HomeMy WebLinkAboutWastewater Design September 15, 2010
Mr. Stephen Maldonado Jr.
City of College Station Water Services Department
1101 Texas Avenue
College Station, TX 77842
Re: Wastewater Design Report
Proposed College Station ISD Transportation Center
800 George Bush Drive
College Station, Texas
Gessner Engineering Job No.: 10 -0407
Dear Mr. Maldonado:
The peak wastewater flow was calculated in accordance with the fixture count
determination method. A total fixture unit count of 88 was determined for this
building. This calculation was determined based on the fixture unit load factor
given in Table I of the Sanitary Sewer Chapter of the Bryan /College Station
Unified Design Guidelines. The values are shown below in Table One.
Load Total
Fixture Number Factor Value
Lavatory 12 2 24
Dishwasher 2 2 4
Water Fountain 2 2 4
Urinals 2 4 8
Water Closets, 6 8 48
Valve Operated
Total 88
Table One: Fixture Units Gessner
The peak wastewater flow based on the fixture units is 125 gallons per Engineering
minute for Tess than 500 fixture units. Using the Manning equation with
an n value of 0.013, the velocity in all sections of the proposed sewer 25Ol Ashford Drive
line were calculated as shown in Table Two below. Suite 102
Pipe Size Pipe Slope College Station, Texas 77840
Pipe Section (in) (oho) Pipe Velocity (ft/s)
BLDG - TIE -IN _ 6 1.00 2.86 P.O. Box 10763, 77842
Table Two: Pipe Size, Slope and Velocity 979.680.8840
All pipe slopes are within the required range of minimum /maximum fax 979.680.8841
pipe slopes for sanitary sewer from the Bryan /College Station Unified
Design Guidelines.
2204 S. Chappell Hill Street
Brenham, Texas 77833
116979.836.6855
4 - 16 . 10 fax 979.836.6847
!Dig
Please contact us if you have any questions or if we can be of further assistance.
Sincerely,
GESSNER ENGINEERING, F -7451