HomeMy WebLinkAboutDomestic Water Report July 25, 2011
Mr. Stephen Maldonado Jr.
City of College Station Water Services Department
1101 Texas Avenue
College Station, TX 77842
Re: Domestic Water Report
Stepping Stone School
205 Rock Prairie Road
College Station, Texas
Gessner Engineering Job No.: 11 -0152
Dear Mr. Maldonado:
The peak water demand was calculated in accordance with the fixture count
determination method. A total fixture unit count of 72 was determined for this
building, and values are shown below in Table One.
Fixture Number Load Total
Factor Value
Lavatory 11 2 22
Dishwasher 1 2 2
Washer (Clothes) 1 4 4
Shower 1 3 3
Water Closet,Tank 8 4 32
Operated
Commercial Sink 3 3 9
(Service)
Total 72
Table One: Fixture Units
The peak water demand (based on 500 fixtures) for the domestic Gessner
service line and meter is 125 gallons per minute, and the average Engineering
water demand is 31 gallons per minute. The maximum continuous
capacity of the 1.5" Sensus OMNI T water meter is 160 gallons per
2501 Ashford Drive
minute, well over the expected peak demand. The specification sheet
for the Sensus OMNI T water meter is attached. Suite 102
Please contact us if you have any questions or if we can be of further college station, Texas 77840
assistance. ���� P.O. Box 10763, 77842