v ° +; ❑ u c oo w CO c a o d L. ' . , a; w w w a b a.) ... cc w +� O • !" i C 7 , "Fl., OA , b4 e b .Q to to b0 y p p t t b ? ° ��aaxz�� a v) v) v) as.a A ctS d rqN. 000 0 0 O 6 000 0 0 0 O - 0 0 0 00 0 0 0 0 000 0 ,� E 000 f E co O O v In v i kr) ) h, p N N N p - N N N N I 4 e t 0 N N O N ' V ,g, R , I • N 0 N 00 • 00 N �• 00 00' ,� t •-••• I) en M O O C -- •- m '. M N 0 ti0 00 00 • +s .�'-A or:ric • • • zg° aI— A Kiorio0000 o) ee: 78 0..=g" t a= a) >, ON kn kn 00 00 0 00 tel N E >, , In l • oo N to In oo 0 h 0 q -4.) { O t - N ON •--. H N O:. • W N t- . O. M_ d• •--- M ON t) A ,- ' C C C I tie A � ' n O N O O O O O O I 1 • = a 0 O O O ,�` a f,4 A o 4.a 'A v 01 rh O) O\ 00 00 0 00 - - v) ON 00 N �O N 00 gyp. N N E - p N et:' O 0 0 0 y O O ON O O O N N c on A 6 6 o0 0 0 0- tin A o00 Oo00 0 75 ao op. �� i at G7i r 1 et ' d i. "''' _ 0 0? 0 '0 0 ..i. M � M r- 's Y Q N r V) O M to ol, wi wO "; `.$ ". O a N— N M M M ,,t H O 0? , 6 �. N a) a) a N O M M 3.n a M er ■ U H " � .. � V M 4 y w a, M N aD 40 OA O a -4-, ^' . yd a -4.) 4r t� ' o0 rt t� M M ] �O �p d' M N '4:' •`'. ..d O 0 0' M� N N d o M as- O M h Mt 'b N r. 14 N N ° Z y •-, N M ,. r34 1 • = -, ° a 1 .-r 'b N N 00 O0 -• N N h ,�.: 'O N rt M t4 t- 0 m - 0 to 01 01 m M O . M 00 0 . 44.1 r 1 d 00 N [� O M N O O @ ,y Z E L L c).1- C\ 00 '� o. ,, -1 j= al L oo �O 04 M ^• 00 M rt• •.1• ::a N C U N N t O.-tC eil - N N w . YL., � G 4 l Q eat O _ y Irs iti O C O c 0 V A F o Q o . 'C b O x O a a a +, a, " G a +r ° v a a m a a a. a) ..7 a Q o �.' .4 a c s- O �, a) �. r.+ a r Iii d '� b .b R . g. b b b y e 0 3 n O • 6 .. v� . N .L: y • C4 ..;.aa .N y 7) s E ; cxs N a O a) R L1; v Lam c 3 o a) N t, O O > cis ; a) _� OO et a'+ cY+ O W p ° d P4 Q' fx O 0 O F? o ,a cc' + � N l ... :~ 0.i � . • -~ " V ed '� �" • y am v) t� 0 0 •rJ 1. Q Q y, - • t o , cg 5 4. Lt. q a is O q � + ) y om .0 w W k. a -0 .-. is a) •C,�, d v) .5 n rs: g t::4 Z U 4 a in cn z a a a aG U .c '° ' O O O O O O �c 0 0 0 0 0 0 O ^ 0 0 0 0 0 0 ^ 0 0 0 0 0 0 0 8 a _ a, 3 0 0 0 In 1 /, In cn r pp 0 0 0 N N r 8 '�. O G4 •--i N N N N �' 4, � U LL ;.T., ` , 0t 00 00 %O Ni N '�t 10. •akr vi• i 1 1 N ,O N op 00 N 00 00 + H ^ to Tr — M M O el 0 O ^ 0— M Va N 0 M NU 00 00 +' .W 6 A , o .--. •-• 0 C O O O O s I a f " A vi C e7 0 0 0 O 6 O � r X ea Ai 0 �_ Qu In If If In 00 'PI Iry N N a b >1 V'I V'1 00 r` N ,n 00 10 1 r) 0 0 N N N : N •-k N N N O. C7 N t` .--a O M •--• M O, In ( I as A r co N O O N O O" y A ^ '- • I` C N '" O O O d. O R , A t` O O O E M C O 1/i O O C °a E A O is et et am e t l� l� O, M 00 01/4 •� rl N N o 00 VO N N M Ni M 0 1O 0 0 0 0 O o [N- � 0 O Oc 0 0 0 0. N N ^ •--■ O 0 cV 0 0 0 0 0 6) ^ 0 0 0 0 0 0 0 0 0 O •'.Ix`3 1 021 w F £ 0 " 0.1 In •--- N M M M u O as it .-4 — % ~ O N ONO Ni M a) a, g ° r U w w • M N as ;" CU O V) O C v ,o a) ..� Ca g 1 It —. tia [ OY O a L Tj U C N •-. 00 )40 r 00 in _ M M s �. 10 k0 *Tr : M N .-. '0 ., — 4y O N M 1 / 4 0 ' N 0 00 0, : H 'b O M .1 , O M 1/40 N "d O .4., •--∎ N [ rr to N 00 N N `4 O 0 as •-- : O M v) '0 "+ .•i p, O Q a e4 I - d y U o o vi \p v In 01 •- • In r" 1 o rr M r` h N n o, vI If) ` 00 00 •--I 00 00 , O •-• H 5 "t7 t` t` OO N --- M H co O ^p h Cl N 1 ' cT a `c. ,, +— z : H 00 '0 N V' ^' h 44 tr.; IA ' = 0; A L 6 O0 O, 00 —. ). .�.. L L t` G\ M ""' 00 P N N . s s ., W ti O y 0 O , 73 sa r O MI -' 4 a) CI. O Q y � 0... y ' . a Z' 0 4' on O v7 O Q O o A o ( cn ' g A i s as o,-, Q A ea c �a o CY aa) Al )-4 5 . c o 41 C .a . o ., a • v 71°. O 0 b b ° •Y °' , -. b , d b 0 0 > y �i o c cn c a au a > v a a a c 0 > CD 1. I.. N 0 O W p cu CY 0; Q: O 0 o W r . +-' • O cd ct — a' H " w " ` U o w Q ' y __ ' v , 0 0 MI k k., .0 0 0 O d ... s,. a a? w w w 0 b 0 d a 1. ea cd %.b E 4 .4: b 4 O .O E 't7 y .� ,� b �� " v .. O v � � y ''a` 0 74 44 I-i - 0 .'.I b0 00 . 7, '00 .1:4 5 o , i az oq oA on 7, G 5 a o Aa v) V .E4 a) 04 a a 04 U 4 4 r Table 5 CITY OF COLLEGE STATION WATER DISTRIBUTION SYSTEM EXISTING CONDITIONS A. Water Demands Average Day . 91 Peak Hour 'TOTAL SYSTEM DEMAND 10.98 MGD 35.12 MGD B. System Operation Tank Avg Day/ Avg Day/ Fill Time ;° r i:, s Peak Hour Peak Hour Drain Time Tank Vol. Tank Refillin a Tank Refillin a Avg Day ; t I L i Et , aEte Inflow Current at Pk Hr Location MG MGD Status hr * _ �� E L.t =te•r M GD Status hr * Greens Prairie Tank 2.00 6.22 Filling 5.15 r -3.74 Draining 8.55 Park Place Tank 3.00 7.72 Fillin: 6.22 _ ,1; t , -5.20 Drainin: 9.24 DELIVERY SOURCE Inflow Pressure `E' x IEEE • Inflow Pressure (MGD) (E si ri (MGD) E si) Dowlin: RoadP.S. 24.93 93 k `` ` 26.17 88 Maximum System Pressure 124 118 Minimum S stem Pressure 65 L 61 C. System Operation with 24" line to existing Greens Prairie 24" Tank Avg Day/ Avg Day/ Fill Time t; Pt'i 1 ( ` < � a Peak Hour Peak Hour Drain Time Tank . Tank Refilln a Tank Refillin a Avg Day, 4E4.€tE L,4 9 t tie E Inflow Current at Pk Hr Location MG) (MGD) Status (hr)* 6 ) # tt (MGD Status hr)* Greens Prairie Tank 2.00 9.54 Filling 3.35 r -2.98 Draining 10.75 Park Place Tank 3.00 5.60 Fiilin: 8.57Biu} -5.75 Drainin: 8.35 DELIVERY SOURCE Inflow Pressure i�� fE , i ' - � Inflow Pressure MGD) E si) i i t t ` i� (MGD (E si Dowlin: Road P.S. 26,13 88 26.38 87 Maximum System Pressure 123 118 Minimum S stem Pressure 63 i 61 * Drain Time @ Peak Hour is based on 2/3 of the tank volume * Fill Time @ Average Day is based on 2/3 of the tank volume. Table 6 CITY OF COLLEGE STATION WATER DISTRIBUTION SYSTEM INTERIM CONDITIONS (BUILDOUT FOR PEBBLE CREEK & 7 YEAR CONDITIONS FOR ANIMATE HABITAT, LTD.) A. Water Demands Average Day k Peak Hour 'TOTAL SYSTEM DEMAND 12.6 MGD k1 41.0 MGD B. System Operation Tank Avg Day/ Avg Day / Fill Time f Peak Hour Peak Hour Drain Time Tank Vol. Tank Renillin!, Tank Refillin y Avg Day �t i� ° : it t�97 Inflow Current at Pk Hr Location MG MGD Status hr * ���;�au % MGD Status hr * Greens Prairie Tank 2.00 5.82 Filling 5.50 =ts. -f k, 9 „ -7.87 Draining 4.07 Park Place Tank 3.00 6.89 Fi11in• 6.96, ( .� -5.47 Drainin_ 8.78 Inflow Pressure 1 Inflow Pressure DELIVERY SOURCE [ MGD) psi p _` €° ykk ` MGD) Isi Dowlin: Road P.S. 25.30 9I �� a = 27.60 82 Maximum System Pressure 124 G 108 Minimum S stem Pressure 64 L_ C. System Operation with 24" line to existing Greens Prairie 24" Tank Avg Day/ Avg Day/ Fill Time bt tCt 0,1 Peak Hour Peak Hour Drain Time Tank Vol. Tank Refillin Et Tank Refillin IA Avg Day;( &i�i(� : tfi tilt? Inflow Current at Pk Hr Location (MG) (MGD) Status (hr)* d it( .1 _ • MGD) Status (hr)* Greens Prairie Tank 2.00 8.73 Filling 3.66 g "``o ,K �� ��� ���� -7.23 Draining 4.43 Park Place Tank 3.00 5.00 9.59?eri+ -5.94 Draining 8.09 DELIVERY SOURCE Inflow Pressure i (10, k ; t Inflow Pressure MGD ( i si) , _g.���"' ,� .MGD) (I si Dowlin: Road P.S. 26.40 87 27.80 81 Maximum System Pressure 123 9. 112 Minimum S stem Pressure 63 - 54 * Drain Time @ Peak Hour is based on 2/3 of the tank volume * Fill Time @ Average Day is based on 2/3 of the tank volume. Table 7 CITY OF COLLEGE STATION WATER DISTRIBUTION SYSTEM BUILDOUT CONDITIONS FOR PEBBLE CREEK & ANIMATE HABITAT, LTD. A. Water Demands Average Day + k Peak Hour 1 'TOTAL SYSTEM DEMAND 14.1 MGD 46.8 MGD B. System Operation Tank Avg Day / Avg Day/ Fill Time '41 H = aar� ' a Peak Hour Peak Hour Drain Time Tank Vol. Tank Refillin u Tank Refillin Avg Day € Inflow Current at Pk Hr Location MG MGD Status hr * s , t € . i , MGD Status hr * Greens Prairie Tank 2.00 7.39 Filling 4.33 -12.15 Draining 2.63 Park Place Tank 3.00 4.92 Fiilin 9.76 - •r. -6.69 Drainin_ 7.18 DELIVERY SOURCE Inflow Pressure , 41Piic t Inflow Pressure (MGD psi F d t «ig (MGD (psi) Dowlin: RoadP.S. 26.40 87 LFi _�v� 28.00 80 Maximum System Pressure 122 r - - 105 Minimum S stem Pressure 63 a 53 * Drain Time @ Peak Hour is based on 2/3 of the tank volume * Fill Time @ Average Day is based on 2/3 of the tank volume. Draft Water System Analysis Report of Animate Habitat, Ltd. and Pebble Creek Developments August 11, 2004 Page 2 of 8 FNI developed populations and water demand projections for the following four demand conditions: • Average Day Demands, • Maximum Day Demands, • Peak Hour Demands and • Maximum Day Demands under Fire Flow Conditions. The assumptions used for developing the projected populations and water demands are summarized in Table 1. For the Pebble Creek development, the proposed number of units for a majority of the development has previously been determined; therefore, the actual number of units was used for projecting population. In areas where the number of units was unknown, the number of units was calculated based on the proposed land use densities. Table 1 Land Use & Demand Assumptions for Proposed Pebble Creek and Animate Habitat, Ltd. Developments Low Density Residential 2 units /acre Medium Density Residential 4.5 units /acre High Density Residential 9 units /acre Residential Attached 15 units /acre Residential People per Unit 2.67 Commercial People per Acre 30 Industrial People per Acre 15 Average Day to Peak Hour Peaking Factor 4 Average Day to Maximum Day Peaking Factor 2.25 Residential Average Day Demand 165 gpcd Commercial (Retail) Average Day Demand 30 gpcd Commercial (Office) Average Day Demand 60 gpcd Industrial Average Day Demand 60 gpcd Residential Fire Flow 1000 gpm Commercial & Industrial Fire Flow 2500 gpm The projected average day per capita demands shown in Table 1 for residential, commercial and industrial land uses were developed using historical water use records from the 2003 Southside Water Study performed by FNI. A higher per capita water use was used than the Development Guidelines because historical water usage for existing residences in Pebble Creek showed to be higher than 100 gpcd. Peaking factors and people per acre were obtained from the Development Guidelines. Freese and Nichols, Inc. • Engineers • Environmental Scientists • Architects 4055 International Plaza • Suite 200 • Fort Worth, Texas 76109 -4895 (817) 735 -7300 • Metro (817) 429 -1900 • Fax (817) 735 -7491 Draft Water System Analysis Report of Animate Habitat, Ltd. and Pebble Creek Developments August 11, 2004 Page 3 of 8 2.1 Existing Population & Water Demands The existing estimated residential population for Pebble Creek is 2,814 and is shown in Table 2. Approximately 13.76 commercial acres are developed, and approximately 51.9 industrial acres are developed. The population was estimated based on the total number of existing residential lots that were developed as of July 2004. Animate Habitat, Ltd. is expected to begin development in late 2004 or early 2005. The resulting average day demand is 0.53 MGD. The maximum day demand is 1.19 MGD, and the peak hour demand is 2.12 MGD. 2.2 Projected 2011 (Interim) Population & Water Demands The interim phase analyzed was for the buildout of the Pebble Creek development and partial development of the Animate Habitat, Ltd. development. The Animate Habitat, Ltd. development is expected to develop from west to east. The projected 2011 populations and water demands are shown in Table 3. The residential population for Pebble Creek was developed from a blend of land use by acreage and the number of units currently built. The projected residential populations for Animate Habitat, Ltd. are a product of the number of acres, the units /per acre and residential people per unit for each land use category. The buildout residential population for Pebble Creek is 5,541, and the projected 2011 residential population for Animate Habitat, Ltd. is 5,351. The total residential population for both developments is 10,892. The resulting average day demand is 2.27 MGD. The maximum day demand is 6.11 MGD, and the peak hour demand is 9.08 MGD. 2.3 Projected Buildout Population & Water Demands The second phase analyzed was for the buildout of both developments. The projected buildout populations and water demands are shown in Table 4. The buildout residential population for Animate Habitat, Ltd. is 14,126. The total buildout residential population for both developments is 19,667. The resulting average day demand is 3.73 MGD. The maximum day demand is 8.40 MGD, and the peak hour demand is 14.92 MGD. 3. WATER SYSTEM ANALYSIS The water distribution system was analyzed for the two phases: interim and buildout. The proposed development average day, maximum day and peak hour demands were added to the current water system model for each phase. The recently constructed improvements and near term improvements were also added to the model. Because of the lower elevations in the developments, pressures were not a controlling factor in determining future improvements. Additional transmission capacity will be needed to supply both interim and buildout water demands and projected fire flows. The model results are summarized in Tables 5, 6 and 7 for existing, 2011 and buildout demand conditions. The proposed system improvements are shown on Figure 2 by phase. Freese and Nichols, Inc. • Engineers • Environmental Scientists • Architects 4055 International Plaza • Suite 200 • Fort Worth, Texas 76109 -4895 (817) 735 -7300 • Metro (817) 429 -1900 • Fax (817) 735 -7491 Draft Water System Analysis Report of Animate Habitat, Ltd. and Pebble Creek Developments August 11, 2004 Page 4 of 8 3.1 Interim (2011) Improvements The improvements needed to support interim development, or the buildout of Pebble Creek and seven year development of Animate Habitat, are all on -site water system improvements. These improvements are shown as red dashed lines on Figure 2. The following improvements are recommended to serve 2011 demands: • A 12" line along Hwy. 6 from Greens Prairie Road to the existing 12" line to support future retail development in Pebble Creek. • A 16" water line loop along Rock Prairie Road from Greens Prairie Road and along the south property line of Pebble Creek to an extension of the existing 12" line in Pebble Creek Parkway. It is anticipated that this line will be extended further east on Rock Prairie Road for future development outside the scope of this study. • A 12" water line extension along a future road in the far east portion of Pebble Creek. • An extension of the 12" line along Pebble Creek Parkway as a 12" water line to the south property line of Pebble Creek and as a 16" to the future major thoroughfare in Animate Habitat, Ltd. • A proposed 16" line south along Pebble Creek Parkway and west along a future thoroughfare to the 18" line in the Animate Habitat, Ltd. development. • An extension of the existing 18" water line in Lakeway Drive to the proposed 16" line in Animate Habitat, Ltd. • A 12" line connecting the existing 8" line along Hwy. 6 and the proposed 16" loop in the Animate Habitat, Ltd. development. 3.2 Buildout Improvements The improvements to support buildout water demands in both developments include both on -site and off -site system improvements. These improvements are shown as dashed green lines on Figure 2. Additional off -site improvements will also be needed to improve the operation of the Greens Prairie Tank. The improvements needed for buildout demands include: • A 12" loop along future major thoroughfares in the Animate Habitat, Ltd. development that will supply the eastern portion of the development. (on -site) • A 24" line along FM 2154 from the existing 30" at Rock Prairie Road to the existing 12" in Graham Road and along future SH 40 from FM 2154 to the existing 24" line. (off -site) Freese and Nichols, Inc. • Engineers • Environmental Scientists • Architects 4055 International Plaza • Suite 200 • Fort Worth, Texas 76109 -4895 (817) 735 -7300 • Metro (817) 429 -1900 • Fax (817) 735 -7491 Draft Water System Analysis Report of Animate Habitat, Ltd. and Pebble Creek Developments August 11, 2004 Page 5 of 8 4. RECOMMENDATIONS The proposed phasing and sizing of water system improvements are shown on Figure 2. The proposed 18" line along Lakeway Drive and the proposed 16" line along Rock Prairie Road were also sized to allow for future water system expansion to the south and east. At least one off -site system improvement, the 24" line in FM 2154 and future SH 40, will be needed to serve buildout demands. Additional off -site system improvements will be needed to improve the operation of the Greens Prairie Elevated Tank and provide additional transmission capacity to this area. It is recommended that additional off -site improvements be evaluated as a part of the Water Master Plan to ensure that the improvements will be adequately sized for future development in the existing City limits and future service area in the ETJ. Freese and Nichols, Inc. • Engineers • Environmental Scientists • Architects 4055 International Plaza • Suite 200 • Fort Worth, Texas 76109 -4895 (817) 735 -7300 • Metro (817) 429 -1900 • Fax (817) 735 -7491 0 0 0 O 0 0 •••••••• 000 0 0 0 0 O 0 0 0 N N N y o O O O N N N N 0 r few 0 0 GiG4 O ^ 000000 0 0 00 0 ..-.. N'0 00 0 00 0 O 0 0 00 N N ,..4 a L A O O a `' A O O ,-4 O O O O O N d c g a : g Au, x � 0 0 0 0 0 0 O 0 © o 1, II 1n eh 0 In kn t in .-1 - 0 0 S N 0 N N O N ." E - O 0 � . O p� • 0 . -� O O O • —. O H =" E E C� V O O O 6 0 0 r et - .. g a.) oio _ - — a) 0 0 0 0 0 0 0 0 0 0 r N ,O 0 N 0n M O O O 0 0 0 0 0 0 in Q 0, A O O bD A O • O O O 0 0 0 0 0 0 ✓ et 0 I aC L„ C.Xo . p Q " Q A E U M 00 v O M O M O\ CT .O N' t 00 N ---- e N N 0 0 �� + E-, p" N N e} a) N G y M 00 s 7 „'� C G N - 0 1 h .) r 00 O C U N C A o 0., F : U 0 0 0 0 0 0 0 0 0 0 0 d o o o o o M oo o a • an p” a a W 0 _ 00000 b 0 0 0 0 0 oo0 , o0co�o0 o vo as 0 0 a? 0 0 0 O 0 N 0 N a, 0; vi O O - L y 0 0 0 0 0 ,O M ., ." . N ,� /''' L .� v� 1A ■p r.S E o I .3 Z I Z d x c 3 O 0 ca O 4. an .a Q ,�, v) 0 4 • W a cn d a, E o . et a 3 g a os a x o c 0 a o 0 ■ 0 • �+ v' ^C D a a aZ a aZ a C. . O © W O C [ p W CI . • a o a d c a a o ` '5 7)., � a = bbb� a) a .> 0 a) ai a) 0 i s a s a) )i a p , c 01 03 5 x al) a: a; a: R o g c �% o ►A�i a' A' Q a .v o W a W >, >, >, a b ;° W W a s W a) ea a, "00 ac ww c e o d. s,.F aJ www M•d ap E. r... ) to y y • bn . 1:4 = "a F . 0C) 00 by • .fl • W q D F c/) CO C c c y a) a) a) a) ' b a) c g g a) , o N c 2 '0 CA CA xa xZ �.9 a CACA s. � n Qa. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 L.-) v, in n 6 0 O O co N N N L p 0 0 N N N N O GTr W., OD 4:1 W as ^ C 4+ a N- N (V 0 N 7 " ' 00 N VD N 00 N 00 M 00 00 N „, l- Ul M M O O .00 r.+" a 6 A o r) 0 0 0 0 en a a A ° ri o ri o 0 0 0 0 o v) et ax a.. A d a y y >, O, v, v, 00 00 0 00 N N O 00 N in kr) Cr) 00 O M o- M CT In Q: ”4 eel R • A ^ ° .� O O O �N A N O • N O 0 • 0 O 0 N .. 0' O O O E C 0 "' 0 R R , O w C • C N 000 0 O 00 0 00 0 0 �' C 00 N N 00 VD N N O E O S O ON O O O N N e p p° 0 0 0 0 6 0 0 0 e A o 0 0 0 0 0 0 0 0 0 '.-+ i C7 ; Cd U 04 ', '. Q A vs CC C- s C - ,-, M N ,-, \D '.D O tel 00 '.D 00 'V 7 en 1 / 4 0 M N N In L." y C N S N O M O\ VD vD " Q. N H as '1 I ,--, N M M M O o? ,- M v) y y A ' N O M M Ca a, M *et U ell 0.) U � M 0 w , z M sl e U y bA 0 0 ,� N .r Xk z Ce4 O N C 0 V r•-• �O 00 r, 4 r-I M M en �O �O M N ,.0 Q+ e..+ = O S ‘.0 V) 0 v v1 .. ■ . . O M rn ■' o M N b O O d N M vO N N N' M 0 O ^ ^ MI b >> N^ ' -"' N N 0 0 N M ., C4 0 I a. V N N d' 00 0 •--■ N N N I( b O M S l- N kn OT v, 1A •l M O\ ---- C+) 00 00 -, ' N N. d t` N 00 N t` 0 M H O O V! M 01 . R y 0 0 0 4 M 0O 7r O, - .1. 0 +.+ R y \O 00 , 46 N 4 ^' 00 4 kn 1A 00 0 Cl.) , C Q ,-1 N N es Q] z 0? Q o z z t 023 c 0 �o 0 7� OF" cn Q - 6 . o te a, , � �' o za Cd O y 0 0 O 0 2 y 3 y to y 0 . E- C PI , , a 0.. ° ' a x ° ° w ^o 0 • W . a a, a a� ° c R v "CI �, O o b 'b . .>. • ► b '0 ' 0 ed 0 > R r n. c a `0 ) . a 04_ c ._ w 0w rz�a FA o o o�w 0w °O � 1 ¢ a. ° w e $ ., ' = . � .'>' a. > 7 a ct o c 0� E E 0 u: 'u d U E -d .N a : u w 4 a a) V, et a' v �0 a .. et : O CC 01) L". t3 O O v m E~ " 0 O 8 � + r✓„ 7 < a C Fr N Cd •� 01) OD • N 'y pi) . 00 E 0 0 b A W oo 'q p 'pn (-1 0 .., a) eu 0 N O 'd "O 0) 0 ❑ C 0 0 0 0 - 0 ' V) r /D X Z - 4 a v)� cn xa.a.xv .E 4 0 0 0 O 0 0 0 0 0 0 0 0 0 .. 0 0 0 0 0 0 .. 0 0 0 0 0 0 0 a> 0 O O O N N N L 3 O O O N N N N 00 00 0 N N 0 7 N N 00 N 00 00 N �' 00 00 O H ,-. 0 d• --- M M 0 M 0 0 I`- _ D - M vD N 0 M v:, o0 00 N ..... 6 ' A 0 ,--i ^ O∎ O O O O O O1: a 1. A M 6 M 6 0 0 0 0 0 In 0 ea O d C 0 E a x g a= g a 0 Ta �, an v7 00 o) 1 4 v1 N N v1 v7 0o n � oo VD ul O M c a l- N N el ^ N N N O 'et ea N r- .--- O M V• -- M O, 1t) A, 04 A .. r 000 N O O N O O N A ^ O N O O O C O O N A £' A M 6 O vi C O O -Er eel ea � (ri kn 0 00 N �O N 00 VD N N 'O Z co 0. M N M 00 . C. 0 0 0 Tr O N- O O\ O O O N N M ^ -� o O N 0 0 0 0 O N ^ 0 0 0 0 0 0 0 0 0 0 .. et _ CD v 0 — i ca 0 Q `. Q C d - 0 00 0 O 0 00 0 et M 0O M N N V M ) )-•� a G N N 14 O M .11 ON VO sO I* O a) [ : a d• vi N M c'i N7 ti o L > U M ,r, CD :r C •�� a N N N O■ O O N oo M M SZ tj .1 w a? w rnc%,N ela .0 as o a) 17) U C N ,-. 00 ' N oo )n M M d' 0 � � M N -. Q ^.. N M 0 N O 00 O� ^� 1-4 { "C M of l0 7r M 0 S "', w ° '-. N .-4 N 00 N N N , �? y ° D\ ^-- O M an '.0 0 ° co N ,--i 7r N N . (1) = ^' N M a 'V a U � a GE to so .1t tin 0\ — V) h. N '. O M N r-- N an 4n ”.1 ^ 00 00 -� 00 00 \O .--4 VY'.. d ^ N N 00 N N O M .-- 0 O In CI �' N N O� �O O� 'd• • O h oo ,O N V' -. kn r-1 u7 V) a0 Ce A � � „ 0\ �' 00 ^• •�+ . O r L L N O\ M — 00 H N N . "0 er CI l el 7 ce Q 4 O c �c° O 15 CQ O N 0 CA O i4 Q'S V) O Z Cl a4 1:10 cn Po E Au Q c o aQ • c c a cn Q 0 Q ea = o a ++ on . on Q .-. b a x a o w , x o o o m l o a 4- . a+ O al b b „ ea 7 ' d 'b 'b as a> >. 2 C/) O (-4 " ai a) a) 7 0 O > a a a a O e i.., N N 0 C4 -5 o C4 F ? • w y a' L� R; c O o F ? � ' ed o _ .. _ a) w vs oo d v�vrx fx p4Z U ,, a v)vnvnP4aaaU.. c, Table 5 CITY OF COLLEGE STATION WATER DISTRIBUTION SYSTEM EXISTING CONDITIONS A. Water Demands Average Day Max r Day Peak Hour 'TOTAL SYSTEM DEMAND 10.98 MGD 21.95 MGD' 35.12 MGD B. System Operation Tank Avg Day/ Avg Day/ Fill Time Max Day Max Day Peak Hour Peak Hour Drain Time Tank Vol. Tank Refilling Tank Refilling Avg Day Inflow Current: Inflow Current at Pk Hr Location (MG) (MGD) Status (hr)* (MGD) l' Statu s'o. (MGD) Status (hr)* Greens Prairie Tank 2.00 6.22 Filling 5.15 2, . iiV 1 "` -3.74 Draining 8.55 Park Place Tank 3.00 7.72 Filling 6.22 , 2.17e t t'ii I 1 g: -5.20 Draining 9.24 DELIVERY SOURCE Inflow Pressure Inflow' ,Pressure; Inflow Pressure (MGD) (psi) (MGD) = psl)n: (MGD) (psi) Dowling Road P.S. 24.93 93 .24.97 w_ 93 .0 26.17 88 Maximum System Pressure 124 ° ' r ' 118 Minimum System Pressure 65 = 7 61 C. System Operation with 24" line to existing Greens Prairie 24" Tank Avg Day/ Avg Day/ Fill Time Max Day Max Day Peak Hour Peak Hour Drain Time Tank Vol. Tank Refilling Tank Refilling Avg Day Inflow Current Inflow Current at Pk Hr Location (MG) (MGD) Status (hr)* (MGD) § Status . (MGD) Status (hr)* Greens Prairie Tank 2.00 9.54 Filling 3.35 3.84! = Filling ; -2.98 Draining 10.75 Park Place Tank 3.00 5.60 Filling 8.57 1,19 Fi lling -5.75 Draining 8.35 DELIVERY SOURCE Inflow Pressure Inflow Pressure Inflow Pressure (MGD) (psi) (MGD) (psi) (MGD) (psi) Dowling Road P.S. 26.13 88 '25.774:- ' ` '' ,' 26.38 87 Maximum System Pressure 123 225' , 118 Minimum System Pressure 63 � 71 61 * Drain Time @ Peak Hour is based on 2/3 of the tank volume * Fill Time @ Average Day is based on 2/3 of the tank volume. Table 6 CITY OF COLLEGE STATION WATER DISTRIBUTION SYSTEM INTERIM CONDITIONS (BUILDOUT FOR PEBBLE CREEK & 7 YEAR CONDITIONS FOR ANIMATE HABITAT, LTD.) A. Water Demands Average Day 1 Max Day Peak Hour 'TOTAL SYSTEM DEMAND 12.6 MGD 24.0' MGD 41.0 MGD B. System Operation Tank Avg Day/ Avg Day/ Fill Time Max Day Max Day Peak Hour Peak Hour Drain Time Tank Vol. Tank Refilling Tank Refilling Avg Day Inflow . - Current Inflow Current at Pk Hr Location (MG) (MGD) Status (hr)* (MGD), Status (MGD) Status (hr)* Greens Prairie Tank 2.00 5.82 Filling 5.50 0.24 ° Filling -7.87 Draining 4.07 Park Place Tank 3.00 6.89 Filling 6.96 2.16 , Filling -5.47 Draining 8.78 DELIVERY SOURCE Inflow Pressure Inflow , Pressure` Inflow Pressure (MGD) (psi) (MGD). (psl) (MGD) (psi) Dowling Road P.S. 25.30 91 26,50 -r87_, ,, 27.60 82 Maximum System Pressure 124 116 108 Minimum System Pressure 64 ' _ - 54 C. System Operation with 24" line to existing Greens Prairie 24" Tank Avg Day/ Avg Day/ Fill Time Max Day Max Day Peak Hour Peak Hour Drain Time Tank Vol. Tank Refilling Tank Refilling Avg Day Inflow Current Inflow Current at Pk Hr Location (MG) (MGD) Status (hr)* (MGD) , ,Status ` (MGD) Status (hr)* Greens Prairie Tank 2.00 8.73 Filling 3.66 2. ' Flling -7.23 Draining 4.43 Park Place Tank 3.00 5.00 Filling 9.59 0.58 '„'Fining, , -5.94 Draining 8.09 Inflow Pressure Inflow 'Pressure' Inflow Pressure DELIVERY SOURCE (psi) G (MGD) (psi) ) (p i) ) 'si) ( ) (p ) Dowling Road P.S. 26.40 87 27.00 1 1' ' , 84r 27.80 81 Maximum System Pressure 123 , , 1 }19 112 Minimum System Pressure 63 60 54 * Drain Time @ Peak Hour is based on 2/3 of the tank volume * Fill Time @ Average Day is based on 2/3 of the tank volume. Table 7 CITY OF COLLEGE STATION WATER DISTRIBUTION SYSTEM BUILDOUT CONDITIONS FOR PEBBLE CREEK & ANIMATE HABITAT, LTD. A. Water Demands Average Day Max Day �' Peak Hour 'TOTAL SYSTEM DEMAND 14.1 MGD '2 3:OT?, " 46.8 MGD B. System Operation Tank Avg Day/ Avg Day/ Fill Time Max Day Max Day Peak Hour Peak Hour Drain Time Tank Vol. Tank Refilling Tank Refilling Avg Day InfIoW Current Inflow Current at Pk Hr Location (MG) (MGD) Status (hr)* (MOD) x (MGD) Status (hr)* Greens Prairie Tank 2.00 7.39 Filling ., _ 4.33 ' 52 I * [ j -12.15 Draining 2.63 Park Place Tank 3.00 4.92 Filling 9.76 . 0 2 &+ + Rti g -6.69 Draining 7.18 DELIVERY SOURCE Inflow Pressure Infio *, trilekifi Inflow Pressure (MGD) (psi) e (MOD) 1904) < (MGD) (psi) Dowling Road P.S. . 26.40 87 , - 27;10 _ 41 " 84 28.00 80 Maximum System Pressure 122 ,113 , 105 Minimum System Pressure 63 60 53 * Drain Time @ Peak Hour is based on 2/3 of the tank volume * Fill Time @ Average Day is based on 2/3 of the tank volume.