HomeMy WebLinkAbout02-00500162- 00074506CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
January 12, 2004
TO: Lenwood S. Adams, PE, Via fax 693.4243'/
FROM: Bridgette George, Assistant Development Manager
SUBJECT: EMERALD PARK PLAZA LOT 4 BLK 1 (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information for further staff review: j~
-ff
4A
One (1) complete set of construction documents for the proposed
development with the revised site and landscaping plans attached.
If there are comments that you are not addressing with the revised site plan, please
attach a letter explaining the details. If you have any questions or need additional
information, please call me at 764-3570.
Attachments: Staff review comments
cc: Dr. Jeannie Williams, DDS, Via fax 695.2438,./
Williamson Group Architects, 775.1884 ✓
Case file #02-00500162
Home of Texas A&M University
STAFF REVIEW COMMENTS NO. 3
Project: EMERALD PARK PLAZA LOT 4 BLK 1 (SP) - 02-00500162
PLANNING
1. Please show the actual development area in landscape plan calculation. The area
did not change when phase line was removed.
2. Fire lane must be shown around entire turn around; not arced stripes but painted
curbs.
Reviewed by: Jennifer Prochazka Date: January 5, 2004
ENGINEERING
1. Please refer to Fire Department Design Guidelines. The minimum radius allowed on
the "hammerhead" is 30-ft.
2. Please provide dumpster enclosure detail. (Sheet 7/8)
3. Concerning 6-ft wide curb leave-outs.... Will sidewalk be steel plate, concrete,
supported....? Will erosion control be provided on backside? Are these details on
other sheets?
Reviewed by: Spencer Thompson Date: January 8, 2004
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the
City, will constitute a completely new review.
2 of 2
'I 3
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone (979) 764-3570 / Fax (979) 764-3496
MEMORANDUM
September 4, 2002
TO: Lenwood S. Adams, MDG, Via fax 693-4243
FROM: Bridgette George, Assistant Development Manager
SUBJECT: EMERALD PARK PLAZA LOT 4 BLK 1 (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page
is a list of staff review comments detailing items that need to be addressed. The
next submittal will be the third and final review by staff for this round of reviews.
If all items have not been addressed on the next submittal, another $200
processing fee will need to be submitted for the subsequent set of three (3)
reviews. Please address the comments and submit the following information for
further staff review:
Two (2) revised site and landscaping plans.
If there are comments that you are not addressing with the revised site plan,
please attach a letter explaining the details. If you have any questions or need
additional information, please call me at 764-3570.
Attachments: Staff review comments
cc: Dr. Jeannie Williams, DDS, Via fax 695-2438
Williamson Group Architects, Via fax 775-1884
Case file #02-00500162
Home of Texas A&M University
T
STAFF REVIEW COMMENTS NO. 2
Project: EMERALD PARK PLAZA LOT 4 BLK 1 (SP) - 02-00500162
PLANNING
1. The portion of the first phase that is along the western property line is
approximately 245-feet. You are required to have 10 canopy trees and 82
shrubs within this required 5-foot planted buffer. Please remember that the
buffer plantings do not count toward your total landscape point requirement.
2. The portion of the first phase that is along eastern property line is
approximately 220-feet. You are required to have 9 canopy trees and 74
shrubs along this boundary line for phase one. Please call out the required
masonry wall for this portion of the buffer.
3. "Dwarf Holly" is not on our approved planting list. Please contact me if you
need information on approved plantings.
4. Please be aware that Live Oaks should not be used in the buffer area
because there is a required 35-foot separation distance between Live Oaks.
5. Please be aware that a 6" raised curb is required around all paved areas,
including parking islands. From the site plan I was unable to tell if the parking
area was curbed. Please add this to the general notes.
6. You are required to provide an additional 180-s.f. of landscaped islands for
every 15 interior parking spaces. This requirement is in addition to your
required end islands. You are proposing 66 interior parking spaces, and
therefore need 900-s.f of additional interior parking islands. You may count
any extra square footage of landscaped end islands toward this requirement
(anything over 180-s.f. for each end of each parking row). The current
proposal includes only 196-s.f. of "extra" landscaped islands.
7. Please show the location of all transformers, a/c units, utility connections on
buildings, etc., and show screening from the public R.O.W.
8. The minimum width for parking spaces is 9-feet. This includes handicapped
spaces.
Reviewed by: JENNIFER FLANERY Date: August 26, 2002
ENGINEERING
1. No comments
Reviewed by: Spencer Thompson Date: 8/29/02
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be
explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on these plans
that have not been pointed out to the City, will constitute a completely new review.
2 of 2
City of College Station
Development Services
P. O. Box 9960 - 1101 Texas Avenue - College Station, Texas
77842
(979) 764-3570
MEMORANDUM
August 16, 2002
TO: Lenwood S. Adams, MDG, Via fax 693-4243
FROM: Bridgette George, Assistant Development Manager
SUBJECT: Emerald Park Plaza, Lot 4, Block 1
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information for further staff review:
Two (2) sets of revised construction documents.
If there are comments that you are not addressing with the revised site plan, please
attach a letter explaining the details. If you have any questions or need additional
information, please call Jennifer Flanery or myself at 764-3570.
Attachments: Staff Review Comments
CC: Dr. Jeannie Williams, D.D.S., Via fax 695-2438
Williamson Group Architects, Via fax 775-1884
Case file no. 02-162
STAFF REVIEW COMMENTS No. 1
PROJECT: Emerald Park Plaza Lot 4 Block 1 (SP) 02-00500162
PLANNING
1. If the project is proposed in multiple phases, a phase line must be shown. Each
phase will be required to stand on its own for parking, buffering, and landscaping.
2. The dumpster enclosure looks good, but the distance between the bollards shown
(sheet 8) on the approach side is too narrow. Please remove the inside set of
bollards. (Per Pete Caler)
3. Please indicate on the site plan the zoning of all abutting properties.
4. Please show distance from the proposed curb cut to all opposite and adjacent
driveways.
5. Please show all buildings on abutting properties.
6. All parking spaces must be a minimum of 9'x20' (or 18' with a 2' overhang). You
indicate that several spaces are only 8' wide.
7. All parking shown on your proposal is considered "interior" parking and requires an
additional 180-sq. ft. of landscaped islands for every 15 parking spaces. If your
end islands are larger than 180-sq. ft., then you may count the extra area in the
end islands toward the additional island area needed. Please indicate the area in
the sq. ft. of the end islands if you choose to count the additional square footage
toward your interior island requirement.
8. Please indicate the location of the proposed fire lanes along the length of the
lances to be striped. You are currently showing only a line at the end of each aisle.
9. You are required to provide a 15' wide landscaped buffer and a solid masonry wall
between the R-1 single-family residential abutting the property. A 5' wide
landscaped buffer is also required between adjacent A-P zoning designations. A
tree for every 25 linear feet and a shrub for every 3 linear feet are required in the
landscaped buffer. These plantings in the buffer areas do not count toward your
total landscape points.
10. On your landscaping plan please indicate the species of trees and shrubs to be
installed.
11. Please show irrigation to all planted areas or provide a note that says that an
approved irrigation plan must be approved prior to C.O.
12. Please remove the words "WATER METER" on the east side of the building if
there is not a water meter there. All meters must be located in an easement or
public R.O.W.
13. Please show the location of all transformers, a/c units, utility connections on
buildings, etc., because these need to be screened from the public R.O.W.
Reviewed by: Jennifer Flanery Date: August 9, 2002
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must
be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on
these plans that have not been pointed out to the City, will constitute a completely new review.
ENGINEERING
1. Please connect domestic water out from under pavement.
2. Please show handicap accommodations at driveway and sidewalk interface.
3. Please show water and sewer demands for sizing meter(s) and service(s).
Reviewed by: Spencer Thompson Date: August 16, 2002
ELECTRICAL
1. Developer installs conduit per city specs and design.
2. Developer provides 30' of #4 rigid conduit for riser poles. Developer installs
first 10'. City installs remainder.
3. Developer pours transformer pad(s) per city specs and design.
4. Developer installs pull boxes as per city specs and design.(pull boxes
provided by the city.
5. Developer provides digital AutoCAD 14 version of plat and/or site plan.
email to rbolina-ci.college-station.tx.us
6. Developer provides load data for project.
7. Developer provides temporary blanket easement for construction
purposes.
8. Developer provides easements for electric infrastructure as installed for
electric lines (including street lights).
Reviewed by: Ronnie Bolin Date:
MISCELLANEOUS
1. Irrigation system must be protected by either a Pressure Vacuum Breaker or
Reduced Pressure Principle Back Flow Devise and installed as per City Ordinance
2394.
2. All Back Flow devices must be installed and tested upon installation as per City
Ordinance 2394.
Reviewed by: Rob Werley
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must
be explained in your next transmittal letter and "bubbled" on your plans. Any additional changes on
these plans that have not been pointed out to the City, will constitute a completely new review.