HomeMy WebLinkAboutResponse to staff comments4 Jeff Haeber, P.E., CFM Assistant City Engineer City of College Station Public Works Department 300 Krenek Tap College Station, Texas 77840 MITCHELL MORGAN RE: EMERALD FOREST PARK IMPROVEMENTS Dear Jeff, Attached please find the following: • Written response to Staff comments with a transmittal letter; STAFF REVIEW COMMENTS NO. 1 July 11,2011 1. Note that no spoils beyond the specified fill are to be stockpiled on site. Response: A note has been added to Sheet 01. 2. Depict floodplain and floodway and limits of construction. Response: Floodplain and floodway depictions are on Sheets 01 & 02. A note was added to Sheet 02 to address the limits of construction. 3. Proposed utilities and structures (in the absence of being elevated one foot above the BFE) shall be certified as flood - proofed meaning watertight and impermeable to the intrusion of water, and shall resist the structural Toads and buoyancy effects from the hydrostatic and hydrodynamic conditions. Response: The only new utilities being proposed are several extra lights to add illumination to the existing path. These lights have a concrete base which will sit 2 ft above grade. This will not get the light connection to the base 1 ft above the BFE. But we have attached the catalog information regarding the Cooper Bussman Fuse Holder that is specified for the Emerald Park lights. This fuse holder and connector is water resistant. This is the fuse holder CSU uses on all streetlights installed in College Station. This fuse holder is also approved by TX DOT for use on projects within TX DOT R.O.W. For you information the following elevations are flood elevations for different storm events within the park. a. 10 year BFE = 244.77 b. 50 year BFE = 245.22 c. 100 year BFE = 245.35 d. Pad El = 243.00 511 UNIVERSITY DRIVE EAST, SUITE 204 • COLLEGE STATION, TX 77840 • T 979.260.6963 • + 979.260.3564 CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS SITE PLANS • SUBDIVISIONS info @mitchellandmorgan.com • www.mitchellandmorgan.com 4. The slope of the northernmost proposed sidewalk appears backward. Response: It is correct. It is a negative slope. 5. The sidewalk detail and general notes appear to conflict with regard to joints and bedding /compaction. Response: The detail has been modified to match the general notes. 6. Confirm if the River Stat 7063 appears Min Chan elev is actually -2 ft higher than the upstream Stat 7255. Is there standing water in this reach? If not, update the model. Response: The model was confirmed to have an increase in the channel flowline in this location. 7. Address why Stat 7063 appears to have proposed net fill, but the flow area increases and there is an increase in velocity. Response: The flow area decreases from 5503.03 sf to 5307.30 sf (145.73 sf). 8. Fyi, a licensed plumber and electrician will be required to install applicable improvements including necessary permits. Response: This has been noted in the special provisions. 9. Fill in SFHA requires a post Certification of Compaction of fill in accordance with FEMA Technical Bulletin 10 -01. Response: As discussed, we will be happy to sign a certification that the fill was compacted to a certain density based upon Gessner's testing reports. If the certification is more than just compaction densities then we will need to revisit the subject. If you have any questions or comments, please feel free to call our office at 979 - 260 -6963. Sincerely, cs ames Batenhorst, PE Cc: File Bussmann® • TRON® In -Line Fuseholders Single -Pole for 1 % 2 " x 1 Fuses Non- Breakaway Holders Catalog Symbol: HEB -AA( ( ( HEB- AB( HEB- AC( HEB- AD( HEB- AE( }-IEB -AJ, HEB -AK, HEB -AL, I"'IFB -AR, HEB -AY, HEB- BA( HEB- BB( HEB- BC( 1- IEB- BD(. FIEB -CC( FIEB- DD( f- IEB -JJ, HEB-JK, FIEB -JL, HEB -.1Y, HEB -LL, HEB -NN, HEB- PP( HEB- QQ( HEB -RR( FIEB -SS I- IEB- T1( -LA. In -Line Fuseholders Single -Pole Water- Resistant Agency Information: ( Recognized, Guide IZLT2, File E14853 ( Certified, Class 6225 -01, File 47235 (3 )CE For breakaway holders See Page 2 HEB — For i %2" x 1 % (midget) fuse. Fusehoider rated 30A, 600V Typical fuse types: BAF, FNM, FNQ, and KTK ( / -30A). Ordering Information: HEB 1 COOPER Bussmann 7 -16 -03 NO3082 Load Terminal Line Terminal Also See Table on Page 3 Example: A single -pole, in -line holder for 1 %2` x 1 % fuses, A single #12 solid copper wire is on the load side. A copper crimp is desired. Two 46 solid copper wire is on the line side. A copper set -screw is desired. 1. Choose HEB- Series. 2. Choose "A" for load side. 3. Choose "K" for line side. Complete Catalog Number: HEB -AK. For Insulating boots See Page 2 — Insulating boots are not included with non - breakaway parts and must be ordered separately. They come standard with the breakaway series. When boots are utilized, extra heat retention requires that fuses are sized at a minimum of 2005' of the RMS load current. Recommended Torque on Coupling Nut: 10 -20 in -Ib Specification Data - Non - Breakaway & Load -Side Breakaway Conductor Terminals Terminal Type Copper Crimp 111 Copper Set -Screw 11111111 s 1 ■ "n al l Solid Copper Terminal for Aluminum Wire Connector #8 to #12 /0 Aluminum Crimp . ..„1„.1 , , Aluminum Set -Screw 410to #4 • Conductor Data Size #1210 #8 1 #12 2 #10 2 -6 #4 1 #8 2 #4 1 46 2 1 ;14 2 #20to #18 1 #12 to #3 #12 to #3 #8 t:6 #6 #4 ?3 #4 #2 - -1/ #12 to #2 m c o d Z 2 #12 to #M2 2 v 0 HEB Series d to Catalog Symbol Load & Line (2) & (3) A B c D E z J K S N p Q R T L Y Form No. HEB Sexes Page 1 al 3 Data Sheet: 2127 Bussmanne TRON® In -Line Fuseholders Single -Pole for 1%2" x 1 Fuses Breakaway Holders Breakaway Holders consist of two parts for a complete unit. One part is the Fuseholder, which contains the Load Terminal, and the other part is the Breakaway, which contains the Line Terminal. These can be ordered as a complete unit or as individual parts. Catalog Symbols: Breakaway Unit: (Includes Fuseholder, Breakaway part and Insulating Boots) I {EB- AW -RLA, HEB -AW- RLC -A( ( ( HEB -AW- RLC -B, HEB -AW RLC -C, f {EB AW RLC J, HEB-AW-RYA, I- 1EB -AW -RYC, HEB -BW- RLC -A, F- IEB -BW- RLC -B, HEB -BW -RYC, HEB -JW- RLC -J, HEB -JW -RYC, HEB -KW- RLC -J, FIEB -KW -RYC. FIEB- LW -RLA, HEB -LW- RLC -J, I iEB LW RYA Fuseholder Only: F-IEB- AW( I IEB- BW( F1EB- DW( I lEB JW, HEB -LW Breakaway Part: RLC -A, RLC -B, RLC -C, RLC -J, RYC, RLA, RYA Agency Information: ' Recognized, Guide IZLT2, File E14853 ( Certified, Class 6225 -01, File 47235 i Ordering Information: HEB 0 COOPER Bussmann 7 -16 -03 NO3082 Load Terminal w Line Terminal Example: A single -pole, breakaway, in -line holder for 13 % 2 " x 1 fuses. A single #12 solid copper wire is on the load side. A copper crimp is desired. Two #6 solid copper wire is on the line side. A copper set -screw is desired. 1. Choose HEB Series. 2. Choose "AW" for load side. 3. Choose "RYC" for line side. Complete Catalog Number: HEB -AW -RYC. Recommended Torque on Coupling Nut: 10-20 in lb. Specification Data - Line Side Breakaway Breakaway Receptacles Terminal Type Copper Crimp Copper Set -Screw Aluminum Set -Screw � llilili X111111111 Solid Breakaway Insulating Boots Conductor Data Size g '01 - g °' o z1— *12to#8 #12 to i2 (Required with Breakaway Receptacle) 0 et) Catalog Numbers Type HEB Series Catalog Symbol in -RLC -A -RLC -J #12 to . ' . 2 - RYC #12 to r2 - RLA 1112 to #2 - RYA w 2A0660 Single Conductor 2A0661 Two Conductor Two Insulating boots come standard with the Breakaway units (ex. FIEB -AW- RLC -A). The insulating boots are not included with the Non - Breakaway Holders (ex. HEB - AA) or the individual pieces of the Breakaway parts (ex. I-- IEB -AW, RLC -A). Two insu- lating boots must be ordered for each holder when ordering them separately. When insulated boots are utilized, extra heat retention requires that fuses are sized at a minimum of 200% of the 1.2MS load current. the. only control•ed copy of this Data Sheet is we electronic read-only version icu ated on the Bust-smarm Network Drive. All other copies of the document are by definition uncontrolled. This hulieri n i> intended to clearly r rwa a u.rnp Oonseo product, data anci provide technical information that will help the end userw.ih l ::n applications. Bussmann n .rugs the nght, w hou notice. to change desi or construction of any products and to discontinue or limit distribution of any products Bussmann also reserves the right to change or update without notice, any technical intb mation con- tained in this bulletin. Once a product has been selected; it should he tested by the user in ail possible -. applications. Forrn No. HEB Series Page 2 01 3 Data Sheet: 2127 Bussmann® For HEB Holders Only Directions:To select complete holder P/N, work from left to right starting with load terminal options and then line terminal options. Then determine breakaway or non - breakaway style. p p p p p p p p p p p p p p p p p p p p p p Load Terminal Wire Size #12 to #8 #12 #12 to #8 #12 #12 to #8 #12 #12 to #8 #12 #12 to #8 #12 #12 to #8 #12 #12 to #8 #12 #12 to #8 #12 #12 to #8 #12 #12 to #8 #12 #6, #4 #10 #6, #4 #10 #6, #4 #10 #6, #4 #10 #4 #8 #2 #6 #20, #18 #12 to #3 #12 to #3 #12 to #3 #12 to #3 #12 to #2 #8 #6 #6 #4 #3, #4 #2 #1, #2 1/0 #8 to #12 #10 to #14 No. of Wires per Terminal Solid Wire Stranded Wire 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 Y Y 2 Y Y 1 N Y 2 Y Y 1 N Y 2 Y Y 1 Y Y 1 Y Y 1 Y Y 1 Y Y 1 Y Y 1 Y Y 1 N Y 1 Y N 1 N Y 1 Y N 1 N Y 1 Y N 1 N Y 1 N Y 1 Y N 1 N Y Line Terminal Terminal Type Wire Size No. of Wires per Terminal Solid Wire Stranded Wire Copper #12 to #8 1 Y Y Crimp #12 2 Y Y Copper #6 to #4 1 Y Y Crimp #10 2 Y Y Copper #4 1 N Y Crimp ( #8 2 Y Y Copper #2 1 N Y Crimp #6 2 Y Y Copper 2/0 1 N Y Crimp #3 2 N Y Copper #12 to #3 1 Y Y Set -Screw Copper #12 to #3 2 Y Y set -screw Aluminum #12 to #2 1 Y Y Set -Screw Aluminum #12 to #2 2 Y Y Set -Screw Aluminum Crimp #1, #2 1 N Y Copper #12 to #8 1 Y Y Crimp #12 2 Y Y Copper #6, #4 1 Y Y Crimp #10 2 Y Y Copper #4 1 N Y Crimp #8 2 Y Y Copper #2 1 N Y Crimp #6 2 Y Y Copper #4 1 N Y Crimp #8 2 Y Y Copper #2 1 N Y Crimp #6 2 Y Y Copper #12 to #8 1 Y Y Crimp #12 2 Y Y Copper #12 to #3 1 Y Y Set -Screw Copper Set Screw #12 to #3 2 Y Y Aluminum #12 to #2 1 Y Y Set -Screw Aluminum #12 to #2 2 Y Y Set -Screw Aluminum #12 to #2 1 Y Y Set -Screw Aluminum #8 1 N Y Crimp #6 1 Y N Aluminum #6 1 N Y Crimp #4 1 Y N Aluminum #3, #4 1 N Y Crimp #2 1 Y N Aluminum Crimp #1, #2 1 N Y Aluminum Crimp 1/0 1 N Y SolidTerminal #8 to #12 1 Y N for aluminum connector #10 to #14 1 N Y Availa Non - Breakaway P/N (Boots not included) HEB- AA( (3) HEB -AB( HEB -AC( HEB -AD( HEB -AE( HEB -AJ HEB -AK HEB -AL HEB -AY HEB -AR HEB -BA( HEB -BB( HEB -BC( HEB -BD( HEB -CC( HEB-DD( HEB -ZA HEB-JJ HEB -JK HEB -JL HEB -JY HEB -LL HEB -NN HEB -PP( HEB -QQ( HEB-RR( HEB-TT( HEB -SS Terminal Type Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Crim Copper Set -Screw Copper Set -Screw Copper Set -Screw Copper Set -Screw Aluminum Set -Screw Aluminum Crim Aluminum Crim Aluminum Crim Aluminum Crim Aluminum Crim SolidTerminal for aluminum connector ( 11 UL Recognized, Guide IZLT2, File E14853 ( Certified, Class 6225 -01, File 47235 ( ( AW- RI..0 -C is for (1) #4 Stranded Wire only. 0 COOPER Bussmann 7 -16 -03 NO3082 le P /N's Breakaway P/N (Boots included) HEB- AW- RLCA( (3) HEB -AW -RLC -B HEB -AW- RLC -C( N/A N/A HEB -AW -RLC -J HEB -AW -RYC HEB -AW -RLA HEB -AW -RYA N/A HEB -BW -RLC -A HEB -BW -RLC -B N/A N/A N/A N/A N/A HEB-JW-RLC-J HEB-JW-RYC N/A N/A HEB -LW -RLA N/A N/A N/A N/A N/A N/A Contact your local Bussmann representative for other possible terminations not listed. Forrn No. HEB Series Page 3 of 3 Data Sheet: 2127