HomeMy WebLinkAbout00072735forward towards the parking lot to avoid queuing at the entrance to the adjoining property. The gate detail needs to show how it meets fire department specifications. A keypad pedestal detail needs to be provided. (See # 15 on the site plan.) 16. Indicate curb leave-outs more clearly on the site plan. 17. Show proposed sidewalks and their dimensions. 18. These two dumpsters need to be relocated. (See the # 18's on the site plan.) Dumpsters need to be placed where they can not be seen from the R.O.W. and they can not be located in the 24' landscape reserve. The dumpsters need to be screened and landscaped. 19. Show proposed easements with proposed utility lines. 20. Show all proposed utility lines-both public and private. 21. Where are the proposed meters located? 22. Show fire lanes and fire department connections. 23. Only 6,752 landscape points are required. The measurement of driveways and sight distances are not included in the point calculation. 24. Vegetation needs to be set back 45' from the curb at the intersection of streets and 10' from driveway curbs. 25. Live oaks need to be back 30' behind the street curb and planted at a minimum of 35' from other live oaks. 26. The landscape/streetscape plan does not contain the following requirements: • The location of proposed property lines and dimensions of the tract. • The location of proposed utilities and all easements on or adjacent to the lot. • A barricade plan for existing trees. 27. Show barricade detail. For each caliper inch, there needs to be 1' radius protected area. 28. Are the hackberry and post oak in the R.O.W. or on the property? 29. An irrigation plan needs to be provided before a Certificate of Occupancy can be issued. Reviewed by: Molly Hitchcock Date: 20-Mar-00 Staff Review Comments Page 2 of 1 HOLLEMAN VILLAGE ADDITION SECTION TWO---DEV. REVIEW (Infrastructure) Date: 3/20/00 Reviewer: Ted May2=~_e_py~ Sheet 1- OK Sheet 2-No Review (Final Plat) Sheet 3-Flood Plain Boundry(see note 4) Where is note 4? 36.9' dimension-8" ss -where to where Sheet 4-No Review(Site Plan) Sheet 5-Dimension Control Plan-Need to convert to actual dimensions Note-All dimensions and coordinates shown are to centerline or face of curb unless otherwise noted.Use face of curb only. Sheet 6 -Top right-Elev. 519.30 should be 319.30. Sheet 7-Rt. Side-Cox Areial---Aerial Secl pg. 18 should be Sec. 1 pg. 25 Sheet 8-Storm sewers C/L stations-24"@7+18 should be 36'@ 6+80 : 48" @ 7+50 should be 48" @ 7+29 Sheer 9-OK Sheet 10 -Missing Sheet 11-Show gate valves off main to building service lines and irrigation line (isolation valve) Show gas and telephone lines Sheet 12-Water services to buildings-add 4" gate valve @ main 2" water service for irrigation-add 8"x 2" reducer, 2" gate valve and backflow preventor. Add 8" gate valve in main line at approximate station 4+50(isolation valve) Sewer : Line A sta 0+00-- 1+24.3-label as 8" ss Line A sta 3+29,30-3+85.07-label as 8" ss Line A sta 3+85.07 Bldg. 14-note 6" ss Sheet 13- Add blow-off@ end of 8" water line @ sta 9+20. Service to Bldg. 12-label 6" ss Show new manhole on existing 8" ss, flowline elevation and dimension from some known point.. Add low flow concrete flume to detention pond Sheet 14-Sewer lines -note SDR 26(ASTM D3034) Typ, Add detail for new 4" manhole on existing 8" ss service to Bldg. 12. Sheet 15-Sta. 1+47,50 should be sta. 1+61.25 Sta. 1+79.39-add 1-8" 90* bend Sta. 3+51.98 -add 1-8" 90* bend. Sta 5+76.98 tie-in waterline B-There is no waterline B. Sta 7+18.33-FL 24" RCP should be 36" RCP. Sta 8+82.22 Install Add-I -8"x 6" reducer. Sheet 15 A--OK Sheet 16- (Landscape Plan ) No Review Sheets 17-22 -OK Sheet 23-City Specifications-WS 304.0-------Letters A----G do not match spec. "Clarify" Detail -Class A-1 Embedment Note #4@ 10" oc etc. Where does this apply? Sheet 24-Detail 6 C-Note-curb ramps w/ truncated dome -see detail this sheet none provided. Sheets 25,26 -OK Sheets 26,27-Jeff to comment. CITY OF COLLEGE STATION PLANNING DIVISION POST OFFICE BOX 9960 1101 TEXAS AVENUE COLLEGE STATION. TEXAS 77842-9960 TELEPHONE: (979) 764-3570 MEMORANDUM February 10, 2000 TO: George E. Walker, Jr., The Wallace G ,Via fax (254) 776-2924 FROM: Natalie Ruiz, Development Coordinat r SUBJECT: Holleman Village Phase 11 - Site Plan Staff reviewed the above-mentioned site plan as requested. There were many items missing from the "Site Plan Minimum Requirements" checklist. Staff stopped review and determined that the site plan was not a complete submittal. Please review the items on the "Site Plan Minimum Requirements" checklist and submit the following information for a complete staff review: Ten (10) folded copies of the complete site plan; and, The attached redlined site plans with staff comments. If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. Attachments: Sanitation Division Comments Engineering Redlined Construction Plans Electrical Redlined Construction Plans cc: Edsel G. Jones, 301 University Drive East, College Station, TX 77840 Day' Wright, Fairfield Residential, Inc., Via fax (817) 640-9474 Ose file #00-20 CITY OF COLLEGE STATION PLANNING DIVISION POST OFFICE BOX 9960 1101 TEXAS AVENUE COLLEGE STATION, TEXAS 77842-9960 TELEPHONE: (979) 764-3570 MEMORANDUM March 21, 2000 TO: George E. Walker, Jr., The Wallace Group, Via fax (254) 776-2924 FROM: Bridgette George, Asst. Development Coordinate U SUBJECT: Holleman Village Phase 11 - Site Plan Staff reviewed the above-mentioned site plan as requested but had to stop review due to an incomplete submittal. The following page is a list of preliminary staff review comments detailing items that need to be addressed. The next submittal will be the third and final review by staff for this round of reviews. If all items have not been addressed on the next submittal, another $100 processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the comments and submit the following information for further staff review: Two (2) copies of the revised site and landscaping plans If there are comments that you are not addressing with the revised site plan, please attach a letter explaining the details. If you have any questions or need additional information, please call me at 764-3570. Attachments: Staff review comments cc: Edsel G. Jones, 301 University Drive East, College Station, TX, 77840 David Wright, Fairfield Residential, Inc., Via fax (817) 640-9474 Case file #00-20 STAFF REVIEW COMMENTS No. 2 Project: HOLLEMAN VILLAGE PH 2 (SP) (0-20) 1. On the site plan, please designate the public line that will be abandoned. Those that will remain need to be shown with their easement. 2. Show the water line on Holleman. 3. Wheelstops need to be removed from 18' parking spaces. 4. Please verify the size of the bedroom in 2 -bedroom units. This is needed to calculate parking requirements. 5. We are assuming the dark, heavy lines are curbing. Please verify or clearly show where there will be curb leave -outs. 6. Show the landscape reserve line on the site plan. 7. The dumpster needs to be removed from the landscape reserve. The dumpster closest to the mail kiosk needs to be angled further so that the dumpster will not be visible from the Jones -Butler ROW. 8. Regarding the dumpster enclosure detail on sheet 24, please designate on the site plan where this will be used. 9. Walls around dumpsters need to be 8' high. 10. On the curb detail on sheet 17, it needs to be shown that #4 bar will be used in the curb construction. 11. Please show or provide the sidewalk along Holleman. 12. Please verify there is 10' between the boundary line and edge of parking. 13. The 20' easement needs to be correctly identified. 14. The easement lines need to continue on the east side. 15. Please designate purpose of easement by mail kiosk. 16. 228 ft.2 of interior islands are still needed. 17. Show landscaping on islands on the site plan. 18. All dumpster locations need to be screened from the ROW. 19. Please label tree (seems to be live oak). 20. The transformer needs to be screened. Should other transformers be located on site, they will need to be screened also. 21. Show irrigation system plan (or provide note on how irrigation system requirement will be met prior to issuance of C.O.). 22. What are the boxes beside the buildings in the site plan? Staff Review Comments Page 1 of 1 23. The water and sanitary sewer legend needs to include the minimum, maximum, and average demands of water in gallons per minute and maximum demands of sewer loadings in gallons per day. 24. Add low flow concrete flume to detention pond. 25. Add profile detail for new 4' manhole on existing 8" SS service to Building 12. In regards to your letter dated 4/10/00: 1. On the original and topographic boundary survey, add a note that the current lot boundary for Lot 3 Block A has changed from the depicted configuration. 2. Also add note that the 100 year floodplain is incorrect and to refer to sheet 27 for the correct location. 3. Add not to site plan that is any above grade riser is needed within the project, GTE will coordinate the location with the City of College Station so that the riser will be adequately landscaped and screened. 4. A low flow concrete flume will be needed for the detention pond. A french drain will not be acceptable (see College Station Drainage Standards, pages 73 and 61 A). Reviewed by: Molly Hitchcock, Ted Mayo Date: 10 -Jun -14 Staff Review Comments Page 2 of 1 STAFF REVIEW COMMENTS No. 3 Project: HOLLEMAN VILLAGE PH 2 (SP) (0-20) 1. On the original topographic boundary survey, add a note that the current lot boundary for Lot 3 Block A has changed from the depicted configuration. 2. Also add not that the 100 year floodplain is incorrect and to refer to sheet 27 for the correct location. 3. Please add a note to the site plan that the square footage of each bedroom in two-bedroom units is less than 132. 4. Remove gate from dumpster detail. 5. Landscape along Jones Butler Road and mail kiosk area with red tip photinia and/or dwarf wax myrtle to screen dumpster by mail kiosk from the ROW. Reviewed by: MOLLY HITCHCOCK Date: 10 -Jun -14 Staff Review Comments Page 1 of 1 STAFF REVIEW COMMENTS No. 1 Project: HOLLEMAN VILLAGE PH 2 (SP) (0-20) REVIEW STOPPED. Most of the site plan requirements are not coordinated on the Site Plan. One or two attachments may be included as long as related requirements are on the same sheet, e.g., water lines, water easements, fire hydrants and fire lanes. Also, not enough fire -related information was on the plans to ensure adequate fire protection. Staff began review and has the following preliminary comments: 1. Call out dimensions on site plan. 2. Give the legal description of the property. 3. Complete the address for the listed architect. 4. The survey is incorrect and needs to match the latest legal description. This information needs to be consistent across all pages. 5. Show only the current property line. 6. Clean up lines that have no designations. 7. Clarify the development of property outside of the property line. 8. Call out street R.O.W.s and whether or not they are to scale. Call out the sidewalks and their widths. 9. Easements need to be shown on a document submitted as part of the site plan. Include public and private utilities. Complete the legend on Sheet 3. 10. Where are meters located? 11. What is this building? (See #11 on the site plan.) 12. Dimension the parking spaces. Interior spaces need to be 9' x 20'. Only seven contiguous parking spaces are allowed in the landscape reserve. 13. Indicate that end islands are landscaped on the site plan. 14. From the edge of the curb, many access isles are only 4'. 15. What is the proposal for this entrance? If there is a raised median, it needs to be identified. If this is a circle drive, the aisles need to maintain 20' width and 6" of concrete to meet fire lane requirements. Indicate driveway throat length. The gate is not planned as formerly discussed with the City of College Station's transportation planner. The whole controlled entry should be moved forward towards the parking lot to avoid queuing at the entrance to Staff Review Comments Page 1 of 1 the adjoining property. The gate detail needs to show how it meets fire department specifications. A keypad pedestal detail needs to be provided. (See # 15 on the site plan.) 16. Indicate curb leave -outs more clearly on the site plan. 17. Show proposed sidewalks and their dimensions. 18. These two dumpsters need to be relocated. (See the # 18's on the site plan.) Dumpsters need to be placed where they can not be seen from the R.O.W. and they can not be located in the 24' landscape reserve. The dumpsters need to be screened and landscaped. 19. Show proposed easements with proposed utility lines. 20. Show all proposed utility lines—both public and private. 21. Where are the proposed meters located? 22. Show fire lanes and fire department connections. 23. Only 6,752 landscape points are required. The measurement of driveways and sight distances are not included in the point calculation. 24. Vegetation needs to be set back 45' from the curb at the intersection of streets and 10' from driveway curbs. 25. Live oaks need to be back 30' behind the street curb and planted at a minimum of 35' from other live oaks. 26. The landscape/streetscape plan does not contain the following requirements: The location of proposed property lines and dimensions of the tract. The location of proposed utilities and all easements on or adjacent to the lot. A barricade plan for existing trees. 27. Show barricade detail. For each caliper inch, there needs to be 1' radius protected area. 28. Are the hackberry and post oak in the R.O.W. or on the property? 29. An irrigation plan needs to be provided before a Certificate of Occupancy can be issued. Reviewed by: Molly Hitchcock Date: 10 -Jun -14 Staff Review Comments Page 2 of 1 Reviewed by: TED MAYO Date: 10 -Jun -14 Staff Review Comments Page 3 of 1