HomeMy WebLinkAboutStaff comments 1 CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM August 30, 2004 TO: Kendall Gillum, via fax 254.771.3739 FROM: Jennifer Prochazka, Staff Planner SUBJECT: QUALITY SUITES HOTEL (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised set of plans. Easement Dedication Sheet and required documents. Please note that the Easement Dedication Sheet and the necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Christian A. Galindo, via fax 979.846.8868 Case file #04- 00500199 STAFF REVIEW COMMENTS NO. 1 Project: QUALITY SUITES HOTEL (SP) — 04- 00500199 STOP REVIEW. Staff has received comment from TxDOT that a driveway permit will not be issued along Texas Avenue. Due to the impact this causes, a full review at this time would be futile. Preliminary comments are being returned at this time. PLANNING 1. The following comment is from TxDOT: "Based on TxDOT's 'Regulations for Access Driveways to State Highways' access to the west frontage road is denied. Access regulations are primarily based on posted speed limits (WFR = 45 MPH) and distances to adjacent access points. Additionally, driveway location distance (upstream) from the proposed new SH 6 exit ramp @ Ponderosa Dr. could be a factor." 2. The proposed parking area is not permitted in the drainage easement. 3. Please show all fire lanes throughout the site. 4. Please show proposed FDC location. 5. Please label existing fire hydrant on Ponderosa. 6. The opposite drive on Ponderosa near intersection that is labeled as "Abandoned Drives" is gated, but still in use. 7. Please call out the actual height and material of dumpster enclosures. The southernmost enclosure will require gates because it is visible from the right -of -way. The minimum clear opening is 12' for each dumpster. 8. A 23' drive aisle is required if there is any head -in parking off of the drive. 9. The minimum separation distance required for drives on a local or collector street is 175', measured from the center line of one to the nearest edge of the other. The two proposed drives on Ponderosa do not meet this requirement. You will only be allowed one drive on Ponderosa. 10. Please call out distance to the next closest adjacent and opposite drives. 11. The maximum driveway width is 36 feet and is measured at the property line. 12. Please either remove all signs from the plan or add a note that signs may be permitted separately. As discussed in the Pre - Application Conference, this will be considered one building plot for the purposes of signage. 13. Provide a general note that all roof and ground- mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right - of -way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. Reviewed by: Jennifer Prochazka Date: August 20, 2004 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 2 of 4 LANDSCAPING /STREETSCAPING /BUFFER 1. An office development adjacent to multifamily zoning or development does not require a buffer. 2. Please add a note that an irrigation plan must be approved prior to C.O. 3. Please make sure that the number of plants that you are claiming points for match what is drawn on the plan. 4. If parking screening is to be accomplished using a shrub hedge, plants must be no more than 3' apart. A dwarf species may not be used for parking screening. 5. Please provide the size of your proposed non - canopy trees in caliper inches for a single cane. The minimum allowable single cane size is 1.25 ". 6. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights -of -way, and adjacent property disturbed during construction. Reviewed by: Jennifer Prochazka Date: August 20, 2004 ENGINEERING 1. I will need to confirm the impact of the fire flow to the existing public system. The fire flow scenario should be calculated and/ or modeled from the existing fire hydrant on Ponderosa to the existing water line at Sara. Only 2 hydrants permitted on a 6 -in line. Please see BCS Unified Design Guidelines. 2. In addition, each fire flow scenario must stand on its own. The calculations should be separate for each building. 3. I will need to confirm that the drainage has been accounted for upstream of this project. No drainage map was submitted with the report. Due to the point discharge situation of this project, it is extremely important to not increase flows downstream. 4. In addition, two drainage reports have been submitted and approved for the adjacent sites to the west. Since this project is changing the drainage in the easement, what has been previously approved must be accommodated. 5. The storm sewer in the easement must be designed to meet City standards. The storm sewer outside the easement is private. 6. Place fire hydrant between buildings out from behind parking areas for easy, emergency access. Reviewed by: Spencer Thompson Date: August 20, 2004 ELECTRICAL NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 3 of 4 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of rigid conduit for riser poles. Developer installs first 10'. City installs remainder. 3. Developer pours transformer pad(s) per city specs and design. 4. Developer installs pull boxes as per city specs and design.(pull boxes provided by the city. 5. Developer provides digital AutoCAD 2000 version of plat and /or site plan. email to tmichalscstx.gov 6. Developer provides load data for project. 7. Developer provides temporary blanket easement for construction purposes. To release temporary blanket easement meet and bounds descriptive easements are requires. 8. Contact Tony Michalsky at 979 - 764 -3438 to coordinate electric service requirements. Reviewed by: Tony Michalsky Date: 8 -19 -04 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 4 of 4 (k I G S OF TATION CI ng & Development Services Planning D Box 9960 1 101 Texas Avenue, P.O 77842 College Station Texas 979.764.3496 Phone 979.764.3570 / Fax 979. MEMOR April 23, 2 008 TO: Senior Planner (SP) _Site Plan FROM: Lindsay Boyer, AICP, CENTER 'REVISED SOUTHWEST BUSINESS SUB JECT: age is a list of staff The following p comments plan as reque Please address the above-mentioned site p to be a ddressed. the above -m items that need Staff reviewed comments detailing review Comm owing information for further staff review: One M) and submit the foll of elevations (Sheet SP Ian with required spot One (1) revised site p E (Sheet A-1) revised elevations for Building One () re Ian, please attach a lease are not site you estions or need additional information, p comments that y t addressing with the re If you have any qu If there are com the details. Y letter explaining call me at 979.76 Attachmen Staff review comments cc: Case file #04-00500201 H ome of Texas A &M University (kff 1101 Texas Avenue, P.O. Box 9960 College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 CITY OF COLLEGE STATION MEMORANDUM April 18, 2008 TO: Becky Poe, JHW General Contractors, via fax 979.846.9143 FROM: Lindsay Boyer, AICP, Senior Planner SUBJECT: Southwest Business Center Site Plan (04 -201) Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised site plan One (1) revised set of elevations If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments pc: Case file #04- 00500201 Home of Texas A & M University STAFF REVIEW COMMENTS NO. 6 Project: SOUTHWEST BUSINESS CENTER - REVISED (SP) - 04- 00500201 PLANNING 1. The site plan we have does not reflect the parking as it has been built out on the site. The grading plan in the construction documents that I found do show what may have been built out there, but we need a revised sheet SP -M for Building E showing the correct parking layout. Also, since the building is different than what is shown on site, the parking count must be recalculated to show what is required parking, and a count of what is actually built on site. We cannot proceed with out a correct sheet SP -M. 2. The elevations we have do not reflect the building that has been built. The pages that were faxed were insufficient, and sheet A -1 in its entirety must be revised and submitted. 3. We need spot elevations along the back wall across from each end of the building and where there is a projection of the building in between for a total of 4 elevations. Because the back of the building steps back towards the residential area, and it appears that that are of the site slopes down, there may be a height issue, and we must have verification that the roof height meets the requirements set out in section 7.1 of the Unified Development Ordinance. Below is a JPG showing bubbles where we need the changes in elevations measured. 20 UrIur AND DRAINAGE ESMT — EDELWEISS ESTATES. PHASE 7 -8 _ LOT 11, BLOCK 22 - -- _ VOL PC 48 E %IST - ZONED D - 81 — 6'70 B' HIGH CMU BLOCK FENCE "- — 14241 5;4.13.3 ,. I '` LANDSCAPE LANDSCPPF BUFF E – ._ _- E Bf /FFEP _ * I -, i 54 7 5T' 1 73 41 BI.IB - 3 _ . _ 45a 2]'3SE ,Z S_ - _r - I 55 CE 6 S g 1n — - - _ =-)"' PHAS = I PHASE 22 0" _ } 190' -0' ., \ _ ° BLDG E ��4 5 7,368 SF v HAND/CAP P RAMP E %IST CONC WAL RE :6 -SP2 I I CO NC CURB �RE:4d: -SP2 I 6" � __ 108 O E Isr 9' 36' -0 IH / IH "E9r - a / � ...\ J G ' I I t , .. 12 .;P ®9' IE%ISr 4 SP O 9' / FHETLANE .. _ k15r 1111L ESMT / �� :t �:S E xlsr 34•_0" b , "� / II N r 6" CONC PVMT TYP NEW - --y N I / �_ ... 1 — .= ' . 1 1 o I 1 I 1 1 r ?—.'m Reviewed by: Lindsay Boyer Date: April 23, 2008 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and 'bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 2 VERIFICATION REPORT 4 18;55 TIME CO OS DEVELOPMENT SER TRANSMISSION COOS NAME : • 9 ?97643496 FAX TEL B SER.0 ROE2J341073 09113 10:54 8800 00: DE 82 DURATION �TANDARD PAGES) ECM RESULT MODE COLLEGE ST A.TIOI CITY O� DEVELOPMENT s? wJI�CES *�� 1101 Texas Avenue South, PO Box 9960 e Station, Texa (979) 764 -3496 COLLEGE STATION Colleg 77842 P hone (979) 764 -3570 / Fax MEMOR September 13, 20p4 TO: Mike McClure, Via fax (979) 693 -2554 P roject Manager - Site Plan FROM: Jennifer beeves, SS CENTER - REVISED (SP) BUSINESS ..� SOUTHWE B .-�. e SUBJECT: ------- Ian as reque Please adtlr above-mentioned site p be addressed• reviewed the comments d b Staff rev comments de tailing items that need to Information for further staff review: of staff review site and IandscaA One( ) revised site and landscaping plans. comments One (1) complete set of civil $204 site plan review fee site plan, If there are comments that You are not addressing with the revised TRANSMISSION VERIFICATION REPORT TIME : 09/13/2004 11:00 NAME : COCS DEVELOPMENT SER FAX : 9797643496 TEL : 9797643570 SER.# : BROE2J341073 DATE,TIME 09/13 10:59 FAX NO. /NAME 98469133 DURATION 00:00:39 PAGE {S) 02 RESULT OK MODE STANDARD ECM CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE sTATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 7643496 MEMORANDUM September 13, 2004 TO: James H. Woods, Via fax 846 -9133 FROM: Jennifer Reeves, Project Manager SUBJECT: SOUTHWEST BUSINESS CENTER - REVISED (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of civil drawings, including site and landscape plan One (1) revised site and landscaping plans. $200 site plan review fee. If there are comments that ynii are not addressing with the revised site plan, please ( CITY OF COLLEGE STATION Planning 6 Development Services 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM October 28, 2004 TO: Kendall Gillum, via fax 254.771.3739 ;/ FROM: Bridgette George, Assistant Development Manager SUBJECT: QUALITY SUITES HOTEL (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $200 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please contact Spencer Thompson or Jennifer Prochazka at 979.764.3570. Attachments: Staff review comments cc: Christian A. Galindo Via fax 846.8868 Case file #04- 00500199 Home of Texas A&M University STAFF REVIEW COMMENTS NO. 2 Project: QUALITY SUITES HOTEL (SP) - 04- 00500199 PLANNING 1. Please add to the Landscape Analysis that the caliper size for non - canopy trees are measured on a single cane. Reviewed by: Jennifer Prochazka Date: October 4, 2004 ENGINEERING 1. You do know about and have the BCS Unified Design Guidelines? 2. Note 13. Change to conform to the BCS Unified Design Guidelines and Specifications. 3. Note 19. Change to C909. 4. Note 22. Change to a copy of the BCS Unified Design Guidelines and Specifications on site 5. Note 24. Why? All plumbing must meet Plumbing Code. 6. Note 28. Wrong reference. 7. Note 29. Site is dedicating a Temporary Blanket PUE. In order for TB to be removed, required easements must be dedicated by separate instrument. 8. Note 35. Where is lay -down curb allowed? 9. Note should be added that construction not to disturb/ damage existing sewer line. 10. Show sewer services to buildings. If a restaurant is proposed, include grease trap information. All private sewer lines to meet Plumbing Code. 11. Provide detail for 11 water meters and manifold. Show water lines to building. All private waterlines to meet Plumbing Code. All water meters to be out of ROW, on- site and in PUE. 12.Add note to replace curb at former driveway locations on Ponderosa. 13. Change all references to C900 to C909. 14. Structural fill required on fire line to building under pavement. 15.1s the contractor planning on installing sleeving under pavement for required irrigation? 16. Driveway Surface Detail is being taken as meeting the minimum requirement for the Fire Lane. Please denote detail as Driveway/ Fire Lane Surface. Waterline Plan 1. Sta.0 +00. There should be a tee there. This project can remove 6 -in line and insert 8 -in line into tee. 2. Install 8 -in valve at Sta. 2 +45. 3. At end of line, remove note concerning reducer. 4. Structural fill is required under pavement; street, driveway. Reviewed by: Spencer Thompson Date: October 27, 2004 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 3 CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM November 10, 2004 TO: Kendall Gillum, via fax 254.771.3739 FROM: Jennifer Prochazka, Staff Planner SUBJECT: QUALITY SUITES HOTEL (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: Six (6) sets of revised set of plans. Two (2) revised site plans One (1) revised landscape plan Easement Dedication Sheet and required documents. Please note that the Easement Dedication Sheet and the necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments cc: Christian A. Galindo, via fax 979.846.8868 Case file #04- 00500199 STAFF REVIEW COMMENTS NO. 3 Project: QUALITY SUITES HOTEL (SP) — 04- 00500199 PLANNING 1. No Comments Reviewed by: Jennifer Prochazka Date: 11 -8 -04 ENGINEERING 2. Need NOI from TCEQ for Development Permit. Reviewed by: Spencer Thompson Date: 11 -8 -04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 2 of 2 GALINDO ENGINEERS AND PLANNERS INC. 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 12 -04 PUBLIC UTILITY EASEMENT NO. 1 4,350 -SQ. FT PART OF LOTS 7 AND 8, BLOCK 18 SOUTHWOOD VALLEY SECTION 4 -B COLLEGE STATION, TEXAS Being a 4,350 -sq. ft. tract or parcel of land lying and being a part of Lots 7 and 8, Block 18, Southwood Valley Section 4 -B, an addition to the City of College Station according to the plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas, and said 4,350 -sq. ft. tract being more particularly described as follows: BEGINNING at a 1/2" iron rod found on the southwestern right of way line of Texas Avenue South, also called State Highway 6 South, said rod also marking the easternmost corner of said Lot 7, and the northernmost corner of said Lot 8; THENCE S 42 °56' 46" E, along the northeastern boundary line of said Lot 8, for a distance of 5.51'; THENCE S 49 °26' 48" W, through said Lot 8, parallel to and 5.51' away from the common boundary line between said Lots 7 and 8, for a distance of 290.00'; THENCE N 42 °56' 46" W, continuing through said Lot 8 and into Lot 7, for a distance of 15.01'; THENCE N 49 °26' 48" E, continuing through said Lot 7, parallel to and 9.50' away from the common boundary line between said Lots 7 and 8 for a distance of 290.00' to the southwestern right of way line of Texas Avenue South and the northeastern boundary line of said Lot 7; THENCE S 42 °56' 46" E, along said northeastern boundary line for a distance of 9.50' to the POINT OF BEGINNING containing 4,350 sq. ft. of land more or less. Note: Bearing source is plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas. ♦ ° j C' - - ' . GALINDO, R.P.L.S. # 4473, P.E. 53425 ,t • 0 September 24, 2004 %1 CHRISTIAN ANZE G L aDO ;:s • c' :� 44 '3 : 2 - ,1 17 4,"*"'` S' ■ S . p` C iinimm> GALINDO ENGINEERS AND PLANNERS, INC. O L I -1419 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 1 ?.4Y4 12 -04 PUBLIC UTILITY EASEMENT NO. 1 ^ 4,050-SQ. FT �( P ART OF LOTS 7 AND 8, BLOCK 18 SOUTHWOOD VALLEY SECTION 4 -B COLLEGE STATION, TEXAS Being a 4,050 -sq. ft. tract or parcel of land lying and being a part of Lots 7 and 8, Block 18, Southwood Valley Section 4 -B, an addition to the City of College Station according to the plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas, and said 4,050 -sq. ft. tract being more particularly described as follows: BEGINNING at a 1/2" iron rod found on the southwestern right of way line of Texas Avenue South, also called State Highway 6 South, said rod also marking the easternmost corner of said Lot 7, and the northernmost corner of said Lot 8; THENCE S 42 °56' 46" E, along the northeastern boundary line of said Lot 8, for a distance of 7.51'; THENCE S 49 °26' 48" W, through said Lot 8, parallel to and 7.5' away from the common boundary line between said Lots 7 and 8, for a distance of 270.00'; THENCE N 42 °56' 46" W, continuing through said Lot 8 and into Lot 7, for a distance of 15.01'; THENCE N 49 °26' 48" E, continuing through said Lot 7, parallel to and 7.5' away from the common boundary line between said Lots 7 and 8 for a distance of 270.00' to the southwestern right of way line of Texas Avenue South and the northeastern boundary line of said Lot 7; THENCE S 42 °56' 46" E, along said northeastern boundary line for a distance of 7.51' to the POINT OF BEGINNING containing 4,050 sq. ft. of land more or less. Note: Bearing source is plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas. CHRISTIAN A. GALINDO, R.P.L.S. # 4473, P.E. 53425 A Q.• s •• � ' August 12, 2004 ' ; Q * `Acp • CHRISTIAN ANZE GALINDO 1? ' ;9 0 4473 Q' F Js �p O 2. •.. > <animmoni GALINDO ENGINEERS AND PLANNERS INC. 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 12 -04 PUBLIC UTILITY EASEMENT 2 1,084 S.F. PART OF LOT 10, BLOCK 18 SOUTHWOOD VALLEY SECTION 4 -B BRAZOS COUNTY, TEXAS Being a 1,084 -S.F. tract or parcel of land lying and being a part of Lot 10, Block 18 Southwood Valley, Section 4 -B, an addition to the City of College Station according to the plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas, and said 1,084 -S.F tract being more particularly described as follows: COMMENCING at a 1/2" iron rod marking the southernmost corner of said Lot 10, said rod also marking the northern right of way line of Ponderosa Road, a 70' -wide public right of way. THENCE N 49 °20'47" E, along said right of way line for a distance of 103.55' to the POINT OF BEGINNING; THENCE N 42 °56'46" W, through said Lot 10 for a distance of 72.00'; THENCE N 47 °03'14" E, continuing through said Lot 10, for a distance of 15.00'; THENCE S 42 °56'46" E, continuing through said Lot 10, for a distance of 72.60' to the northern right of way line of said Ponderosa Road; THENCE S 49 °20'47" W, along said right of way line, for a distance of 15.01' to the POINT OF BEGINNING, containing 1,084 -S.F of land more or less. Note: Bearing source is plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas. C - ISTI . ALINDO, R.P.L.S. # 4473, P.E. 53425 �.. ' s T E Q. in %CP August 12, 2004 �•• Q CHRISTIAN ANZE GAt$fl)C . ) V 447.; ,F'' { c.;J U ,sue GALINDO ENGINEERS AND PLANNERS, INC. 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 12 -04 ACCESS EASEMENT 2,600 -SQ. FT PART OF LOTS 7 AND 8, BLOCK 18 SOUTHWOOD VALLEY SECTION 4 -B COLLEGE STATION, TEXAS Being a 2,600 -sq. ft. tract or parcel of land lying and being a part of Lots 7 and 8, Block 18, Southwood Valley Section 4 -B, an addition to the City of College Station according to the plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas, and said 2,600 -sq. ft. tract being more particularly described as follows: BEGINNING at a 1/2" iron rod found on the southwestern right of way line of Texas Avenue South, also called State Highway 6 South, said rod also marking the easternmost corner of said Lot 7, and the northernmost corner of said Lot 8; THENCE S 42 °56' 46" E, along the northeastern boundary line of said Lot 8, for a distance of 20.00'; THENCE S 47 °03' 14" W, through said Lot 8, for a distance of 65.00'; THENCE N 42 °56' 46" W, continuing through said Lot 8 and into Lot 7, for a distance of 40.00'; THENCE N 47 °03' 14" E, continuing through said Lot 7, for a distance of 65.00' to the southwestern right of way line of Texas Avenue South and the northeastern boundary line of said Lot 7; THENCE S 42 °56' 46" E, along said boundary line for a distance of 20' to the POINT OF BEGINNING containing 2,600 sq. ft. of land more or less. Note: Bearing source is plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas. / / iv CHRISTIAN A. GALINDO, R.P.L.S. # 4473, P.E. 53425 August 12, 2004 f` OF • CHRISTIAN ANZE GALINDO 4473 ;: Q . t GALINDO ENGINEERS AND PLANNERS INC. 3833 South Texas Ave., Suite 21 B an, Texas 77802 ry (979) 846 -8868 ` 12 -04 5 5 PUBLIC UTILITY EASEMENT NO. 1 4,050 -SQ. FT PART OF LOTS 7 AND 8, BLOCK 18 Ar.41 SOUTHWOOD VALLEY SECTION 4 -B COLLEGE ST ATION, TEXAS Being a 4,050 -sq. ft. tract or parcel of land lying and being a part of Lots 7 and 8, Block 18, Southwood Valley Section 4 -B, an addition to the City of College Station according to the plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas, and said 4,050 -sq. ft. tract being more particularly described as follows: BEGINNING at a 1/2" iron rod found on the southwestern right of way line of Texas Avenue South, also called State Highway 6 South, said rod also marking the easternmost corner of said Lot 7, and the northernmost corner of said Lot 8; THENCE S 42 °56' 46" E, along the northeastern boundary line of said Lot 8, for a distance of 7.51'; THENCE S 49 °26' 48" W, through said Lot 8, parallel to and 7.5' away from the common boundary line between said Lots 7 and 8, for a distance of 270.00'; THENCE N 42 °56' 46" W, continuing through said Lot 8 and into Lot 7, for a distance of 15.01'; THENCE N 49 °26' 48" E, continuing through said Lot 7, parallel to and 7.5' away from the common boundary line between said Lots 7 and 8 for a distance of 270.00' to the southwestern right of way line of Texas Avenue South and the northeastern boundary line of said Lot 7; THENCE S 42 °56' 46" E, along said northeastern boundary line for a distance of 7.51' to the POINT OF BEGINNING containing 4,050 sq. ft. of land more or less. Note: Bearing source is plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas. • 4 - i . OF CHRISTIAN A. GALINDO, R.P.L.S. # 4473, P.E. 53425 ;Q s r 9 F� ' August 12, 2004 I ; Q * 0 4 .. CHRISTIAN ANZE GAL NDO \ 4473 ° �r.4 7 o`:' O C ounimm> GALINDO ENGINEERS AND PLANNERS INC. • 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 12 -04 PUBLIC UTILITY EASEMENT 2 1,084 S.F. PART OF LOT 10, BLOCK 18 SOUTHWOOD VALLEY SECTION 4 -B BRAZOS COUNTY, TEXAS Being a 1,084 -S.F. tract or parcel of land lying and being a part of Lot 10, Block 18 Southwood Valley, Section 4 -B, an addition to the City of College Station according to the plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas, and said 1,084 -S.F tract being more particularly described as follows: COMMENCING at a 1/2" iron rod marking the southernmost corner of said Lot 10, said rod also marking the northern right of way line of Ponderosa Road, a 70' -wide public right of way. THENCE N 49 °20'47" E, along said right of way line for a distance of 103.55' to the POINT OF BEGINNING; THENCE N 42 °56'46" W, through said Lot 10 for a distance of 72.00'; THENCE N 47 °03'14" E, continuing through said Lot 10, for a distance of 15.00'; THENCE S 42 °56'46" E, continuing through said Lot 10, for a distance of 72.60' to the northern right of way line of said Ponderosa Road; THENCE S 49 °20'47" W, along said right of way line, for a distance of 15.01' to the POINT OF BEGINNING, containing 1,084 -S.F of land more or less. Note: Bearing source is plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas. zZ/9 /. / _ OF T' `r'; C - ISTI , ■ . ALINDO, R.P.L.S. # 4473, P.E. 53425 i s r t q � ;! August 12, 2004 A « :.... .... . ... .. .... .... ,', CHRISTI' ,4'.■Zc i GALINDO ENGINEERS AND PLANNERS, INC. 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 12 -04 ACCESS EASEMENT 2,600 -SQ. FT PART OF LOTS 7 AND 8, BLOCK 18 SOUTHWOOD VALLEY SECTION 4 -B COLLEGE STATION, TEXAS Being a 2,600 -sq. ft. tract or parcel of land lying and being a part of Lots 7 and 8, Block 18, Southwood • Valley Section 4 -B, an addition to the City of College Station according to the plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas, and said 2,600 -sq. ft. tract being more particularly described as follows: BEGINNING at a 1/2" iron rod found on the southwestern right of way line of Texas Avenue South, also called State Highway 6 South, said rod also marking the easternmost corner of said Lot 7, and the northernmost corner of said Lot 8; THENCE S 42 °56' 46" E, along the northeastern boundary line of said Lot 8, for a distance of 20.00'; THENCE S 47 °03' 14" W, through said Lot 8, for a distance of 65.00'; THENCE N 42 °56' 46" W, continuing through said Lot 8 and into Lot 7, for a distance of 40.00'; THENCE N 47 °03' 14" E, continuing through said Lot 7, for a distance of 65.00' to the southwestern right of way line of Texas Avenue South and the northeastern boundary line of said Lot 7; THENCE S 42 °56' 46" E, along said boundary line for a distance of 20' to the POINT OF BEGINNING containing 2,600 sq. ft. of land more or less. Note: Bearing source is plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas. � CHRISTIAN A. GALINDO, R.P.L.S. # 4473, P.E. 53425 August 12, 2004 r%= ` OF\ , ,` P �■s r r Q °' r CHRISTIAN ANZ[ CAL dcJu )),, \,,.. 4,,,t, •� 447 °- r •• ° F o;•°:0 a f < 4111■ GALINDO ENGINEERS AND PLANNERS, INC. 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 TRANSMITTAL LETTER GEP Project: 12 -04 Date: August 12, 2004 TO: Bridgette George Assistant Development manager City of College Station FROM: Christian A. Galindo, P.E., R.P.L.S. SUBJECT: Quality Suites Hotel & Quality Office Suites TRANSMITTED: (x) herewith () per your request () under separate cover ACTION REQUESTED: (x) review () approval and signature () information / use DOCUMENTS: (x) drawings () cost estimate (x) report / specifications () correspondence (x ) other date copies description _08 /12 /04_I Plan and Drainage Plan (2 sheets) _08 /12 /04_I of Construction Drawings (5 sheets) _ /10 /04_I Report (amended by letter of Aug. 10, 2004) _08/11/04_ 2 Fire Flow and Water Demand Analysis _08 /12 /04_I Engineer's Cost Estimate _08/11/04_ 1 SWPPP _08 /12 /04_I Plan Application Form _08/12/04_111 Site Plan Check List _08/12/04_1 1,000.00 check for Application Fee as follows: Site Plan $ 200.00, Development $ 200.00, Infrastructure Inspection $ 600.00 _08/12/04_I_2I_Sets of Metes &t Bounds Descriptions for AE, PUE 1 and PUE 2 COMMENTS: 1. Easement Information Sheet and ancillary documents will be submitted separately by Owner/ Developer 2. TX Dot Permits will be secured directly by Owner /Developer cc: David Gillum (x) with enclosures, () w/o enclosures () with enclosures, () w/o enclosures GALINDO ENGINEERS AND PLANNERS, INC. 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 TRANSMITTAL LETTER GEP Project: /2.44 Date: /4 2004 - TO: ALA-A/ G/1343-5 ? � Try f0F• i'OL LAG 5'7 -77€ Az FROM: //1/4104 y': Pe'1 1, SUBJECT: 624/044/7Y p TRANSMITTED: ( erewith f () per your request () under separate cover (� ACTION REQUESTED: review Z () approval and signature () information / use DOCUMENTS: ( rawings (e..)-ti)t estimate ( report / specifications () correspondence () other date copies description / I ,T2& s 4 /VA 'E K e I / 1 dee41 /45 E-17 et= r7 2k 77GA.0 ri itt% /NG I //1!G G L/ .0&"" S PV; TRV<As AVE 1_1_1 L A4r z' CG'.6[T T/ / CG e/OING � ' GO L 'MAC 1 / I /.: / r_ / - G -� - _ I / I 7 !1 G ✓ y,: . 7 , 1 / I d' W. V/P _� " COMMENTS: cc: XENDA.LL G / GLUM () with enclosures, () w/o enclosures ,'AX; 0 with enclosures, 0 w/o enclosures 4C".111.1.1111:rlir JUN -08 -04 TUE 17:15 GALINDO ENGINEERS 979 8468868 P.01 OVN GALINDO ENGINEERS AND PLANNERS, INC. 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 FAX MEMO GEP Project: Date: JUNk" 3, 2D04 TO: MA I.aY ALP€ C /TY aF" COccEta6 .S774776Al FAX : 764 - 34 FROM: !� SUBJECT: _ A. ,. : LL/Ad d l i - _ i RETURN FAX # 979.846.8868 NUMBER OF PAGES: Fdt/AZ COMMENTS: /7 1'7k' Ott4Z PRAW/4/a 9 A'Dw MDNPA Y 5 6/IliVE /4) o if7' /AY 45 yea! 'EA/'. P[ ��. Z £ 4, b4/ 7)'/,47" 7: /. 6 /M /NARy .P. VE-L doc . Cc; 4'4" 6/GLUM n4lx:2,54- 77/ - 37c x4. From: "Christian A. Galindo" <chrisgal @myriad.net> To: "Jennifer Prochazka" <JProchazka @cstx.gov> Date: 9/1/2004 10:24:34 PM Subject: Re: Re: Quality Suites Hotel & Office Suites Site Plan on SH6South Jennifer, Thanks for your email. I need to share this response with Kendall. Chris Christian A. Galindo, P.E., R.P.L.S. http://pages.tca.net/chrisgal Original Message From: "Jennifer Prochazka" <JProchazka @cstx.gov> To: <chrisgal @myriad.net> Cc: "Spencer Thompson" <Sthompson @cstx.gov> Sent: Wednesday, September 01, 2004 12:16 PM Subject: Fwd: Re: Quality Suites Hotel & Office Suites Site Plan on SH6South > Chris, > please see response from TxDOT. Thanks! > Jennifer Prochazka > Staff Planner > Development Services > City of College Station > tel.: 979.764.3570 > fax: 979.764.3496 > »> "Jay Page" <JPAGE @dot.state.tx.us> 9/1/2004 11:59:36 AM »> > Yes, based on the posted 45 MPH @ this location, there should > be 360' between (not c -c) Ponderosa Drive & the proposed > driveway for Quality Suites Hotel. Please call (778 -6233) if you > have any questions. > »> "Jennifer Prochazka" <JProchazka @cstx.gov> 9/1/2004 9:26:58 AM »> > Based on the following comment received for the Quality Suites Hotel & > Office Suites Site Plan on SH 6 South... > "Based on TxDOT's "Regulations for Access Driveways to State > Highways" one access point to the west frontage road is > approved. Access regulations are primarily based on posted > speed > limits (WFR = 45 MPH) and distances to adjacent access points. > With a proposed one -way frontage road to be developed @ this > site, it is TxDOT's recommendation that a right -in & right -out > driveway with median divider island (small) be incorporated in > the access driveway design." > ...is the proposed location of the drive approved or should it be move > to the north to meet the spacing requirements? I understand the > comment > to mean that since it is possible to meet spacing requirements, that > they must do this. The applicant understands that the proposed > location > was approved. Please let me know as soon as possible! Thanks! > Jennifer Prochazka > Staff Planner > Development Services > City of College Station > tel.: 979.764.3570 > fax: 979.764.3496 > College Station. Heart of the Research Valley. > College Station. Heart of the Research Valley. GALINDO ENGINEERS AND PLANNERS, INC. 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 TRANSMITTAL LETTER GEP Project: /2.— ©4 Date: /WI, zs ,24964 TO: SPEW' eR 7 M PSOM CrTY TiK1 /DN FROM: 7 so,/ bz/A/cRN SUBJECT: cQu#?L/TV 5cirr S No - rEL * &/A1.iTY suirE5 TRANSMITTED: K herewith () per your request () under separate cover ACTION REQUESTED: () review () approval and signature ( ) information / use DOCUMENTS: w drawings ( ) cost estimate () report / specifications () correspondence () other date copies description f? -Z4 - O'1 1 1 I PERMIT T© Cwn/srR/icr ,/CLESS DR, vE wAY F4e ie lTir - s Y o. f /Z `l74 I f I S/TE AND /AMi>seAP /I'/4 9 —/Z -04 I I I C7RI<ta;N1 AAID 2>earn/,4cE / ■N I I I I I I COMMENTS: S PE ET. ,& E z1EVE T/ /S /5 1WG /JFOi n/i 14TaW Y ©c! PI3C FED cc: 10E/V 4 /c.4-e%M ("), FAX) 0 with enclosures, *w/o enclosures // () with enclosures, () w/o enclosures 4D%L m -),S igq GALINDO ENGINEERS AND PLANNERS, INC. 3833 South Texas Ave., Suite 213 Bryan, Texas 77802 (979) 846 -8868 12 -04 ACCESS EASEMENT 3,200 -SQ. FT PART OF LOT 7, BLOCK 18 SOUTHWOOD VALLEY SECTION 4 -B COLLEGE STATION, TEXAS Being a 3,200 -sq. ft. tract or parcel of land lying and being a part of Lot 7, Block 18, Southwood Valley Section 4- B, an addition to the City of College Station according to the plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas, and said 3,200 -sq. ft. tract being more particularly described as follows: COMMENCING at a 1/2" iron rod found on the southwestern right of way line of Texas Avenue South, also called State Highway 6 South, said rod also marking the easternmost corner of said Lot 7, and the northernmost corner of Lot 8, said Block 18; THENCE N 42 °56' 46" W, along the southwest right of way of Texas Avenue South which is also the northeastern boundary line of said Lot 7, for a distance of 24.80' to the POINT OF BEGINNING; THENCE S 47 °03' 14" W, through said Lot 7, for a distance of 40.00'; THENCE S 42 °56' 46" E, continuing through said Lot 7 to the northwestern boundary line of said Lot 8, for a distance of 23.20'; THENCE S 49 °20' 47" W, along said northwestern boundary line, for a distance of 30.02'; THENCE N 42 °56' 46" W, through said Lot 7, for a distance of 58.00'; THENCE N 47 °03' 14" E, continuing through said Lot 7, to the northeastern boundary line of said Lot 7, said line also the southwest right of way line of Texas Avenue South, for a distance of 70.00'; THENCE S 42 °56' 46" E, along said right of way line, for a distance of 36.00', to the POINT OF BEGINNING containing 3,200 sq. ft. of land more or less. Note: Bearing source is plat recorded in Volume 367, Page 239, Deed Records, Brazos County, Texas. "1.541t--rjaLLIFLO .... 74- ti CHRISTIAN � ANZE (ALkIDO V CH - . • LINDO, R.P.L.S. # 4473, P.E. 53425 9 4473 September 24, 2004 '✓ CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM August 23, 2004 TO: James H. Woods, Via fax 846 -9133 FROM: Jennifer Reeves, Project Manager SUBJECT: SOUTHWEST BUSINESS CENTER - REVISED (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised site and landscaping plan, and Two (2) revised drainage reports If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764 -3570. Attachments: Staff review comments cc: C. Barbu Architect, Via fax 775 -5642 LA Berry, PE 1811 Rose Street, Bryan TX 77802 Case file #04- 00500201 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 1 of 3 STAFF REVIEW COMMENTS NO. 2 Project: SOUTHWEST BUSINESS CENTER - REVISED (SP) - 04- 00500201 PLANNING 1. It is not necessary to break the square footage out by buildings, lots, nor by office or retail. This is considered a shopping center less than 75,000 square feet which requires 1 -150 parking regardless of how much retail or office use. However you can note the percentage of restaurant /bar use. Once the shopping center reaches 25% restaurant /bar use then anything over 25% will be required to meet the strictest of the parking requirement for that use. This will keep the parking legend less confusing. 2. Please adjust building square footages to match what the building permits that have been pulled. 3. As of 8 -23 -04 parking required = 160, parking provided = 201, parking available = 41 spaces (or) 6,150 square feet. Over all parking requirement = 308 parking spaces, parking provided = pending site plan approval. 4. Please consolidate the landscape and streetscape requirements. This will help simplify the landscape and streetscape legend. 5. FYI: As stated previously in review comments #1. A buffer is not required between commercial and commercial. Reviewed by: Jennifer Reeves Date: 08 -23 -04 ENGINEERING 1. As previously commented, drainage report for the proposed additional parking lot indicates there will not be a Building C. Detention requirements for this parking lot take this into account by reducing detention requirement. Are there plans for a Building C? 2. As previously commented, the design of the existing drainage channel with flume tying into the buffer wall was not approved on the original Site Plan. It was accepted with additional engineering design including a berm to recover lost capacity. Original design called for flume in bottom center channel with sloped sidewalls. Provide detail of drainage channel showing how flume ties into wall and ground and how capacity will be attained. 3. As previously commented, Drainage Report for parking on Lot 9 needs to show that the drainage channel can carry the flow that is going there now from upstream. Are your design elevations adequate to allow for the upstream properties to discharge into the channel? Reviewed by: Carol Cotter Date: 08 -23 -04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 3 ELECTRICAL 1. We currently have temporary blanket easements on property. Developer needs to provide meets and bounds descriptive easements for electric infrastructure as installed in order for blanket easement to be released. 2. Contact College Station Utilities, Tony Michalsky at 979 - 764 -3438 on process for permanent easement dedication. Reviewed by: Tony Michalsky Date: 8 -19 -04 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 3 of 3 if CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM August 23, 2004 TO: LA Berry, PE 1811 Rose Street, Bryan TX 77802 FROM: Jennifer Reeves, Project Manager SUBJECT: SOUTHWEST BUSINESS CENTER - REVISED (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised site and landscaping plan, and Two (2) revised drainage reports If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764 -3570. Attachments: Staff review comments cc: James H. Woods, Via fax 846 -9133 C. Barbu Architect, Via fax 775 -5642 Case file #04- 00500201 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 1 of 3 STAFF REVIEW COMMENTS NO. 2 Project: SOUTHWEST BUSINESS CENTER - REVISED (SP) - 04- 00500201 PLANNING 1. It is not necessary to break the square footage out by buildings, lots, nor by office or retail. This is considered a shopping center less than 75,000 square feet which requires 1 -150 parking regardless of how much retail or office use. However you can note the percentage of restaurant /bar use. Once the shopping center reaches 25% restaurant /bar use then anything over 25% will be required to meet the strictest of the parking requirement for that use. This will keep the parking legend less confusing. 2. Please adjust building square footages to match what the building permits that have been pulled. 3. As of 8 -23 -04 parking required = 160, parking provided = 201, parking available = 41 spaces (or) 6,150 square feet. Over all parking requirement = 308 parking spaces, parking provided = pending site plan approval. 4. Please consolidate the landscape and streetscape requirements. This will help simplify the landscape and streetscape legend. 5. FYI: As stated previously in review comments #1. A buffer is not required between commercial and commercial. Reviewed by: Jennifer Reeves Date: 08 -23 -04 ENGINEERING 1. As previously commented, drainage report for the proposed additional parking lot indicates there will not be a Building C. Detention requirements for this parking lot take this into account by reducing detention requirement. Are there plans for a Building C? 2. As previously commented, the design of the existing drainage channel with flume tying into the buffer wall was not approved on the original Site Plan. It was accepted with additional engineering design including a berm to recover lost capacity. Original design called for flume in bottom center channel with sloped sidewalls. Provide detail of drainage channel showing how flume ties into wall and ground and how capacity will be attained. 3. As previously commented, Drainage Report for parking on Lot 9 needs to show that the drainage channel can carry the flow that is going there now from upstream. Are your design elevations adequate to allow for the upstream properties to discharge into the channel? Reviewed by: Carol Cotter Date: 08 -23 -04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 3 ELECTRICAL 1. We currently have temporary blanket easements on property. Developer needs to provide meets and bounds descriptive easements for electric infrastructure as installed in order for blanket easement to be released. 2. Contact College Station Utilities, Tony Michalsky at 979 - 764 -3438 on process for permanent easement dedication. Reviewed by: Tony Michalsky Date: 8 -19 -04 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 3 of 3 CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM September 13, 2004 TO: C. Barbu Architect, Via fax 775 -5642 FROM: Jennifer Reeves, Project Manager SUBJECT: SOUTHWEST BUSINESS CENTER - REVISED (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of civil drawings, including site and landscape plan One (1) revised site and landscaping plans. $200 site p lan review fee. If there are comments that ou are not addressing with the revised site plan, please Y 9 P ,P attach a letter explaining the details. If you have any questions or need additional P g Y Yq information, please call me at 764 -3570. Attachments: Staff review comments cc: Mike McClure, Via fax (979) 693 -2554 James H. Woods, Via fax 846 -9133 Case file #04- 00500201 STAFF REVIEW COMMENTS NO. 3 Project: SOUTHWEST BUSINESS CENTER - REVISED (SP) - 04- 00500201 PLANNING 1. (FYI) Per staff review comments #2 for the Master Parking Plan: Please adjust building square footages to match the building permits that have been pulled. Please include the latest two building permit request. 2. The landscape legend includes lots 7, 8 & a portion of 9, however it is noted. Please lots 7, 8 & 9 to the Project Analysis. 3. The most southerly driveway has been constructed, please show this on the plans. Reviewed by: Jennifer Reeves Date: 09 -01 -04 ENGINEERING 1. A Building Permit will be required for the buffer wall since it is taller than 6 feet. 2. Add the revised Flume Section Detail to the plans. Reviewed by: Carol Cotter Date: 09 -10 -04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 2 CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STAIION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM September 13, 2004 TO: James H. Woods, Via fax 846 -9133 FROM: Jennifer Reeves, Project Manager SUBJECT: SOUTHWEST BUSINESS CENTER - REVISED (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of civil drawings, including site and landscape plan One (1) revised site and landscaping plans. $200 site plan review fee. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764 -3570. Attachments: Staff review comments cc: C. Barbu Architect, Via fax 775 -5642 Mike McClure, Via fax (979) 693 -2554 Case file #04- 00500201 STAFF REVIEW COMMENTS NO. 3 Project: SOUTHWEST BUSINESS CENTER - REVISED (SP) - 04- 00500201 PLANNING 1. (FYI) Per staff review comments #2 for the Master Parking Plan: Please adjust building square footages to match the building permits that have been pulled. Please include the latest two building permit request. 2. The landscape legend includes lots 7, 8 & a portion of 9, however it is noted. Please lots 7, 8 & 9 to the Project Analysis. 3. The most southerly driveway has been constructed, please show this on the plans. Reviewed by: Jennifer Reeves Date: 09 -01 -04 ENGINEERING 1. A Building Permit will be required for the buffer wall since it is taller than 6 feet. 2. Add the revised Flume Section Detail to the plans. Reviewed by: Carol Cotter Date: 09 -10 -04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 2 CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM September 13, 2004 TO: Mike McClure, Via fax (979) 693 -2554 FROM: Jennifer Reeves, Project Manager SUBJECT: SOUTHWEST BUSINESS CENTER - REVISED (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of civil drawings, including site and landscape plan One (1) revised site and landscaping plans. $200 site plan review fee. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764 -3570. Attachments: Staff review comments cc: James H. Woods, Via fax 846 -9133 C. Barbu Architect, Via fax 775 -5642 Case file #04- 00500201 STAFF REVIEW COMMENTS NO. 3 Project: SOUTHWEST BUSINESS CENTER - REVISED (SP) - 04- 00500201 PLANNING 1. (FYI) Per staff review comments #2 for the Master Parking Plan: Please adjust building square footages to match the building permits that have been pulled. Please include the latest two building permit request. 2. The landscape legend includes lots 7, 8 & a portion of 9, however it is noted. Please lots 7, 8 & 9 to the Project Analysis. 3. The most southerly driveway has been constructed, please show this on the plans. Reviewed by: Jennifer Reeves Date: 09 -01 -04 ENGINEERING 1. A Building Permit will be required for the buffer wall since it is taller than 6 feet. 2. Add the revised Flume Section Detail to the plans. Reviewed by: Carol Cotter Date: 09 -10 -04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your • next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 2 CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM August 5, 2004 TO: C. Barbu Architect, Via fax 775 -5642 FROM: Jennifer Reeves, Project Manager SUBJECT: SOUTHWEST BUSINESS CENTER I (SP) Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: Two (2) revised site and landscaping plans. $200 site plan review fee. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764 -3570. Attachments: Staff review comments cc: LA Berry, PE 1811 Rose Street, Bryan TX 77802 James H. Woods, Via fax 846 -9133 Case file # 03- 00500110 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 1 of 3 CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM August 23, 2004 TO: C. Barbu Architect, Via fax 775 -5642 FROM: Jennifer Reeves, Project Manager SUBJECT: SOUTHWEST BUSINESS CENTER - REVISED (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) revised site and landscaping plan, and Two (2) revised drainage reports If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764 -3570. Attachments: Staff review comments cc: LA Berry, PE 1811 Rose Street, Bryan TX 77802 James H. Woods, Via fax 846 -9133 Case file #04- 00500201 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 1 of 3 STAFF REVIEW COMMENTS NO. 2 Project: SOUTHWEST BUSINESS CENTER - REVISED (SP) - 04- 00500201 PLANNING 1. It is not necessary to break the square footage out by buildings, lots, nor by office or retail. This is considered a shopping center less than 75,000 square feet which requires 1 -150 parking regardless of how much retail or office use. However you can note the percentage of restaurant /bar use. Once the shopping center reaches 25% restaurant /bar use then anything over 25% will be required to meet the strictest of the parking requirement for that use. This will keep the parking legend Tess confusing. 2. Please adjust building square footages to match what the building permits that have been pulled. 3. As of 8 -23 -04 parking required = 160, parking provided = 201, parking available = 41 spaces (or) 6,150 square feet. Over all parking requirement = 308 parking spaces, parking provided = pending site plan approval. 4. Please consolidate the landscape and streetscape requirements. This will help simplify the landscape and streetscape legend. 5. FYI: As stated previously in review comments #1. A buffer is not required between commercial and commercial. Reviewed by: Jennifer Reeves Date: 08 -23 -04 ENGINEERING 1. As previously commented, drainage report for the proposed additional parking lot indicates there will not be a Building C. Detention requirements for this parking lot take this into account by reducing detention requirement. Are there plans for a Building C? 2. As previously commented, the design of the existing drainage channel with flume tying into the buffer wall was not approved on the original Site Plan. It was accepted with additional engineering design including a berm to recover lost capacity. Original design called for flume in bottom center channel with sloped sidewalls. Provide detail of drainage channel showing how flume ties into wall and ground and how capacity will be attained. 3. As previously commented, Drainage Report for parking on Lot 9 needs to show that the drainage channel can carry the flow that is going there now from upstream. Are your design elevations adequate to allow for the upstream properties to discharge into the channel? Reviewed by: Carol Cotter Date: 08 -23 -04 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 3 ELECTRICAL 1. We currently have temporary blanket easements on property. Developer needs to provide meets and bounds descriptive easements for electric infrastructure as installed in order for blanket easement to be released. 2. Contact College Station Utilities, Tony Michalsky at 979 - 764 -3438 on process for permanent easement dedication. Reviewed by: Tony Michalsky Date: 8 -19 -04 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 3 of 3 /2-0* .S.EP77 2, 200.4. cl C OF COLLEGE STATION 1 DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone (979) 764 -3570 / Fax (979) 764 -3496 MEMORANDUM August 30, 2004 TO: Kendall Gillum, via fax 254.771.3739 FROM: Jennifer Prochazka, Staff Planner SUBJECT: QUALITY SUITES HOTEL (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comment and submit the following information for further staff review: One (1) revised set of plans. V -e / Easement Dedication Sheet and required documents.' 'fr � Please note that the Easement Dedication Sheet and the necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 979.764.3570. Attachments: Staff review comments , 414 cc: Christian A. Galindo, via fax 979.846.8868 f' (29 Case file #04- 00500199 STAFF REVIEW COMMENTS NO. 1 Project: QUALITY SUITES HOTEL (SP) - 04 00500199 STOP REVIEW. Staff has received comment from TxDOT that a driveway permit will not be issued along Texas Avenue. Due to the impact this causes, a full review at this time would be futile. Preliminary comments are being returned at this time. PLANNING 7ZE's OZ. vEn - 1. The following comment is from TxDOT: "Based on TxDOT's 'Regulations for A s _ Driveways to State Highways' access to the west frontage road is denied. Access regulations are primarily based on posted speed limits (WFR = 45 MPH) and distances to adjacent access points. Additionally, driveway location distance (upstream) from the proposed new SH 6 exit ramp @ Ponderosa Dr. could be a factor." v 2' The proposed parking area is not permitted in the drainage easement. i _. - - 50G✓� °� Please show all fire lanes throughout t e site. r _� _. Jic Please show proposed FDC location. , I AI (4'1.. f/v. Please label existing fire hydrant on Ponderosa. �J �6. he opposite drive on Ponderosa near intersection th t is labeled as "Abandoned Drives" is gated, but still in use. PO prOSCx 61,n kit oG€i.TL(JY tz . Please call out the actual height and material of dumpster en clos The southernmost enclosure will require gates because it is visible from the right-of-way. ✓,, 'he minimum clear opening is 12' for each dumpster. toccubtrA C41 em� J k A 23' drive aisle is required if there is any head -in parking off of the drive. rofio <"n.�. P'Ez-F7aD VThe minimum separation distance required for drives on a local or collector street is 175'Tmeasured from the center line of one to the nearest edge__. 1 _., ..-r. The two pro osed drives on Ponderosa do not meet this requirement. ou will only Ilovri one drive on Ponderosa. IAj4• v ie - t.A..p 14)( () • i 1lease call out distance to the next closest adjacent and opposite eves. (.- . he maximum driveway width is 36 feet and i •• t• _ -: . - - ::: _ , ine. V .Please either remove all signs from the plan or add a note that signs may be permitted separately. As discussed in the Pre - Application Conference, this will be onsidered one building plot for the purposes of signage 1 O _• • • L. YAW . ✓ fg. Provide a general note that all roof and ground- mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right - of -way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. Reviewed by: Jennifer Prochazka Date: August 20, 2004 l\ e \, d 101.60 1 04 INCA 4 Ci- CtLQ 41 & cal NOTE: Any changes made to the plans, that have not been requested 6 the City of College Station must be explained in Y 9 your p Y next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 2 of 4 • LAN SCAPING /STREETSCAPING /BUFFER t ,/ 1,7An office development adjacent to multifamily zoning or development does not r equire a buffer. ,/' K. add a note that an irrigation plan must be approved prior to C.O. c/3( Please make sure that the number of plants that you are claiming points for match what is drawn on the plan. 4. If parking screening is to be accomplished using a shrub hedge, plants must be no , more than 3' apart. A dwarf species may not be used for parking screening. ■10! 'b- 5. )Please provide the size of your proposed non- canopy trees in caliper inches for a iii single cane. The minimum allowabl single cane is 1.25 ". ✓ 67 Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights -of -way, and adjacent property disturbed during construction. Reviewed by: Jennifer Prochazka Date: August 20, 2004 ENGINEERING (1. I will need to confirm the impact of the fire flow to the existing public system. The i! \ fire flow scenario should be calculated and/ or modeled from the existing fire hydrant PI- . ' on Ponderosa to the existing water line at Sara. Only 2 hydrants permitted on a 6 -in �;L l' line. Please see BCS Unified Design Guidelines. ICI P. In addition, each fire flow scenario must stand on its own. The calculations should be separate for each building. 3. I will need to confirm that the drainage has been accounted for upstream of this jj.1.4 project. No drainage map was submitted with the report. Due to the point discharge situation of this project, it is extremely important to not increase flows downstream. 4. In addition, two drainage reports have been submitted and approved for the ?" adjacent sites to the west. Since this project is changing the drainage in the easement, what has been previously approved must be accommodated. i /5. The storm sewer in the easement must be designed to meet City standards. The storm sewer outside the easement is private. /6. Place fire hydrant between buildings out from behind parking areas for easy, emergency access. Reviewed by: Spencer Thompson Date: August 20, 2004 ELECTRICAL NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 3 of 4 1. Developer installs conduit per city specs and design. 2. Developer provides 30' of rigid conduit for riser poles. Developer installs first 10'. City installs remainder. 3. Developer pours transformer pad(s) per city specs and design. 4. Developer installs pull boxes as per city specs and design.(pull boxes provided by the city. 5. Developer provides digital AutoCAD 2000 version of plat and /or site plan. email to tmichals©cstx.gov 6. Developer provides load data for project. 7. Developer provides temporary blanket easement for construction purposes. To release temporary blanket easement meet and bounds descriptive easements are requires. 8. Contact Tony Michalsky at 979 - 764 -3438 to coordinate electric service requirements. Reviewed by: Tony Michalsky Date: 8 -19 -04 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 4 of 4