Loading...
HomeMy WebLinkAboutStaff Comments STAFF REVIEW COMMENTS NO. 2 Project: OZONA GRILL & BAR -DECK ADD.(SDSP) - 04- 00500019 PLANNING 1. Please note that for a tree to receive 'protected points' the barricade must be placed no closer to the tree than at the drip line. 2. Any trees that are required to meet planting requirements must be replaced 'caliper for caliper' if it dies. 3. All lighting needs to be approved by the Design Review Board. Please submit information (including aesthetic information) with your next submittal. 4. All proposed plantings need to be on your property. 5. Please provide caliper information for all non - canopy trees proposed. 6. Please note that the parking islands nearest to the curb cut do not currently have any approved ground cover. Please note on the plan the ground cover that you are proposing. Reviewed by: Jennifer Prochazka Date: September 3, 2004 ENGINEERING 1. In regard to the question of floodplain/ floodway location, City staff retrieved the LOMR study that was done to revise the floodplain map to determine the intent of the revision. This was done due to the inaccuracy of the FIRM. The working map shows a similar floodplain/ floodway location as shown on your plans. The Floodplain Administrator is comfortable with this determination. 2. Erosion control is a required component of construction, especially in the floodplain. 3. Dedication of the drainage and public access easement is required with this development. Reviewed by: Spencer Thompson Date: October 11, 2004 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 2 STAFF REVIEW COMMENTS NO. 2 Project: OZONA GRILL & BAR -DECK ADD.(SDSP) - 04- 00500019 PLANNING 1. Please note that for a tree to receive 'protected points' the barricade must be placed no closer to the tree than at the drip line. 2. Any trees that are required to meet planting requirements must be replaced 'caliper for caliper' if it dies. 3. All lighting needs to be approved by the Design Review Board. Please submit information (including aesthetic information) with your next submittal. 4. All proposed plantings need to be on your property. 5. Please provide caliper information for all non - canopy trees proposed. 6. Please note that the parking islands nearest to the curb cut do not currently have any approved ground cover. Please note on the plan the ground cover that you are proposing. Reviewed by: Jennifer Prochazka Date: September 3, 2004 ENGINEERING 1. In regard to the question of floodplain/ floodway location, City staff retrieved the LOMR study that was done to revise the floodplain map to determine the intent of the revision. This was done due to the inaccuracy of the FIRM. The working map shows a similar floodplain/ floodway location as shown on your plans. The Floodplain Administrator is comfortable with this determination. 2. Erosion control is a required component of construction, especially in the floodplain. 3. Dedication of the drainage and public access easement is required with this development. Reviewed by: Spencer Thompson Date: October 11, 2004 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 2 "EXHIBIT A" August 17, 2004 r--r CD Design Review Board City of College Station Development Services 1101 Texas Avenue South, P.O. Box 9960 CD College Station, Texas 77842 RE: Ozona Grill & Bar - Deck Addition 520 Harvey Rd. College Station, TX Members of the Design Review Board -T In response to city comments dated January 30, 2004, we hereby request a parking waiver for the Ozona - College Station located at 520 Harvey Road. Current requirements for the property as of the current date are 124 spaces. We are requesting a waiver of 38 parking spaces to accommodate the deck expansion to the side of Ozona Grill. It is our view that the addition of the deck will add to the beauty of the Wolf Pen Creek master plan. Creek pathway access facilities will be provided for pedestrians to enjoy the creek from the deck. These facilities will be in the form of a ramp to the deck, stairway and new landscaping to enhance the deck itself. In addition the side approach of the restaurant will now be able to better address the many positive aspects of the Wolf Pen Creek preservation area. If you have any further questions or comments, please feel free to call. Sincerely, nca Architecture Loren Boynton Associate 6500 Greenville Ave. Suite 307 Dallas, TX 75206 214.361.9901 Fax 361.9906 nca @ncaarchitecture.com STAFF REVIEW COMMENTS NO. 1 Project: OZONA GRILL & BAR - DECK ADD.(SDSP) — 04 00500019 PLANNING 1. Please change the site plan to reflect the current conditions in the area. For instance, the "footbridge" at the front of the property is not "per WPC Master Plan," it is already constructed. Also, if something is already constructed, do not label as "proposed." 2. Elevations of the rear and side are also required. The one elevation provided does not show the ramp or a canopy. 3. The number of parking spaces required is 156. You will need a waiver of 32 parking spaces from the DRB. Please submit a letter addressed to the DRB explaining why the waiver is needed and how the addition is meeting the intent of the Wolf Pen Creek district. 4. The minimum reservation dedication is required with this development in the form of a public access easement and drainage easement. This agreement will need to be in place prior to final approval of the site plan. 5. Provide a general note on the site plan that all roof and ground- mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right -of -way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. 6. Please provide information about any proposed outside lighting in this area. All lighting and details must be approved by the DRB. 7. Is the deck the only change to the site? Any change to existing landscaping or irrigation? (The approved plan shows landscaping / irrigation underneath the deck area.) 8. The location map provided on the plan has the wrong lot highlighted. Please also state the lot and block on the site plan. 9. Please provide current utility and easement information to insure that the development will not interfere with the existing conditions. 10. Fire lanes, fire hydrants, etc., must be shown on the plan to insure that there is adequate fire coverage of the new addition. You are showing the fire hydrant as "proposed." 11. What is the distance between the ground and the deck? What ground cover will be used under there? 12.1s any cut /fill proposed with this development? Please provide grading information. 13. Please provide floodway information. 14. There is a 2000 LOMR for this area. Please refer to this document and not to the 1998 Maier study. We will need further information on the floodplain, floodway, and elevations as they relate to the site. Reviewed by: Jennifer Prochazka Date: January 30, 2004 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 2 of 4 LANDSCAPING /STREETSCAPING /BUFFER 1. The approved landscape plans for this site show required plantings in the area of the new addition. Please I showing that these plantings are provided provide a plan s o t at t ese la t s a e P P g P 9 p elsewhere on the site. 2. Provide an updated landscape plan / tree survey for this area. 3. A detail of the opening of the deck for the existing trees is required for the DRB. 4. Will any existing trees be removed for this development? 5. Please provide information on how the existing trees will be protected during construction. 6. Provide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the parking lot setback, rights -of -way, and adjacent property disturbed during construction. Reviewed by: Jennifer Prochazka Date: January 30, 2004 ENGINEERING 1. A Development Permit will be required for this development. Development Permit requirements deal with erosion control and floodplain issues. 2. Staff visited the site this week to see how the proposed deck would fit on the site since no existing contour information has been provided to date. Photographs were taken and are available if desired. What is of concern is the 4 to 6 foot drop -off this site would be "filling ". Filling is allowed in the fringe areas. The drop -off area is obviously a stream flow area. 3. In addition, this site is required to dedicate to the City a Drainage and Access Easement. Any construction in a Drainage Easement is required to "not impede the flow ". The profile drawing shows a fire place that would not comply with this requirement. 4. What I would propose is: • If the desire is to go out into the drop off area, no fill, just elevate everything on piers including the fire place above the 100 -yr elevation. • Or, same as above but relocate the fire place to an area that is not in the drop off area. • Please contact me if you would like to discuss further. 5. By the way, the large post oak to the south is practically dead. It appears the plans incorporate this tree into the deck. Please see photos. 6. You will need to make a provision, as part of the drainage easement to be dedicated, that the property owner will maintain, mow, trim, etc., the private property. Drainage maintenance by the City will be only as the City deems necessary. Reviewed by: Spencer Thompson Date: 2/5/2004 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 3 of 4 ELECTRICAL 1. No Comments. Reviewed by: Ronnie Bolin Date: 1 -29 -04 STANDARD MISCELLANEOUS COMMENTS 1. The irrigation system must be protected by a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 4 of 4 TRANSMITTAL Date: August 20, 2004 .r. To: Jennifer Prochazka rD Company: City of College Station - Development Services From: Loren Boynton Via: Fed -Ex Reference: Ozona's Grill and Bar - Deck Addition nca Job No: 4001 Remarks: Jennifer - Please find the attached: All drawings are schematic design. (7) Copies of revised site plan - A101 (7) Copies of (Existing Landscape plan) (7) Copies of revised landscaping plan - LS2 (7) Copies of deck plan - A201 (7) Copies of Color renderings (1) Development Application w/ $200.00 fee (1) Letter for a parking waiver to the DRB board. (1) Itemized response to all comments from previous submittal. Per discussions with the City of College Station Engineer, our civil engineer was told that his services with regards to this project were not needed. As noted in the comments response the deck will now be entirely supported on piers. We will do whatever is necessary to expedite the process through approval. Please give me a call next week and let me know if what we have sent is sufficient. We will detail the construction of this project with a full set of architectural CDs when it is required for building permit. Kind Regards Loren 6500 Greenville Ave. Suite 307 Dallas, TX 75206 214.361.9901 Fax 361.9906 nca @ncaarchitecture.com r(q Date: November 11, 2004 Jennifer Prochazka City of College Station C Development Services 1 101 Texas Avenue South, P.O. Box 9960 r�-r- College Station, Texas 77842 CD RE: Ozona Grill & Bar -Deck Addition 520 Harvey Road College Station, Texas 77840 Jennifer: In response to your letter dated October 22,2004, the design drawings have been revised as follows to comply with your comments: Planning Comments: 1. Comment: Please note that for a tree to receive 'protected points' the barricade must be placed no closer to the tree than at the drip line. Response: We have revised the line of the erosion protection fence and added additional notation on sheet LS2. These revisions have been clouded for your reference. 2. Comment: Any trees that are required to meet planting requirements must be replaced 'caliper for caliper' if it dies. Response: We will comply. 3. Comment: All lighting needs to be approved by the Design Review Board. Please submit information (including aesthetic information) with your next submittal Response: We have added light fixture locations to the floor plan on sheet A201 I have also attached cut sheets for the proposed fixtures. 4. Comment: All proposed plantings need to be on your property. Response: We have revised the planting plan to comply please refer to the landscape plan sheet LS2. The changes have been clouded for your reference. 5. Comment: Please provide caliper information for all non - canopy trees proposed. Response: We have noted the minimum requirements for caliper size on sheet LS2 general note 7. 6. Comment: Please note that the parking islands nearest to the curb cut do not currently have any approved ground cover. Please note on the plan the ground cover that you are proposing Response: We have noted new grass at existing landscape islands' on sheet LS2. This change has been clouded on the sheet for your reference. 6500 Greenville Ave. Suite 307 Dallas, TX 75206 214.361.9901 Fax 361.9906 nca@ncaarchitecture.com Engineering Comments: 7. Comment: In regard to the question of floodplain/ floodway location, City staff retrieved the LOMR study that was done to revise the floodplain map to determine the intent of the revision. This was done due to the inaccuracy of the FIRM. The working map shows a similar floodplain/ floodway location as shown on your plans. The Floodplain Administrator is comfortable with this determination. Response: Thank you for your consideration in this matter. 8. Comment: Any trees that are required to meet planting requirements must be replaced 'caliper for caliper' if it dies. Response: We will comply. 9. Comment: A Dedication of the drainage and public access easement is required with this development. Response: We understand. If you have any further questions or comments, please feel free to call. Sincerely, nca Architecture Brian E. Fetz Associate August 19, 2004 C`) Design Review Board. City of College Station e-+ N Development Services C") 1101 Texas Avenue South, P.O. Box 9960 r-t College Station, Texas 77842 -I rD RE: Ozona Grill & Bar - Deck Addition 520 Harvey Rd. College Station,Tx Members of the Design Review Board - In response to your letter dated 1 -30 -2004, the construction documents have been revised as follows to comply with your comments: PLANNING X Please change the site plan to reflect the current conditions in the area. For instance, the "footbridge" at the front of the property is not "per WPC Master Plan," it is already constructed. Also, if something is already constructed, do not label as "proposed." Response: All errors noted above have been corrected as required. (Refer sht. 101) Elevations of the rear and side are also required. The one elevation provided does not show the ramp or a canopy. Response: The design of the deck has been altered so new elevations have been drawn and colored to reflect requirements stated above. v e . The number of parking spaces required is 156. You will need a waiver of 32 parking spaces from the DRB. Please submit a letter addressed to the DRB explaining why the waiver is needed and how the addition is meeting the intent of the Wolf Pen Creek district. Response: A letter has been drafted and attached to submittal package. (Refer Exhibit "A ") .0 1 (4 . f . \ \, Y . > he minimum svaedud eop fm o 0.3 0) (\3411. access easement reer and tion drainage dication easement is req. ire This with agreement et will l need ment to in be the in or place f a public prior to final approval of the site plan. Response: Application will be submitted for dedication required. 4 rovide a general note on the site plan that all roof and ground- mounted mechanical equipment shall be screened from view or isolated so as not to be visible from any public right -of -way or residential district within 150' of the subject lot, measured from a point five feet above grade. Such screening shall be coordinated with the building architecture and scale to maintain a unified appearance. Response: Note has been added to site plan and landscape plan. 6500 Greenville Ave. Suite 307 Dallas, TX 75206 214.361.9901 Fax 361.9906 nca @ncaarchitecture.com 6. Please provide information about any proposed outside lighting in this area. All lighting and details must be approved by the DRB. Response: Deck wilt be run with low wattage string lights and trees will be lit and shielded from all adjacent properties as required. 7. Is the deck the only change to the site? Any change to existing landscaping or irrigation? (The approved plan shows landscaping / irrigation underneath the deck area.) Response: Existing landscaping in area of new deck will need to be replaced or relocated. Irrigation will need to be relocated as well. (Please refer to new landscape plan for details) le/The location map provided on the plan has the wrong lot highlighted. Please also state the lot and block on the site plan. Response: Map has been corrected. 9. Please provide current utility and easement information to insure that the development will not interfere with the existing conditions. Response: Existing easements will be located on resubmitted site plan. ‘Atlire lanes, fire hydrants, etc. must be shown on the plan to insure that there is adequate fire coverage of t e new addition. You are showing the fire hydrant as "proposed." Response ire hydrant is existing, fire lanes will be noted on site plan. 1.4 What is the distance between the ground and the deck? What ground cover will be used under there? Response: Distance will vary, however a minimum distance will be around 24" above grade and a maximum could be as much as 6'0" over the drainage area. Ground cover will be drainage gravel to limit erosion. There will be some perimeter shrubs and landscaping to help screen the underside of the deck (Refer to Lqndscape plan Is any cut /fill proposed with this development? Please provideegrading information 7 Response: Not at this time. Deck will be entirely on piers. 13. Please provide floodway information. r Response: Refer to site plan (sht 101) for flood plain info.1 here is a 2000 LOMR for this area. Please refer to this document and not to the 1998 Maier study. We will need further information on the floodplain, floodway, and elevations as they relate to the site. Response: Reference has been changed per 2000 LOMR Reviewed by: Jennifer Prochazka Date: January 30, 2004 LANDSCAPING /STREETSCAPING /BUFFER The approved landscape plans for this site show required plantings in the area of the new addition. Please provide a plan showing that these plantings are provided elsewhere on the site. _ einvp_AJL paws ate U ,I • (:)() , 7 Response: Refer to revised landscape plan vide an updated landscape plan / tree survey for this area. Response: Refer to revised landscape plan detail of the opening of the deck for the existing trees is required for the DRB. Response: Refer to Sht LS2 Will any existing trees be removed for this development? Response: Only the dead trees that have been indicated on Sheet LS2 — ',... lease provide information on how the existing trees will be protected durin g _ construction. Response: General note has been added to Sheet LS2. – f&-V(L 5-1- Lz al amp , va!rrovide a general note that 100% coverage of groundcover, decorative paving, decorative rock, or a perennial grass is required in parking lot islands, swales and drainage areas, the lot setback, parking ac , n hts -of wa and adjacent y. �acent property disturbed during construction. Response: General note has been added to Sheet LS2. Reviewed by: Jennifer Prochazka Date: January 30, 2004 ENGINEERING 1. A Development Permit will be required for this development. Development Permit requirements deal with erosion control and floodplain issue. v 2!Staff visited the site this week to see how the proposed deck would fit on the site since no existing contour information has been provided to date. Photographs were taken and are available if desired. What is of concern is the 4 to 6 foot drop off this site would be "filling ". Filling is allowed in the fringe areas. The drop off area is obviously a stream flow area. Response: The entire deck will be supported on piers as suggested above the 100 year � pipvntinn . ? ✓s. In addition, this site is required to dedicate to the City a Drainage and Access Easement. Any construction in a Drainage Easement is required to "not impede the flow ". The profile awing shows a fire place that would not comply with this requirement. 7 What 1 ould propose is: If the desire is to go out into the drop off area, no fill, just elevate everything on piers including the fire place above the 1 nfl -yr Alevnt on. • Or, same as above but relocate the fire place to an area that is not in the drop off area. • Please contact me if you would like to discuss further. ,j the way, the large post oak to the south is practically dead. It appears the plans incorporate this tree into the deck. Please see photos. 1i Y�� - eel 6. You will need to make a provision, as part of the drainage e as ment to be dedicated, that the property owner will maintain, mow, trim, etc the private property. Drainage maintenance by the City will be only as the City deems necessary. Response: Provision will be made. Reviewed by: Spencer Thompson Date: 2/5/2004 ELECTRICAL 1i1 Comments. Reviewed by: Ronnie Bolin Date: 1 -29 -04 STANDARD MISCELLANEOUS COMMENTS irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. Response: Added general note L ,.2�11 BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. If you have any further questions or comments, please feel free to call. Sincerely, nca Architecture L r en Boynton Associate