Loading...
HomeMy WebLinkAboutFire Flow Water System Fire Flow Report for Breezy Heights Addition Block 4, Lot 8R College Station, Texas March, 2011 Prepared By: SCHULTZ ENGINEERING, LLC. TBPE Firm Registration No. 12327 2730 Longmire, Suite A College Station, Texas 77845 979.764.3900 �,��•.�.,�,� ,11/ OF 7441. \ *,` * JOSEPH P. SCHULTZ t 6 8j' 4 F -12327 SCHULTZ ENGINEERING, LLC. 1) 3.aS General Information Location: The Breezy Heights Addition Block 4, Lots 5R, 6R, 7R & 8R. General Note: The existing water lines to serve these lots is a 12" line along Welsh and there is already an existing fire hydrant in front of Lot 8R. Land Use: Single family residential Design Criteria/Analysis Fire Flow: 1,000 gpm for Single Family Residential Conclusion The existing fire hydrant on Welsh near the intersection with Holleman Drive had a flow test done (exhibit A) with a result of 1,425 gallons per minute; this exceeds the required 1,000 gpm. The available flow and location of the existing fire hydrant meets the fire hydrant coverage requirements for lots 5R through 8R. EXHIBIT A FLOW TEST REPORT q f CoIIege station Utilities Reliable, Affordable, Community Owned EXHIBIT A Date test completed Tuesday, March 15, 2011 Time completed 11:30 A.M. Test completed by Vincent Rodriquez Witness Wyatt Jefferson FLOW HYDRANT Location 1014 Welsh Nozzle size 2.5 Hydrant number J -138 Pitot reading in PSI 72 Flow in G.P.M. 1425 STATIC HYDRANT Location 911 Welsh Hydrant number J -137 Static PSI 79 Residual PSI 76 Comments Requested Flow I __