HomeMy WebLinkAboutAsphalt Density ResultsCORING/THICKNESS REPORT
Report Number: Al 111023.0023
Service Date: 11/16/11
Report Date: 11/29/11
Task: Creek Meadows, Section 2, Phase 3
Client
Brazos Valley Services
Attn: Ricky Palasota
PO Box 985
Bryan, TX 77806
On November 16, 2011, a Terracon Consultants, Inc., representative was present at the above referenced project to obtain Hot -Mix
Asphaltic Concrete (HMAC) cores and returned to the laboratory. Results of the tests performed are shown below.
DATE
CORED
11/16/11
MATERIAL
DESIGNAT
OR
(1) Brazos Valley Services, Rebecca Rice
(1) Terracon Consultants, Inc., Mark
Dorsals
SUMMARY DENSITY TEST RESULTS OF ASPHALTIC CONCRETE PAVEMENT CORES
LOCATION
1) 10' S of Sta 1 +00, northbound
2) 15' N of Sta 3 +00, southbound
3) Lot 10, Sta 5 +00, northbound
4) CL of Lots 8 & 18, Sta 8 +00, southbound
Average
DATE PAVED
NOTE: Air voids based on Theoretical Maximum Density
*Does not meet B /CS Unified Specifications (8% or less)
Services: Asphalt Coring
Terracon Rep.: Matcek, James
Reported To: Wayne with Brazos Valley Services
Contractor:
Report Distribution:
(I) Brazos Valley Services
(I) Brazos Valley Semites, Elaine
Palasota
(1) City of College Station TX, Israel
Koite
THICKNESS
(IN.)
2.60
2.25
2.60
2.50
2.50
THEORETICAL MAXIMUM
SPECIFIC GRAVITY
Project
Brazos Valley Services - Misc. Testing
6988 Raymond Stotzer Pkwy
College Station, TX 77845
Project Number: A1111023
DENSITY AIR VOIDS
(pct) (Vol
143.2 5.5
136.5 9.9
140.1 7.5
136.1 10.2
138.9 X8.3
THEORETICAL MAXIMUM
DENSITY (pep
Started: 0830
Finished: 1130
Reviewed By:
lierracon
6198 Imperial Loop
College Station, TX 77845
979 - 846 -3767 Reg No: F -3272
MATERIAL
DESIGNATOR
.0022
.0022
.0022
.0022
MATERIAL TYPE
.0022 11/12/11 2.428 151,5 1-IMAC Typo 'D'
Mark E.Dornak, E,I.T.
Project Manager
The tests were performed In general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except In full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the locations) referenced and are not necessarily Indlcative of the properties of other apparently similar or Identical materials.
C70ee1. s.5.I O. Rev.7 Page 1 of 1