HomeMy WebLinkAboutRMDL2003-01984 ZALES REMODEL 1500 HARVEY RD 4003 BUILDING PERMITPREPARED 11/03/03, 12:11:46 INSPECTION TICKET PAGE 3
City of College Station INSPECTOR: BUILDING INSPECTOR DATE 11/03/03
-------------------------------------------------------------------------------------------------
ADDRESS 1500 HARVEY RD 4003 SUBDIV: POST OAK MALL
TENANT, NBR: ZALES REMODEL
CONTRACTOR : NACCO, INC. PHONE : (792) 620-9975
OWNER : C B L & ASSOCIATES PROPERTIES PHONE :
PARCEL : 514000-0001-0040
APPL NUMBER: 03-00001984 COMMERCIAL, REMODEL/RENOVATION
------------------------------- =---------------------------------------------------------------
PERMIT: BLDG 00 BUILDING PERMIT
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
B115 01 10/14/03 OC BLDG, FRAMING TIME: 17:00 r
10/16/03 AP- 10/14/2003 10:09 AM SSTANLEY
B: 01 11/03/03 BI BLDG, FINAL TIME: 17:00
aI z 11/03/2003 09:40 AM GCARRILLO
---- ----� � -------------------- COMMENTS AND NOTES -- �`/
1.4
DATE: 9-23-03
ATTN: Carl Warren
FACSIMELE TRANSMISSION
FROM:
SUBJECT:
FIRM: College Station Building
Department
PHONE: 979-764-3744
FAX: 979-764-3496 PAGES:
NOTE:
John Sutton
Zale's Jewelers, store 91277
Post Oak Mall, Space #4003
1500 Haryey Road
College Station, Texas 77540
(4) (including cover page)
Here are the results of the Asbestos Survey done for Zale Corporation on the above mentioned
Mall space.needed prior to the remodel construction. If this is not sufficient or you are in need of
added information please call me John Sutton at 972-620-9975, Extension 206 or Troy Lancaster
at 361-510-0104,
Thank you,
John Sutton, Project Manager for NACCO, Inc.
Q 2435 Southwell, #3, Was, TX 75229 . Phone: (972) 620-9975 . Fax: (972) 620-9979
17iti'd 6Z66 029 2Z6 DWI 0 3 0 d N WdSZ:90 60, EZ d3S
SEP 23 '03 06:15PM N A C C 0 INC 972 620 9979
P.2/4
aeftuta l PO!Wd
.S.a N'H'd'W Iw08 wet
-"WftIl
,pew uea noA wdojd ajrgnj due ao sn &jn„aouoo ou'Wogsanb IV £4-6LB 1e aw
•A�o �aqe� A10 wo-. uogsluaumom A na osu HE au►MOSU
tat c" Ytage ul noA of 'µ,is aq 1pm jj0d&j p" V 'scgse see 1
-Cl
auo�l, aq of I�u sajohu8s llV gel ��A�S IIaJ 'IfoW -I d 044
ut OJINg 9WZ aye ;Q pewnpuoo.ari wopodgul 04R UJ0+11Insea olduum eye wn eueH
UlCUB48
61SA66N ommd 0 SPUN as"" -WA X vAssiff p
� ► 'gIs$1 aldums sopagsy wo
{ -40*d ms-oes-alu Mai
IURW ivais amour IWA*O U*WgF :eL
ML-BZE 'L :11aw no L
92ZL-L@L-OL6 3NOHd
sO91c Sal `NVAVG
Td Wd6O:EO 5VWZ 9:0 "Tnf C,F.ZTT91f,P.6 : 'ON XH=l 7NT -jdImq wmT 4 Ni I+fit
£0/20 "E"ON *75=5L .£0, ZZ/60 L*r0'h ML6 uotZeuWJOO/a1eZ '
SEP 23 '03 06:15PM N A C C 0 INC 972 620 9979
P.3/4
apsayg W. W) - pat-m3a WON
vie a .nz) - pol"Q atwN
*gnyq "31 RA Ps Q=x
a.Mg . ,►� - P�u�i .aa.+h
SIM laci3 - pownQ awx
zikL JGM • Palama auoN
*Run A&OaA - Pmmma =UK
nif L .,fit - aooN
&'M I�3 /d • F wOly
dlUJ1& m913 N410 - ,d =oH
oil"" Rmle - v3pnlod MON
uu► IrAu[ Imam 1. • li3Mwa QUUK
d1uM Rod / s xlsa - P&oMaL[ gWK
diula Adel fT`ID ` PMM90 =WK
a,rn"w v�la - pomaq aUoN
dw's tn°:t / j#kd . Pampd woN
duM JQq!A 9mic) - POWU WON
OURIN pfflo too suom
otl.l.i!�J - pasaitaq arax
ma smvw) powmau =aK
y[iy "ON
)datM oouogoV
W1Sh�1j:�1" q•1 AWlafl IMA 13% 'Itr"X 100la 'aanVN Pate atafi ae00 i
wUu,0 407 umunvog 'Mag w+rims •IUSVN pus me VA00
m�aeutsa� -PISMO ' 000s p9-AMS 'a !.L-14old Auld -Z[ lK..ZI
wonuumd `wove[ comcgg '81►1.100113RJ,ZI a .Z!
2111 XUlF3 GAOyr uwag auams 'aP'P4 Sand I1a e i
a11y 9u,1pv3 aAOgV WOOX 03WMS 'ZUTS [aati(l ll*Vlg
0111 lUqTQ;) anOqd UW011 Of"$ 'aaapy�
�H 1� ►ti[ a� Ry
yWlaQ farad luou r• m "IV --if 03wm5 '01!.L lowz, V< PCs•),
jM.%, *Aoqv waoit -Sows '*V.L ftipaD u!-Ac-1
zfogpoQ^! / nogdrs'MaQ aidWt!y tuatl�
voo-se
a£0• SL
et:o-sz
t►i0'SZ
3zo-cz
OtirSZ
Mtn-s�z
�ltrcr.
�lo-sz
bl(rSL
mgtmK oldLuffS
!AWpq;M••••;•a as MpsW ayl -miMc i pmmU aq Wu ua lUa0p, faj fpirc'�WoeAa �n Hoag* Map 4Rl � i01n1�
ulmla iq —givue +-114 rout 'tltttMMIM!euy uaC+r JO ,plq.VR a LLVd At PONW9 e — taldtu- mrZmw *Rq (91) aWVs'EQQ"0/L0 uo
t d0 1 99m
ECMZ/MLC) :alWl Uod2a
LLFZ01 4471 tbd
"Wl*nE •axa0Wt 6140.1 11
osoZO 'oN Qs't -tV7AN
9 i L / t ErN 1009 POW" W3
• (ShcW let) 6, yt��S urnttadsld / I[dtr�so�;yjN 340!l Ps�$iad � PoR�W >soy
• o��loud a[dweS xl+'{13 •oo1r,+�V : uogeaktltu�I
eooz/Lotjp : aiaq a[dw E0av
IIBW Neo wd 'sela2
L. �p lob'5u! •1igluowuojjAu3 unsnv ,um
• Zttibwtit t246) 9{)OsG scxay'ugttivus,
too o+lnS '4d[opvv-[ o l s 1
•�t/f sdae"I oa�Yyt► ,tnr, N --Aais
Po',�?t
2d Ldd50 : E0 CMz M • l ht S2Zt i r_4GL(S : -ON xbd .:)NI 'ltj.LN:JWh Zl I AN3 N i lSnkl _. 4iPiN-1
E0/ LO +i'iZ' ON 55 : S V £0 . ZZ/60 L+1017095ZL6 uo «ej odj o3 /aj eZ ,
O
L
Lo W
U-%
Z
N Q
c9
J
N
x
n
'
Z 1. 1
1.
�r
a
v
N
•y a
o�
T�
�
.V �
yp
It I
Q
C3
O•
•+
21
���
s
a�
a►-
All
4 4
9
g -
N ni
r4
N,
J
Cyy
C!
•s a
�s36
$�a4
g
I
Permit Number
Lighting Compliance Certificate Checked By/Date
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Data filename: J:\ClientsK-Z\Zales\ActiveProjects\03M203\ Drawings\1277\03m203.cck
Section 1: Project Information
Project Name: ZALES
1500 HARVEY RD,
SUITE #4003
COLLEGE STATION, TX 77840
Designer/Contractor:
Telephone:
Document Author:
Telephone:
Date:
Section 2: General Information
Building Use Description by:
Activity Type(s)
Retail Sales, Wholesale Showroom
Activity Type
Floor Area
1308
Project Description (check one):
_ New Construction _ Addition _ Alteration _ Unconditioned Shell (File Affidavit)
Section 3: Requirements Checklist
Bldg.
Dept.
Use
[ ] Interior Lighting
1. Total actual watts must be less than or equal to total allowed watts
Allowed Watts Actual Watts Complies(Y/N)
3695 3667 YES
Exterior Lighting
[ ] 2. Efficacy greater than 451umens/W
Exceptions:
Specialized lighting highlighting features of historic buildings; signage; safety or security lighting;
low -voltage landscape lighting.
Controls, Switching, and Wiring
[ ] 3. Independent controls for each space (switch/occupancy sensor).
Exception: Areas that must be continuously lighted.
[ ] 4. Master switch at entry to hotel/motel guest room
[ ] ( 5. Two switches or dimmer in each space to provide uniform light reduction capability.
Exceptions:
Only one luminaire in space; An occupant -sensing device controls the area;
The area is a corridor, storage, restroom, or lobby; Areas that must be continuously lighted;
[ ] 6. Photocell/astronomical time switch on exterior lights.
Exceptions: Areas requiring lighting during daylight hours
7. Tandem wired one -lamp and three -lamp ballasted luminaires.
Exceptions:
Electronic high -frequency ballasts; Luminaires not on same switch
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent with the building plans, specifications and other
calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2000
IECC requirements in COMcheck-EZ Version 2.4 Release 2b and to comply with the mandatory requirements in the
Requirements Checklist.
r&_'0606*11 J 645"1'+
Principal Lighting Designer -Name
l� -C'r-D3
Date
Lighting Application Worksheet
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Section 1: Allowed Lighting Power Calculation
A B
C
D
Total
Floor
Allowed
Allowed
Area
Watts
Watts
Area CateQory (ft21
watts/ft2
B x C
Retail Sales, Wholesale Showroom 1308
2.1
2747
Allowance: Fine Merchandise Display / Fix. ID: A 243(a)
3.9
948(b)
(a) Area claimed must not exceed the illuminated area permitted for this allowance type.
(b) Allowance is (B x C) or the actual wattage of the fixtures given in Section 2, whichever is less.
Total Allowed Watts = 3695
Section 2: Actual Lighting Power Calculation
A B C D E F
Fixture Fixture Description / Lamps/ # of Fixture
ID Lamp Description / Wattage Per Lama / Ballast Fixture Fixtures Watt. x E
A
SHOW CASE LTG. / Metal Halide 35W / Magnetic
1
41
45
1845
B
DOWN LTG. / Twin Tube 24/26/27W / Electronic
2
2
32
64
B2
NIGHT LIGHT / Twin Tube 24/26/27W / Electronic
2
3
32
96
D
ACCENT & GRAPHICS / Incandescent 75W
1
9
75
675
F4
BACK ROOM / 48" T8 32W / Electronic
1
2
32
64
FE
BACK ROOM / 48" T8 32W / Electronic
1
1
32
32
S3
WALL LTG. / Twin Tube 24/26/27W / Electronic
1
4
27
108
Z
TOILET ROOM / 48" T8 32W / Electronic
1
1
32
32
9
LT RAILS / Other / Electronic
1
6
4
24
10
LT RAILS / Other / Electronic
1
1
21
21
11
LT RAILS / Other / Electronic
1
4
35
140
12
LT RAILS / Other / Electronic
1
17
28
476
13
LT RAILS / Other / Electronic
1
2
45
90
Total Actual Watts = 3667
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 3695
Total Actual Watts = 3667
Project Compliance = 28
Lighting PASSES: Design 1% better than code
Permit Number
Mechanical Compliance Certificate Checked By/Date
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Data filename: J:\ClientsK-Z\Zales\ActiveProjects\03M203\ Drawings\1277\03m203.cck
Section 1: Project Information
Project Name: ZALES
1500 HARVEY RD,
SUITE #4003
COLLEGE STATION, TX 77840
Designer/Contractor:
Telephone:
Document Author:
Telephone:
Date:
Section 2: General Information
Building Location (for weather data): College Station, Texas
Climate Zone: 4b
Heating Degree Days (base 65 degrees F): 1788
Cooling Degree Days (base 65 degrees F): 2776
Project Description (check one):
_ New Construction _ Addition _ Alteration _ Unconditioned Shell (File Affidavit)
Section 3: Mechanical Systems List
Quantity System Type & Description
1 HVAC System 1: Heating: Central Furnace, Electric / Cooling: Rooftop Package Unit, Capacity <65
kBtu/h, Air -Cooled Condenser / Single Zone
1 Water Heating 1: Service Water Heater
Section 4: Requirements Checklist
Bldg.
Dept.
Use
Requirements Specific To: HVAC System 1
[ ] 1. Newly purchased cooling equipment meets the cooling efficiency requirements
Requirements Specific To: Water Heating 1
[ ] 1. Heat traps in inlet/outlet fittings
[ ] 2. 1/2-in. insulation on 8 ft of inlet/outlet piping if no integral heat traps
Generic Requirements: Must be met by all systems to which the requirement is applicable
[ ] 1. Load calculations per 1997 ASHRAE Fundamentals
[ ] 2. Plant equipment and system capacity no greater than needed to meet loads
- Exception: Standby equipment automatically off when primary system is operating
- Exception: Multiple units controlled to sequence operation as a function of load
3. Mini num one temperature control device per system
4. Minimum one humidity control device per installed humidification/dehumidification system
5. Thermostatic controls has 5 deg. F deadband
- Exception: Thermostats requiring manual changeover between heating and cooling
6. Automatic Controls: Setback to 55 deg. F (heat) and 85 deg. F (cool); 7-day clock,
2-hour occupant override, 10-hour backup
- Exception: Continuously operating zones
- Exception: 2 kW demand or less, submit calculations
7. Automatic shut-off dampers on exhaust systems and supply systems with airflow >3,000 cfin
8. Outside -air source for ventilation; system capable of reducing OSA to required minimum
9. R-5 supply and return air duct insulation in unconditioned spaces
R-8 supply and return air duct insulation outside the building
R-8 insulation between ducts and the building exterior when ducts are part of a building assembly
- Exception: Ducts located within equipment
- Exception: Ducts with interior and exterior temperature difference not exceeding 15 deg. F.
10. Ducts sealed - longitudinal seams on rigid ducts; transverse seams on all ducts;
UL 181A or 181B tapes and mastics
11. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
12. Operation and maintenance manual provided to building owner
13. Balancing devices provided in accordance with IMC 603.15
14. Newly purchased service water heating equipment meets the efficiency requirements
15. Water heater temperature controls: 110 deg. F for dwelling units or 90 deg. F
for other occupancies
Section 5: Compliance Statement
The proposed mechanical design represented in this document is consistent with the building plans, specifications and
other calculations submitted with this permit application. The proposed mechanical systems have been designed to
meet the 2000 IECC requirements in COMcheck-EZ Version 2.4 Release 2b and to comply with the mandatory
requirements in the Requirements Checklist. _ 1111RA..._
Principal Mechanical Designer -Name
6- / F-d 3
Date
Mechanical Requirements Description
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Data filename: J:\ClientsK-Z\Zales\ActiveProjects\03M203\ Drawings\1277\03m203.cck
The following list provides more detailed description of the requirements in Section 4 of the Mechancal Compliance Cei
Requirements Specific To: HVAC System 1
1. The specified cooling equipment is covered by Federal minimum efficiency requirements. New equipment of this
type can be assumed to meet or exceed ASHRAE 90.1 Code requirements for equipment efficiency.
Requirements Specific To: Water Heating 1
1. Heat traps are required on noncirculating water heating systems on both inlet and outlet connections. Heat traps
may be purchased or field -fabricated by creating a loop or inverted U-shaped arrangement on the inlet and outlet
pipes.
2. Pipe insulation for the specified noncirculating service hot water system is required for all piping in the following
categories:a) the first 8 ft of outlet piping from any constant -temperature, noncirculating storage systemb) the inlet
piping between the storage tank and a heat trap in a noncirculating storage systemPipe insulation must be at least
1/2 in. and have a conductivity no >0.28 Btu-in/(h-ft2 °F).
Generic Requirements: Must be met by all systems to which the requirement is applicable
1. Design heating and cooling loads for the building must be determined using procedures equivalent to those in
Chapters 27 and 28 of the ASHRAE Handbook of Fundamentals or an approved equivalent calculation procedure.
2. All equipment and systems must be sized to be no greater than needed to meet calculated loads. A single piece of
equipment providing both heating and cooling must satisfy this provision for one function with the capacity for the
other function as small as possible, within available equipment options.
- Exception: The equipment and/or system capacity may be greater than calculated loads for standby purposes.
Standby equipment must be automatically controlled to be off when the primary equipment and/or system is
operating-
- Exception: Multiple units of the same equipment type whose combined capacities exceed the calculated load are
allowed if they are provided with controls to sequence operation of the units as the load increases or decreases.
3. Each heating or cooling system serving a single zone must have its own temperature control device.
4. Each humidification system must have its own humidity control device.
5. Thermostats controlling both heating and cooling must be capable of maintaining a 5 degree F deadband (a range
of temperature where no heating or cooling is provided).
- Exception: Deadband capability is not required if the thermostat does not have automatic changeover capability
between heating and cooling.
6. The system or zone control must be a programmable thermostat or other automatic control meeting the following
criteria:a) capable of setting back temperature to 55 degree F during heating and setting up to 85 degree F during
coolingb) capable of automatically setting back or shutting down systems during unoccupied hours using 7
different day schedulesc) have an accessible 2-hour occupant overrided) have a battery back-up capable of
maintaining programmed settings for at least 10 hours without power.
- Exception: A setback or shutoff control is not required on thermostats that control systems serving areas that
operate continuously.
- Exception: A setback or shutoff control is not required on systems with total energy demand of 2 kW (6,826
Btu/h) or less.
7. Outdoor -air supply systems with design airflow rates >3,000 c$n of outdoor air and all exhaust systems must have
dampers that are automatically closed while the equipment is not operating.
8. The system must supply outside ventilation air as required by Chapter 4 of the International Mechanical Code. If
the ventilation system is designed to supply outdoor -air quantities exceeding minimum required levels, the system
must be capable of reducing outdoor -air flow to the minimum required levels.
9. Air ducts must be insulated to the following levels:a) Supply and return air ducts for conditioned air located in
unconditioned spaces (spaces neither heated nor cooled) must be insulated with a minimum of R-5. Unconditioned
spaces include attics, crawl spaces, unheated basements, and unheated garages.b) Supply and return air ducts and
plenums must be insulated to a minimum of R-8 when located outside the building.c) When ducts are located
within exterior components (e.g., floors or roofs), minimum R-8 insulation is required only between the duct and
the building exterior.
+ ♦ s
- Exception: Duct insulation is not required on ducts located within equipment.
- Exception: Duct insulation is not required when the design temperature difference between the interior and
exterior of the duct or plenum does not exceed 15 degree F.
10. All joints, longitudinal and transverse seams, and connections in ductwork must be securely sealed using
weldments; mechanical fasteners with seals, gaskets, or mastics; mesh and mastic sealing systems; or tapes. Tapes
and mastics must be listed and labeled in accordance with UL 181A or UL 181B.
11. Mechanical fasteners and seals, mastics, or gaskets must be used when connecting ducts to fans and other air
distribution equipment, including multiple -zone terminal units.
12. Operation and maintenance documentation must be provided to the owner that includes at least the following
information:a) equipment capacity (input and output) and required maintenance actionsb) equipment operation
and maintenance manualsc) HVAC system control maintenance and calibration information, including wiring
diagrams, schematics, and control sequence descriptions; desired or field -determined set points must be
permanently recorded on control drawings, at control devices, or, for digital control systems, in programming
commentsd) complete narrative of how each system is intended to operate.
13. Each supply air outlet or diffuser and each zone terminal device (such as VAV or mixing box) must have its own
balancing device. Acceptable balancing devices include adjustable dampers located within the ductwork, terminal
devices, and supply air diffusers.
14. Service water heating equipment must meet minimum Federal efficiency requirements included in the National
Appliance Energy Conservation Act and the Energy Policy Act of 1992, which meet or exceed ASHRAE 90.1
Code. New service water heating equipment can be assumed to meet these requirements.
15. Water -heating equipment must be provided with controls that allow the user to set the water temperature to 110 °F
for dwelling units and 90 °F for other occupancies. Controls must limit output temperatures of lavatories in public
facility restrooms to 110'F.
City of College Station Page of
`� Building Inspection Department
PLANS EXAMINATION REPORT
Address:
Project Name:
Drawing Code
Number Ref. Number Questions or. Comments
s �
Date:
Received by: Date:
Permit Number
Lighting Compliance Certificate Checked By/Date
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Data filename: J:\ClientsK-Z\Zales\ActiveProjects\03M203\ Drawings\1277\03m203.cck
Section 1: Project Information
Project Name: ZALES
1500 HARVEY RD,
SUITE #4003
COLLEGE STATION, TX 77840
Designer/Contractor:
Telephone:
Document Author:
Telephone:
Date:
Section 2: General Information
Building Use Description by: Activity Type
Activity Tvae(s) Floor Area
Retail Sales, Wholesale Showroom 1308
Project Description (check one):
_ New Construction _ Addition _ Alteration _ Unconditioned Shell (File Affidavit)
Section 3: Requirements Checklist
Bldg.
Dept.
Use
[ ] Interior Lighting
1. Total actual watts must be less than or equal to total allowed watts
Allowed Watts Actual Watts Complies(Y/1)
3695 3667 YES
Exterior Lighting
[ ] 2. Efficacy greater than 451umens/W
Exceptions:
Specialized lighting highlighting features of historic buildings; signage; safety or security lighting;
low -voltage landscape lighting.
Controls, Switching, and Wiring
[ ] 3. Independent controls for each space (switch/occupancy sensor).
Exception: Areas that must be continuously lighted.
[ ] 4. Master switch at entry to hotel/motel guest room.
[ ] 5. Two switches or dimmer in each space to provide uniform light reduction capability.
Exceptions:
Only one luminaire in space; An occupant -sensing device controls the area;
The area is a corridor, storage, restroom, or lobby; Areas that must be continuously lighted;
[ ] 6. Photocell/astronomical time switch on exterior lights.
Exceptions: Areas requiring lighting during daylight hours
[ ] 7. Tandem wired one -lamp and three -lamp ballasted luminaires.
Exceptions:
Electronic high -frequency ballasts; Luminaires not on same switch
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent with the building plans, specifications and other
calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2000
IECC requirements in COMcheck-EZ Version 2.4 Release 2b and to comply with the mandatory requirements in the
Requirements Checklist. _
fixtu lte, -3 . GO&I-IA
Principal Lighting Designer -Name
ly -/S-os
Date
Lighting Application Worksheet
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Section 1: Allowed Lighting Power Calculation
A B
C
D
Total
Floor
Allowed
Allowed
Area
Watts
Watts
Area Category (ft2Z
watts/ft2
x C
Retail Sales, Wholesale Showroom 1308 2.1 2747
Allowance: Fine Merchandise Display / Fix. ID: A 243(a) 3.9 948(b)
(a) Area claimed must not exceed the illuminated area permitted for this allowance type.
(b) Allowance is (B x C) or the actual wattage of the fixtures given in Section 2, whichever is less.
Total Allowed Watts = 3695
Section 2: Actual Lighting Power Calculation
A
B
C
D
E
F
Fixture
Fixture Description /
Lamps/
# of
Fixture
ID
Lamp Description / Wattage Per Lamp / Ballast
Fixture
Fixtures
Watt.
x E
A
SHOW CASE LTG. / Metal Halide 35W / Magnetic
1
41
45
1845
B
DOWN LTG. / Twin Tube 24/26/27W / Electronic
2
2
32
64
B2
NIGHT LIGHT / Twin Tube 24/26/27W / Electronic
2
3
32
96
D
ACCENT & GRAPHICS / Incandescent 75W
1
9
75
675
F4
BACK ROOM / 48" T8 32W / Electronic
1
2
32
64
FE
BACK ROOM / 48" T8 32W / Electronic
1
1
32
32
S3
WALL LTG. / Twin Tube 24/26/27W / Electronic
1
4
27
108
Z
TOILET ROOM / 48" T8 32W / Electronic
1
1
32
32
9
LT RAILS / Other / Electronic
1
6
4
24
10
LT RAILS / Other / Electronic
1
1
21
21
11
LT RAILS / Other / Electronic
1
4
35
140
12
LT RAILS / Other / Electronic
1
17
28
476
13
LT RAILS / Other / Electronic
1
2
45
90
Total Actual Watts =
3667
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 3695
Total Actual Watts = 3667
Project Compliance = 28
Lighting PASSES: Design 1% better than code
Permit Number
Mechanical Compliance Certificate Checked By/Date
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Data filename: J:\ChentsK-Z\Zales\ActiveProjects\03M203\ Drawings\1277\03m203.cck
Section 1: Project Information
Project Name: ZALES
1500 HARVEY RD,
SUITE #4003
COLLEGE STATION, TX 77840
Designer/Contractor:
Telephone:
Document Author:
Telephone:
Date:
Section 2: General Information
Building Location (for weather data): College Station, Texas
Climate Zone: 4b
Heating Degree Days (base 65 degrees F): 1788
Cooling Degree Days (base 65 degrees F): 2776
Project Description (check one):
New Construction _ Addition _ Alteration _ Unconditioned Shell (File Affidavit)
Section 3: Mechanical Systems List
QuantityS3TLern Type & Description
1 HVAC System 1: Heating: Central Furnace, Electric / Cooling: Rooftop Package Unit, Capacity <65
kBtu/h, Air -Cooled Condenser / Single Zone
1 Water Heating 1: Service Water Heater
Section 4: Requirements Checklist
Bldg.
Dept.
Use
Requirements Specific To: HVAC System 1
1. Newly purchased cooling equipment meets the cooling efficiency requirements
Requirements Specific To: Water Heating 1
[ ] 1. Heat traps in inlet/outlet fittings
[ ] 2. 1/2-in. insulation on 8 ft of inlet/outlet piping if no integral heat traps
Generic Requirements: Must be met by all systems to which the requirement is applicable
[ ] 1. Load calculations per 1997 ASHRAE Fundamentals
[ ] 2. Plant equipment and system capacity no greater than needed to meet loads
- Exception: Standby equipment automatically off when primary system is operating
i
- Exception: Multiple units controlled to sequence operation as a function of load
] 3. Minimum one temperature control device per system
] 4. Minimum one humidity control device per installed humidification/dehumidification system
] 5. Thermostatic controls has 5 deg. F deadband
- Exception: Thermostats requiring manual changeover between heating and cooling
] 6. Automatic Controls: Setback to 55 deg. F (heat) and 85 deg. F (cool); 7-day clock,
2-hour occupant override, 10-hour backup
- Exception: Continuously operating zones
- Exception: 2 kW demand or less, submit calculations
] 7. Automatic shut-off dampers on exhaust systems and supply systems with airflow >3,000 cfm
] 8. Outside -air source for ventilation; system capable of reducing OSA to required minimum
] 9. R-5 supply and return air duct insulation in unconditioned spaces
R-8 supply and return air duct insulation outside the building
R-8 insulation between ducts and the building exterior when ducts are part of a building assembly
- Exception: Ducts located within equipment
- Exception: Ducts with interior and exterior temperature difference not exceeding 15 deg. F.
] 10. Ducts sealed - longitudinal seams on rigid ducts; transverse seams on all ducts;
UL 181A or 181B tapes and mastics
] 11. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
] 12. Operation and maintenance manual provided to building owner
] 13. Balancing devices provided in accordance with IMC 603.15
] 14. Newly purchased service water heating equipment meets the efficiency requirements
] 15. Water heater temperature controls: 110 deg. F for dwelling units or 90 deg. F
for other occupancies
Section 5: Compliance Statement
The proposed mechanical design represented in this document is consistent with the building plans, specifications and
other calculations submitted with this permit application. The proposed mechanical systems have been designed to
meet the 2000 IECC requirements in COMcheck-EZ Version 2.4 Release 2b a4d to comply with the mandatory
requirements in the Requirements Checklist. 9tas000n
Principal Mechanical Designer -Name
°o
_
A,; Q
e Pi�O •,•�, p°} per,
ead a
f_/' -/e-03
Date
Mechanical Requirements Description
2000 IECC
COMcheck--EZ Software Version 2.4 Release 2b
Data filename: J:\ClientsK-Z\Zales\ActiveProjects\03M203\ Drawings\1277\03m203.cck
The following list provides more detailed description of the requirements in Section 4 of the Mechancal Compliance Cei
Requirements Specific To: HVAC System 1
1. The specified cooling equipment is covered by Federal minimum efficiency requirements. New equipment of this
type can be assumed to meet or exceed ASHRAE 90.1 Code requirements for equipment efficiency.
Requirements Specific To: Water Heating 1
1. Heat traps are required on noncirculating water heating systems on both inlet and outlet connections. Heat traps
may be purchased or field -fabricated by creating a loop or inverted U-shaped arrangement on the inlet and outlet
pipes.
2. Pipe insulation for the specified noncirculating service hot water system is required for all piping in the following
categories:a) the first 8 ft of outlet piping from any constant -temperature, noncirculating storage systemb) the inlet
piping between the storage tank and a heat trap in a noncirculating storage systemPipe insulation must be at least
1/2 in. and have a conductivity no >0.28 Btu-in/(h-ft2•°F).
Generic Requirements: Must be met by all systems to which the requirement is applicable
1. Design heating and cooling loads for the building must be determined using procedures equivalent to those in
Chapters 27 and 28 of the ASHRAE Handbook of Fundamentals or an approved equivalent calculation procedure.
2. All equipment and systems must be sized to be no greater than needed to meet calculated loads. A single piece of
equipment providing both heating and cooling must satisfy this provision for one function with the capacity for the
other function as small as possible, within available equipment options.
- Exception: The equipment and/or system capacity may be greater than calculated loads for standby purposes.
Standby equipment must be automatically controlled to be off when the primary equipment and/or system is
operating-
- Exception: Multiple units of the same equipment type whose combined capacities exceed the calculated load are
allowed if they are provided with controls to sequence operation of the units as the load increases or decreases.
3. Each heating or cooling system serving a single zone must have its own temperature control device.
4. Each humidification system must have its own humidity control device.
5. Thermostats controlling both heating and cooling must be capable of maintaining a 5 degree F deadband (a range
of temperature where no heating or cooling is provided).
- Exception: Deadband capability is not required if the thermostat does not have automatic changeover capability
between heating and cooling.
6. The system or zone control must be a programmable thermostat or other automatic control meeting the following
criteria:a) capable of setting back temperature to 55 degree F during heating and setting up to 85 degree F during
coolingb) capable of automatically setting back or shutting down systems during unoccupied hours using 7
different day schedulesc) have an accessible 2-hour occupant overrided) have a battery back-up capable of
maintaining programmed settings for at least 10 hours without power.
- Exception: A setback or shutoff control is not required on thermostats that control systems serving areas that
operate continuously.
- Exception: A setback or shutoff control is not required on systems with total energy demand of 2 kW (6,826
Btu/h) or less.
7. Outdoor -air supply systems with design airflow rates >3,000 cfin of outdoor air and all exhaust systems must have
dampers that are automatically closed while the equipment is not operating.
8. The system must supply outside ventilation air as required by Chapter 4 of the International Mechanical Code. If
the ventilation system is designed to supply outdoor -air quantities exceeding minimum required levels, the system
must be capable of reducing outdoor -air flow to the mini 1Lm required levels.
9. Air ducts must be insulated to the following levels:a) Supply and return air ducts for conditioned air located in
unconditioned spaces (spaces neither heated nor cooled) must be insulated with a minimum of R-5. Unconditioned
spaces include attics, crawl spaces, unheated basements, and unheated garages.b) Supply and return air ducts and
plenums must be insulated to a minimum of R-8 when located outside the building.c) When ducts are located
within exterior components (e.g., floors or roofs), minimum R-8 insulation is required only between the duct and
the building exterior.
R • r
- Exception: Duct insulation is not required on ducts located within equipment.
- Exception: Duct insulation is not required when the design temperature difference between the interior and
exterior of the duct or plenum does not exceed 15 degree F.
10. All joints, longitudinal and transverse seams, and connections in ductwork must be securely sealed using
weldments; mechanical fasteners with seals, gaskets, or mastics; mesh and mastic sealing systems; or tapes. Tapes
and mastics must be listed and labeled in accordance with UL 181A or UL 181B.
11. Mechanical fasteners and seals, mastics, or gaskets must be used when connecting ducts to fans and other air
distribution equipment, including multiple -zone terminal units.
12. Operation and maintenance documentation must be provided to the owner that includes at least the following
information:a) equipment capacity (input and output) and required maintenance actionsb) equipment operation
and maintenance manualsc) HVAC system control maintenance and calibration information, including wiring
diagrams, schematics, and control sequence descriptions; desired or field -determined set points must be
permanently recorded on control drawings, at control devices, or, for digital control systems, in programming
commentsd) complete narrative of how each system is intended to operate.
13. Each supply air outlet or diffuser and each zone terminal device (such as VAV or mixing box) must have its own
balancing device. Acceptable balancing devices include adjustable dampers located within the ductwork, terminal
devices, and supply air diffusers.
14. Service water heating equipment must meet minimum Federal efficiency requirements included in the National
Appliance Energy Conservation Act and the Energy Policy Act of 1992, which meet or exceed ASHRAE 90.1
Code. New service water heating equipment can be assumed to meet these requirements.
15. Water -heating equipment must be provided with controls that allow the user to set the water temperature to 110 °F
for dwelling units and 90 °F for other occupancies. Controls must limit output temperatures of lavatories in public
facility restrooms to 110'F.
.r
a3-1 If 'I
Permit Number
- Lighting Compliance Certificate Checked By/Date
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Data filename: J:\ClientsK-Z\Zales\ActiveProjects\03M203\ Drawings\1277\03m203.cck
Section 1: Project Information
Project Name: ZALES
1500 HARVEY RD,
SUITE #4003
COLLEGE STATION, TX 77840
Designer/Contractor:
Telephone:
Document Author:
Telephone:
Date:
Section 2: General Information
Building Use Description by:
Activity Tyue(s)
Retail Sales, Wholesale Showroom
Activity Type
Floor Area
1308
Project Description (check one):
New Construction _ Addition _ Alteration _ Unconditioned Shell (File Affidavit)
Section 3: Requirements Checklist
Bldg.
Dept.
Use
[ ] Interior Lighting
1. Total actual watts must be less than or equal to total allowed watts
Allowed Watts Actual Watts Complies(Y/1)
3695 3667 YES
Exterior Lighting
[ ] 2. Efficacy greater than 451umens/W
Exceptions:
Specialized lighting highlighting features of historic buildings; signage; safety or security lighting;
low -voltage landscape lighting.
Controls, Switching, and Wiring
[ ] 3. Independent controls for each space (switch/occupancy sensor).
Exception: Areas that must be continuously lighted.
[ ] 4. Master switch at entry to hotel/motel guest room.
[ ] 5. Two switches or dimmer in each space to provide uniform light reduction capability.
Exceptions:
Only one luminaire in space; An occupant -sensing device controls the area;
The area is a corridor, storage, restroom, or lobby; Areas that must be continuously lighted;
[ ] 6. Photocell/astronomical time switch on exterior lights.
To
ELDER-JONES
BUILDING PERMIT SERVICE, INC.
1120 East 80th Street, Suite 211
Bloomington, MN 55420
(952) 854-2854 FAX (952) 854-4909
203. 2%.
* 'SS7c
{ rocs .
LETTER
Subject_�� •__� ._._______._ _ _._ ___ ______.__
�.rtl►ct'QiL-.M 1....rQi'_?at s!Et..-.._.__...__.__..._._..__..._...�.
_.............._....__...__..._._............_.._._..__---__.___...__..___.....__.___...__.__._Tl.�..._
Z)
❑ Please reply', ❑ No reply necessary
SIGNED
4, 0 - ``ft
JI,
. Litj - - .
• 1%
Exceptions: Areas requiring lighting during daylight hours
[ ] 7. Tandem wired one -lamp and three -lamp ballasted luminaires.
Exceptions:
. Electronic high -frequency ballasts; Luminaires not on same switch
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent with the building plans, specifications and other
calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2000
IECC requirements in COMcheck-EZ Version 2.4 Release 2b and to comply with the mandatory requirements in the
Requirements Checklist. - _ tiIIIuIaII._
Principal Lighting Designer -Name
`/f -63
Date
e
11
Lighting Application Worksheet
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Section 1: Allowed Lighting Power Calculation
A
B
C
D
Total
Floor
Allowed
Allowed
Area
Watts
Watts
Area Category
(ft2)
watts/ft2
x C
Retail Sales,
Wholesale Showroom
1308
2.1
2747
Allowance:
Fine Merchandise Display / Fix. ID: A
243(a)
3.9
948(b)
(a) Area claimed must not exceed the illuminated area permitted for this allowance type.
(b) Allowance
is (B x C) or the actual wattage of the fixtures given in Section 2, whichever is less.
Total Allowed Watts =
3695
Section 2:
Actual Lighting Power Calculation
A
B
C
D
E
F
Fixture
Fixture Description /
Lamps/
# of
Fixture
ID
Lamp Description / Wattage Per Lamp / Ballast
Fixture
Fixtures
Watt. x E
A
SHOW CASE LTG. / Metal Halide 35W / Magnetic
1
41
45
1845
B
DOWN LTG. / Twin. Tube 24/26/27W / Electronic
2
2
32
64
B2
NIGHT LIGHT / Twin Tube 24/26/27W / Electronic
2
3
32
96
D
ACCENT & GRAPHICS / Incandescent 75W
1
9
75
675
F4
BACK ROOM / 48" T8 32W / Electronic
1
2
32
64
FE
BACK ROOM / 48" T8 32W / Electronic
1
1
32
32
S3
WALL LTG. / Twin Tube 24/26/27W / Electronic
1
4
27
108
Z
TOILET ROOM / 48" T8 32W / Electronic
1
1
32
32
9
LT RAILS / Other / Electronic
1
6
4
24
10
LT RAILS / Other / Electronic
1
1
21
21
11
LT RAILS / Other / Electronic
1
4
35
140
12
LT RAILS / Other / Electronic
1
17
28
476
13
LT RAILS / Other / Electronic
1
2
45
90
Total Actual Watts = 3667
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero, the building complies.
Lighting PASSES: Design 1% better than code
Total Allowed Watts = 3695
Total Actual Watts = 3667
Project Compliance = 28
i
Permit Number
Mechanical Compliance Certificate Checked By/Date
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Data filename: J:\ClientsK-Z\Zales\ActiveProjects\03M203\ Drawings\1277\03m203.cck
Section 1: Project Information
Project Name: ZALES
1500 HARVEY RD,
SUITE #4003
COLLEGE STATION, TX 77840
Designer/Contractor:
Telephone:
Document Author:
Telephone:
Date:
Section 2: General Information
Building Location (for weather data): College Station, Texas
Climate Zone: 4b
Heating Degree Days (base 65 degrees F): 1788
Cooling Degree Days (base 65 degrees F): 2776
Project Description (check one):
_ New Construction _ Addition _ Alteration _ Unconditioned Shell (File Affidavit)
Section 3: Mechanical Systems List
Quantitx item Type & Description
1 HVAC System 1: Heating: Central Furnace, Electric / Cooling: Rooftop Package Unit, Capacity <65
kBtu/h, Air -Cooled Condenser / Single Zone
1 Water Heating 1: Service Water Heater
Section 4: Requirements Checklist
Bldg.
Dept.
Use
Requirements Specific To: HVAC System 1
[ ] 1. Newly purchased cooling equipment meets the cooling efficiency requirements
Requirements Specific To: Water Heating 1
[ ] 1. Heat traps in inlet/outlet fittings
[ ] 2. 1/2-in. insulation on 8 R of inlet/outlet piping if no integral heat traps
Generic Requirements: Must be met by all systems to which the requirement is applicable
[ ] 1. Load calculations per 1997 ASHRAE Fundamentals
[ ] 2. Plant equipment and system capacity no greater than needed to meet loads
- Exception: Standby equipment automatically off when primary system is operating
- Exception: Multiple units controlled to sequence operation as a function of load
[ ] 3. Minimum one temperature control device per system
[ ] 4. Minimum one humidity control device per installed humidification/dehumidification system
[ ] 5. Thermostatic controls has 5 deg. F deadband
- Exception: Thermostats requiring manual changeover between heating and cooling
[ ] 6. Automatic Controls: Setback to 55 deg. F (heat) and 85 deg. F (cool); 7-day clock,
2-hour occupant override, 10-hour backup
- Exception: Continuously operating zones
- Exception: 2 kW demand or less, submit calculations
[ ] 7. Automatic shut-off dampers on exhaust systems and supply systems with airflow >3,000 cfin
[ ] 8. Outside -air source for ventilation; system capable of reducing OSA to required minimum
[ ] 9. R-5 supply and return air duct insulation in unconditioned spaces
R-8 supply and return air duct insulation outside the building
R-8 insulation between ducts and the building exterior when ducts are part of a building assembly
- Exception: Ducts located within equipment
- Exception: Ducts with interior and exterior temperature difference not exceeding 15 deg. F.
[ ] 10. Ducts sealed - longitudinal seams on rigid ducts; transverse seams on all ducts;
UL 181A or 181B tapes and mastics
[ ] 11. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
[ ] 12. Operation and maintenance manual provided to building owner
[ ] 13. Balancing devices provided in accordance with IMC 603.15
[ ] 14. Newly purchased service water heating equipment meets the efficiency requirements
[ ] 15. Water heater temperature controls: 110 deg. F for dwelling units or 90 deg. F
for other occupancies
Section 5: Compliance Statement
The proposed mechanical design represented in this document is consistent with the building plans, specifications and
other calculations submitted with this permit application. The proposed mechanical systems have been designed to
meet the 2000 IECC requirements in COMcheck-EZ Version 2.4 Release 2b and to comply with the mandatory
requirements in the Requirements Checklist.
Principal Mechanical Designer -Name
,V,D A
.4Goof,.,'
gx
O
nn C
l V
Date
r � a
Mechanical Requirements Description
2000 IECC
COMcheck-EZ Software Version 2.4 Release 2b
Data filename: J:\ClientsK-Z\Zales\ActiveProjects\03M203\ Drawings\1277\03m203.cck
The following list provides more detailed description of the requirements in Section 4 of the Mechancal Compliance Cei
Requirements Specific To: HVAC System 1
1. The specified cooling equipment is covered by Federal minimum efficiency requirements. New equipment of this
type can be assumed to meet or exceed ASHRAE 90.1 Code requirements for equipment efficiency.
Requirements Specific To: Water Heating 1
1. Heat traps are required on noncirculating water heating systems on both inlet and outlet connections. Heat traps
may be purchased or field -fabricated by creating a loop or inverted U-shaped arrangement on the inlet and outlet
pipes.
2. Pipe insulation for the specified noncirculating service hot water system is required for all piping in the following
categories:a) the first 8 ft of outlet piping from any constant -temperature, noncirculating storage systemb) the inlet
piping between the storage tank and a heat trap in a noncirculating storage systemPipe insulation must be at least
1/2 in. and have a conductivity no >0.28 Btu•in/(h-ft2-°F).
Generic Requirements: Must be met by all systems to which the requirement is applicable
1. Design heating and cooling loads for the building must be determined using procedures equivalent to those in
Chapters 27 and 28 of the ASHRAE Handbook of Fundamentals or an approved equivalent calculation procedure.
2. All equipment and systems must be sized to be no greater than needed to meet calculated loads. A single piece of
equipment providing both heating and cooling must satisfy this provision for one function with the capacity for the
other function as small as possible, within available equipment options.
- Exception: The equipment and/or system capacity may be greater than calculated loads for standby purposes.
Standby equipment must be automatically controlled to be off when the primary equipment and/or system is
operating-
- Exception: Multiple units of the same equipment type whose combined capacities exceed the calculated load are
allowed if they are provided with controls to sequence operation of the units as the load increases or decreases.
3. Each heating or cooling system serving a single zone must have its own temperature control device.
4. Each humidification system must have its own humidity control device.
5. Thermostats controlling both heating and cooling must be capable of maintaining a 5 degree F deadband (a range
of temperature where no heating or cooling is provided).
- Exception: Deadband capability is not required if the thermostat does not have automatic changeover capability
between heating and cooling.
6. The system or zone control must be a programmable thermostat or other automatic control meeting the following
criteria:a) capable of setting back temperature to 55 degree F during heating and setting up to 85 degree F during
coolingb) capable of automatically setting back or shutting down systems during unoccupied hours using 7
different day schedulesc) have an accessible 2-hour occupant overrided) have a battery back-up capable of
maintaining programmed settings for at least 10 hours without power.
- Exception: A setback or shutoff control is not required on thermostats that control systems serving areas that
operate continuously.
- Exception: A setback or shutoff control is not required on systems with total energy demand of 2 kW (6,826
Btu/h) or less.
7. Outdoor -air supply systems with design airflow rates >3,000 cfm of outdoor air and all exhaust systems must have
dampers that are automatically closed while the equipment is not operating.
8. The system must supply outside ventilation air as required by Chapter 4 of the International Mechanical Code. If
the ventilation system is designed to supply outdoor -air quantities exceeding minimum required levels, the system
must be capable of reducing outdoor -air flow to the minimum required levels.
9. Air ducts must be insulated to the following levels:a) Supply and return air ducts for conditioned air located in
unconditioned spaces (spaces neither heated nor cooled) must be insulated with a minimum of R-5. Unconditioned
spaces include attics, crawl spaces, unheated basements, and unheated garages.b) Supply and return air ducts and
plenums must be insulated to a minimum of R-8 when located outside the building.c) When ducts are located
within exterior components (e.g., floors or roofs), minimum R-8 insulation is required only between the duct and
the building exterior.
+. 1 • s
- Exception: Duct insulation is not required on ducts located within equipment.
- Exception: Duct insulation is not required when the design temperature difference between the interior and
exterior of the duct or plenum does not exceed 15 degree F.
10. All joints, longitudinal and transverse seams, and connections in ductwork must be securely sealed using
weldments; mechanical fasteners with seals, gaskets, or mastics; mesh and mastic sealing systems; or tapes. Tapes
and mastics must be listed and labeled in accordance with UL 181A or UL 181B.
11. Mechanical fasteners and seals, mastics, or gaskets must be used when connecting ducts to fans and other air
distribution equipment, including multiple -zone terminal units.
12. Operation and maintenance documentation must be provided to the owner that includes at least the following
information:a) equipment capacity (input and output) and required maintenance actionsb) equipment operation
and maintenance manualsc) HVAC system control maintenance and calibration information, including wiring
diagrams, schematics, and control sequence descriptions; desired or field -determined set points must be
permanently recorded on control drawings, at control devices, or, for digital control systems, in programming
commentsd) complete narrative of how each system is intended to operate.
13. Each supply air outlet or diffuser and each zone terminal device (such as VAV or mixing box) must have its own
balancing device. Acceptable balancing devices include adjustable dampers located within the ductwork, terminal
devices, and supply air diffusers.
14. Service water heating equipment must meet minimum Federal efficiency requirements included in the National
Appliance Energy Conservation Act and the Energy Policy Act of 1992, which meet or exceed ASHRAE 90.1
Code. New service water heating equipment can be assumed to meet these requirements.
15. Water -heating equipment must be provided with controls that allow the user to set the water temperature to 110 OF
for dwelling units and 90 OF for other occupancies. Controls must limit output temperatures of lavatories in public
facility restrooms to 110 OF.
From: JerryBuffey
To:-- Gina Carrillo; Mandl Alford; Susan. Stanley _
Date: 11/4/2003 4:25:58 PM
Subject: Re: Zale's 1500 Harvey Rd.
Zale's........ is ok for fire final........
>>> Susan Stanley 11 /04/03 02:01 PM >>>
Ready for CO
BP # 03-1984
This is a remodel
All building issue's are clear.
Susan Stanley
City of College Station
CSR Development Services
sstanleyO-cstx.aov
979-764-3741
CC: Raymond.Olson; Steve Smith
Susan Stanley - Re: Zale's 1500 Harvey J Page 1
From: Bridgette George
To: Susan Stanley
Date: 11/4/2003 2:02:48 PM
Subject: Re: Zale's 1500 Harvey Rd.
Ok.
---------------------
Bridgette George
Asst. Development Manager
City of College Station
P.O. Box 9960
College Station, TX 77842-9960
979.764.3570
bgeorge@cstx.gov
www.ci.college-station.tx.us
>>> Susan Stanley 11/4/2003 2:01:59 PM >>>
Ready for CO
BP # 03-1984
This is a remodel
All building issue's are clear.
Susan Stanley
City of College Station
CSR Development Services
sstanleacstx.gov
979-764-3741
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
----------------------------------------------------------------------------
Application Number . . . . .
Property Address . . . . . .
Property ID . . . . . . . . .
R# . . . . . . . . . . . . .
Tenant nbr, name . . . . . .
Application description . . .
Subdivision Name . . . . . .
Property Use . . . . . . . .
Property Zoning . . . . . . .
Application valuation . . . .
Owner
03-00001984 Date 9/22/03
1500 HARVEY RD 4003
514000-0001-0040
R38018
ZALES REMODEL
COMMERCIAL, REMODEL/RENOVATION
POST OAK MALL
MERCANTILE
GENERAL COMMERCIAL
100000
C B L & ASSOCIATES PROPERTIES
2030 HAMILTON PLACE BLVD
STE 500
CHATTANOOGA TN 374216000
Contractor
----------------�--
NACCO, INC. /
P 0 BOX 59513
DALLAS TX 75229
(792) 620-9975
Structure Information
Construction Type . . . . . **NEEDS TO BE ENTERED**
Occupancy Type . . . . . . MERCANTILE
Other struct info . . . . . IMPACT/PRORATA FEES PAID NA
HEATED AREA 1308.00
INTERIOR WALL TYPE EXISTING
SERIAL ZONES 161.00
----------------------------------------------------------------------------
Permit . . . . . . BUILDING PERMIT
Additional desc MA
Permit Fee . . . . 460.00 Plan Check Fee .00
Issue Date . . . . 9/22/03 Valuation . . . . 100000
Expiration Date . . 3/21/04
Qty Unit Charge Per Extension
BASE FEE 260.00
50.00 4.0000 THOU BLDG, VAL 50001-100000 200.00
----------------------------------------------------------------------------
Special Notes and Comments
THE TEXAS DEPARTMENT OF HEALTH REQUIRES AN ASBESTOS SURVEY
IN CERTAIN CIRCUMSTANCES - CALL TDH @ (254) 778-6744 FOR
MORE INFORMATION
ELECTRICAL SHALL BE INSTALLED PER 199 NEC & LOCAL AMENDMENTS
PROVIDE FIRE EXTINGUISHERS) - VERIFY LOCATION AND PLACEMENT
WITH THE FIRE MARSHALL'S OFFICE (MIN. 2A10BC)
POST PERMIT CARD ON JOB SITE
Fee summary Charged Paid Credited Due
----------------------------------------------------------------------------
BUILDING DEPT REPRESENTATIVE:
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
----------------------------------------------------------------------------
Page 2
Application Number . . . . . 03-00001984 Date 9/22/03
---------------------------------------------------------
Permit Fee Total 460.00 460.00 .00 .00
Plan Check Total .00 .00 .00 .00
Grand Total 460.00 460.00 .00 .00
----------------------------------------------------------------------------
BUILDING DEPT REPRESENTATIVE:
APPLICANT:
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979)764-3570 FAX: (979)764-3496
----------------------------------------------------------------------------
Application Number . . . .
. 03-00001984 Date 9/22/03
Property Address . . . . .
. 1500 HARVEY RD 4003
Property ID . . . . . . . .
. 514000-0001-0040
R # . . . . . . . . . . . .
. R38018
Tenant nbr, name . . . . .
. ZALES REMODEL
Application description . .
. COMMERCIAL, REMODEL/RENOVATION
Subdivision Name . . . . .
. POST OAK MALL
Property Use . . . . . . .
. MERCANTILE
Property Zoning . . . . . .
. GENERAL COMMERCIAL
Application valuation . . .
. 100000
Owner
Contractor
------------------------
------�-//-,.-�7►FF - --- ----
C B L & ASSOCIATES PROPERTIES Rl�v�i
2030 HAMILTON PLACE BLVD
P. /,Z��9S��
1W
STE 500
CHATTANOOGA TN 374216000
-------------------------- Structure Information -------------------------
Construction Type . . . . .
**NEEDS TO BE ENTERED**
Occupancy Type . . . . . .
MERCANTILE
Other struct info . . . . .
IMPACT/PRORATA FEES PAID NA
HEATED AREA 1308.00
INTERIOR WALL TYPE EXISTING
SERIAL ZONES 161.00
----------------------------------------------------------------------------
Permit . . . . . . BUILDING PERMIT
Additional desc MA
Permit Fee 460.00
Plan Check Fee .00
Issue Date . . . . 9/22/03
Valuation . . . . 100000
Expiration Date . . 3/21/04
Qty Unit Charge Per
Extension
BASE FEE 260.00
50.00 4.0000 THOU
BLDG, VAL 50001-100000 200.00
----------------------------------------------------------------------------
Special Notes and Comments
THE TEXAS DEPARTMENT OF HEALTH
REQUIRES AN ASBESTOS SURVEY
IN CERTAIN CIRCUMSTANCES -
CALL TDH @ (254) 778-6744 FOR
MORE INFORMATION
ELECTRICAL SHALL BE INSTALLED
PER 199 NEC & LOCAL AMENDMENTS
PROVIDE FIRE EXTINGUISHERS)
- VERIFY LOCATION AND PLACEMENT
WITH THE FIRE MARSHALL'S
OFFICE (MIN. 2A10BC)
POST PERMIT CARD ON JOB SITE
Fee summary Charged
--------------------
BUILDING EPT REPRESE- ATE
APPLICANT:
Paid Credited Due
----------------- -- -----------------
BUILDING PERMIT
CITY OF COLLEGE STATION
1101 TEXAS AVE
COLLEGE STATION, TX 77840
PHONE: (979) 764-3570 FAX: (979) 764-3496
----------------------------------------------------------------------------
Page 2
Application Number . . . . . 03-00001984 Date 9/22/03
---------------------------------------------------------
Permit Fee Total 460.00 460.00 .00 .00
Plan Check Total .00 .00 .00 .00
Grand Total 460.00 460.00 .00 .00
BUILDI DEPT REPRESE A
APPLICANT:
APPLICATION FOR BUILDING
CITY OF COLLEGE STATION
1101 TEXAS AVENUE
COLLEGE STATION, TX 77840
(979) 764-3570 (979) 764-3496 FAX
W WW.CI.COLLEGE-STATION.TX.US
Fo Ofics Use Oefy
PERMIT DATE:
APPLICATION # s
TEMP POLE #
ADDRESS/LOCATION: (ZD. SPACE 400.5
LOT BLOCK SUBDIVISION
BUSINESS/OWNER NAME: ')f%P. PHONE: i"I2` �80.4'SSI
CONTRACTOR/HOMEOWNER: G45-F Tt_9__1HQ N4'eZO 467 - PHONE: '17Z 00 - 9 97F
CONTRACTOR ADDRESS: J �,/� , n
ELECTRICIAN: ,i��.'11 ��tG /�61M� t� 1,1:L�N44 UM4ER:
HVAC: I'rA NIA, Ao M4-41 % Z9C . GOOD CENTS (Residential only):
CLASS OF WORK
ACCESSORY/STORAGE LOCATION RE -ROOF (Total/Partial)
ADDITION MOVING SHELL ONLY
DEMOLITION (Asbestos Survey) NEW CONSTRUCTION SLAB ONLY
DUPLEX (Landscape Plans Req) REMODEURENOVATION SWIMMING POOL
DESCRIPTION OF WORK: :Mc1OEL. OF EXS►STlnl(r tLTA�L `tEni/aty t' S>P/iCE
STRUCTURE USE: animE —(Lew.. saum5
HOMEOWNER ASSOCIATION/ARCHITECTUAL OR DESIGN REVIEW COMMITTEE APPROVAL:
TEXAS ACCESSIBILITY STANDARD (TAS) PROJECT REGISTRATION# EABPRJAr3S36l 7-
VALUATION: $ TOTAL AREA: {308 HEATED AREA: 1308 _
(Cost of Labor and Materials)
PUBLIC SEWER
SEPTIC/TREATMENT SYSTEM
SEWER TAP:
WATER TAP:
OTHER TAP:
TEMP POLE
NUMBER OF BEDROOMS:
NUMBER OF BATHROOMS:
INTERIOR WALL TYPE
EXTERIOR WALL TYPE:
FOUNDATION TYPE:
ROOF TYPE:
f%QrAl.Sil'dOS+.pVWAU_
EX&$Sr1r4c_
e5cQI T-kr4(r
GARAGE TYPE: SINGLE F-1 DOUBLE F__j TRIPLE a
ATTACHED F-1 DETACHED F-1 CARPORT
SIGNATURE OF APPLICANT: ��-S.J�--/� -rim S+C.4eNw. . I-SMS41'0$7-k
Plans Examiner
Official Use Only
Zoning Official
Comments:
YES or NO