CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone (979) 764-3570 / Fax (979) 764-3496
MEMORANDUM
TO: Wallace Phillips, DD&H Investments, Inc. via fax 690-1041
FROM: Bridgette George, Assistant Development Manager
SUBJECT: PARKING LOT IMPROVEMENT (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address
the comments and submit the following information for further staff review and approval:
Four (4) revised site and landscaping plans.
If there are comments that you are not addressing with the revised site plan, please
attach a letter explaining the details. If you have any questions or need additional
information, please call me at 764-3570.
Attachments: Staff review comments
cc: Joe Shultz, Texcon via fax 690.9797
Case file #02-158
Home of Texas A&M University
a
STAFF REVIEW COMMENTS NO. 1
Project: PARKING LOT IMPROVEMENT (SP) - 02-158
PLANNING
1
2
3
4
5
Is there adequate handicapped-accessible parking in the front of the building? If
not, it may be necessary to utilize some of the new parking area to meet code
requirements. Also, please include the number of accessible spaces required and
provided in the parking analysis of the site.
End islands are required at the end of every parking row. Please show an island for
the perimeter parking on the east side and an island to separate the new parking
from the building on the north side.
If the parking will be visible from the abutting residential use to the west, it will need
to be screened. Screening may be accomplished using plantings, berms, structural
elements, or combinations thereof, and must be three feet above the parking lot
elevation.
A fire lane description is included in the construction notes. Please identify the
location of the lanes or remove the note if there aren't any on site.
Please add "and approved before C.O." to site note #8.
Reviewed by: Molly Hitchcock
Date: August 1, 2002
ENGINEERING
1. Please provide an erosion resistant drainage path for water to flow from curb
opening in parking area to drainage easement.
2. Please ensure no drainage way is impeded by development.
Reviewed by: Spencer Thompson
ELECTRICAL
1. No comments.
Reviewed by:
MISCELLANEOUS
Ronnie Bolin
Date: August 5, 2002
Date:7-31-02
1. Irrigation system must be protected by either a Pressure Vacuum Breaker or
Reduced Pressure Principle Back Flow Device and installed as per City Ordinance
2394.
2. All BackFlow devices must be installed and tested upon installation as per City
Ordinance 2394.
Reviewed by: Rob Werley
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.
Page 2 of 2