MEMORANDUM
Q3 la
May 23, 2002
T0: Preston H. Carroll, Via fax 281-367-6419
FROM: Bridgette George, Assistant Development Manager
SUBJECT: WOLF RETAIL CENTER (SP) -Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of
staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information for further staff review:
✓ Six (6) complete copies of the construction documents with the revised site
and landscaping plans attached;
✓ Two (2) copies of the revised site plan;
One (1) copy of the revised landscaping plan;
Easement Dedication Sheet and required documents (if necessary).
Please note that the Easement Dedication Sheet and the necessary documents are
required prior to the issuance of a building permit. If there are comments that you are not
addressing with the revised site plan, please attach a letter explaining the details. If you
have any questions or need additional information, please call me at 764-3570.
Attachments: Staff review comments
Easement Dedication Sheet
cc: James Chang, Ponderosa Land Development Co., Via fax 713-626-3394
Rodney L. Chalkley, Architectural & Engineering Assoc., Via fax 713-777-0709
Case file #02-00500102
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next
transmittal letter and 'bubbled' on your plans Any additional changes on these plans that have not been pointed out to t' e
City, will constitute a completely new review.
979-764-3895
Page 2 cf 5
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone (979) 764-3570 / Fax (979) 764-3496
Page 1 of 3
ft.
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone (979) 764-3570 / Fax (979) 764-3496
MEMORANDUM
May 23, 2002
TO: Preston H. Carroll, Via fax 281-367-6419
FROM: Bridgette George, Assistant Development Manager
SUBJECT: WOLF RETAIL CENTER (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address
the comments and submit the following information for further staff review:
Six (6) complete copies of the construction documents with the revised
site and landscaping plans attached;
Two (2) copies of the revised site plan;
One (1) copy of the revised landscaping plan;
Easement Dedication Sheet and required documents (if necessary).
Please note that the Easement Dedication Sheet and the necessary documents are
required prior to the issuance of a building permit. If there are comments that you are
not addressing with the revised site plan, please attach a letter explaining the details. If
you have any questions or need additional information, please call me at 764-3570.
Attachments: Staff review comments
Easement Dedication Sheet
cc: James Chang, Ponderosa Land Development Co., Via fax 713-626-3394
Rodney L. Chalkley, Architectural & Engineering Assoc., Via fax 713-777-0709
Case file #02-00500102
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.
Page 1 of 3
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone (979) 764-3570 / Fax (979) 764-3496
MEMORANDUM
May 23, 2002
TO: Preston H. Carroll, Via fax 281-367-6419
FROM: Bridgette George, Assistant Development Manager
SUBJECT: DP-WOLF RETAIL CENTER - Development Permit
Staff reviewed the above-mentioned construction documents as requested. The
following page is a list of staff review comments detailing items that need to be
addressed. Please address the comments and submit the following information for
further staff review and approval:
One (1) copy of the Erosion Control Plan
Two (2) copies of the Drainage Analysis
TxDOT permits and required attachments.
If there are comments that you are not addressing with the revised site plan, please
attach a letter explaining the details. If you have any questions or need additional
information, please call Spencer Thompson at 764-3570.
Attachments: Staff review comments
cc: James Chang, Ponderosa Land Development Co., Via fax 713-626-3394
Rodney L. Chalkley, Arch. & Engr. Assoc., Via fax 713-777-0709
Case file #02-00100027
Home of Texas A&M University
STAFF REVIEW COMMENTS NO. 1
Project: DP-WOLF RETAIL CENTER-DEVELOPMENT PERMIT (02-00100027)
ENGINEERING
1. Please provide drainage analysis for this development.
2. Please submit all TXDOT permits as required. One has been received to date for
the storm water connection in TXDOT ROW.
3. Please provide an erosion control plan and show tree protection on existing trees.
Reviewed by: Spencer Thompson Date: May 21, 2002
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.
Page 2 of 2
CITY OF COLLEGE STATION
DEVELOPMENT SERVICES
1101 Texas Avenue South, PO Box 9960
College Station, Texas 77842
Phone (979) 764-3570 / Fax (979) 764-3496
MEMORANDUM
May 23, 2002
TO: Preston H. Carroll, Via fax 281-367-6419
FROM: Bridgette George, Assistant Development Manager
SUBJECT: WOLF RETAIL CENTER (SP) -Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of
staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information for further staff review:
Six (6) complete copies of the construction documents with the revised site
and landscaping plans attached;
Two (2) copies of the revised site plan;
One (1) copy of the revised landscaping plan;
Easement Dedication Sheet and required documents (if necessary).
Please note that the Easement Dedication Sheet and the necessary documents are
required prior to the issuance of a building permit. If there are comments that you are not
addressing with the revised site plan, please attach a letter explaining the details. If you
have any questions or need additional information, please call me at 764-3570.
Attachments: Staff review comments
Easement Dedication Sheet
cc: James Chang, Ponderosa Land Development Co., Via fax 713-626-3394
Rodney L. Chalkley, Architectural & Engineering Assoc., Via fax 713-777-0709
Case file #02-00500102
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next
transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out to the
City, will constitute a completely new review.
Page 1 of 3
STAFF REVIEW COMMENTS NO. 1
Project: WOLF RETAIL CENTER (SP)-SITE PLAN (02-00500102)
PLANNING
1. Please show the zoning for the abutting parcels.
2. Please delineate all building setbacks.
3. Please note on the site plan that there will be an 8-ft. solid screening fence around
the dumpster.
4. Please show existing fire lane.
5. The total distance of your south property line is 240.62-ft., this would require 10
canopy trees and 80 shrubs for the required buffer.
6. The existing oaks in the TXDOT ROW cannot be counted for any points. These
Oaks will no longer be there once the widening of the road takes place.
7. Sanitation is OK with this project.
8. Sheet 1-2: You must obtain TXDOT permission to place private irrigation in their
ROW. Without written permission from TXDOT, this will not be allowed.
Reviewed by: Jennifer Reeves Date: 05/14/02
ENGINEERING
1. It appears that the location of the proposed water meter will require a TXDOT
permit. Please submit one for this purpose.
2. You will be required to submit a drainage analysis for the site to ensure that
drainage to the existing storm sewer system is not being increased. This is a
Development Permit requirement.
3. Please provide estimated water demands. Your meter(s) will be sized by the City in
accordance with the estimated demands provided.
4. Please re-examine your Plumbing/ Piping Materials Schedule to ensure compliance
with the 2000 IBC.
5. On Sheet P1, please add note to #2: backflow preventer required.
Reviewed by: Spencer Thompson Date: May 21, 2002
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.
Page 2 of 3
PLANNING
1. Please show the zoning for the abutting parcels.
2. Please delineate all building setbacks.
3. Please note on the site plan that there will be an 8-ft. solid screening fence around
the dumpster.
4. Please show existing fire lane.
5. The total distance of your south property line is 240.62-ft., this would require 10
canopy trees and 80 shrubs for the required buffer.
6. The existing oaks in the TexDot ROW cannot be counted for any points. These
Oaks will no longer be there once the widening of the road takes place..
7. Sanitation is OK with this project.
8. Please show fire hydrants location to scale. The existing fire hydrant has to be 300
ft. from the property as the fire truck would drive and as the hose would lay ( hose
cannot lay across the median).
Reviewed by: Jennifer Reeves Date: 05/14/02
ELECTRICAL
1. Developer installs conduit per city specs and design.
2. Developer pours transformer pad(s) per city specs and design.
3. Developer provides digital AutoCAD 2000i version of plat and/or site plan.
email to rbolin(a ci.college-station.tx.us
4. Developer provides load data for project.
5. Developer provides temporary blanket easement for construction
purposes.
6. Developer provides easements for electric infrastructure as installed for
electric lines.
Reviewed by: Ronnie Bolin Date:5-14-02
MISCELLANEOUS
1. Irrigation system must be protected by either a Pressure Vacuum Breaker or
Reduced Pressure Principle Back Flow Device and installed as per City Ordinance
2394.
2. All BackFlow devices must be installed and tested upon installation as per City
Ordinance 2394.
Reviewed by: Rob Werley
NOTE: Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your
next transmittal letter and "bubbled" on your plans. Any additional changes on these plans that have not been pointed out
to the City, will constitute a completely new review.
Page 3 of 3
05/23/02 14:47 F-am: Bridgette George 979-7154-3895 Page 4 cf 5
ELECTRICAL
1. Developer installs conduit per city specs and design.
2. Developer pours transformer pad(s) per city specs and design.
3. Developer provides digital AutoCAD 2000i version of plat and/or site plan.
email to rbolin 0ci,college-station.tx.us
4. Developer provides load data for project.
5. Developer provides temporary blanket easement for construction
purposes.
6. Developer provides easements for electric infrastructure as installed for
electric lines.
Reviewed by: Ronnie Bolin Date:5-14-02
MISCELLANEOUS
1. Irrigation system must be protected by either a Pressure Vacuum Breaker or Reduced
Pressure Principle Back Flow Device and installed as per City Ordinance 2394.
2. All BackFlow devices must be installed and tested upon installation as per City
Ordinance 2394.
Reviewed by: Rob Werley
NOTE, Any changes made to the plans, that have not been requested by the City of College Station, must be explained in your next
transmittal letter and 'bubbled` on your plans, Any additional changes on these plans that have not been pointed out to the
City, will constitute a completely new review.
Page 3 of 3