HomeMy WebLinkAboutRMDL2007-01408 SUBWAY 2418 TEXAS AVE S D BUILDING PERMITPREPARED 7/18/07, 7:32:23 INSPECTION TICKET PAGE 21
City of College Station INSPECTOR: BUILDING INSPECTOR DATE 7/17/07
------------------------------------------------------------------------------------------------
ADDRESS . : 2418 TEXAS AVE S D SUBDIV:
TENANT, NBR: SUBWAY INTERIOR REMODEL
CONTRACTOR SUBWAY PHONE (979) 693-3933
OWNER PHONE
PARCEL - -
APPL NUMBER: 07-00001408 COMMERCIAL, REMODEL/RENOVATION
------------------------------------------------------------------------------------------------
PERMIT: BLDG 00 BUILDING PERMIT
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
B125 01 7 / 7 BLDG, FINAL TIME: 17:00
' M my 17, 2007 2:15:57 PM acarter.
---------- �----------------------- COMMENTS AND NOTES--------------------------------------
s
(7/18/2007) Kim Wolfe - Re: Calling for CO @ 2418 Texas Ave S ste-D (Subway remodel) Page 1
From: Eric Dotson
To: Benjamin McCarty; Chris Haver; Jerry Duffey; Kim Wolfe; Steve Smith
Date: 7/18/2007 1:18 PM
Subject: Re: Calling for CO @ 2418 Texas Ave S ste D (Subway remodel)
CC: Amber Carter; Gina Southerland
Good through Fire!!!!!
Eric Dotson '06
Deputy Fire Marshal
College Station Fire Department
edotson@cstx.gov
(979)764-3709
(979)764-3705
Fax(979)764-3403
>>> Kim Wolfe 07/18/07 8:11 AM >>>
Interior remodel of the Subway.
Are there any issues?
BP # 07-1408
Thanks
Kimberly Wolfe, CPS/CAP
City of College Station
Planning & Development Services
(979) 764-3570
www. cstx.4ov
City of College Station
1101 TEXAS AVENUE
COLLEGE STATION TX 77840
C E R T I F I C A T E O F C O M P L E T I O N
P E R M A N E N T
Issue Date . . . . . .
Parcel Number . . . . .
Property Address . . .
Subdivision Name . . .
Legal Description . . .
Property Zoning . . . .
Owner . . . . . . . . .
Contractor
Application number
Description of Work
Construction type . . .
Occupancy type . . . .
Flood Zone . . . . . .
Approved . . . . . . .
7/18/07
2418 TEXAS AVE S D
COLLEGE STATION
GENERAL COMMERCIAL
SUBWAY
979 693-3933
TX 77840
07-00001408 000 000
COMMERCIAL, REMODEL/RENOVATION
NON-COMBUSTIBLE
ASSEMBLY (IBC)
Building Official
VOID UNLESS SIGNED BY BUILDING OFFICIAL
BUILDING PERMTT
CITY OF COLL� �ATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
----------------------------------------------------------------------------
Application Number . . . . .
Application pin number . . .
Property Address . . . . . .
Property ID:
R #.
Tenant nbr, name . . . . . .
Application type description
Subdivision Name . . . . . .
Property Use . . . . . . . .
Property Zoning . . . . . . .
Application valuation . . . .
Owner
------------------------
07-00001408 Date 5/14/07
986880
2418 TEXAS AVE S D
R37094
SUBWAY INTERIOR REMODEL
COMMERCIAL, REMODEL/RENOVATION
GENERAL COMMERCIAL
40000
Contractor
------------------------
OWNER
--- Structure Information 000 000 INTERIOR RESTAURANT REMODEL
Construction Type . . . . . NON-COMBUSTIBLE
Occupancy Type . . . . . . ASSEMBLY (IBC)
Other struct info . . . . . IMPACT/PRORATA FEES PAID NA
HEATED AREA 1400.00
INTERIOR WALL TYPE WOOD STUDS
SEWER TYPE PUBLIC
TAZ 319.00
----------------------------------------------------------------------------
Permit BUILDING PERMIT
Additional desc GS
Permit pin number 502096
Permit Fee . . . . 210.00 Plan Check Fee .00
Issue Date . . . . 5/14/07 Valuation . . . . 40000
Expiration Date . . 11/10/07
Qty Unit Charge Per Extension
BASE FEE 15.00
39.00 5.0000 THOU BLDG, VAL 1001-50000 195.00
----------------------------------------------------------------------------
Special Notes and Comments
PROVIDE ADDRESS ON COMMERCIAL BUILDINGS -FRONT 5" NUMBERS
REAR - 2" HIGH NUMBERS WITH NAME OF BUSINESS
THE TEXAS DEPARTMENT OF HEALTH REQUIRES AN ASBESTOS SURVEY
IN CERTAIN CIRCUMSTANCES - CALL TDH @ (254) 778-6744 FOR
MORE INFORMATION
NOTE FROM WATER DEPT--REDUCED PRESSURE ASSEMBLY REQUIRED FOR
CAR WASH, POSTMIX CARBONATER, AND HEATING/AC WITH DIRECT
----------------------------------------------------------------
BUILDING DEPT REPRES$NTATIVE:
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
Page 2
Application Number . . . . . 07-00001408 Date 5/14/07
Application pin number . . . 986880
----------------------------------------------------------------------------
Special Notes and Comments
CONNECTION TO WATER SUPPLY AND LAWN IRRIGATION SYSTEMS.
ALL DEVICES MUST BE TESTED UPON INSTALLATION BY CERTIFIED
TESTER REGISTERED WITH THE CITY OF COLLEGE STATION PUBLIC
UTILITIES DEPT. LAWN IRRIGATION MAY USE A PRESSURE VACCUM
BREAKER INSTALLED PER AWWA STANDARDS AND CITY'S ORD #2394.
ALL DEVICES MUST BE INSTALLED PER AWWA AND CITY'S ORD#2394
Underground electrical conduit installation shall be
installed per city specs and is the responsibility of the
owner and/or contractor. Contact the electrical division at
(979) 764-6314 for more information.
ELECTRICAL SHALL BE INSTALLED PER 2002 National Electrical
Code & LOCAL AMENDMENTS
PROVIDE EXTERIOR LANDING LEVEL WITH THE INTERIOR FLOOR FOR
REQUIRED EXIT DOOR(S)
PROVIDE FIRE EXTINGUISHER(S) - VERIFY LOCATION AND PLACEMENT
WITH THE FIRE MARSHALL'S OFFICE (MIN. 2A10BC)
Assure Proper GFI Locations, Including One Within 25' Of
Outside A/C Unit
PROVIDE A KNOX BOX FOR FIRE DEPARTMENT ACCESS.
REQUIRED EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE
WITHOUT THE USE OF A KEY,TOOL OR SPECIAL KNOWLEDGE/EFFORT
All outdoor lighting must be in compliance with Section
7.10, Outdoor lighting Standards of the City's Unified
Development Ordinance
All roof and ground -mounted mechanical equipment shall be
sreened from view or isolated so as not to be visible from
any public right-of-way or residential district within 150
feet of the subject lot, measured from a point five feet
above grade. Such screening shall be coordinated with the
building architecture and scale to maintain a unified
appearance. Acceptable methods of screening rooftop
equipment may include, but are not limited to encasement,
parapet walls, or partition screens. -
CONSTRUCTION ACTIVITY BETWEEN THE HOURS OF 10:00 PM AND
7:00 AM MUST COMPLY WITH THE NOISE ORDINANCE (MAX. 55 DBA)
PROVIDE PANIC HARDWARE ON EXIT DOORS
If PEX water supply piping is sleeved below the slab, seal
annular space at ends with caulk, foam or other means.
Also assure proper protection of pipe to U.V. light.
ANY CHANGES OR ALTERATIONS TO SUBMITTED PLANS MUST BE
RESUBMITTED AND APPROVED BEFORE W041K IS DONE IN ORDER TO
----------------------------------------------------------------
'9444
BUILDING DEPT REPRE�NTATIVE.
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
Page 3
Application Number . . . . . 07-00001408 Date 5/14/07
Application pin number . . . 986880
----------------------------------------------------------------------------
Special Notes and Comments
ASSURE CODE COMPLIANCE
POST PERMIT CARD ON JOB SITE
TEMPERED GLASS REQUIRED IN WINDOWS WITHIN 24" OF DOORS IN
ADJACENT WALLS
ALL PLUMBING, ELECTRICAL, AND HVAC (mechanical) WORK MUST
BE PERFORMED BY LICENSED CONTRACTORS. CONTACT BUILDING
DEPARTMENT FOR INSPECTIONS PRIOR TO COVERING ANY WORK
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
---------------------------------------------------------
Permit Fee Total 210.00 210.00 .00 .00
Plan Check Total .00 .00 .00 .00
Grand Total 210.00 210.00 .00 .00
t;;�-
--------------------------------------- -14 -------------------------
BUILDING DEPT REPR TATIVE:
1 z
APPLICANT:
��foff lo, U . onh
1 APPLICATION FOR BUILDING PERMIT DATE: �J1
' 1 V (TRCCf ERfG
CITY OF COLLEGE STATION APPLICATION * 1 `ALO C"�
1101 TEXAS AVENUE
COLLEGE STATION, TX 77840 TEMP POLE #
Cn'Y OP COLLEGE STarloN (979) 764-3670 (979) 764-3496 FAX /�
PLrnndd4vrinpmrnrSmKrrc WWW.CSTX.GOV It _
ADDRESS/LOCATION: "? I l O
LOT BLOCK SUBDIVISION SEC/PH
BUSINESS/OWNER NAME: r p4'0'4q PHONE: &I93 3'33
CONTRACTORIHOMEOWNER: FJE� r �E���' PHONE:
CONTRACTOR ADDRESS: .2631 m lTceff l-L Pi�W �f f CS
ELECTRICIAN: PLUMBER:
HVAC: /1900 /I��'' T. GOOD CENTS (Residential only):
CLASS OF WORK
ACCESSORY/STORAGE LOCATION RE -ROOF go
ADDITION MOVING SHELL ONLY 0 M_
DEMOLITION (Asbestos Survey) NEW CONSTRUCTION * SLAB ONLY
DUPLEX (Landscape Plans MODEL/RENOVATION* SWIMMING POO
Required) 1.10 - 0-
DESCRIPTION M_e- c'rw
OF WORK: %NS � Dl�fm/z
A60tAcer 6LW5T1NI 46�/G/,+G 6;r4,d Al-40 /e1x7"u2E5
STRUCTURE USE: 5yoP
HOMEOWNER ASSOCIATION/ARCHITECTUAL OR DESIGN REVIEW COMMITTEE APPROVAL: ;13 O
TEXAS ACCESSIBILITY STANDARD (TAS) PROJECT REGISTRATION# EABPRJ
VALUATION: $ '36 - ybiGb4 TOTAL AREA: N66 HEATED AREA:
(Cost of Labor and Materials)
2111P0,UBLIC SEWER
SEPTIC/TREATMENT SYSTEM
SEWER TAP:
WATER TAP:
OTHER TAP:
TEMP POLE
SIZE
SIZE
SIZE
GARAGE TYPE: SINGLE ED
ATTACHED
NUMBER OF BEDROOMS:
NUMBER OF BATHROOMS:
INTERIOR WALL TYPE: &100'a fZOj
EXTERIOR WALL TYPE: CONC7�
FOUNDATION TYPE: ccKi4CE/-6
ROOF TYPE:
DOUBLE F__j TRIPLE
gAyp F__j CARPORT
SIGNATURE OF APPLICANT: /l/r'/ --�
*If proposed work involves new commercial construction or facade improvements/renovations to an existing
commercial property, building elevations are required.
'/
Official Use Only C ments:
L , go
Plans Examiner Zoning Official
May 04 07 09:29a Physical Plant 979-862-1661
p.2
Winkler Inspection Service
2450 Enloe
Bryan, TX 77807
Burt Keller
Director of Operations
Centex Subway, Inc.
PO Box 10161
College Station, TX 77842
I conducted a limited asbestos survey for the remodeling project at 2418 D Southwest
Pkwy on May 4, 2007. The ceiling tiles are made of fiberglass. No asbestos containing
materials will be disturbed in this scope of work.
T you
Grady Winkler
TDHS License #602112
RECEIVED 05-04-'07 08:29 FROM- 9798621661 TO- CENTEX SUBWAY P002/003