HomeMy WebLinkAboutFire Flow ti Fire Flow Report For a Renovated /Expanded TireMax Store 2319 Texas Avenue South College Station, Texas Submitted to The City of College Station Prepared by Interplan, LLC 604 Courtland Street Orlando, FL 32804 May 3, 2011 f. ;. %.�;:s -:S . IP Project No 2011.0058 Y' f c at • . • e tsZiegeetss; E. TX Registration #102513 Remodeled TireMax Building Construction type = VB- Sprinkled Building Classification = Unprotected wood frame Total Building Area (1 Floor) = 7,189 SF Fire Flow Calculations per International Fire Code - Appendix B/NFPA Table B105.1— Min. Required Fire Flow and Duration for Buildings Bldg. Square Footage Fire Flow gpm Req'd Flow Duration 7,189 s.f. 2,250 gpm 2 HOURS Due to the fact the building is sprinkled, the needed fire flow should be reduced by 75% - 2,250 x .25 =563 gpm < required minimum of 1,000 gpm. Fire Hydrant Credit Table FIRE FLOW NUMBER AND DISTRIBUTION MAXIMUM REQUIREMENTS OF FIRE HYDRANTS DISTANCE (GPM) MIN. # Avg. Spacing FROM R -O -W 1750 or less 1 Hydrant 500 ft. 250 ft. Conclusion: One existing fire hydrant located on the southeast comer of the property will provide the needed fire flow for the sprinkled existing building and addition. In addition, another fire hydrant is located at the southwest comer of the property. Please see attached site plan (Sheet C -2) for fire hydrant locations. The design meets the intent of the referenced IFC/NFPA code, the distance between the two considered fire hydrants is roughly 300 feet and the maximum distance of the hydrants from existing paved streets is 10 feet. Both fire hydrants are located within 200 feet of the existing building.