MEMORANDUM
October 23, 2003
TO: Veronica J. B. Morgan, Mitchell & Morgan, LLP, Via fax 979.260.3564
FROM: Bridgette George, Assistant Development Manager
SUBJECT: AUTUMN CHASE (FP) — Construction Documents
Staff reviewed the above - mentioned engineering documents as requested. The
following page is a list of staff review comments detailing items that need to be
addressed. Please address the comments and submit the following information
for further staff review and approval of the plans:
One (1) set of revised construction documents.
If you have any questions or need additional information, please call Spencer
Thompson or myself at 764.3570.
Attachments: Staff Review Comments
Cc: Dan Bensimon & Beth Whately, Via fax 512.795.8431
Case file no. 03- 00500252
Home of Texas ABM University
ENGINEERING REVIEW
COMMENTS No. 1
1. This needs to be separated into Final Plat infrastructure and Site Plan
infrastructure. Cornell is required for the FP, as well as water and sewer to all
lots.
2. There are concerns about sewer capacity. The line being extended across
Cornell runs approximately 1500 -ft through a duplex subdivision before it
joins a larger line. City data shows a 6 -in line coming up between Lots 5 and
6 of Brentwood II, Block 3. This line runs approximately 300 -ft before it joins
a larger line. Therefore, Lot 6 of this plat has sewer already. Please confirm
whether this line can serve this property. There is an additional 8 -in sewer to
the rear (west) that could possibly serve Lot 6.
3. Is adjacent property owner allowing of driveway tie -in to Cornell?
4. Sheet 2: Please show station and pavement widths in transition areas.
5. Sheets 5 and 7: separation distances between public water and sewer
appear to be an issue. Separation distances apply to public sewer mains and
not laterals. Note on plan /profile sheet where Utility Crossing Detail applies.
6. Cornell is not slated for a Bike Lane. Please see Subdivision Regulations
concerning proper roadway pavement section.
7. Include detail concerning Structural Fill Area on utility lines or note at each
individual location.
8. Service Line Type I detail. Change lateral line type to SDR -21 or SCH 40.
See Spec S.203.5.C.1
9. Sidewalk Adjacent to Curb detail: add 2 -in sand cushion.
10. It appears hydrants are needed along Cornell for fire protection of duplexes.
This is a Major Collector. The Fire Marshall will not lay hose across this
street.
11. Please include "Permanent Erosion Control Measures" in designing the storm
drain system. It appears an energy dissipation device is needed at the end of
the 42 -in storm line.
12. HGLs (10, 100) on public storm sewer need to be shown either on the plans
or as part of the Drainage Report as per the ordinance. For instance, 10 -yr
peak flow for Pipe 5 is 76.72 cfs. However, capacity of a 42" line at 0.36%
slope is 56.3 cfs.
Reviewed by: Spencer Thompson Date: October 21, 2003
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must
be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on
these plans that have not been pointed out to the City of College Station will constitute a
completely new review.
Page 2 of 2
CITY OF COLLEGE STATION
`I DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
COLLEGE STATION College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
October 20, 2003
TO: Veronica J. B. Morgan, Mitchell & Morgan, LLP, Via fax 979.260.3564 ✓
FROM: Bridgette George, Assistant Development Manager
SUBJECT: AUTUMN CHASE (FP) - Final Plat
Staff reviewed the above - mentioned final plat as requested but will not be able to
complete the review until the Preliminary Plat has been processed and approved. The
following page is a preliminary list of staff review comments detailing items that need to
be addressed. Please address the comments and submit the following after Preliminary
Plat approval:
Two (2) copies of the revised final plat;
Parkland Dedication will be required prior to the issuance of a building
permit;
One (1) Mylar original of the revised final plat; and
One (1) copy of the digital file of the final plat on diskette or e-mail to
nmanhart@ci.college - station.tx. us
Upon receipt of the required documents for the Planning & Zoning meeting, your project
will be considered formally filed with the City of College Station. Please note that if all
comments have not been addressed your project will not be scheduled for a Planning &
Zoning Commission meeting. Your project may be placed on a future agenda once all
the revisions have been made and the appropriate fees paid. If you have any questions
or need additional information, please call or myself at 764 -3570.
Attachments: Staff review comments
cc: Dan Bensimon & Beth Whatley, Via fax 512.795.8431
Case file #03- 00500252
Home of Texas A8&M University
. •,
STAFF REVIEW COMMENTS NO. 1
Project: AUTUMN CHASE (FP) - 03- 00500252
THIS IS A STOP REVIEW. THESE COMMENTS DO NOT CONSTITUTE A
COMPLETE REVIEW.
ENGINEERING
1. Final Plat will not be approved until the Preliminary Plat has been processed. At
which time, the Final Plat may proceed. Please address all Preliminary Plat issues
on the Final Plat.
Reviewed by: Planning- Jennifer Reeves Date: 10 -16 -03
Engineering- Spencer Thompson
ELECTRICAL
1. Developer installs conduit per city specs and design.
2. Developer provides 30' of rigid conduit for riser poles. Developer installs
first 10'. City installs remainder.
3. Developer pours transformer pad(s) per city specs and design.
4. Developer installs pull boxes as per city specs and design.(pull boxes
provided by the city.
5. Developer provides digital AutoCAD 2000i version of plat and /or site plan.
email to rbolin@cstx.gov
6. Developer provides load data for project.
7. Developer provides temporary blanket easement for construction
purposes.
8. Developer provides easements for electric infrastructure as installed for
electric lines (including street lights).
9. Developer provides 10' PUE along the back of lots 1 -5 of block 2.
10. Developer provides 10' PUE along the front of lots 1 -7 of block 1.
Reviewed by: Ronnie Bolin Date: 10 -20 -03
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.
Page 2 of 2
Ei L.4 S (4-1(Y1
YVLck
October 24, 2003
Bridgette George
COCS - Development Services
.. P.O. Box 9960
e o College Station, TX 77840
O N c
u d Re: Autumn Chase Final Plat Submittal
ti Is v,
0 fo c v't
c 4 € es Dear Bridgette,
O >- ma�
U =a c
dS c60,0_ E Attached please find 2 sets of revised construction documents. We have provided
e �i g an additional set because we have included a streetscape plan. The following are
Qi c c c
O •o, k c o our responses to the Staff Review Comments #1 for Autumn Chase Subdivision.
C >
a ;>
W u B 05 _a Comment: This needs to be separated into Final Plat infrastructure and Site Plan
infrastructure. Cornell is required for the FP, as well as water and
sewer to all lots.
ui Answer: Done.
a
6 ui Comment: There are concerns about sewer capacity. The line being extended
n Cl. across Cornell runs approximately 1500 -ft. through a duplex
°� c subdivision before it joins a larger line. City data shows a 6 -in. line
E a r a� coming up between Lots 5 and 6 of Brentwood II, Block 3. This line
oa c ,: runs approximately 300 -ft. before it joins a larger line. Therefore, Lot
ri ( Tr • Z a 6 of this plat has sewer already. Please confirm whether this line can
, A' serve this property. There is an additional 8 -in. sewer to the rear
c 8 (west) that could possibly serve Lot 6.
n Answer: Under a separate letter this information was submitted to Spencer
Thompson on October 27, 2003.
Comment: Is adjacent property owner allowing of driveway tie -in to Cornell?
a. It Answer: We have tried to contact the adjacent property owner to us avail.
J
n 0 Therefore we are stopping the driveway at the right-of-way line.
(.9 • ' n Comment: Sheet 2: Please show station and pavement widths in transition areas.
�
Answer: Added.
p
LS �
0 I — f Comment: Sheets 5 & 7: separation distances between public water and sewer
,o
°� c , appear to be an issue. Separation distances apply to public sewer
W •= --,, N mains and not laterals. Note on plan/profile sheet where Utility
2 N Crossing Detail applies.
V c ^ Answer: Corrected.
1— _ l" 1 = V v
, , ,.r., off- a5"�- (j P
Comment: Cornell is not slated for a Bike Lane. Please see Subdivision
Regulations concerning proper roadway pavement section.
Answer: Because of the contention with the right -of -way and street
designation here we would not recommend constructing any more
pavement then absolutely necessary until it is warranted. The 48'
paved section does not have to be initially striped with a bike lane
and could be striped as 3 or 4 lanes initially. If the City ever extends
Cornell and reworks the adjacent section to a 54' paved section, the
ROW exists here to allow widening. We do not believe this section of
roadway will ever warrant the 54' cross section. It is not prudent to be
constructing additional imperious cover given the new NPDES
regulations when it may be years before we need this additional
pavement.
Comment: Include detail concerning Structural Fill Area on utility lines or note
at each individual location.
Answer: Added.
Comment: Service line Type I detail. Change lateral line type to SDR -21 or SCH
40. See spec S.203.5.C.1
Answer: Changed.
Comment: Sidewalk Adjacent to Curb detail: add 2 -in. sand cushion.
Answer: We have changed our detail to add cement stabilized sand or lime
stabilized natural soil. We would rather not use regular sand because
it has a tendency to wash out from under the sidewalk.
Comment: It appears hydrants are needed along Cornell for fire protection of
duplexes. This is a major Collector. The Fire Marshal will not lay
hose across this street.
Answer: Two fire hydrants have been added.
Comment: Please include "Permanent Erosion Control Measures" in designing
the storm drain system. It appears an energy dissipation device is
needed at the end of the 42 -in. storm line.
Answer: Energy dissipation has been added.
Comment: HGLs (10, 100) on public storm sewer is needed to be shown with
the plans or as part of the Drainage Report as per the ordinance. For
instance, 10 -yr. peak flow for Pipe 5 is 76.72 cfs. However, capacity
of a 42" line at 0.36% slope is 56.3 cfs.
Answer: Have been added on sheet 02.
We hope this has answered all your questions and answers. Thank you for your
corporation on this project. If you have any question please give us a call.
S erely,
1 / '"p _______.
Veronica J. t'Mo4an
Managing Partne
Attachments
Cc: File
Dan Bensimon
Gr. \ n.o3
)) 0 )w ())
ee 0
October 27, 2003
Bridgette George
COCS - Development Services
P.O. Box 9960
i o, College Station, TX 77840
O 6
tz Y3 as t .— Re: Autumn Chase (FP) - 03- 00500252
ti �
Rig
c 13 E C as Dear Bridgette,
Co ,>.- °'c
ca c : 13 c Please find attached ten copies of the revised final plat, one mylar original of the
—as mi
E g S a , a revised final plat. The digital copy of the final plat has been emailed to
rn ; : g g nmanhart@cstx.gov. The following are our responses to the Final Plat &
c s; g a Preliminary Plat Staff Review Comments #1 for Autumn Chase Subdivision.
al _ o a •—
W u = in a Engineering:
LLi Comment: Final Plat will not be approved until the Preliminary Plat has been
a; processed.
c u:a Answer: Per our recent email we have requested that the preliminary plat be
ra a pulled and consider only the final plat application. The preliminary
C -g ) plat was submitted for information purposes only.
Xa . Co
a p 2.§ Electrical:
r; W g a
. (5 U ri Comment: Developer installs conduit per city specs and design.
o 6 Answer: Acknowledged.
o
n
> Comment: Developer provides 30' of rigid conduit for riser poles. Developer
installs first 10'. City installs remainder.
Answer: Acknowledged.
-+ N 0 Comment: Developer pours transformer pad(s) per city specs and design.
Z 4 S Answer: Acknowledged.
a • • n
0 • v ` In Comment: Developer installs pull boxes as per city specs and design. (pull
6 LLi boxes provided by the city).
6 4 z. g C g ` Answer: Acknowledged.
`.o
al I 3 N3
a N
U . n r.
1 ? Wa^
,‘. pi — u
in U0� 1 -
Comment: Developer provides digital AutoCAD 2000i version of plat and/or
site plan.
Email to rbolin @cstx.gov.
Answer: The plat and site plan have been emailed to Ronnie Bolin.
Comment: Developer provides load data for project.
Answer: Provided to Ronnie Bolin.
Comment: Developer provides temporary blanket easement for construction
purposes.
Answer: If required, will be provided prior to construction.
Comment: Developer provides easements for electric infrastructure as installed
for electric lines (including street lights).
Answer: Site plan for Lot 6 has been sent to Ronnie Bolin. Any additional
easements needed will be provided.
Comment: Developer provides 10' PUE along the back of lots 1 -5 of block 2.
Answer: Provided on the final plat.
Comment: Developer provides 10' PUE along the front of lots 1 -7 of block 1.
Answer: Provided on the final plat.
Re: Autumn Chase (PP) - 3- 00500251
Planning!En2ineerinE:
Comment: As per Section7.3.B.1.C. Major Collector Streets: No single- family
dwelling, townhouse, or duplex shall take direct access to major
collector streets. Please consider joint access easements every other
lot.
Answer: Joint access has been shown on the final plat. Each lot closest to
manual will have a single access point at their north lot line.
Comment: As per Section 5.2 Residential Dimensional Standards, Note (E) The
Minimum lot width for a duplex dwelling may be reduced to 30 feet
per dwelling unit when all required off - street parking is provided in
the rear or side yard. Please provide rear and side access to Lots 1 -7
of Block 1. Please add a note to the plat to this effect for all but lots 1,
2 & 3 Block 2.
Answer: See general note #4 & #5.
2 -4
Comment: Please remove certificates, not required on preliminary plats.
Answer: Preliminary plat no longer being considered.
Comment: Please enlarge P.U.E. to cover service tap to Lots 1, 2, 3 & 4 Block 2.
Answer: P.U.E. increased to cover these services.
Comment: Lot 3 & 4 of Block 1 do not require side street setbacks. This is a
driveway.
Answer: Changed.
Comment: Developer installs conduit as per city specs and design.
Answer: Acknowledged.
Comment: Developer provides 30' of #4 rigid conduit for riser pole(s).
Developer installs first 10'. City installs remainder.
Answer: Acknowledged.
Comment: Developer pours transformer pad(s) per city specs and design.
Answer: Acknowledged.
Comment: Developer installs pull boxes as per city specs and design. (pull boxes
provided by the city).
Answer: Acknowledged.
Comment: Developer provides digital AutoCAD 2002 version of plat and/or site
plan. Email to rbolin@cstx.gov.
Answer: Plat & site plan have been emailed to Ronnie Bolin.
Comment: Developer provides load data for project.
Answer: Provided to Ronnie Bolin.
Comment: Developer installs street lighting per city specs and design.
Answer: Acknowledged.
Comment: Developer provides temporary blanket easement for construction
purposes.
Answer: If required, will be provided prior to construction.
3 -4
Comment: Developer provides easements for electrical infrastructure as installed
for electric lines (including street lighting).
Answer: Acknowledged.
Thank you for your cooperation on this project. Please let us know if you have any
questions.
Sic ely,
u / , al 1
Veronica J.131 Morgan, P.E.
Managing Partner
Cc: Dan Bensimon
File
4 -4
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
COLLEGE STATION College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
December 2, 2003
TO: Veronica J. B. Morgan, Mitchell & Morgan, LLP, Via fax 979.260.3564
FROM: Bridgette George, Assistant Development Manager
SUBJECT: AUTUMN CHASE (FP)
Staff reviewed the above - mentioned engineering documents as requested. The
following page is a list of staff review comments detailing items that need to be
addressed. Please address the comments and submit the following information
for further staff review and approval of the plans:
Two (2) sets of revised construction documents.
If you have any questions or need additional information, please call * or myself
at 764.3570.
Attachments: Staff Review Comments
Cc: Dan Bensimon & Beth Whately, Via fax 512.795.8431
Case file no. 03- 00500252
Home of Texas AS&M University
i
AUTUMN CHASE (FP) (03- 00500252)
ENGINEERING REVIEW
COMMENTS No. 2
1. It appears there is insufficient cover on sewer line C -1. Minimum slope for 6-
in sewer is 0.5 %. Will this allow more cover? Construct MH #1 at existing
end of line? Or further back in easement?
2. Are there any water line plan changes?
3. It appears the street is now showing driveways to be constructed? Has the
street design changed?
4. Sewer line "A" has insufficient cover.
5. Sewer line "B" has insufficient cover where it crosses the drainage channel.
This channel will be regraded when the storm sewer is put in?
Reviewed by: Spencer Thompson Date: December 2, 2003
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must
be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on
these plans that have not been pointed out to the City of College Station will constitute a
completely new review.
Page 2 of 2