»> "George Torres" <gtorres @kcunited.com> 7/28/2011 4:22 PM »>
Erika,
Attach is the revised Site plans and detail sheet. Relocated the FDC shown on plans. Please let me know if this
will work or you suggest a better location for FDC.
Thanks,
George Torres
K. Chen Engineering
6161 Savoy
From: Lauren Hovde [mailto:Lhovde @cstx.gov]
Sent: Thursday, July 28, 2011 1:50 PM
To: George Torres
Subject: Fwd: McDonald's Comments
George,
Page 1 of 2
Below are the remaining engineering comments.
Lauren
Lauren Amelia Hovde '06
file: / /C: \Documents and Settings \ebridges \Local Settings \Temp \XPgrpwise \4E32D347City of C81946 El
Staff Planner
Planning & Development Services Department
979 -764 -3570
»> Erika Bridges 7/28/2011 11:34 AM »>
Lauren,
Here re my remaining comments for McDonald's:
. (Repeat) C -1 — Provide a note with minimum, average, and maximum water and sanitary sewer
emands. Why is the average water demand less than the minimum? How is the maximum
d omestic demand 1500gpm?
( Repeat) C -1 — Signs, light fixtures, and other private infrastructure are not permitted within PUEs.
Please remove. FYI...The McDonald's monument sign will not be permitted within a PUE with
future sign permit application.
,(Repeat) C -2 — Private grate inlets need to be located outside of PUE's and privately maintained. The
storm grate inlets need to be shown on Sheets C -1 and C -2 as well.
(Repeat) C -1.2 — The FDC needs to be relocated so that it is not blocked by parking. If a remote FDC is
roposed, it needs to be a separate line originating in the building and terminating with the FDC.
It should be located along the fire line and not blocked by parking.
(Repeat) C -5 — Please remove the Roll -Up Curb and Gutter Detail. The roll -up curb does not meet the
City's Site Design Standards. Please revise.
(Repeat) Please provide a Letter of Acknowledgment and sealed Engineer's Cost Estimate for the
proposed fire line. A Letter of Acknowledgment was not included in the submittal. A standard form
for this letter can be found at www.cstx.gov.
Thanks,
Erika
Erika Bridges, EIT, CFM
Graduate Civil Engineer
Department of Public Works
1101 Texas Ave.
College Station, TX 77842
Phone: 979.764.3570
Fax: 979.764.3496
ebridges(a,cstx.gov
* * * * * * * * * * * * * * * * * * **
City of College Station
Home of Texas A &M University
Page 2 of 2
file: / /C: \Documents and Settings \ebridges \Local Settings \Temp \XPgrpwise \4E32D347City of amp Bi