HomeMy WebLinkAboutFlow Hydrant and Static Hydrant Analysis 0 4.- CoIiega Station Utilities
Reliable, Affordable, Community Owned
Date test completed Monday November 7, 2011
Time completed 10:30 A.M.
Test completed by Justin Tamplin and Floyd Anderson
Witness Lorenza Nutall
4 €%, ii i %��`�?, ,...:? : /e . rte.: � .,..
FLOW HYDRANT
Location Castle Gate 2 Section 200
Nozzle size 2.5
Hydrant number V -092
Pitot reading in PSI 45
Flow in G.P.M. 1130
STATIC HYDRANT
Location Castle Gate 2 Section 200
Hydrant number V -091
Static PSI 90
Residual PSI 68
Comments Initial