HomeMy WebLinkAboutSTAFF REVIEW COMMENTS CITY OF COLLEGE STATION ci % DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 College Station, Texas 77842 COLLEGE STATION Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM October 23, 2003 TO: J. Dale Brown, Jr., P.E., Via fax 846.8914 FROM: Bridgette George, Assistant Development Manager SUBJECT: TWIN CITY CHURCH OF CHRIST (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested. The following page is a list of staff review comments detailing items that need to be addressed. Please address the comments and submit the following information for further staff review: One (1) complete set of construction documents for the proposed development with the revised site and landscaping plans attached. Easement Dedication Sheet and required documents. Please note that the Easement Dedication Sheet and the necessary documents are required prior to the issuance of a building permit. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764 -3570. Attachments: Staff review comments cc: Wayne Moody, Twin City Church of Christ, 810 Southwest Parkway E, College Station, TX, 77840 Case file #03- 00500253 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 1 of 3 STAFF REVIEW COMMENTS NO. 1 Project: TWIN CITY CHURCH OF CHRIST (SP) — 03- 00500253 PLANNING ;/ 1. A Shared Parking Study Form and a Shared Parking Agreement must be on record prior to Site plan approval. LANDSCAPING /STREETSCAPING /BUFFER 2. Please note on the site plan that all disturbed earth must be 100% covered with established grass or groundcover prior to C.O. 3. Dwarf species may not be used as a screening shrub. The plants must be at 3 -ft. (36 ") in height at planting stage. 4. The proposed ac /units can be seen from the right -of -way. Please provide 5- gallon screening shrubs 3 -ft. in height. Reviewed by: Jennifer Reeves Date: 10 -20 -03 ENGINEERING 1. Show all easements as existing or proposed. 2. A filed private access easement is required to have fire lane routed through adjacent property. 3. An easement will need to be dedicated over the fire water line. 4. Show existing and proposed meter locations. They need to be in a PUE. 5. Show water service to the buildings. 6. Specify fire hydrant type or provide a detail. 7. You will need additional cleanouts per the building code. 8. Stormwater discharge will need to be returned to sheet flow. 9. Add erosion control measures to inlet side of discharge structure. Reviewed by: Carol Cotter Date: 10 -22 -03 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. Developer provides 30' rigid conduit for riser poles. Developer installs first 10'. City installs remainder. 3. Developer pours transformer pad(s) per city specs and design. 4. Developer installs pull boxes as per city specs and design.(pull boxes provided by the city. 5. Developer provides digital AutoCAD 2000i version of plat and /or site plan. email to rbolin(cr7cstx,gov 6. Developer provides load data for project. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 2 of 3 • 7. Developer provides temporary blanket easement for construction purposes. 8. Developer provides easements for electric infrastructure as installed for electric lines (including street lights). Reviewed by: Ronnie Bolin Date: 10 -20 -03 MISCELLANEOUS 1. Irrigation system must be protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow Device, or a Double -Check Back Flow Device, and installed as per City Ordinance 2394. 2. All BackFlow devices must be installed and tested upon installation as per City Ordinance 2394. NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. Page 3 of 3 ASH & BROWNE ENGINEERING, INC. a' Engineers and Consultants P.O. Box 10838, College Station, Texas 77842 d 979 - 846 -6914 877 -245 -4839 Fax: 979-846-8914 November 10, 2003 Bridgette George Asst. Development Manager City of College Station P.O. Box 9960 College Station, Texas 77842 Re.: Twin City Church of Christ Building and Parking Lot Improvements COCS Case File No. 03- 00500253 ABEI No. 1000024 Dear Bridgette: This letter is in response to your comments for the above referenced project. The following information corresponds to the staff review comments dated October 23, 2003: Planning (Jennifer Reeves) 1. Please find attached the completed Shared Parking Study Form and the filed Shared Parking Agreement for this project. Landscaping /Streetscape (Jennifer Reeves) ;2. Note 14 was added to the General Notes on the Site Plan regarding established grass. 3. As per our discussion, the dwarf variety of wax myrtle is an approved screening shrub as per the College Station Plant List. The height of the shrubs has been revised on the landscaping plan (i.e. height: 30" changed to 36 "). 4. The proposed AC units will be relocated and place on top of the proposed covered walkway between the two budding. They will not be visible from the R.O.W. Engineering (Carol Cotter) 1. Note 15 was added to the General on the Site Plan regarding the existing and proposed easements. 2. The "shared" fire lane with the adjacent property has been in place for at least 15 years. The Twin City Church of Christ provides this shared fire lane for the McCord building and in return, the McCord property allows shared parking; therefore, we both "need" each other to remain in compliance with parking and fire code requirements. 3. Please find the easement dedication sheet and associated forms of the proposed public utility easement for the fire line and water meter. The P.U.E. has been added to the site plan. F:lProjects \1000 - Miscellaneous030 - Twin City Church of Christ Site PlanlLetters \COGS - George02 - Letter.wpd Bridgette George November 10, 2003 Page 2 4. The existing and proposed meters have been shown on the site plan and the new water meter will be within PUE. 5. The water service lines to the existing and proposed building have been shown on the drawings. 6. Because this hydrant will be located at the end of a line, a "fire hydrant type" was not designated. A fire hydrant detail has been added to the construction standard details. 7. Two additional cleanouts have been added to the long run of wastewater service line. 8. The discharge is located at least 15 feet from the property line and the grade between the discharge point and property line is very flat. Therefore, it is my professional opinion that the stormwater discharge will return to sheet flow prior to existing the project. 9. Silt fence is to be place along the property line and down stream of the detention pond discharge point. As long as the contractor maintains the silt fences, no silt should be discharged onto the adjacent property owners. Electrical(Ronnie Bolin) 1. The developer has been informed and made aware of the City's electrical requirements. Miscellaneous 1. See Note 1 of the Landscaping Plan. 2. See Note 1 of the Landscaping Plan. Please find enclosed the following: 1. Revised complete set of construction drawings with the revised site and landscaping plans (1 copy) If you have any additional question or need any additional information, please do not hesitate to call. Sincerely, ASH & B OWNE ENGINEERING, INC. •� 5.••' " ''• rt 1 f / / /// • n C , BROWNE e 12,4 0 * ra t / . Dale Browne, Jr., P.E. /..6_ 81890 • ...... Attachments � `‘ ‘ / o � N:E F: \Projects \1000 - Miscellaneous1030 - Twin City Church of Christ Site Plan \Letters1COCS - George02 - Letter.wpd ALTERNATIVE PARKING PLAN (SITE PLAN) SHARED PARKING STUDY FORM Shared off - street parking spaces shall be located no farther than 250 feet from the building site. What is the rationale for the shared parking alternative forthesedevelopment spaces ? The number of parking required for the proposed improvements can not be located on - site. Please fill out the following for each USE that will be sharing parking: 1. USE: Place of worship Current zoning of property: R -4 Building square footage and / or number of seats: 400 Seats Standard parking requirement: 132 Number of off street parking spaces provided on site: 106 Hours of operation: Sundays: 9:00 a.m. - 11:00 a.m. and 6:00 p.m. - 7:30 p.m.; Wednesdays: 7:30 p.m. - 9:00 p.m. Peak hour(s) of operation: Sundays from 10 :00 a.m. to 11 :00 a.m. Anticipated peak parking & traffic load: 132 Estimated parking turnover rate: N.A. 2. USE: Commercial Current zoning of property: A Building square footage and / or number of seats: +/- 19,845 S.F. Standard parking requirement: S Number of off street parking spaces provided on site: 80 Hours of operation: Monday - Friday: 8:00 a.m. - 5:00 p.m. Peak hour(s) of operation: Monday - Friday: 8 :00 a.m. - 5:00 p.m. Anticipated peak parking & traffic load: 80 Estimated parking turnover rate: 1 per hour 3. USE: Current zoning of property: Building square footage and / or number of seats: Standard parking requirement: Number of off street parking spaces provided on site: Hours of operation: Peak hour(s) of operation: Anticipated peak parking & traffic load: Estimated parking turnover rate: 4. USE: Current zoning of property: Building square footage and / or number of seats: Standard parking requirement: Number of off street parking spaces provided on site: Hours of operation: Peak hour(s) of operation: Anticipated peak parking & traffic load: Estimated parking turnover rate: 6113/03 1 of 1 CITY OF COLLEGE STATION DEVELOPMENT SERVICES 1101 Texas Avenue South, PO Box 9960 COLLEGE STATION College Station, Texas 77842 Phone 979.764.3570 / Fax 979.764.3496 MEMORANDUM November 14, 2003 TO: J. Dale Brown, Jr., P.E., Via fax 846.8914/ FROM: Bridgette George, Assistant Development Manager SUBJECT: TWIN CITY CHURCH OF CHRIST (SP) - Site Plan Staff reviewed the above - mentioned site plan as requested and has no comments. Please submit the following information for the plans to be stamped approved: Six (6) complete sets of construction documents for the proposed development with the revised site and landscaping plans attached (please submit additional copies to be stamped for your records). Two (2) revised site plans; and One (1) landscaping plan. If you have any questions or need additional information, please call me at 764- 3570. Attachments: Staff review comments cc: Twin City Church of Christ, 810 Southwest Pky E, College Station, TX, 77840 Case file #03- 00500253 Home of Texas A &M University STAFF REVIEW COMMENTS NO. 2 Project: TWIN CITY CHURCH OF CHRIST (SP) - 03- 00500253 PLANNING 1. No comment. Reviewed by: Jennifer Reeves Date: 11 -14 -03 ENGINEERING 1. No comment. Reviewed by: Carol Cotter Date: 11 -14 -03 NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the City, will constitute a completely new review. 2 of 2