HomeMy WebLinkAboutWater ReportWater System Report for Castle Rock Subdivision Phase 5 College Station, Texas February, 2010 Prepared Bv: HARLE ENGINEERING COMPANY 3002 Texas Avenue South College Station, Texas 77845 979.693.7191 . ...10SEPH � .,P � ..... 658 • '•F t• f '44538 General Information Location: General Note: Land Use: Single family residential Design Criteria/Analysis Fire Flow: Dometic Use Castle Rock Subdivision, Phase 5 Lots 26 -34, Block 1, Lots 16 -133, Block 3 and Lots 17 -18, Block 4 is located adjacent to the existing Phases 2A and 4 and future phases 6 and 7. The water line to serve these 29 residential Tots will be a 8" line along Rocky Vista Drive and Rock Bend Drive that will connect to the existing 6" water line on Hollow Stone Drive. The 8" waterline will continue along Rock Bend Drive to serve Phase 7. A 6" line and 2 4" lines are stub out along Rocky Vista Drive to serve Phase 6. The waterline layout is shown on Exhibit A. 1,000 gpm for Single Family Residential 1.5 gpm per lot for Single Family Residential The proposed 8' and 6" water lines are in accordance with the Revised Water System Report for the Castle Rock Subdivision prepared in July 2007. This report provides the results of the water system analysis under the fire flow and domestic demand requirements which produced the lowest pressure in the system. The scenario with the lowest pressure was with the fire flow of 2,500 gpm in the commercial area of the Subdivision. This scenario resulted in a residual pressure of 73 psi which is significantly higher than the 35 psi minimum residual pressure required. All scenarios using 1,000 gpm for the fire flow for the hydrants in the residential sections resulted in higher residual pressures. Additional analysis of Phase 5 of the Subdivision was performed for this report to verify that the previous analysis results could be confirmed. Attached is a field fire hydrant flow test, marked Exhibit B, performed by the City of College Station on July 2, 2008. The fire hydrant was located in Phase 2A of the subdivision and the results of the test yielded a flow of 1,300 gpm at a residual pressure of 94 psi. A KYPIPE computer model was developed for the proposed waterlines for the Castle Rock Subdivision, Phase 5. The model was run using a fire flow of 1,000 gpm for each of the proposed Fire Hydrants on Rocky Vista Drive. A maximum daily demand of 174 gpm was also used in the analysis for the domestic demand from Phase 5 and 6 of the Subdivision.. The starting residual pressure was based on the fire hydrant flow test. The node and pipe locations are shown on Exhibit A. Conclusion Exhibit C -2 is the KYPIPE output file with the domestic peak flow and the fire flow from each of the hydrants. All node pressures exceed 89 psi for this scenario which is greater than the 20 psi minimum required. All the pipe velocities are less than 12 fps for this scenario. The maximum velocity in any of the pipes is 7.5fps. Exhibit C -1 is the KYPIPE output file with only the domestic peak flow modeled. All node pressures exceed 99 psi for this scenario which is greater than the 35 psi minimum required. The proposed 8 ", 6" and 4" water lines meet or exceed all of the design criteria for the City of College Station. It will provide adequate water pressure, flowrate and velocity for both domestic and fire flow demands. • z 0 :11 0 8 5 • • 1\-1 r...) / / r iv , /// /// .,, (....,..) , ,..,„ t‘...) ;-.., ..P. `,.." / 7 , -..,, • 27 Dc; ,,,/ 7 /:// 8- A xri 1 1-•-• 00 • oer ; T - 1 - t ;4) ; ; I 1 HT / / / , /77// ■ ( 1 I ; 1 8-A 1—k In••■• 00 N.) N.) t..11 t•..) r"" 0 N.) 00 °Alia puos )Ioo'a 8-A 8-A 8-A 8-A ,, - - \ \ \ i ,.. \ \ \ '...- 7 7' \ a i Auk' i fe ) kll co v) 0 r ri ri \ ....2 \ \ -- \ \ \ , CJ) Date Time Witness Location Nozzle size Pitot reading 60 G.P.M. Static PSI Residual PSI 94 Comments 1:45 Test completed by Matthew Matcek Flow hydrant R - 057 Static hydrant R - 056 Wednesday. July 02, 2008 Aaron Matthews Castlerock Ph 2A 2.5 1300 100 Initial E xh,df- 3 CoIIege Station Utilities Reliable, Affordable, Community Owned reb uy l u 1 L:44p 1 FLOWRATE IS EXPRESSED IN GPM AND PRESSURE IN PSIG A SUMMARY OF THE ORIGINAL DATA FOLLOWS 0 PIPE NO. NODE NOS. LENGTH DIAMETER ROUGHNESS MINOR LOSS K FIXED GRADE (FEET) (INCHES) 1 1 2 19.0 8.0 150.0 .00 2 2 3 307.0 8.0 150.0 .00 3 3 4 95.0 8.0 150.0 .00 4 4 5 280.0 8.0 150.0 .00 5 5 6 283.0 8.0 150.0 .00 6 6 7 321.0 8.0 150.0 .00 7 7 8 165.0 8.0 150.0 .00 8 8 9 34.0 8.0 150.0 .00 9 9 10 335.0 8.0 150.0 .00 10 10 11 235.0 6.0 150.0 . .00 11 11 2 702.0 6.0 150.0 .00 12 10 12 129.0 8.0 150.0 .00 13 7 13 17.0 6.0 150.0 .00 14 6 14 23.0 6.0 150.0 .00 15 5 15 25.0 6.0 150.0 .00 16 0 1 1.0 8.0 150.0 .00 A SUCCESSFUL GEOMETRIC VERIFICATION HAS BEEN COMPLETED 03UNCTION NUMBER DEMAND ELEVATION CONNECTING PIPES 1 .00 287.00 1 16 2 19.50 286.00 1 2 11 3 .00 284.00 2 3 4 36.00 283.00 3 4 5 10.50 281.00 4 5 15 6 7.50 282.00 5 6 14 7 6.00 282.00 6 7 13 8 1,50 282.00 7 8 9 7.S0 282.00 8 9 10 12,00 286.00 9 10 12 11 24.00 287.00 10 11 12 .00 287.00 12 13 9.00 283.00 13 14 15.00 283.00 14 15 25.50 281.00 15 OUTPUT SELECTION: ALL RESULTS ARE OUTPUT EACH PERIOD CR5A.OUT 0 THIS SYSTEM WAS 16 PIPES WITH 15 JUNCTIONS , 1 LOOPS AND 1 FGNS 1 THE RESULTS ARE OBTAINED AFTER 6 TRIALS WITH AN ACCURACY . .00204 OCastle Rock Phase 5 02/09/0 File CRSA 7NH proposed water System w/ FGN (100 psi, 517.5' msl) 4 Castle Rock Dr. B" WL (FH7) Peak Demand of 1.5 gpm /con (116 connections) 0 PIPE N0. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL /1000 1 1 2 174.00 .01 .00 .00 1.11 .SS 2 2 3 109.85 .07 .00 .00 .7D .23 3 3 4 109.85 .02 .0D .00 .70 .23 4 4 S 73.65 .03 .00• .00 .47 .11 5 5 6 37.85 .01 .00 .00 .24 .03 6 6 7 15.35 .00 .00 .00 .10 .01 7 7 $ .35 .00 .00 .00 .00 .00 8 8 9 -1.15 .00 .00 .00 -.01 .00 9 9 10 -8.65 .00 .00 .00 -.06 .00 10 10 11 -20.65 -.01 .00 .00 -.23 -.04 11 11 2 -44.65 -.13 .00' .00 -.51 -.18 12 10 12 .00 .00 .00 .00 .00 .00 13 7 13 9.00 .00 .00 .00 .10 .01 14 6 14 15.00 .00 .00 .00 .17 .02 15 5 15 25.50 .00 .00 .00 .29 .06 16 0 1 174.00 .00 .00 .00 1.11 .SS 0 JUNCTION HUMBER DEMAND GRADE LINE ELEVATION PRESSURE 1 .00 517.50 287.00 99.88 2 19.50 517.49 286.00 100.31 3 .00 517.42 284.00 101.15 4 36.00 517.39 283.00 101.57 5 10.50 517.36 281.00 102.42 6 7.50 517.35 282.00 101.99 7 6.00 517.35 282.00 101.99 8 1.50 517.35 282.00 101.99 9 7.50 517.35 282.00 101.99 10 12.00 517.35 286.00 100.25 11 24.00 517.36 287.00 99.82 12 .00 517.35 287.00 99.82 13 9.00 517.35 283.00 101.55 14 15.00 517.35 281.00 102.42 THE NET SYSTEM DEMAND a 174.00 SUMMARY OF INFLOWS( a) AND OUTFLOWS( -) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 16 174.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES - 174.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES .00 Page 1 517.50 1 ,k do cL2 ke' & 0 r`. p.. Feb 09 10 12:45p 1 FLOWRATE I5 EXPRESSED IN GPM AND PRESSURE IN PSIG 4 A SUCCESSFUL GEOMETRIC VERIFICATION HAS BEEN COMPLETED OJUNCTION NUMBER DEMAND ELEVATION CONNECTING PIPES 1 .00 287.00 1 16 2 19.50 286.00 1 2 11 3 .00 284.00 2 3 4 36.00 283.00 3 4 5 10.50 281.00 4 5 15 6 1007.50 282.00 5 6 14 7 6.00 282.00 6 7 13 8 1.50 282.00 7 8 9 7.50 282.00 8 9 10 12.00 286.00 9 10 12 11 24.00 287.00 10 11 12 .00 287.00 12 13 9.00 283.00 13 14 15.00 283.00 14 15 25.50 281.00 15 OUTPUT SELECTION: ALL RESULTS ARE OUTPUT EACH PERIOD 0 )UNCTION NUMBER DEMAND GRADE LINE ELEVATION PRESSURE 3. .00 503.56 287.00 93.85 2 19.50 503.22 286.00 94.13 3 .00 500.32 284.00 93.74 4 36.00 499.42 283.00 93.78 5 10.50 496.98 281.00 93.59 6 1007.50 494.73 282.00 92.18 7 6.00 495.17 282.00 92.37 8 1.50 495.42 282.00 92.48 9 7.50 495.47 282.00 92.50 10 12.00 496.01 286.00 91.00 11 24.00 497.64 287.00 91.28 12 .00 496.01 287.00 90.57 13 9.00 495.17 283.00 91.94 14 15.00 494.73 283.00 91.75 15 25.50 496.98 281.00 93.59 THE NET SYSTEM DEMAND = 1174.00 SUMMARY OF INFL0W5( +) AND OUTFLOWS(-) FROM FIXED GRADE NODES CRSB.OUT A SUMMARY OF THE ORIGINAL DATA FOLLOWS 0 PIPE NO. NODE NOS. LENGTH DIAMETER ROUGHNESS MINOR LOSS K FIXED GRADE (FEET) (INCHES) 1 1 2 19.0 8.0 130.0 .00 2 2 3 307.0 8.0 150.0 .00 3 3 4 95.0 8.0 150.0 .00 4 4 5 280.0 8.0 150.0 .00 S 5 6 283.0 8.0 150.0 .00 6 6 7 321.0 8.0 150.0 .00 7 7 8 165.0 8.0 150.0 .00 8 8 9 34.0 8.0 150.0 .00 ro. 0' 9 9 10 336.0 8.0 150.0 .00 f 0 0 0 °� 10 10 11 235.0 6.0 150.0 .00 I 11 11 2 702.0 6.0 150.0 .00 13 7 13 17.0 6.0 150.0 .00 /, N 12 10 12 129.0 8.0 150.0 .00 `� 14 6 14 28.0 6.0 150.0 .00 15 S 15 28.0 6.0 150.0 .00 16 0 1 1.0 8.0 150.0 .00 0 THIS SYSTEM HAS 16 PIPES WITH 15 JUNCTIONS , 1 LOOPS AND 1 FGNS 1 THE RESULTS ARE OBTAINED AFTER 5 TRIALS WITH AN ACCURACY = 00014 Ocastle Rock Phase 5 02/09/10 File CR58 JNH Proposed Water System w/ FGN (100 psi, 517.5' msl) 9 Castle Rock Dr. 8" WL (FH7) Peak Demand of 1.5 gpm /con (116 cons) wi 1000 gpm Fire Flow at FH4 (mode 6) 0 PIPE N0. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL /1000 1 1 2 1174.00 .36 .00 .00 7.49 18.86 2 2 3 808.98 2.91 .00 .00 5.16 9.46 3 3 4 808.98 .90 .00 .00 5.16 9.46 4 4 5 772.98 2.44 .00 .00 4.93 8.70 5 S 6 736.98 2.25 .00 .00 4.70 7.96 6 6 7 - 285.52 - .44 .00 .00 -1.82 -1.38 7 7 8 - 300.52 -.25 .00 .00 -1.92 -1.51 8 8 9 - 302.02 -.05 .00 .00 -1.93 -1.53 9 9 10 - 309.52 -.54 .00 .00 -1.98 -1.60 10 10 11 - 321.52 -1.63 .00 .00 -3.65 -6.96 11 11 2 - 345.52 -5.58 .00 .00 -3.92 -7.95 12 10 12 .00 .00 .00 .00 .00 .00 13 7 13 9.00 .00 .0D .00 .10 .01 14 6 14 15.00 .00 .00 .00 .17 .02 15 5 15 25.50 .00 .00 .00 .29 .06 16 0 1 1174.00 .02 .00 .00 7.49 16.86 PIPE NUMBER FLOWRATE 16 1174.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES - 1174.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES .00 Page 1. 503.60 �J.J F UV u 12:44) • 1 FLONMTE IS EXPRESSED IN GPM AND PRESSURE IN PSIG A SUMMARY OF THE ORIGINAL DATA FOLLOWS 0 PIPE NO. NODE NOS. LENGTH DIAMETER ROUGHNESS MINOR LOSS K FIXED GRADE (FEET) (INCHES) 1 1 2 19.0 8.0 150.0 2 2 3 307.0 8.0 150.0 3 3 4 95.0 8.0 150.0 4 4 5 280.0 8.0 150.0 5 5 6 283.0 8.0 150.0 6 6 7 321.0 8.0 150.0 7 7 8 165.0 8.0 150.0 8 8 9 34.0 8.0 150.0 9 9 10 336.0 8.0 150.0 10 10 11 235.0 6.0 150.0 11 11 2 702.0 6.0 150.0 12 10 12 129.0 8.0 150.0 13 7 13 17.0 6.0 150.0 14 6 14 28.0 6.0 150.0 15 5 15 28.0 6.0 150.0 16 0 1 1.0 8.0 150.0 t 503.60 A SUCCESSFUL GEOHETRIC VERIFICATION HAS BEEN COMPLETED °JUNCTION NUMBER DEMAND ELEVATION CONNECTING PIPES 1 .00 287.00 1 16 2 19.50 286.00 1 2 11 3 36.00 284.00 2 4 5 10.50 281.00 4 5 15 6 7.50 282.00 5 6 14 7 6.00 282.00 6 7 13 8 1001.50 282.00 7 8 9 7.50 282.00 8 9 10 12.00 286.00 9 10 12 11 24.00 287.00 10 11 12 .00 287.00 12 13 9.00 283.00 13 14 15.00 283.00 14 15 25.50 281.00 15 OUTPUT SELECTION: ALL RESULTS ARE OUTPUT EACH PERIOD THE NET SYSTEM DEMAND - 1174.00 SUMMARY OF INFLOWS(*) AND OuTFLa1s( - ) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 16 1174.00 CR5C.OUT 0 THI5 SYSTEM HAS 16 PIPES WITH 15 )UNCTIONS , 1 LOOPS AND 1 FGNS 1 THE RESULTS ARE OBTAINED AFTER 4 TRIALS WITH AN ACCURACY .00074 Ocastle Rock Phase 5 02/09/10 File CRSC 3NH Proposed water System w/ FGN (100 psi, 517.5' msl) G Castle Rock Dr. 8" W. (FN7) Peak Demand of 1.S gpm /con (116 cons) w/ 1000 gpm Fire Flow at FHS (Node 8) 0 PIPE NO. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL /1000 1 1 2 1174.00 .36 .00 .00 7.49 18.86 2 2 3 751.38 2.53 .00 .00 4.80 8.25 3 3 4 751.38 .78 .00 .00 4.80 8.25 4 4 5 715.38 2.11 .00 .00 4.57 7.54 5 5 6 679.38 1.94 .00 .00 4.34 6.85 6 6 7 656.88 2.07 .00 .00 4.19 6.44 7 7 8 641.88 1.02 .00 .00 4.10 6.17 8 8 9 - 359.62 -.07 .00 .00 -2.30 -2.11 9 9 10 - 367.12 -.74 .00 .00 -2.34 -2.19 10 10 11 - 379.12 -2.22 .00 .00 -4.30 -9.44 11 11 2 - 403.12 -7.42 .00 .00 -4.57 -10.58 12 10 12 .00 .00 .00 .00 .00 .00 13 7 13 9.00 .00 .00 .00 .10 .01 14 6 14 15.00 .00 .00 .00 .17 .02 15 5 15 25.50 .00 .00 .00 .29 .06 16 0 1 1174.00 .02 .00 .00 7.49 18.86 0 JUNCTION NUMBER DEMAND GRADE LINE ELEVATION PRESSURE 1 .00 503.58 287.00 93.85 2 19.50 503.22 286.00 94.13 3 .00 500.69 284.00 93.90 4 36.00 499.90 283.00 93.99 5 10.50 497.79 281.00 93.94 6 7.50 495.86 282.00 92.67 7 6.00 493.79 282.00 91.78 8 1001.50 492.77 282.00 91.33 9 7.50 492.84 282.00 91.37 10 12.00 493.58 286.00 89.95 11 24.00 495.80 287.00 90.48 12 .00 493.58 287.00 89.52 13 9.00 493.79 283.00 91.34 14 15.00 495.85 283.00 92.24 15 25.50 497.79 281.00 93.94 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES - 1174.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NOOES - .00 -3 Page 1 f-f -1